B ELECTRICAL 2,576,377.00
D LIFTS
E PLUMBING 1,828,147.15
F FIRE FIGHTING
1 ALARM SYSTEM
TOTAL COST
2,632,443.95
51,926,304.75
8,406,895.55
10,983,272.55
7,081,500.00
7,081,500.00
6,374,000.00
6,374,000.00
447,028.00
2,275,175.15
579,970.00
579,970.00
801,575.00
801,575.00
80,021,797.45
80,021,798.00
per DSR-2014
CENTRE FOR RAILWAY RESEARCH (CRR) BUILDING NON STRUCTURAL FINISHING WORK
ESTIMATE OF COST
PROPOSED CENTRE FOR RAILWAY RESEARCH (CRR) BUILDING AT IIT KHARAGPUR
1 2 3 4 5
1.1 1.1.2 Carriage of materials by mechanical transport including loading, Cum 153.07
unloading and stacking of earth
upto 5 km
2.25 Filling available excavated earth (excluding rock) in trenches, Cum 112.40
plinth, sides of foundations etc. in layers not exceeding 20cm in
depth, consolidating each deposited layer by ramming and
watering, lead up to 50 m and lift upto 1.5 m.
2.27 Supplying and filling in plinth with Jamuna sand under floors, Cum 910.25
including watering, ramming, consolidating and dressing
complete.
2.31 Clearing jungle including uprooting of rank vegetation, grass, 100 SqM. 642.00
brush wood, trees and saplings of girth upto 30 cm measured at
a height of 1 m above ground leveland removal of rubbish upto
a distance of 50 m outside the periphery of the area cleared.
4.10 Providing and laying damp-proof course 40mm thick with Sq.m. 257.80
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate 12.5mm nominal size).
4.12 Extra for providing and mixing water proofing material in cement 48.15
cement
Per 50
concrete work @ 1Kg per 50 Kg of cement.
kg
4.0 SUB HEAD - IV REINFORCED CEMENT
CONCRETE
5.13 Providing, hoisting and fixing up to floor five level precast Cum 8,797.80
reinforced cement concrete in small lintels not exceeding 1.5m
clear span up to floor five level including the cost of required
centering, shuttering but excluding the cost of reinforcement,
with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size).
5.34.1 Providing M-30 grade concrete instead of M-25 grade Cum 76.50
BMC/RMC. (Note:- Cement content considered in M-30 is @
340 kg/cum).
(extra above 5.33)
5.35 Add for using extra cement in the items of design mix over and quintal 742.75
above the specified cement content therein.
5.38 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for Cum 174.20
each four floors or part thereof.
5.9.3 Suspended floors, roofs, landings, balconies and access Sqm 401.65
platform
5.9.5 Lintels, beams, plinth beams, girders, bressumers and Sqm 332.15
cantilevers.
5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts Sqm 453.35
6.14 Extra for half brick masonry in superstructure, above floor V sqm 25.60
level for every four floors or part thereof by mechanical means.
6.15 Extra for providing and placing in position 2 Nos. 6mm dia MS sqm 69.50
bars at every 3rd course of half brick masonry (with FPS bricks)
6.34 Brick work with non modular fly ash bricks conforming to cum
IS:12894, class designation 10 average compressive strength in
super structure above plinth level up to floor V level in :
6.45 Half brick masonry with non modular fly ash bricks of class
designation 10, conforming to IS : 12894, in super structure
above plinth and upto floor V level.
6.45.2 Cement mortar 1 : 4 (1 cement : 4 coarse sand) sqm 751.10
9.23 Extra for providing lipping with 2nd class teak wood battens 25 sqm 365.85
mm minimum depth on all edges of flush door shutters (over all
area of door shutter to be measured).
9.24 Extra for providing vision panel not exceeding 0.1 sqm in all
type of flush doors (cost of glass excluded) (overall area of door
shutter to be measured)
9.24.1 Rectangular or square sqm 139.40
9.24.2 Circular sqm 226.50
9.53 Providing 40x5 mm flat iron hold fast 40 cm long including fixing Each 117.35
to frame with 10 mm diameter bolts, nuts and wooden plugs and
embedding in cement concrete block 30x10x15cm 1:3:6 mix (1
cement : 3 coarse sand : 6 graded stone aggregate 20mm
nominal size)
9.84 Providing and fixing aluminium extruded section body tubular each 1,043.60
type universal hydraulic door closer (having brand logo with ISI,
IS : 3564, embossed on the body, door weight upto 36 kg to 80
kg and door width from 701 mm to 1000 mm) with double speed
adjustment with necessary accessories and screws etc.
complete.
9.119 Providing and fixing factory made P.V.C. door frame of size Metre 458.95
50x47mm with a wall thickness of 5mm, made out of extruded
5mm rigid PVC foam sheet, mitred at corners and joined with 2
Nos. of 150mm long brackets of 15x15mm M.S. square tube,
the vertical door frame profiles to be reinforced with 19x19mm
M.S. square tube of 19 gauge, EPDM rubber gasket weather
seal to be provided through out the frame. The door frame to be
fixed to the wall using M.S. screws of 65/100mm size, complete
as per manufacturers specification and direction of Engineer-in-
Charge.
Providing and fixing panic bar / latch (Double point) fitted with a
single body, Trim Latch & Lock on back side of the Panic Latch
9.139 each 6,133.20
of reputed brand and manufacture to be approved by the
Engineer- in- charge, all complete
Providing Carben Steel galvanised dash fastner (min 5 micron)
of 10 mm dia double threaded 6.8 grade counter sunk head
2058 nos 36.50
screw comprising of 10 mm dia polyamide PA 6 grade sleave.
Size 10 mm x120 mm
Providing Carben Steel galvanised dash fastner (min 5 micron)
of 10 mm dia double threaded 6.8 grade counter sunk head
2509 nos 46.00
screw comprising of 10 mm dia polyamide PA 6 grade sleave.
Size 10 mm x 140 mm
Providing Carben Steel galvanised dash fastner (min 5 micron)
of 10 mm dia double threaded 6.8 grade counter sunk head
2510 nos 57.00
screw comprising of 10 mm dia polyamide PA 6 grade sleave.
Size 10 mm x 160 mm
10.14 Providing and fixing pressed steel door frames conforming to IS:
4351, manufactured from commercial mild steel sheet of 1.60
mm thickness, including hinges, jamb, lock jamb, bead and if
required angle threshold of mild steel angle of section 50x25
mm, or base ties of 1.60 mm, pressed mild steel welded or
rigidly fixed together by mechanical means, including M.S.
pressed butt hinges 2.5 mm thick with mortar guards, lock strike
plate and shock absorbers as specified and applying a coat of
approved steel primer after pre-treatment of the surface as
directed by Engineerin- charge:
10.14.1 Profile B
10.14.1.1 Fixing with adjustable lugs with split end tail to each jamb metre 377.70
14.34 Providing and fixing 150 mm bright finished floor brass door each 210.75
stopper with rubber cushion, necessary brass screws etc. to suit
shutter thickness complete
10.6.1 80x1.25mm M.S. laths with 1.25 mm thick top cover. Sqm 2,142.10
10.8 Extra for providing mechanical device chain and crank operation
for operating rolling shutters.
10.8.2 Exceeding 16.80 sqm in area Sqm 724.85
10.11 Providing and fixing factory made ISI marked steel glazed
doors, windows and ventilators, side /top /centre hung, with
beading and all members such as F7D, F4B, K11 B and K12 B
etc. complete of standard rolled steel sections, joints mitred and
flash butt welded and sash bars tenoned and riveted, including
providing and fixing of hinges, pivots, including priming coat of
approved steel primer, but excluding the cost of other fittings,
complete all as per approved design, (sectional weight of only
steel members shall be measured for payment).
10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates kg 90.10
and similar works
10.26 Providing and fixing hand rail of approved size by welding etc.
to steel ladder railing, balcony railing, staircase railing and
similar works, including applying priming coat of approved steel
primer.
10.26.1 M.S. tube kg 104.70
to be used in railing
11.4 52 mm thick cement concrete flooring with concrete hardener sqm 535.25
topping, under layer 40 mm thick cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) and top layer 12 mm thick cement hardener
consisting of mix 1:2 (1 cement hardener mix : 2 graded stone
aggregate 6 mm nominal size) by volume, .hardening
compound mixed @ 2 litre per 50kg of cement or as per
manufacturers specifications. This includes cost of cement
slurry, but excluding the cost of nosing of steps etc. complete.
11.8 Extra for making chequers of approved pattern on cement sqm 33.25
concrete floors, steps, landing, pavements etc.
11.25 Extra for Marble stone in treads of steps and risers using single sqm 320.30
length upto 2.0 m metre .
11.26 Kota stone slab flooring over 20 mm (average) thick base laid
over and jointed with grey cement slurry mixed with pigment to
match the shade of the slab including rubbing and polishing
complete with base of cement mortar 1 : 4 (1 cement : 4 coarse
sand) :
11.26.1 25 mm thick. sqm 1,141.40
11.27 Kota stone slabs 25 mm thick in risers of steps, skirting, dado sqm 1,191.25
and pillars laid on 12 mm (average) thick cement mortar 1:3 (1
cement 3 coarse sand) and jointed with grey cement slurry
mixed with pigment to match the shade of the slabs, including
rubbing and polishing complete.
11.31 Extra for pre finished nosing in treads of steps of Kota stone/ metre 75.80
Marble slab.
11.32 Extra for Kota stone in treads of steps and risers using single sqm 16.90
length up to 1.05 metre .
11.36 Providing and fixing Ist quality ceramic glazed wall tiles sqm 836.65
conforming to IS : 15622 (thickness to be specified by the
manufacturer ) of approved make in all colours, shades except
burgundy, bottle green, black of any size as approved by
Engineer-in-Charge, in skirting, risers of steps and dados over
12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse
sand) and jointing with grey cement slurry @ 3.3kg per sqm
including pointing in white cement mixed with pigment of
matching shade complete.
11.39 Providing and laying rectified Glazed Ceramic floor tiles sqm 950.05
300x300 mm or more (thickness to be specified by the
manufacturer) of 1st quality conforming to IS : 15622 of
approved make in colours White, Ivory, Grey, Fume Red Brown,
laid on 20mm thick cement mortar 1:4 (1 Cement : 4 Coarse
sand) including grouting the joints with white cement and
matching pigments etc., complete.
13.11 18mm cement plaster in two coats under layer 12 mm thick sqm 240.55
cement plaster 1:5 (1 cement : 5 coarse sand) finished with a
top layer 6mm thick cement plaster 1:6 (1 cement : 6 fine sand)
13.26 Providing and applying plaster of paris putty of 2 mm thickness sqm 110.95
over plastered surface to prepare the surface even and smooth
complete.
13.40 Distempering with dry distemper of approved brand and sqm 68.60
manufacture (two or more coats) of required shade on new
work, over and including water thinnable priming coat to give an
even shade.
21.8 Filling the gap in between aluminium frame & adjacent RCC/
Brick/ Stone work by providing weather silicon sealant over
backer rod of approved quality as per architectural drawings
and direction of Engineer-in-charge complete.
21.8.1 Upto 5mm depth and 5 mm width mtr 88.75
21.10 Providing and fixing double glazed hermetically sealed glazing sqm 3,487.10
in aluminium windows, ventilators and partition etc. with 6 mm
thick clear float glass both side, having 12 mm air gap, including
providing EPDM gasket,perforated aluminium spacers,
desiccants, sealant (Both primary and secondary sealant) etc.
as per specifications, drawings and direction of Engineer-in-
charge complete.
22.14.1 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded Cum 5,570.55
stone aggregate 20 mm nominal size)
Dismantling old plaster or skirting raking out joints and cleaning Sqm 20.56
15.56 the surface\for plaster including disposal of rubbish to the
dumping ground within 50 metres lead.
Cutting holes up to 15x15 cm in R.C.C. floors and roofs for Each 193.00
passing drainpipe etc. and repairing the hole after insertion of
drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse
18.77 sand : 4 graded stone aggregate 20mm nominal size), including
finishing complete so as to make it leak proof.
2.0 NDSR Providing and fixing S.S. tower bolts required shade with
necessary screws etc. complete:
450x10 mm Each 350.00
300x10 mm Each 260.00
200x10 mm Each 142.50
3.0 NDSR Providing and fixing S.S. handles required shade with
necessary screws etc. complete :
175 mm Each 200.00
125 mm Each 127.50
100 mm Each 97.50
75 mm Each 82.50
4.0 NDSR Providing and fixing S.S. hanging floor door stopper required
shade with necessary screws etc. complete.
Single rubber stopper Each 90.00
Twin rubber stopper Each 142.50
6.0 NDSR Terracotta tile work for wall lining upto 10 m height with special
adhesive over 12 mm thick bed of cement mortar 1:3 (1
cement : 3 coarse sand), including pointing in white cement with
an admixture of pigment to match the stone shade.
7.0 NDSR Extra for tiles work for wall lining on exterior walls of height Sqm 65.85
more than 10 m from ground level for every additional height of
3 m or part there of.
9.0 NDSR Providing and fixing Antistatic flooring 2mm thick on smooth
damp proof base using rubber based adhesive including rolling
with light weighing roller weighing about 5.0Kg all complere as
per the direction of E.I.C.
2.00mm thick sheet sqm 1,800.00
10.0 NDSR 20 mm wide X 400 micron thickness Block Board skirting (150 sqm 200.00
mm thick) including all complere as per the direction of E.I.C.
11.0 NDSR Applying Interior grade Acrylic Primer of approved quality and
brand on plastered or cencrete surface new surface to receive
Distemper/ Acrylic emulsion paint including scraping and
preparing the surface throughly, complete as per manufacturer's
specification and as per direction of the EIC.
One Coat All floor sqm 33.00
12.0 NDSR Suppluing door rubber buffer fitted, fixed and all complete.
75 mm Each 70.00
15.0 NDSR
Providing and installing galvanised mechanical anchors in
concrete with expansion type wedge sleeve for reliable
anchoring for supporting brackets for pipes, cable, handrails,
minor steel work, etc including drilling holes as per
manufacturer's specifications, scaffolding, all tools and tackles,
etc. (Anchor to be HST type of HILTI make or equivalent)
16.0 NDSR Providing cement slurry grouting in desired proportions with Sqm 200.00
grouting pumps, including providing & fixing suitable nozzles all
complete.
18.0 NDSR Extra for Reinforcement. work above floor V level Kg 0.25
17.0 NDSR Extra for Centering and shuttering. work above floor V level Sqm 35.00
18.0 NDSR Uprooting of Existing Tree with their roots, healthy in all respect Nos 5,000.00
and replanting the same by digging hole, providing manure etc.
all complete within the premises as per direction of EIC (200 to
300 mm girth size)
19.0 NDSR Uprooting of Existing Tree with their roots, healthy in all respect Nos 6,000.00
and replanting the same by digging hole, providing manure etc.
all complete within the premises as per direction of EIC (300
mm - 500mm girth size)
20.0 NDSR Extra for Kota stone in treads of steps and risers using single sqm 20.00
length from 1.05m to 1.5m metre .
ESTIMATE OF COST
AILWAY RESEARCH (CRR) BUILDING AT IIT KHARAGPUR
floor)
R ABOVE G+ 4 OF CENTRE FOR RAILWAY RESEARCH
ILDING AT IIT KHARAGPUR
Qnty. Amount
6 7
500.00 76,535.00
177.60 27,634.56
177.60 19,962.24
276.00 251,229.00
5.52 3,543.84
84.70 395,760.75
33.00 8,507.40
8.80 423.72
10.00 87,978.00
1,944.00 132,386.40
144,600.00 9,847,260.00
84.00 528,876.60
790.56 5,545,422.65
750.00 57,375.00
300.00 222,825.00
750.00 130,650.00
300.00 58,935.00
2,365.00 949,902.25
1,927.00 640,053.05
1,515.28 686,952.19
44.00 17,408.60
2,476.00 393,807.80
59.40 292,167.81
50.00 271,307.50
100.00 28,905.00
616.00 270,054.40
262.40 174,705.92
250.00 6,400.00
262.40 18,236.80
990.00 5,946,138.00
1,250.00 938,875.00
155.00 403,999.75
155.00 56,706.75
10.00 1,394.00
1.00 226.50
287.00 33,679.45
120.00 13,494.00
50.00 4,452.50
40.00 2,224.00
36.00 1,188.00
58.00 60,528.80
30.00 2,094.00
15.00 12,231.75
39.11 17,949.53
102.00 280,459.20
65.00 81,253.25
30.00 188,046.00
3.00 82,976.10
10.00 61,332.00
50.00 1,825.00
50.00 2,300.00
50.00 2,850.00
350.30 132,308.31
10.00 2,107.50
10.00 1,090.00
8,500.00 628,575.00
77.00 164,941.70
10.00 7,248.50
220.00 25,113.00
1,305.00 150,205.50
1,000.00 90,100.00
800.00 83,760.00
120.00 463,920.00
10.00 2,305.50
350.00 187,337.50
75.00 28,293.75
350.00 11,637.50
100.00 5,005.00
25.00 8,007.50
526.00 600,376.40
365.50 435,401.88
451.50 34,223.70
27.00 456.30
822.00 687,726.30
150.00 142,507.50
1,000.00 1,405,950.00
250.00 353,850.00
2,622.00 492,804.90
5,654.10 977,028.48
5,000.70 1,202,918.39
2,403.00 323,684.10
166.20 6,880.68
1,116.00 42,352.20
10,439.20 1,158,229.24
10.00 64.50
500.00 8,100.00
150.00 10,290.00
500.00 17,925.00
8,911.40 846,137.43
58.30 1,920.99
431.20 11,642.40
10,439.20 840,355.60
279.20 20,772.48
6,418.00 1,244,771.10
3,493.00 1,217,310.50
1,866.00 757,409.40
10.00 10,542.00
626.00 55,557.50
357.70 1,247,335.67
1,500.00 605,025.00
965.00 377,266.75
100.00 557,055.00
315.00 164,713.50
1,230.00 1,398,387.00
220.00 50,963.00
25.00 32,557.50
50.00 37,705.00
21.00 52,542.00
2,000.00 4,300.00
75.00 4,710.00
50.00 2,892.50
100.00 6,525.00
1,260.00 25,905.60
30.00 5,790.00
50.00 6,540.00
49,293,860.80
58.00 23,055.00
50.00 17,500.00
70.00 18,200.00
48.00 6,840.00
50.00 10,000.00
40.00 5,100.00
24.00 2,340.00
10.00 825.00
20.00 1,800.00
40.00 5,700.00
300.00 439,905.00
250.00 16,462.50
150.00 270,000.00
25.00 5,000.00
10,718.40 353,707.20
58.00 4,060.00
15.00 75,000.00
1.00 300.00
1.00 450.00
1.00 600.00
10.00 2,000.00
188,777.00 47,194.25
4,983.00 174,405.00
50.00 250,000.00
20.00 120,000.00
40.00 800.00
2,632,443.95
51,926,304.75
Code No.
1 1.10.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
FRLSH PVC insulated copper conductor single core cable in surface / recessed
medium class PVC conduit, with modular switch, modular plate, suitable GI box and
earthing the point with 1.5 sq.mm. FRLSH PVC insulated copper conductor single
core cable etc as required.
Group C
02. 1.11 Wiring for twin control light point with 1.5 sq.mm FRLSH PVC insulated copper
conductor single core cable in surface / recessed medium class PVC conduit, 2 way
modular switch, modular plate, suitable GI box and earthing the point with 1.5
sq.mm. FRLSH PVC insulated copper conductor single core cable etc as required.
Group C
03. 1.14 Wiring for circuit/submain wiring alongwith earth wire with the following sizes of
FLRSH PVC insulated copper conductor,single core cable in
surface/recessedmedium class pvc conduit as required
03.1 1.14.1 2x1.5 sq mm + 1 x 1.5 sq mm earth wire
03.2 1.14.2 2x2.5 sq mm + 1 x 2.5 sq mm earth wire
03.3 1.14.3 2x4 sq mm + 1 x 4 sq mm earth wire
03.4 1.14.4 2x6 sq mm + 1 x 6 sq mm earth wire
03.5 1.14.8 4x4 sq mm + 2 x 4 sq mm earth wire
04. Supplying and drawing following pair 0.5 sq mm FRLSH PVC insulated annealed
copper conductor, unarmored telephone cable in the existing surface / recessed
steel / PVC conduit (MMS) as required.
[Considering wiring in pre-laid steel / PVC conduit (MMS)]
04.1 1.18.2 2 Pair
04.2 1.18.3 4 Pair
05. Supplying and fixing of following sizes of medium class (MMS) PVC conduit along
with accessories in surface / recess including cutting the wall and making good the
same in case of recessed conduit as required.
05.1 1.21.1 20 mm
05.2 1.21.2 25 mm
05.3 1.21.3 32 mm
05.4 1.21.4 40 mm
06. Supplying and fixing metal box of following sizes (nominal size) on surface or in
recess with suitable size of phenolic laminated sheet cover in front including painting
etc as required. (As junction box / pull box)
06.1 1.22.1 75 mm X 75 mm X 60 mm deep
06.2 1.22.2 100 mm X 100 mm X 60 mm deep
06.3 1.22.3 150 mm X 75 mm X 60 mm deep
06.4 1.22.4 150 mm X 150 mm X 60 mm deep
06.5 1.22.5 180 mm X 100 mm X 60 mm deep
06.6 1.22.7 200 mm X 150 mm X 60 mm deep
06.7 1.22.9 200 mm X 250 mm X 60 mm deep
06.8 1.22.13 200 mm X 300 mm X 60 mm deep
06.9 1.22.15 250 mm X 300 mm X 60 mm deep
07. Supplying and fixing following modular switch / socket on the existing modular plate
& switch box including connections but excluding modular plate etc. as required.
8 1.25 Supplying and fixing stepped type electronic fan regulator on the existing modular
plate switch box including connections but excluding modular plate etc. as required.
9 1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch
box excluding modular plate as required.
10 Supplying and fixing following size / modules, GI box along with modular base &
cover plate for modular switches in recess etc as required.
10.1 1.27.1 1 or 2 Module (75mm X 75mm)
10.2 1.27.2 3 Module (100mm X 75mm)
10.3 1.27.3 4 Module (100mm X 75mm)
10.4 1.27.4 6 Module (200mm X 75mm)
10.5 1.27.5 8 Module (125mm X 125mm)
10.6 1.27.6 12 Module (200mm X 150mm)
11 1.33 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden
block including connection etc as required.
12 1.34 Supplying and fixing brass batten / angle holder including connection etc. as
required.
13 1.35 Erection of wall bracket / ceiling fittings of all sizes and shapes containing upto two
CFL lamps per fitting, complete with all accessories including connection etc. as
required.
15 1.45 Installation, testing and commissioning of ceiling fan, including wiring the down rods
of standard length (upto 30 cm) with 1.5 sq.mm FRLSH PVC insulated, copper
conductor, single core cable, including providing and fixing phenolic laminated sheet
cover on the fan box etc. as required.
16 1.46 Installation, testing and commissioning of electorinic fan regulator, in existing switch
box including connection with 1.5 sq. mm FRLSH PVC insulated, copper conductor,
single core cable, earthing the regulator etc. as required.
17 1.47 Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy
gauge including painting etc. as required. (Note : More than 5 cm length shall be
rounded to the nearest 10 cm and 5 cm or less shall be ignored).
18 1.48 Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia,
heavy gauge including painting etc. as required. (Note : More than 5 cm length shall
be rounded to the nearest 10 cm and 5 cm or less shall be ignored).
22 Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board (IP43), 240 volts, on surface / recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. ( But without MCB / RCCB / Isolator ).
23 Supplying and fixing following way, horizontal type three pole and neutral, sheet
steel, MCB distribution board (IP43), 415 volts, on surface / recess, complete with
tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder
painted including earthing etc. as required. ( But without MCB / RCCB / Isolator ).
24 Supplying and fixing of following ways surface / recess mounting, vertical type, 415
volts, TPN MCB distribution board of sheet steel (IP43), dust protected, duly powder
painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth
bar, din bar for mounting MCB's ( but without MCB's and incomer ) as required.
25 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB DB
complete with connections, testing and commissioning etc. as required.
25.1 2.10.1 Single pole
25.2 2.10.3 Double pole
25.3 2.10.4 Triple pole
25.4 2.10.5 Tripple pole & neutral
26 2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc.
as required.
27 2.21 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild
steel, at least 2 mm thick, and vitreous enameled white on both sides, and with
inscription in single red colour on front side as required.
28 5.90 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip
earth electrode, including connection / terminating with G.I. nut, bolt, spring, washer
etc. as required. (Jointing with anti corrosive paint shall be done by welding only
after 4" overlapping of the strips etc.)
29 5.11 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth
electrode including connection with G.I. nut, bolt, spring, washer excavation and re-
filling etc. as required.
30 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections
etc. as required.
31 7.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1
KV grade of following size direct in ground including excavation, sand cushioning,
protective covering and refilling the trench etc as required.
7.1.4 Above 185 sq. mm and upto 400 sq. mm
32 7.2 Laying of one number additional PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size direct in ground in the same trench in one tier
horizontal formation including excavation, sand cushioning, protective covering and
refilling the trench etc as required.
7.2.4 Above 185 sq. mm and upto 400 sq. mm
33 7.5 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1
KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
34 7.6 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1
KV grade of following size in the existing masonry open duct as required.
7.6.4 Above 185 sq. mm and upto 400 sq. mm
35 7.6 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size on wall surface as required.
7.6.4 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
36 8.1 Laying of one number PVC insulated and PVC sheathed / XLPE H.T 3core, power
cable of 11 KV grade of following size direct in ground (in any type of soil) below
1000 mm from ground level 460 mm wide on 6 mm thick sand cushioning including
transportation of cable to site excavation, protection with bricks @ 16 bricks per
meter in a box form, refilling with sand between bricks and cables and then back
filling the trench with shifted soil, leveling up and restoring surface duly rammed etc
as required.
39 10.5 Supplying and making outdoor cable end termination with heat shrinkable jointing kit
complete with all accessories including lugs suitable for following size of 3 core,
XLPE aluminium conductor cable of 11 KV grade as required :
10.5.2 120 sq. mm
40 10.6 Supplying and making straight through cable jointing with heat shrinkable jointing kit
complete with all accessories including ferrules suitable for following size of 3 core,
XLPE aluminium conductor cable of 11 KV grade as required :
10.6.2 120 sq. mm
1 Non- Supplying and fixing of 240/415 V MCB type under voltage release (UVR) on din rail
CPWD/DSR of existing DB / enclosure and necessary connection.
Undervoltage release, 230V AC, 1 module (MZ206)
5 Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C" curve, miniature
Non- circuit breaker suitable for inductive load of following poles in the existing MCB DB
CPWD/DSR complete with connections, testing and commissioning etc. as required.
7 Supplying and fixing following way, single pole and neutral, sheet steel, MCB
Non- distribution board, 240 volts, IP : 43, on surface/ recess, complete with tinned
CPWD/DSR copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. ( But without MCB / RCCB / Isolator ).
8 Supplying and fixing of following ways surface / recess mounting, vertical type, 415
volts, IP : 43, TPN MCB distribution board of sheet steel, dust protected, duly
Non- powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link,
CPWD/DSR earth bar, din bar for mounting MCB's ( but without MCB's and incomer ) as
required.
6 way (12 + 18), Double door
9 Supplying and fixing following ways surface / recess mounting, vertical type, 415
volts, IP : 43, TPN MCCB distribution board of sheet steel, dust protected, duly
Non- powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link,
CPWD/DSR earth bar, din bar for mounting MCB's, with provision of 160 amps FP 25 KA MCCB
as incomer, interconnection between incomer MCCB and bus bars (but without
MCB's / MCCB) as required.
10 Non- Supplying and fixing surge protection device, type-III, 8 kA complete with
CPWD/DSR connections, testing and commissioning etc. as required.
10.1 Double pole
10.2 Four pole
11 Fixing decorative light fitting on ceiling using of 2 nos. wooden round blocks &
Non- ceiling rose for making connection complete, testing and commissioning etc. as
CPWD/DSR required.
The flush mounted pin type hinged construction panel door shall be interlocked with
switchgear such that no door can be opened when the switch is in ON position. The
switchgear shall have mechanical arrangement for interlock defeat. The doors shall
have neoprene gasket of not less than 3mm. thickness and shall have copper braid
connection for effective earthing. The covers of bus bar chamber shall be of bolted
type.
The panel shall be totally enclosed, dust and vermin proof, duly painted by either 2
coats of synthetic enamel final paint shall be made over 2 coats of zinc / red oxide
primer or the finished paint shall be stove enameled / powder coated, opaline green
( colour no. 275 of 13:5 ) for external surface & light dove grey / broken white / off-
white / any other colour ( should be approved by Engineer-in-Charge ) for interior
surface after rinsing & providing anti corrosion coats after final paint. All sheet metal
part of the panel should be thoroughly degreased, de-rusted & hot dip phosphatised
before primer is applied.
The design of panel shall be such as to offer maximum safety, ease of maintenance
& replacements. The busbar shall be of high conductivity aluminum alloy electrolytic
grade copper strips. The support for the busbar shall be made by means of non
hygroscopic, non inflammable, epoxy, cast resin insulators, high tensile nuts & bolts
spring washers etc. so that the supports shall be able to withstand thermal &
dynamic stresses due to the system short circuits. All the live parts shall be properly
shrouded with Bakelite barriers. The minimum clearance between live parts, neutral
and earth shall be at least 25mm. The colour coding shall be made with heat
shrinkable PVC sleeves. Arrangement & fixing of bus bars, internal connections etc.
shall be in accordance with IS 375 or its latest version.
The cable termination shall be from bottom for incomer and from top for outgoing
feeders. The detachable gland plates of adequate thickness shall be provided for
cable terminations. Feeder nameplates shall be provided.
Thickness of sheet shall not be less than 1.8mm. upto 600mm. length / width of any
compartment and be of 2mm. above 600mm. Load bearing structure shall be of
2mm. thick sheet supported by base M.S. channel if required.
Side walls & cable alley compartments having bolted type doors with detachable
extension type structure.
All incoming & outgoing feeders of the panel should have individual name inscription
plate(s) giving description(s) of the feeder(s) with 25mm. high letters for identification
of panel & 6mm. high letters for incoming or outgoing feeder(s).
It will be the contractors responsibility to get the fabrication arrangement drawing /
general arrangement drawing approved by Client / Engineer before installation.
ACCL units to be consider for panel lighting/to be attach rate analysis for panel
Main Section
Incoming
1 no. 63A, 10 KA, TP MCB
1 no. ( 0 - 60 )A range Ammeter with 60 / 5A CT and selector switch.
1 no. ( 0 - 500 )V range voltmeter with protective MCBs and selector switch .
1 set of phase indicating lamps with protective MCBs.
Busbar
1 set of 100 (20x10) Amps Al conductor, 3-phase, 4-wire Bus Bar
Outgoing
2 nos. 32A, 10 KA, TP MCB
1 no. 32A, 10 KA, SP MCB
Sub Section
Incoming
1 no. 32A, 10 KA, FP MCB
1 no. 415 Volts, 40/40A, FP, Automatic change over cum current limiter.
1 no. ( 0 - 500 )V range voltmeter with protective fuses and selector switch .
1 set of indicating lamps with protective fuse.
Busbar
1 set of 100 (20x10) Amps Al conductor, 3-phase, 4-wire Bus Bar
Outgoing
1 no. 32A, 10 KA, DP MCB
3 nos. 25A, 10 KA, DP MCB
1 no. 20A, 10 KA, DP MCB
Incoming
1 no.250A, 35 KA, FP, MCCB, With MP based release, extended rotary handle,
spreader links, ON-OFF, Trip indications etc. as required.
1 no. ( 0 - 250 )A range Ammeter with 250 / 5A CT and selector switch.
1 no. ( 0 - 500 )V range voltmeter with protective MCBs and selector switch .
1 set of phase indicating lamps with protective MCBs.
Busbar
1 set of 300 (30x10) Amps Al conductor, 3-phase, 4-wire Bus Bar
Outgoing
5 nos. 63A, 10 KA, TP, MCB.
15 Providing and fixing following rating and breaking capacity MCCB with extended
Non- rotary handle, spreader links, ON-OFF, Trip indications etc. as required to fix in
CPWD/DSR existing cubicle panel board including drilling holes in cubicle panel, making
connections, etc. as required.
15.1 100 Amp, 25 KA
15.2 125 Amp, 25 KA
15.3 160 Amp, 25 KA
15.4 200 Amp, 25 KA (MP & E/F)
15.5 250 Amp, 35 KA (MP & E/F)
15.6 400 Amp, 35 KA (MP & E/F)
15.7 630 Amp, 35 KA (MP & E/F)
16 Providing of L.T. cable working voltage 1.1 KV grade, heavy duty XLPE insulated,
Non- armoured, screened, stranded, Al distribution power conductor cable (A2XFY),
CPWD/DSR conforming to IS : 7098 ( Part - I ) / 1554 ( Part - I ) of following size in the existing
RCC/ HUME/ METAL pipe or existing cable tray as required.
16.1 3.5C, 25 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16.2 4C, 10 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16.3 2C, 10 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16.4 2C, 6 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16a Laying of L.T. cable working voltage 1.1 KV grade, heavy duty XLPE insulated,
armoured, screened, stranded, Al distribution power conductor cable (A2XFY),
conforming to IS : 7098 ( Part - I ) / 1554 ( Part - I ) of following size in the existing
RCC/ HUME/ METAL pipe or existing cable tray as required.
16a.1 3.5C, 25 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16a.2 4C, 10 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16a.3 2C, 10 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
16a.4 2C, 6 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
17 Supply of L.T. cable working voltage 1.1 KV grade, heavy duty XLPE insulated,
Non- armoured, screened, stranded, Al distribution power conductor cable (A2XFY),
CPWD/DSR conforming to IS : 7098 ( Part - I ) / 1554 ( Part - I ) of following size on wall
surface with supply & fixing of saddle & clamps etc. as required.
17.1 3.5C, 300 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY.
17.2 3.5C, 25 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
17.3 4C, 6 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
17a Laying of L.T. cable working voltage 1.1 KV grade, heavy duty XLPE insulated,
armoured, screened, stranded, Al distribution power conductor cable (A2XFY),
conforming to IS : 7098 ( Part - I ) / 1554 ( Part - I ) of following size on wall
surface with supply & fixing of saddle & clamps etc. as required.
17a.1 3.5C, 300 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY.
17a.2 3.5C, 25 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
17a.3 4C, 6 sqmm. 1.1 KV grade, heavy duty XLPE insulated, armoured, screened,
stranded, Al distribution power conductor cable (A2XFY
18 Supplying and fixing of double compression type brass cable gland along with
rubber rings for dust and moisture proof entry of following rating 1.1 KV grade XLPE
Non- aluminium conductor cable and finishing the end by crimping method including
CPWD/DSR supply and fixing of Dowell make solderless socket, tapes and jointing materials as
required to be completed in all respect.
18.1 3.5C, 300 sqmm. with termination making connections, etc. as required.
18.2 3.5C, 25 sqmm. with termination making connections, etc. as required.
18.3 4C, 10 sqmm. with termination making connections, etc. as required.
18.4 4C, 6 sqmm. with termination making connections, etc. as required.
18.5 2C, 10 sqmm. with termination making connections, etc. as required.
18.6 2C, 6 sqmm. with termination making connections, etc. as required.
19 Supply of folowing light fittings / lamps
19.1 Similar to Siska Cat No. : TL - 22W - F / Similar to Wipro Cat No. : WIO80-1208,
Non- Coral LED with suitable 20W ProLED, indoor decorative channel housing compared
CPWD/DSR with FTL (T8) as required to complete set.(Regal butten-Havells 22 watt)
19.2 Similar to Siska Cat No. : SLFL250 44W 5700K (22w X 2 Led fixture 44W) / Similar
to Wipro Cat No. : WCO12-2208, WCO 12 with suitable 2x20W ProLED, industrial
Non- channel housing compared with FTL (T8) as required to complete set.
CPWD/DSR (Similar to Hevells-Regal butten-Havells 2x22 watt)
19.3 Similar to Siska Cat No. : SSK-PL 10 W - 5.7 K / 4K or, Similar to Wipro Cat No. :
Non- LW02-101-XXX-60-XX, Moon LED SQ with suitable 13W LED, wall / true ceiling
CPWD/DSR mounted square light compared with CFL (23/28W) as required to complete set.
(Similar to Hevells-Endura DL surface 15W)
19.4 Similar to Siska Cat No. : SSK - ML - 02 [Led Moisture proof Light 22 W X 2 (Tube
Light)] / Similar to Wipro Cat No. : CRCO13S038HP57, Aura Plus with suitable 38W
Non- LED, indoor surface mounted with PMMA diffuser compared with Twin FTL (2xT8)
CPWD/DSR as required to complete set.(Similar to Hevells-Pluto 36 watt)
19.5 CFL Bulkhead light Similar to Wipro Cat No. : WKP 14109, 1x9W CFL (TC-S).
(Similar to Hevells-Rugby)/3PIN THREDEAD TYPE
19.6 28W CFL of Philips make
19.7 18W CFL of Philips make
19.8 11W CFL of Philips make
19.9 equivalet Havell's make model from the syska &wipro
The enclosure shall be fabricated from 1.6 mm thick ( min. ) electro galvanised steel
sheet, non-ventilated, naturally cooled, totally enclosed protected from any
mechanical damages & dust accumulation. All necessary hardware shall be supplied
along with it. Under normal operating conditions, the temperature rise should not
exceed 55C above an ambient of 40C. Earth strip of min. 25 mm x 6 mm GI on
each side of bus riser shall run continuously all along the system inside. All flanges
shall be suitably jumpered to provide earth continuity.
The flanged end box made of 2mm thick ( min. ) with powder coating and the size of
the holes shall match with the equipment where bus duct will be terminated. There
shall have a MCCB unit of approved make within the flange end box for a better
protection & ease of maintenance.
A maximum three / four units of plug-in holes shall be designed in 3000mm standard
feeder unit on both sides and each plug-in hole shall have 500mm intervals ( min. ).
Plug-in holes should be well designed to prevent improper installation of plug-in box.
The tap off boxes shall be made out of 1.8 mm ( min. ) sheet with lockable door
latch arrangement and suitable for fixing MCB / MCCB / SDF etc. The tap-off-box
should be mechanically locked with the housing.
The entire system consists of required length of straight feeders; wall mounted
flange end box with required flanges, on wall fixing bracket; one no. each of spring
suspension hanger & suspension bracket with proper spacer unit at each floor;
required no. of tap-off-box(es) & all other fixing materials as required in all respect.
The complete system of bus riser is required for following rating, inclusive of all as
specified above & all taxes, transportation charges etc. The tap off outlets are with
finger proof safety block to prevent access to live bus bars when not in use.
22 Supply & Installation of Electro zinc Galvanised Wiremesh cable Tray in accordance
with standard BSEN 12329-2000 with all mounting accessories. All trays should be
3005mm long. Cable tray shall be manufactured from steel wires, welded together
and bent into final shape prior to surface treatment. Steel Wire Cable Tray should be
Non-
produced from lateral and longitudinal sidewall steel wires, with minimum diameters
CPWD/DSR
between 3.7 mm to 5.9 mm for trays depending on the widths of the trays as per the
design parameters. The tray shall be mounted on wall / from ceiling as per site
condition.
Trays should be manufactured with a longitudinal T-welded safety edge along the
top wire of the sidewall. Trays should be constructed with a 50mm x 100mm mesh
configuration. Trays should be coupled together using fast spring coupler. The
coupling will have the same surface finish as the tray. Loading and deflection
characteristics of the tray should be tested and the results published in accordance
with the European Standard IEC 61537. Fire test certification should be published in
accordance with the E30/E90 standard. Electrical continuity across a coupling
should be demonstrated by means of a published test method and result.
24
25
Supply and laying of GI flats 25 mm x 6 mm using spacer saddles with all GI fixing
materials required when laid inside the building and trench and inclusive the
excavation and refilling the earth with brick protection on top when laid in ground.
Using welding for all joints, anti rust paints at joints and terminations and
connection complete with feeder pillars, service DBs, earth stations inclusive of
supply and fixing of all hardware.
26
Supply and laying of GI flats 50 mm x 6 mm using spacer saddles with all GI fixing
materials required when laid inside the building and trench and inclusive the
excavation and refilling the earth with brick protection on top when laid in ground.
Using welding for all joints, anti rust paints at joints and terminations and
connection complete with feeder pillars, service DBs, earth stations inclusive of
supply and fixing of all hardware.
ESE
27a Supply and laying of 25mm dia 2mm thick PVC conduit concealed in
wall/ceiling/floor including all accessories such as junction boxes conduit bends etc
completed as required for Telephones/Lan etc
27b Supply and fixing of Telephone outlet (RJ11)with anodised GI box of approved
make with front plate and plug in type telephone socket with top.
27c Supply and laying of 2pair 0.5mm dia PVC insulated copper conductor Telephone
wire conforming to IS and as approved by Engineer-In-Charge
27d Supply and installation of following size Krone connections in MS powder coated
box complete as required
i 10 Pair
ii 20 Pair
iii 50 Pair
L WORK
0 Metre 45.00 -
0 Each 8,185.00 -
2,576,377.00
1 No. 1,260.00
1,260.00
0 Each 9,565.00 -
0 Each 10,500.00 -
0 Each 13,925.00 -
0 Each 130.00 -
3 Each 110,000.00 330,000.00
0 Each 4,960.00 -
0 Each 6,050.00 -
0 Each 7,460.00 -
0 Each 8,990.00 -
0 Each 19,550.00 -
0 Each 80,000.00 -
0 Each 80,000.00 -
470 Metre 253.61 119,196.70
0 Set 20,701.20 -
2 Set 31,980.00 63,960.00
1 Set 27,105.00 27,105.00
16.00 SET
8,500.00 136,000.00
50 mts.
310.00 15,500.00
250 mts.
590.00 147,500.00
8,406,895.55
10,983,272.55
EXTENSION OF THREE FLOOR ABOVE G+ 4 OF CENTRE FOR RAILWAY RESEARCH
BUILDING AT IIT KHARAGPUR
BILL OF QUANTITY FOR SUBSTATION SHIFTING & CABLES
Rate
Sl.N Description of Items Quantity Unit
( Rs. )
1 no. 630A, 50 KA, FP, MCCB, With E/F & MP based release.
1 no. ( 0 - 600 )A range Ammeter with 600 / 5A CT and selector switch.
1 no. 630A, 50 KA, FP, MCCB, With E/F & MP based release.
1 no. ( 0 - 600 )A range Ammeter with 600 / 5A CT and selector switch.
1 no. 400A, 50 KA, FP, MCCB, With E/F & MP based release.
1 no. ( 0 - 400 )A range Ammeter with 400 / 5A CT and selector switch.
1 no. 630A, 50 KA, FP, MCCB, With E/F & MP based release.
1 no. ( 0 - 600 )A range Ammeter with 600 / 5A CT and selector switch.
1 no. 400A, 50 KA, FP, MCCB, With E/F & MP based release.
1 no. ( 0 - 400 )A range Ammeter with 400 / 5A CT and selector switch.
36,000.00
50,000.00
2,883,000.00
3,367,500.00
220,000.00
110,000.00
165,000.00
165,000.00
20,000.00
5,000.00
60,000.00
7,081,500.00
EXTENSION OF THREE FLOOR ABOVE G+ 4 OF CENTRE FOR RAILWAY RESEARCH
BUILDING AT IIT KHARAGPUR
BILL OF QUANTITY FOR LIFT
Serial
Description of Items Quantity Unit
Number
D LIFTS
RAILWAY RESEARCH
2,889,000.00 2,889,000.00
3,485,000.00 3,485,000.00
6,374,000.00
CENTRE FOR RAILWAY RESEARCH (CRR) BUILDING SANITARY PLUMBING WORKS
I. SANITARY FIXTURES
1 17.78 Providing and fixing white vitreous china extended wall mounting water closet of size
780x370x690 mm of approved shape including providing & fixing white vitreous china
cistern with dual flush fitting, of flushing capacity 3 litre/6 litre (adjustable to 4 litre/8
litres), including 'seat cover, and cistern fittings, nuts, bolts and gasket etc complete.
Each 21 10,100.90
2 17.3 Providing and fixing white vitreous china pedestal type water closet '(European type)
with seat and lid, 10 litre low level white vitreous 'china flushing cistern & C.P. flush
bend with fittings & C.I.brackets, '40 mm flush bend, overflow arrangement with
specials of standard 'make and mosquito proof coupling of approved municipal design
'complete, including painting of fittings and brackets, cutting and making good the walls
and floors wherever required :
17.3.1 W.C. pan with ISI marked black solid plastic seat and lid Each 2 4,784.60
4 17.7 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm
C.P. brass waste of standard pattern, including 'painting of fittings and brackets, cutting
and making good the walls wherever require :
17.7.1 White Vitreous China Wash basin size 630x450 mm with 'a pair 15 mm C.P. brass pillar
tap
Each 21 2,331.15
5 17.10 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS
13983 with C.I. brackets and stainless steel plug 40 mm including painting of
fittings and brackets, cutting and making good the walls wherever required :
6 17.31 Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved
quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P.
brass screws and washers complete.
Each 21 793.95
8 17.73 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with
CP brass screws with concealed fittings arrangement of approved quality and colour.
a) 17.73.2 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of
88 mm, weighing not less than 190 gms
Each 21 541.50
9 18.49 Providing and fixing C.P. brass bib cock of approved quality conforming to
IS:8931
a) 18.49.1 15 mm nominal bore. Each 25 459.50
10 18.51 Providing and fixing C.P. brass long body bib cock of approved quality
conforming to IS standards and weighing not less than 690 gms.
a) 18.51.1 15 mm nominal bore. Each 25 610.65
11 18.52 Providing and fixing C.P. brass stop cock (concealed) of standard design and
of approved make conforming to IS:8931.
a) 18.52.1 15 mm nominal bore. Each 25 619.75
12 18.53 Providing and fixing C.P. brass angle valve for basin mixer and geyser points
of approved quality conforming to IS:8931
a) 18.53.1 15 mm nominal bore. Each 51 507.70
13 18.18 Providing and fixing ball valve (brass) of approved quality, High or low pressure, with
plastic floats complete :
a) 18.18.3 25 mm nominal bore Each 20 449.95
14 17.71 Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112
mm distance from wall of standard shape with bracket of the same materials with snap
fittings of approved quality and colour, weighing not less than 105 gms.
Each 21 228.85
15 18.21 Providing and fixing uplasticised PVC connection pipe with brass unions :
18.21.2 45 cm length
18.21.2.1 15 mm nominal bore Each 65 68.60
TOTAL
17 17.36 Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 ( 1
cement : 2 fine sand) in S.C.I./ C.I. Pipes :
a) 17.36.1 75 mm dia pipe Each 60 65.70
b) 17.36.2 100 mm dia pipe Each 60 77.40
18 17.37 Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast
iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of
1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size),
including cost of cutting holes and making good the walls etc. :
19 17.38 Providing and fixing bend of required degree with access door, insertion rubber washer
3 mm thick, bolts and nuts complete.
a) 17.38.1 100 mm
i) 17.38.1.2 Sand cast iron S&S pipe as per IS: 3989 Each 50 385.70
b) 17.38.2 75 mm
i) 17.38.2.2 Sand cast iron S&S pipe as per IS: 3989 Each 60 318.50
21 17.43 Providing and fixing single equal plain junction of required degree with access door,
insertion rubber washer 3 mm thick, bolts and nuts complete.
a) 17.43.1 100 x 100 x 100 mm
i) 17.43.1.2 Sand cast iron S&S as per IS - 3989 Each 15 623.80
22 17.44 Providing and fixing single equal plain junction of required degree :
a) 17.44.1 100 x 100 x 100 mm
i) 17.44.1.2 Sand cast iron S&S as per IS - 3989 Each 15 576.20
23 17.54 Providing and fixing sand cast iron S&S off sets as per IS: 3989
a) 17.54.3 152 mm off sets
i) 17.54.2 With 100 mm dia. Pipe Each 4 486.30
24 17.60 Providing and fixing trap of self cleansing design with screwed down or hinged grating
with or without vent arm complete, including cost of cutting and making good the walls
and floors:
25 17.65 Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent pipes and fittings
with paint of any colour such as chocolate grey, or buff etc. over a coat of primer (of
approved quality) for new work :
26 17.50 Providing and fixing single equal plain invert branch of required degree:
a) 17.50.1 100x100x100 mm
i) 17.50.1.2 Sand cast iron S&S pipe as per IS: 3989 Each 6 521.60
27 17.70 Providing and fixing PTMT Bottle Trap for Wash basin and sink.
a) 17.70.2 Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail
pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm
minimum water seal, weighing not less than 263 gms
Each 30 518.15
28 17.52 Providing and fixing single unequal plain invert branch of required degree :
17.52.1 100x100x75 mm
17.52.1.2 Sand cast iron S&S as per IS - 3989 Each 6 660.95
29 18.58 Providing and fixing PTMT grating of approved quality and colour.
18.58.1 Circular type
18.58.1.1 100 mm nominal dia Each 35 49.25
30 18.59 Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts,
rubber insertions etc. complete (The tail pieces, tapers etc if required will be paid
separately) :
18.59.2 80 mm dia Each 1 6,172.10
31 18.65
Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm,
height of 75mm with concealed fitting arrangements, weighing not less than 106 gms.
Each 30 164.95
TOTAL
32 18.7 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, 'having thermal
stability for hot & cold water supply, including all 'CPVC plain & brass threaded fittings,
including fixing the pipe with 'clamps at 1.00 m spacing. This includes jointing of pipes
& fittings 'with one step CPVC solvent cement and testing of joints complete 'as per
direction of Engineer in Charge.
33 18.8 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal
stability for hot & cold water supply, including all CPVC plain & brass threaded fittings,
i/c at 1.00 m spacing. This includes jointing of pipes & fittings with onefixing the pipe
with clamps step CPVC solvent cement and the cost of cutting chases and making
good the of same including testing of joints complete as per direction Engineer in
Charge.
Concealed work, including cutting chases and making good the walls etc.
34 18.9 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, 'having thermal
stability for hot & cold water supply including all CPVC 'plain & brass threaded fittings
This includes jointing of pipes & fittings 'with one step CPVC solvent cement
,trenching ,refilling & testing of 'joints complete as per direction of Engineer in Charge.
External work
a) 18.9.6 50 mm nominal outer dia Pipes Metre 1 524.10
35 18.19 Providing and fixing gun metal non- return valve of approved quality (screwed end) :
36 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank,
ISI : 12701 marked, with cover and suitable locking arrangement and making
necessary holes for inlet, outlet and overflow pipes but without fittings and the base
support for tank.
per litre 28000 7.25
TOTAL
37 2.10 Excavation of trenches of required width upto 1.5m depth for pipes, including
excavation for sockets, and dressing of sides, ramming of bottoms, including getting
out the excavated soil, and then returning soil as required, in layers not exceeding
20cm depth including consolidating each deposited layer by ramming, watering etc.
and disposing of surplus excavated soil as directed outside the site to the approved
dumping ground. Minimum width of the trench should be external dia plus 400mm.
38 19.1 Providing, laying and jointing glazed stoneware pipes grade A with stiff mixture of
cement mortar in the proportion of 1:1 (1 cement: 1 fine sand) including testing of joints
etc. complete.
39 19.3 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded
stone aggregate 40 mm nominal size) up to haunches of S.W. pipes including bed
concrete as per standard design :
40 19.4 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating
brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size
(inside) the weight of cover to be not less than 4.50 kg and frame to be not less than
2.70 kg as per standard design :
41 19.30 Constructing brick masonry chamber for underground C.I. inspection chamber and
bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with
frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to
be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top
slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone
aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3
(1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on
walls and bed concrete etc. complete as per standard design :
a) 19.30.1 Inside dimensions 455x610 mm and 45 cm deep for single pipe line :
i) 19.30.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 30 4,692.05
b) 19.30.2 Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets :
i) 19.30.2.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 30 5,375.20
43 19.27 Constructing brick masonary road gully chamber 50x45x60cm with bricks of class
designation 75 in cement morter 1:4 (1 cement : 4 coarse sand) including 500x450mm
precast RCC horizontal grating complete as per standard design
44 19.32 Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb
shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per
standard design.
19.32.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 0 18,309.50
45 19.6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars
jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine
sand) including testing of joints etc. complete :
V NON SCHEDULE
1 Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350
mm 'with fittings, standard size C.P. brass flush pipe, spreaders with 'unions and
clamps (all in C.P. brass) with waste fitting as per IS : '2556, C.I. trap with outlet grating
and other couplings in C.P. brass, including painting of fittings and cutting and making Each 15 5,800.00
good the walls 'and floors wherever required :
2 Reciving, handling and fixing of white vitreous china standard urinal partition of size
618 x 310mm with C.P. brass screws and washer fixed to Rawlplugs complete.
Each 15 1,459.00
3 Supplying, fitting & fixing approved patent vent cowl I.C.I. conforming to I.S.S and
painting two coats to the exposed surface with approved paint complete. (Payment of
Painting will however be paid seperately).
4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, 'having thermal
stability for hot & cold water supply, including all 'CPVC plain & brass threaded fittings,
including fixing the pipe with 'clamps at 1.00 m spacing. This includes jointing of pipes
& fittings 'with one step CPVC solvent cement and testing of joints complete 'as per
direction of Engineer in Charge.
5 Providing and fixing C.I butterfly valve, wafer end type class PN 1.6 as per I.S:13095 or
BS:5155, including necessary nuts, bolts, gaskets etc., complete (flanges to be paid
separately)
7 Hand Shower(Health Faucet) with 1mtr Flexible Tube with Wall Hook Each 21 1,650.00
8 Supplying,fitting and fixing approved brand 32 mm dia.P.V.C. waste pipe, with PVC
coupling at one end fitted with necessary clamps.
a) 900 mm long Each 12 95.00
TOTAL
OR PUMBING SERVICES
AMOUNT
212,118.90
9,569.20
48,954.15
7,052.15
16,672.95
8,733.90
11,371.50
11,487.50
15,266.25
-
15,493.75
-
25,892.70
8,999.00
4,805.85
4,459.00
400,876.80
165,195.00
47,478.00
3,942.00
4,644.00
26,757.50
6,024.00
19,285.00
19,110.00
7,050.75
5,971.20
9,357.00
8,643.00
1,945.20
40,836.00
5,797.50
1,475.00
3,129.60
15,544.50
3,965.70
1,723.75
6,172.10
4,948.50
408,995.30
-
-
2,313.00
2,967.00
2,039.50
581.55
8,100.00
35,568.00
10,539.00
524.10
1,209.40
203,000.00
266,841.55
-
72,905.00
94,305.00
23,107.50
136,935.00
26,827.50
6,377.40
140,761.50
161,256.00
8,561.60
15,830.00
13,932.00
50,635.00
14,118.00
751,433.50
1,828,147.15
87,000.00
21,885.00
4,500.00
10,500.00
75,000.00
220,000.00
3,000.00
3,000.00
34,650.00
1,140.00
47,628.00
25,725.00
447,028.00
###
1 60 3,800.00 228,000.00
a)Analog addressable Multicriteria type detector
with mounting based LED, Address switch,
complete as required.
SL.N
O
a)
b)
c)
d)
4
a)
b)
5
a)
b)
c)
d)
i)
D
1
a)
b)
c)
E
1
a)
b)
c)
d)
e)
f)
g)
h)
F2
EXTENSION OF THREE FLOOR ABOVE G+ 4 OF CENTRE FOR RAILWAY RESEARCH BUILDING
ITEM OF WORK
HYDRANT SYSTEM
Supply, Erection, Testing and commissioning of C.I.Gate valves as per IS: 14846
(PN 1.6 Rating) and Non rising spindle type with flanges,bolts, nuts,
washers, gaskets etc.
Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN 1.6) slim seal
standard lever operated
150mm nominal dia type with required flanges, nuts, bolts etc. complete.
80mm nominal dia
Supplying, Installation,Testing and commissioning of Hydrant valve comprising of the following in the
Fire duct;
Single headed hydrant valve as per IS 5290, made of gunmetal with 63 mm dia instantaneous outlet of
80 mm dia fanged inlet ,Blank caps , chain and hand wheels etc complete.
15 M long, 63mm dia RRL hose with instantaneous couplings and Hoses shall be stored in side the
hose cabinet.
1 no. Gun metal short branch pipe with nozzle.
M.S. Hose cabinet stands mounted type fabricated out of M.Ssheet of 16 swg. with glass
fronted ( 4mm thick glass with rubber beading) door and size of the cabinet shall be
750 mm x 600mm x 250 mm Quoted rate shall be includes suitable stand for mounting, all
fasteners etc, and cabinet shall be powder coated of approved color both both inside and .
out side.
Supplying, installing, testing and commissioning of Gun metal chrome finished Ball valves
with fittings of screwed end type.
50mm dia.
FIRE EXTINGUISHERS
hose and ABS type branch pipe and wall mounting bracket etc complete, confirming to
IS: 15683
Dry chemical powder type fire extinguisher of 5 Kgs. Capacity, with initial filling in brand new
cylinder with powder coated finish, fitted with Gun metal union,high pressure CO2 gas
cartridge, discharge hose, wall mounting bracket etc. complete, confirming to IS:15683
Water CO2 type fire extinguisher 9 lts. Capacity, initial filling in brand new cylinder of powder
Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets.of 9 ltr cap each
SIGNAGES
Providing and installing in position the following type of AUTOGLO Photoluminescent Signages
complete
with fasteners
Signage with printed EXIT"( Model : D29/D30 , Size :100mmX300mm)
Floor identification signage ( i.e., 1/2/3 etc.) Size 200mm x 200 mm at each stair enclosure
on every floor
Providing and fixing in position the signage FIRE ORDER" it should contain the following matter
on 3mm thick "Opaque" PVC foam board of computerized cut,PVC non-reflective self
adhesive vinyl painted foam board of 3' x 4'.
A) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT
ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATIONS.
B) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND EMERGENCY EXITS ONLY AND
ASSEMBLE AT VARIOUS ASSEMBLY POINTS.
D) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO NOT RUN.
Supplying, Installing, testing and commissioning CI butterfly valves ( PN 1.6) as per BS 5155
slim seal standard lever operated type with required flanges, nuts, bolts etc. complete
150mm dia
100mm dia
80mm dia
40mm dia( For Drain Connection)
Supplying, installing, testing and commissioning conventional Sprinkler quartzoid bulb type with
15mm screwed end connection of 68 deg. C. temperature rating and orifice shall not be
less than 6mm.Sprinklers shall be UL Listed / FM approved with Chrome finished.
Pendent sprinkler
The Rosette shall be fabricated by M.S. plate of 2mm thick and the finish shall be powder
coated and color shall be as approved by architects / clients.
WORK
Rmt
Rmt
Nos.
Nos.
Nos.
Nos.
Nos.
Sets
Rmt
Nos
Nos
Nos 3 6,500.00 19,500.00
Nos 3 5,250.00 15,750.00
Nos.
801,575.00