OMICRON PTL SEL751A PTT User Manual

OMICRON PTL

SEL751A PTT

User Manual

V2.000

OMICRON electronics GmbH 1/5


OMICRON PTL SEL751A PTT User Manual

Content
1. General ............................................................................................................................................ 3
1.1 Supported Relays........................................................................................................................... 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 4
4. Functional Range ............................................................................................................................ 4
5. XRIO Converter ............................................................................................................................... 5
6. Test Template .................................................................................................................................. 5
6.1 Residual Ground and Neutral Ground Overcurrent tests ................................................................. 5

OMICRON electronics GmbH 2/5


OMICRON PTL SEL751A PTT User Manual

1. General
This user manual describes details of testing SEL751A relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: SEL
Model: 751A

1.1 Supported Relays


The following relay types can be tested with the Protection Test Template:
SEL751A

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 3.01 software or
higher versions and the following test modules:
Control Center
Quick CMC
Overcurrent

Any CMC test set can be used with this Protection Test Template.

OMICRON electronics GmbH 3/5


OMICRON PTL SEL751A PTT User Manual

3. Hardware
The SEL751A relay can be connected with the CMC test set using the shown setup.

Connection diagram for SEL751A Feeder


IC
IA
IB

Trip

Figure 1: SEL751A test setup

4. Functional Range
Supported functions:
Phase Overcurrent Characteristic
Ground Overcurrent Characteristic
Residual Overcurrent Characteristic
Negative Sequence Overcurrent Characteristic

OMICRON electronics GmbH 4/5


OMICRON PTL SEL751A PTT User Manual

5. XRIO Converter
The Test Object already contains the SEL751A XRIO Converter, which includes setting parameters of
the modelled protection relay. The setting parameters are built as an image of the
SEL5030 AcSELerator Quickset software.

The Filter for SEL 5030 txt Settings can be used for importing settings into the Relay Parameter
Section.

6. Test Template

6.1 Residual Ground and Neutral Ground Overcurrent tests


The Residual Ground Overcurrent elements are defined using the I0 option as their supervised current.
As the fault type for Residual Overcurrent tests is 3I0, the relative test points for testing the 51G1
characteristic are multiplied with 3. They are preset to 3.3, 3.9 and 4.5 times the I0 based 51G element
pickup value.
Neutral Ground Overcurrent elements are defined using IN as their supervised current. The fault type
used is A-N and the fault current is directly injected into the relays IN CT inputs.
This setup is used to clearly differentiate between Residual Ground and Neutral Ground Overcurrent
elements during testing.