IPS TECHNICAL SPECIFICATIONS

2 PHASE INPUT-1PHASE OUTPUT


I STRUCTURE
1 Capacity 2 Phase Input-1Phase Output available in below ratings
Customizations can
5KVA, 7.5 KVA, 10 KVA, 15 KVA, and 25 KVA.
2 be done
INTEGRATED POWER SYSTEM
1.6mm thick CRCA sheet with 1400(H)*600(W)*600(L) coated
3 Cabinet with Siemens gray , and IP protection is IP 21 for indoor ,
IP 65 for outdoor

II LINE CONDITIONER UNIT


Micro controller, thyristors based , true RMS, static line
Type
1 Conditioner
Input and output
Input 240V to 480V and output 220±, 10%
2 voltage
Input Frequency
47- 53 Hz
3 range
4 Transformer isolation Class F isolation
5 Efficiency at full load >95%
Input: over voltage cutoff >480 volts after 5sec(L-L)
under voltage cutoff the <240 volts after 5sec (L-L)
6 Voltage protection
output: over voltage cutoff >250 after 5sec (L -N)
Under voltage cutoff the <190 volts after 5sec (L-N)
III CENTRAL PROCESSING UNIT
Micro controller based working voltage 8V to 16V,
AMF functions are incorporated
Display with LED and LCD
1 Micro controller
Program the parameters using Keypad
Smoke, Temperature, Hooter, Intruder, Aviation lamp monitoring
DG program parameters are also incorporated

2 Time Real time and date programmable

3 Events logs 100 events with date and time

4 RS232 port For the PC interface and configure the parameters

5 Fuel level Fuel level monitoring is incorporated

6 AC controller If air conditioners fails ,indication with potential free contact output
IV AUTO MAINS FAILURE SYSTEM
Diesel Generator (DG)
Starts in auto and manual mode
Operation
1

DG Protection DG will trip for LLOP, HWT, Low fuel level, over voltage and under voltage
2
Three attempts for DG start with 50 seconds time delay
3 DG delays DG cooling time 5 minutes
10-second delay between mains and DG contactor change over
DG will start automatically based on the power plant battery
4 Fuel saver logic
Condition and room temperature in auto mode
V POTENTIAL-FREE CONTACTS
1 Mains on
2 Mains in load
3 DG on
4 DG on load
5 DG fails to start
6 DG fails to stop
7 LLOP
8 HWT
9 Low Fuel Level
10 Power plant battery low
11 Room temperature high
12 Smoke/Fire
13 Intruder
14 Air conditioner 1 fail
15 Air conditioner 2 fail
VI ALARM AND LED INDICATION
1 Mains on
2 Mains in load
3 DG on
4 DG on load
5 DG fails to start
6 DG fails to stop
7 LLOP
8 HWT
9 Low Fuel Level
10 Power plant battery low
11 Room temperature high
12 Smoke/Fire
13 Intruder
14 Air conditioner 1 fail
15 Air conditioner 2 fail
16 LCU on load
VII AC DISTRIBUTION BOARD
1 Power plant supply 32A, 3 no.
2 Power plant 16A, 2 no.
3 Air conditioner 16A, 2 no.
4 Lighting 6A, 1 no.
5 Aviation Lamp 6A, 1 no.
6 Battery charger 6A, 1 no.
7 Spares 6A, 3 no.
VIII MISCELLANEOUS ITEMS IN UNIT
1 Surge protection device Class B and Class C Type SPD
2 Smoke Detector Photoelectric type Smoke detector
3 Energy meter Energy meter to Measure the DG Energy
4 Temperature sensor PT 100 Room temperature sensor
5 Door Sensor Magnetic type door sensor
6 Hooter AC Hooter
7 DG battery charger 13.8Volts , 10A
IX DESIGN STANDARDS
1 Conducted Emission CLASS A CISPR 22
2 Radiated Emission CLASS A CISPR 22
3 Electric Fast Transient (EFT) IEC 61000 -4 -4
Electric Static Discharge
4 IEC 61000 -4 -2
(ESD)
3 Surge Immunity IEC 61000 -4 -5
4 R F Conducted Immunity IEC 61000 -4 -6
5 Safty IEC 60950
6 Environment TEC QM-333 B2
All material & workmanship shall be of professional quality to ensure MTBF
7 MTBF
requirement. The MTBF of the IPS shall be more than 100000 hrs.