AC/DC Room Input Data

07/31/2013
10:35AM

1. General Details:
Air System Name AC/DC Room
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: AC/DC Room


AC & DC Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 23.6 C
Cooling T-stat: Unocc. 23.6 C
Heating T-stat: Occ. 22.2 C
Heating T-stat: Unocc. 22.2 C
T-stat Throttling Range 0.83 K

Thermostat Schedule Full Time Operation


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 14.4 C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 C
Heating Source Air Source Heat Pump
Schedule JFMAMJJASOND

Fan Control Cycled


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 2.00 ACH
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 14.4 C
Heating Supply Temperature 35.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 15 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 1350.0 - - 9.6

Hourly Analysis Program v4.51 Page 1 of 8


AC/DC Room Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 14.9 35.0 Auto-Sized 16.4 10 - 3.22 EER -17.8

Terminal Heating Units - ASHP

Estimated Gross Capacity Compressor


Maximum Design Heating Oversizing + OD Fan ARI
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.5 8.3 Auto-Sized 3.8 10 - 3.20 COP -26.1

Hourly Analysis Program v4.51 Page 2 of 8


Communication Room Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

1. General Details:
Air System Name Communication Room
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Communication Room


Communication Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 23.6 C
Cooling T-stat: Unocc. 23.6 C
Heating T-stat: Occ. 22.2 C
Heating T-stat: Unocc. 22.2 C
T-stat Throttling Range 0.83 K

Thermostat Schedule Full Time Operation


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 14.4 C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 C
Heating Source Air Source Heat Pump
Schedule JFMAMJJASOND

Fan Control Cycled


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 2.00 ACH
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 14.4 C
Heating Supply Temperature 35.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 15 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 789.0 - - 7.5

5. Equipment Data

Hourly Analysis Program v4.51 Page 3 of 8


Communication Room Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.6 35.0 Auto-Sized 9.5 10 - 3.22 EER -17.8

Terminal Heating Units - ASHP

Estimated Gross Capacity Compressor


Maximum Design Heating Oversizing + OD Fan ARI
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.8 8.3 Auto-Sized 4.2 10 - 3.20 COP -26.1

Hourly Analysis Program v4.51 Page 4 of 8


Control Room Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

1. General Details:
Air System Name Control Room
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Control Room


Control Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 23.6 C
Cooling T-stat: Unocc. 23.6 C
Heating T-stat: Occ. 22.2 C
Heating T-stat: Unocc. 22.2 C
T-stat Throttling Range 0.83 K

Thermostat Schedule Full Time Operation


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 14.4 C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 C
Heating Source Air Source Heat Pump
Schedule JFMAMJJASOND

Fan Control Cycled


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 2.00 ACH
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 14.4 C
Heating Supply Temperature 35.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 15 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 1817.2 - - 29.5

5. Equipment Data

Hourly Analysis Program v4.51 Page 5 of 8


Control Room Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 19.9 35.0 Auto-Sized 21.9 10 - 3.22 EER -17.8

Terminal Heating Units - ASHP

Estimated Gross Capacity Compressor


Maximum Design Heating Oversizing + OD Fan ARI
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.4 8.3 Auto-Sized 11.5 10 - 3.20 COP -26.1

Hourly Analysis Program v4.51 Page 6 of 8


Office Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

1. General Details:
Air System Name Office
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Office
Office x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 23.6 C
Cooling T-stat: Unocc. 23.6 C
Heating T-stat: Occ. 22.2 C
Heating T-stat: Unocc. 22.2 C
T-stat Throttling Range 0.83 K

Thermostat Schedule Full Time Operation


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 14.4 C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 C
Heating Source Air Source Heat Pump
Schedule JFMAMJJASOND

Fan Control Cycled


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 2.00 ACH
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 14.4 C
Heating Supply Temperature 35.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 5 %
Cooling Latent 5 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 526.7 - - 7.7

5. Equipment Data

Hourly Analysis Program v4.51 Page 7 of 8


Office Input Data
Project Name: LENA Farm 66kV Substation - Control Building 07/31/2013
Prepared by: PSP 10:35AM

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized 6.3 10 - 3.22 EER -17.8

Terminal Heating Units - ASHP

Estimated Gross Capacity Compressor


Maximum Design Heating Oversizing + OD Fan ARI
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 8.3 Auto-Sized 3.2 10 - 3.20 COP -26.1

Hourly Analysis Program v4.51 Page 8 of 8