Professional Documents
Culture Documents
1- Loss of power
2- Decrease the reliability of system
3- Damage to equipments
4- Maintenance cost to release the
fault reason
5- Loss of renew
What types of faults in power
system?
Insulation failure
Mechanical damage
Generator Protection
Concept
Faults
Damage
Abnormal Operations
Generator
& Abnormal System Conditions
Protection system
Cost :
Protect the unit
- Repair and replacement
Reduce the damage and loss of profit from failures
- Purchasing the replacement power
during the period when unit
is out of service
Generator Protection
Faults Classification
hase
p
to
as e
Ph
Inter-turn short-circuit
Normal operation
IO/P = I1 I2
=0 I2 I1
(Also, external)
Internal faults
IO/P = I1 + I2
>0
Generator Stator Fault Protection
Differential Relaying Practice :
Current transformer
- Same characteristics ( ratio, type and manufacture )
- Not used for any other function => cause unequal secondary loading
For minimizing mismatch errors for external faults. Sufficient to cause a relatively large spill
current flow through the relay operating coil. the difference between the currents is relatively
large to avoid disturbances on network
Generator Stator Fault Protection
Stator Phase Fault Protection
Differential Relaying Characteristic :
ID = |I1 I2| => spill current for relay operation ID
Internal fault
IR = |I1 + I2| => through fault current causing it
2 Operated
During through fault conditions the setting of relay is
increased and relay operation due to spill current is
prevented. External fault
Tripping modes :
- Trip the main generator breaker's)
advantage :
Able to detect ground faults for high impedance grounding machine
Able to detect any phase faults which develop into ground faults
Generator Stator Fault Protection
Stator Ground Fault Protection
64G-1 : 95% stator ground fault protection
85%
V = 0.85 pu 0.85 pu
X = 85% Vx = 0.85 pu
Loading resistor
Generator Stator Fault Protection
Stator Ground Fault Protection
64G-1 : 95% stator ground fault protection
X = 5%
0.05 -1.00 pu
Re Us Re Us
No load
Full load
Generator Stator Fault Protection
Stator Ground Fault Protection
64G-2 : with third harmonic scheme
VT
Operated
Operated
VN
- Measured the ratio of 3rd harmonic voltages between the neutral and terminal
Generator Rotor Field Protection 64F
Rotor Field Protection
Purpose :
Against ground fault on rotor field winding
--
- Use voltage divider and sensitive over voltage relay between the divider midpoint and ground
- Not able to detect ground fault at midpoint of field winding
Generator Rotor Field Protection
Low frequency injection method
Watt
Var
Generator Loss of field 40G
Causes
Field winding part failure
Excitation system part failure
Partial Loss of Field
VAR
Var decreasing
Gen absorbs vars
Power system looses vars
Voltage stability -> Low
Full Loss of Field
VAR
Loss of synchronism
Speed > synchronous speed
Full load -> slip 2-5 %
Light load -> slip 0.1-0.2%
Damage
Coil end
Retaining ring
For normal operation, the high field current corresponding to the overexcited condition keep the retaining ring saturated,
So that end leakage flux is small. However, in the underexcited region the field current is low and retaining ring is not saturated
; this permits an increase in armature end leakage flux , this causes eddy currents in the laminations and results in heating in the
End region.
Damage
(Damage)
Full loss of field
Acts as induction generator, its loss of synchronism ( high speed). The flux from stator windings would induce large eddy current
On any parts of rotor. Resulting in high temperature and extensive damage.
Damage
Concept
Apply the mho relay (distance relay) to monitor the impedance deviation
Protection schemes
Impedance Characteristic
Protection schemes
Trip
62
usually applied to the low Xd (1.0 1.2 per unit) => old machine
If Xd > 1.5 2.0 per unit => Large circle => high sensitive to under-excitation mode
Protection schemes
+DC
Z2 Z1 62
-DC
usually applied to the high Xd (1.5 2.0 per unit up) => modern machine
Generator Abnormal Operating Conditions
24G :Over excitation
- Providing the protection for all type of faults in the generator zone / generator abnormal conditions.
- For system phase backup => two types of relays are commonly used.
- Distance relay
- Time over current relay
- For system ground fault backup =>apply time over current relay at star-point of power transformer
- Setting depends on the co-ordination with other protections.
How to work
SECTION 2
Transformer Protection
Faults In Transformer
Causes of Fault
Core Fault Over Load
Tank Fault System Fault
Over Voltage
Winding to System Frequency
tank Fault Reduced
Faults in Transformer
External Faults (Through Faults)
A very high current pass through the winding due
to Over Load or External Short circuit of
Transformer
Internal Faults
Short Circuit or Fault inside the Transformer
Two kind of faults can be happened
Incipient Fault (Accidental)
Electrical fault Phase Fault , Ground Fault ,
Inter-Turn Fault, etc..
Incipient Fault
This Fault can cause of internal and External Faults,
Its not occur suddenly
The Causes may be from :
100%
Percentage
Primary Secondary Earth Fault Fault Current (If)
Current 80
60
40
Primary
20
Current (Ip)
100%
20 40 60 80
Distance of Fault From Neutral
(Percentage of Winding)
Ground Fault Current for Solid Ground
Fault Current depend on Coil Leakage Reactance ( If )
Leakage Reactance Vary by location of fault
High Fault Current Occur when Fault
100%
Location far from Neutral Poin
Percentage
Earth Fault
Current 80
Fault
60 Current (IF)
40
Primary
20
Current (Ip)
100%
20 40 60 80
Distance of fault Distance of Fault From Neutral
(Percentage of Winding)
Delta Connection (D)
4 25 2
5 20 3
6 16.6 4
7 14.2 5
Over Voltage
Over Voltage at Rated Frequency
Insulation High Stress
Over Flux in Magnetic Core
Core loss increase
Magnetic Core Saturation (Core Overheat)
Insulation Breakdown
Transient Surge Voltage
Temporary Very High Voltage Increasing
(generate from Switching, Lightning)
High Frequency
Very high of Rate of Change of Voltage
(dv/dt)
Cause of Coils to Coils short circuit
Protect by Surge arrestor
System Frequency Reduced
Cause of Over Flux in Magnetic Core
If System Voltage increase and Freq. decrease the Over Flux
will be increased (Over heating in Magnetic Core)
The transformer will be operated in proportion of
Volt / Hz ( Usually about 1.05 to 1.1 p.u.)
Transformer Protection
Overheating
Over Fluxing
Tank-earth Current Detect
Gas Detect
Over Current
Earth Fault
Differential Protection
TRANSFORMER PROTECTION Diagram
SOURCE SOURCE
CT
FUSE 52-1
50/51 51N
CT
49
TRANSFORMER
TRANSFORMER
49
CT R
53
51G
CT 51 51N 87T 86
51
52
52-2
To network and Load
CT
R
Gas Detection Protection
Large Transform immerse in oil
Both External and Internal Fault are cause of oil temp. high
and separate Gas-in-oil
The Gas will be floated and go into the conservator tank and
accumulate until enough pressure to make relay operate
Buchholz Relay used for accumulating of gas
Sudden pressure Relay used for large amount of gas changing
Buchholz Relay
Transformer with Conservator Tank ( more than
1 MVA)
Monitor Gas changing in tank
2 steps operation
Alarm
Trip
Buchholz Relay To Conservator Tank
Alarm
Floating
Blade
Trip
50
Transformer Tank
Over Current Protection Relay
Small size Transformer uses Fuse for Protection
For Larger than 100 KVA. Over Current Relay will
be applied
Over Current Relay should be Coordinated with
other by using Inverse Time delay
Instantaneous Over Current Relay apply for high
short circuit current
Ground Fault Protection
Transformer Star-Connection with Neutral to
Ground
Ground Fault Over Current Relay (50N/51N)
Differential Relay
Protect Transformer short circuit to ground
Higher than 10 MVA
Factor to be Recognized
DIFFERENTIAL Different of Voltage high side and Low side
PROTECTION Different of Vector diagram due to connection
Percent of Current Miss-match
Magnetizing Inrush Current
Basic Concept
I in I out
Equipment
I=0
I in I out
I Relay I
TRANSFORMER DIFFERENTIAL RELAY
I1 I2
I1 I2
87 I1-I2 = 0
TRANSFORMER DIFFERENTIAL RELAY
I1 I2
87 I1-I2 = 0
TRANSFORMER DIFFERENTIAL RELAY
I1 I2
87 I 1I 2 0
due to CT error
TRANSFORMER DIFFERENTIAL RELAY
CT Mismatch
I1 I2
I1 I2
87 I 1I 2 0
TRANSFORMER DIFFERENTIAL RELAY
Change Tap
I1 I2
I1 I2
87 I 1I 2 0
TRANSFORMER DIFFERENTIAL RELAY
I1 I2
I1 I2
87 Wrong Mark
I 1I 2 0
TRANSFORMER DIFFERENTIAL RELAY
I1 I2
I1
87 I 1I 2 0
TRANSFORMER DIFFERENTIAL
RELAY
Sympathetic Inrush
BClosed Closed
C
S A
Closing Open
Transformer tests
1-winding
2-core
3-Bushing
4-insulating oil
5-tanks and auxiliaries
6-Conervator
Winding tests
DC resistance
Turns ratio
Capacitance {winding and oil} [DOBLE test]
Power factor / dissipation factor
Core tests
Insulation resistance
Ground test
Bushing tests
The aim of this test to determine the value of resistance of winding coils to calculate the
amount of losses amount of heat will generate . This done to each coil separately
as shown:
Ammeter
DC Voltage source
R=V/I
Winding tests
Turns ratio
The aim of this test to determine the value of a for the transformer
AC source Voltmeter
a = V source / V mess.
Winding tests
Capacitance
Purpose ::
changes I these values due to transformer ages and
event occurs. Indicate winding deformation and structural problems
such as displaced wedging and winding supports.
Power factor
Winding tests
Purpose ::
to determine the state of the winding s and insulation system and to
determine a power factor for overall insulation including bushing ,oil
and winding.
Insulation resistance Core tests
Insulation resistance ::
This test is done to sure the value of insulation between the ungrounded
limitations of the core and tank [ground]
** the requirement of this test may be needed after oil sample analysis ,some
gases indicate that there was some problems in core
**this done by an DC Megger, connect its two lead between the core and tank
body after remove the grounded limitation .
Healthy transformer should read greater than 1000 Mega ohms
Ground test ::
this test use to ensure the connection of grounded limitation of the core
Dissolved Gas analysis Insulating oil tests