Outer diameter of pipe 0.300 m 0.98 ft Inner diameter of pipe 0.295 m 0.97 ft Wall Thickness 0.005 m 0.02 ft Perimeter 0.94 m 3.09 ft Soil Depth 4m 13.12 ft Soil Temperature/Avg Annual Temperature 23.50 C 74.3 F Ambient Air temperature 35.6 C 96.08 F Dt 15.00 F Pipe Thermal conductivity 0.45 W/mK Btu/hrft2 15.87 Pipe Thermal conductivity 90 W/m2K F Btu/hrft2 Total Thermal conductivity F Rate of heat transfer / unit length 736 Btu/hrft Estimation Air side heat removal rate Air Quantity 315 CFM Earth Tunnel Air inlet Conditions Temperature 35.6 C 96.08 F Specific Humidity 116.4 gr/lb Dew point temperature 21.88 C 71.39 F Relative humidity 45 % Earth Tunnel Air outlet Conditions Design supply air Temperature 27 C 80.6 F Specific humidity at saturation 159.6 gr/lb* Design supply air Specific humidity 116.4 gr/lb Design supply air Relative humidity 73.65 % Heat Removal required 5266.3 Btu/hr Min Length of pipe 2.18 m 7.2 ft Total No of Pipes required 1 Nos Air quantity per pipe 315 CFM Total Air Quantity 315 CFM * As dew point temperature of outside air is less than design conditions no latent heat considered. At a depth of about 4 m below ground, the temperature inside the earth remains nearly constant round the year and is nearly equal to the annual average temperature of the place.