TC Series 60Hz - HFC-410A Submittal Data Eng/I-P

Electrical Data High Static Blower

Compressor Fan Total Min Max


TC Voltage Rated Voltage
Motor Unit Circuit Fuse/
Model Code Voltage Min/Max
QTY RLA LRA FLA FLA Amp HACR

G 208/230/60/1 197/254 1 6.0 29.0 1.20 7.2 8.7 15


015
E 265/60/1 239/292 1 5.4 28.0 0.86 6.3 7.6 15
G 208/230/60/1 197/254 1 7.2 33.0 1.50 8.7 10.5 15
018
E 265/60/1 239/292 1 5.9 28.0 1.30 7.2 8.7 15
G 208/230/60/1 197/254 1 12.8 58.3 1.50 14.3 17.5 30
E 265/60/1 239/292 1 9.6 54.0 1.30 10.9 13.3 20
024
H 208/230/60/3 197/254 1 7.7 55.4 1.50 9.2 11.1 15
F 460/60/3 414/506 1 3.6 28.0 0.76 4.4 5.3 15
G 208/230/60/1 197/254 1 14.1 73.0 3.00 17.1 20.6 30
E 265/60/1 239/292 1 11.2 60.0 2.70 13.9 16.7 25
030
H 208/230/60/3 197/254 1 8.9 58.0 3.00 11.9 14.1 20
F 460/60/3 414/506 1 4.2 28.0 1.70 5.9 7.0 15
G 208/230/60/1 197/254 1 16.7 79.0 3.00 19.7 23.9 40
E 265/60/1 239/292 1 13.5 72.0 2.70 16.2 19.6 30
036
H 208/230/60/3 197/254 1 10.4 73.0 3.00 13.4 16.0 25
F 460/60/3 414/506 1 5.8 38.0 1.70 7.5 9.0 15
G 208/230/60/1 197/254 1 17.9 112.0 3.00 20.9 25.4 40
H 208/230/60/3 197/254 1 13.5 88.0 3.00 16.5 19.9 30
042
F 460/60/3 414/506 1 6.0 44.0 1.70 7.7 9.2 15
N 575/60/3 518/633 1 4.9 34.0 1.40 6.3 7.5 15
G 208/230/60/1 197/254 1 21.8 117.0 4.90 26.7 32.2 50
H 208/230/60/3 197/254 1 13.7 83.1 4.90 18.6 22.0 35
048
F 460/60/3 414/506 1 6.2 41.0 2.50 8.7 10.3 15
N 575/60/3 518/633 1 4.8 33.0 1.90 6.7 7.9 15
G 208/230/60/1 197/254 1 26.3 134.0 5.80 32.1 38.7 60
H 208/230/60/3 197/254 1 15.6 110.0 5.80 21.4 25.3 40
060
F 460/60/3 414/506 1 7.8 52.0 2.60 10.4 12.4 20
N 575/60/3 518/633 1 5.8 38.9 2.30 8.1 9.6 15

All fuses Class RK-5

ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

LC405 - 52 Rev.: February 18, 2016 Page ______ of ______