Development ProNo.

Page
1

Pos.
1

HALFEN - Sandwich Panel Anchor Type SP-SPA Calculation based: - DIBt Zul.Nr. Z-21.8-1926
The printed report was produced with version 4.30.0.0
Position was calculated with version: 4.30.0.0

All data, in particular the static values are for the HALFEN Sandwich panel anchors system.
Load capacities for apparently identical non HALFEN products can deviate significantly;
this can lead to load failure and therefore to damage.
HALFEN GmbH is not liable for damage caused when using third-party products.

Pos. amount.: 1
Comment:

Geometry: (all dimension are in cm)


Centre of gravity in the facing layer S x =254 cm S y =123 cm
(View into the empty formwork)
HALFEN GmbH, Germany Liebigstrae 14 D-40764 Langenfeld - Tel. +49 (0) 21 73 970-0, Telefax: +49 (0)21 73 970-123

500
160 120
175
Sy = 123

User input:
Concrete grade of the facing layer: C30/37 Facing colour: dark Gradient T = 5 K
Thickness of the facing layer: 7.0 cm Specific weight concrete: 25 kN/m
Heat insulation layer thickness: 10.0 cm
Load layer thickness: 12.0 cm Specific weight concrete: 25 kN/m
Length of the facing layer: 500 cm Height of the facing layer: 230 cm Area = 10.06 m
Length of the supporting layer: 500 cm Height supporting layer: 230 cm Area = 10.06 m

Date
29/10/2017
Development ProNo. Page
2

Pos.
1

Loads:
Total weight facing: G k,V = 17.6 kN Load layer weight: G k,T = 30.18 kN
Total weight: G k,V+T = 47.78 kN

Design value (facing) G d,V = 23.77 kN


Additional installation load: F = 0.0 kN
Wind loads: User input
Wind pressure: w d,D = 1.20 kN/m Wind suction w d,S = 1.32 kN/m

Positioning behaviour of the anchors:


Panel rotated: No
Autom. pos. behaviour anchors: 1. Torsion anchor 2. Load bearing anchor

Connector Pin:
Selected pin: 18 x SP-SPA-N-04-220-A4 Order-Id. 0274.020-00004
HALFEN GmbH, Germany Liebigstrae 14 D-40764 Langenfeld - Tel. +49 (0) 21 73 970-0, Telefax: +49 (0)21 73 970-123

The horizontal load action of the pins was determined by the FEM calculation method.
Max. distance of pins: e H 1000 cm
Concrete load capacity Tension: N Rd,Z = 6.6 kN Pressure: : N Rd,D = 4.3 kN

Position and action for the maximum charged pin(s): (Ref. to left lower corner facing)

Torsion anchor:
Selected anchor: 1 x SP-SPA-1-07-220-A4 Order-Id. 0270.010-00006

The horizontal action of the torsion anchor was determined by FEM calculation method.

Embedment depth in facing: min. 50 mm


Embedment depth in the load layer: min. 55 mm
Max. distance intersect. anchors: emax 306 cm

Date
29/10/2017
Development ProNo. Page
3

Pos.
1

Additional reinforcement:
Additional reinforcement B500A, B500B
(r) = placed in facing (s) = placed in load layer

Load bearing anchor r = 2 x 8 x 450 mm s = 2 x 8 x 700 mm


Torsion anchor
r = 1 x 8 x 450 mm s = 1 x 8 x 700 mm

Underlying rules:

SPA Traganker- und Torsionsanker sowie Nadeln und Verbundbgel


Allgemeine bauaufsichtliche Zulassung Nr. Z-21.8-1926 DIBt 2016
Windlasten nach DIN EN 1991-1-4/ NA Deutschland
HALFEN GmbH, Germany Liebigstrae 14 D-40764 Langenfeld - Tel. +49 (0) 21 73 970-0, Telefax: +49 (0)21 73 970-123

Date
29/10/2017
Development ProNo. Page
4

Pos.
1

Explanatory and calculation notes:

Following documents have to be observed: All Technical Information included in the General
certificate of DIBt approval and current valid type testing for anchoring systems.
Additionally, all relevant dimensions and units for building construction have to be observed.

The wind loads must be checked by the responsible engineer.

The embedment depth of all internal components has to be verified!


Only the minimum embedment depths are considered, in the calculation.

Please observe. The panel must not be rotated during transport and during installation,

* Explanation for the verficationtable for the SPA anchor system:


HALFEN GmbH, Germany Liebigstrae 14 D-40764 Langenfeld - Tel. +49 (0) 21 73 970-0, Telefax: +49 (0)21 73 970-123

- Concrete load capacity

V Ed / V' Rd,c 1,0


V' Rd,c => Residual concrete load-bearing capacity,
existing horizontal effects taking into account

V' Rd,c = V Rd,c * ( 1- |N Ed | / N Rd,c ) (in accordance with DIBt approval Z-21.8-1926)

- Steel load capacity

V Ed / V' Rd,s 1,0


V' Rd,s => Residual steel load capacity
existing horizontal effects taking into account

V' Rd,s = V Rd,s - |N Ed,D | (in accordance with DIBt approval Z-21.8-1926)

Date
29/10/2017
Development ProNo. Page
5

Pos.
1

Calculation based: DIBt Zul.Nr. Z-21.8-1926 SPA Ver. 4.30.0.0


Position was calculated with version: 4.30.0.0
Geometry: (all dimension are in cm) View into the empty formwork
Please observe. The panel must not be rotated during transport and during installation,

500
160 120 220

10
HALFEN GmbH, Germany Liebigstrae 14 D-40764 Langenfeld - Tel. +49 (0) 21 73 970-0, Telefax: +49 (0)21 73 970-123

105

230
175
Sy = 123

105
10
10 120 120 120 120 10

Sx = 254

250
130 240 130
124 116

Drawing shows the plate in assembled state

Parts list for the current position:


Load bearing anchor 2 x SP-SPA-2-07-220-A4
Torsion anchor 1 x SP-SPA-1-07-220-A4
Pins 18 x SP-SPA-N-04-220-A4

Date
29/10/2017