You are on page 1of 4

Impact of DC Grid Topology on Transient Stability of

HVDC-Segmented Power System


Rehan Naeem1, M.Asad Sarfraz Khan2, Zeshan Ali3, Wajahat Sultan4, Farhan Naeem5
Department of Electrical Engineering, The University of Lahore, Lahore, Pakistan1,2,3,4
Department of Electrical Engineering, KTH Royal Institute of Technology, Stockholm, Sweden5
eengineer107@gmail.com1

Abstract This paper compares the effects of ring, radial and segmented areas can be connected to each other using radial,
interconnected DC grid topologies on the transient stability of a ring or interconnected topology. These topologies affect the
segmented 15 - bus electric grid for different HVDC schemes. steady state losses and transient overcurrents of a multiterminal
For this purpose, three HVDC convertor technologies and four HVDC network as discussed in [12]. In this paper, the
HVDC station configurations are considered. A three phase AC influence of radial, ring and interconnected topology on the
bus fault is applied and the rotor angle disturbance is analyzed. transient stability of HVDC-segmented 15-bus electrical grid is
The results show that the transient stability is dependent on the investigated. The work done in this paper is an extended
topology for bipolar configuration of line commutated current version of the work done in [11] by taking into account all the
source and capacitor commutated convertor technologies. For
three HVDC technologies and all the HVDC station
rest of the HVDC schemes, transient stability is independent of
the topology used.
configurations except for the back to back configuration. All
the simulations are carried out in PSSE software provided by
KeywordsHVDC system; grid segmentation; rotor angle SIEMENS.
stability; grid topology. This paper is structured as follows: Section II describes the
methodology. Simulation results are discussed in section III
I. INTRODUCTION followed by conclusion in section IV
In the mid 1950s, direct current (DC) systems were used to
generate, transmit and distribute electrical power. DC systems II. METHODOLOGY
were not used excessively for long distance power transmission
due to high transmission line losses and low voltage level at A. Terminology
consumer end. With rapid advancement in the field of power The following terms are defined for the sections to follow.
electronics, it is now possible to transmit power to far away
loads at high voltage levels using high voltage direct current CMG is the name of the HVDC scheme which
(HVDC) systems. incorporates CCC convertor technology and MG
station configuration.
The advantages and disadvantages of HVDC system are
discussed in detail in [1]. The main components of HVDC CMM is the name of the HVDC scheme which
system are discussed in detail in [2] and [3]. One of the main incorporates CCC convertor technology and MM
components of HVDC system is the convertor. Presently three station configuration.
convertor technologies exist i.e. capacitor commutated
CBG is the name of the HVDC scheme which
convertors (CCC), line commutated current source convertors
incorporates CCC convertor technology and BG
(LCC) and voltage source convertors (VSC) [1], [2]. The main
station configuration.
configurations of HVDC stations are monopole with metallic
return (MM), monopole with ground return (MG), bipole with CBM is the name of the HVDC scheme which
metallic return (BM), bipole with ground return (BG) and back incorporates CCC convertor technology and BM
to back configuration [1]. station configuration.
Long distance power transmission, offshore power LMG is the name of the HVDC scheme which
transmission, power transmission through cables, power incorporates LCC convertor technology and MG
transmission to urban areas and grid segmentation are some of station configuration.
the applications of HVDC system [1], [2], [4]. In grid
segmentation, a huge electric grid is divided into a number of LMM is the name of the HVDC scheme which
smaller size grids which are then connected to each other incorporates LCC convertor technology and MM
through HVDC links. The concept of grid segmentation was station configuration.
introduced by authors in [5] [7]. One of the advantages of
grid segmentation is improvement in the stability of power
system.
By using grid segmentation technique, the stability of
electric grid is shown to be improved in [8] [11]. The

978-1-4673-8753-8/16/$31.00 2016 IEEE


(a) (b)

(c)

Fig. 1. Power systems under study: (a) Radial topology. (b) Ring topology. (c) Interconnected topology.

LBG is the name of the HVDC scheme which VBM is the name of the HVDC scheme which
incorporates LCC convertor technology and BG incorporates VSC convertor technology and BM
station configuration. station configuration.
Rotor angle disturbance The difference between
the maximum value of rotor angle after application of
LBM is the name of the HVDC scheme which fault and the steady state value of rotor angle before
incorporates LCC convertor technology and BM application of fault. It is denoted by in this paper.
station configuration.
VMG is the name of the HVDC scheme which B. Power systems and scenarios under study
incorporates VSC convertor technology and MG
station configuration Three scenarios are investigated for a four area, 15-bus
VMM is the name of the HVDC scheme which electric grid using PSSE simulation software. The schematic
incorporates VSC convertor technology and MM of electric grid is used as a case study by NTDCL (National
station configuration. Transmission and Dispatch Company Limited) Pakistan, for
implementing HVDC system in Pakistan. In the first scenario,
VBG is the name of the HVDC scheme which all the four areas are connected to each other by HVDC links
incorporates VSC convertor technology and BG
station configuration.
(a) (b)

(c)

Fig. 2. Rotor angle of generator in area 1: (a) Radial topology. (b) Ring topology. (c) Interconnected topology.

TABLE I. ROTOR ANGLE DISTURBANCE ( DEGREES )


HVDC
CCC LCC VSC
Technology

Monopole Bipole Monopole Bipole Monopole Bipole

HVDC Station
Configurations
Metallic

Metallic

Metallic

Metallic

Metallic

Metallic
Ground

Ground

Ground

Ground

Ground

Ground
return

return

return

return

return

return

return

return

return

return

return

return
Scheme name CMG CMM CBG CBM LMG LMM LBG LBM VMG VMM VBG VBM

Radial 123 118 263 288 128 128 133 153 57 57 188 190

Ring 125.5 117.5 139.5 400 132.5 117.5 67 72 59.5 59.5 188.5 188.5

Interconnected 110 103 250 128 127.5 127.5 129 146 57 57 185 187

radially as shown in Fig.1(a). In the second scenario, all the software. For each convertor technology, four different HVDC
four areas are connected to each other in the form of a ring as station configurations i.e. MG, MM, BG and BM were studied.
shown in Fig.1(b). In the third scenario, all the four areas are
interconnected to each other [Fig.1(c)]. In all the three scenarios, a three phase AC fault was
applied at bus 12 (area 3) for 0.18 seconds and rotor angle
In each scenario, three different convertor technologies i.e. disturbance () of generator in area 1 was analyzed. The total
CCC, LCC and VSC were studied. Capacitive reactance of 40 simulation time was 30 s. PSSE has built-in models of power
ohms was used to convert LCC to CCC technology in PSSE system components. The built-in models used in this study are
GENSAL (for generator), EXDC2 (for exciters), HYGOV (for IV. CONCLUSION
turbines), CDC4T (for LCC link) and VSCDCT (for VSC In this paper the effects of ring, radial and interconnected
link). DC grid topologies on the transient stability of a 15-bus electric
grid was investigated for different HVDC schemes by applying
III. SIMULATION RESULTS AND DISCUSSION a three phase AC bus fault. We conclude that the disturbance
For all the scenarios, the value of for generator in area 1 in the rotor angle of generator is least in case of VMG and
was found and recorded in Table 1. Fig. 2(a), 2(b) and 2(c) are VMM schemes irrespective of the topology used. Simulation
graphical representations of rotor angle for radial, ring and results show rotor angle disturbance to be independent of DC
interconnected topologies respectively. In each figure, the red, grid topologies for CMG, CMM, LMG, LMM, VMG, VMM,
green and yellow curves represent the rotor angle for CMG, VBG, VBM schemes and dependent on DC grid topologies for
LMG and VMG schemes respectively. Data in Table 1 is CBG, CBM, LBG and LBM schemes. In future, this study can
presented in the form of bar graphs in Fig.3. be extended for a larger electric grid and for fault types other
than the three phase AC bus fault.
In Fig. 2(a), the peak value of rotor angle for LMG scheme
is 140 while the pre-fault value is 12. The difference ()
REFERENCES
between the peak and pre-fault values of the rotor angle is
128. The values of for other schemes and topologies are [1] Mohamed H. Okba, Mohamed H. Saied, M.Z. Mostafa and T. M Abdel-
Moneim, High Voltage Direct Current Transmission - A Review, Part
determined in a similar way and are summarized in Table 1. I, in IEEE Energytech, Cleveland, OH, 2012, pp. 1-7.
In all of the scenarios, the least value for was about 57 [2] J. Setreus and L. Bertling, Introduction to HVDC technology for
in VMG and VMM schemes. These two schemes provided reliable electrical power systems, in 10th Int. Conf. Probabilistic
Methods Applied to Power Systems, Rincon, 2008, pp. 1- 8.
more stability to the whole power system than rest of the
[3] Mohamed H. Okba, Mohamed H. Saied, M.Z. Mostafa and T. M Abdel-
schemes. Moneim, High Voltage Direct Current Transmission - A Review, Part
II - Converter Technologies, in IEEE Energytech, Cleveland, OH,
In CMG scheme, there is not a large difference between the 2012, pp. 1-7
values of for ring, radial and interconnected topologies (see
[4] M. P. Bahrman and B. K. Johnson, The ABCs of HVDC transmission
Table 1). Similar trend is observed in CMM, LMG, LMM, technologies, IEEE Power Energy Mag., vol. 5, no. 2, pp. 32 - 44,
VMG, VMM, VBG and VBM schemes. For these schemes, Mar. 2007.
rotor angle stability is not affected significantly when the [5] G. C. Loehr. (2007, Jan). Enhancing the grid, smaller can be better.
topology is changed. Energybiz Mag. [online]. 4(1), pp. 35-36.
Available:http://www.nxtbook.com/nxtbooks/energycentral/energybiz01
In CBG, CBM, LBG and LBM schemes, the difference 07.
between the values of for ring, radial and interconnected [6] H. Clark, A.-A. Edris, M. M. El-Gasseir, K. Epp, A. Isaacs and D.
topologies is very significant as shown in Table 1. For these Woodford, Softening the blow of disturbances, IEEE Power Energy
schemes, rotor angle stability is affected significantly when the Mag., vol. 6, no. 1, pp. 30 - 41, Jan. 2008.
topology is changed. [7] H. K. Clark, M. M. El-Gasseir, H. D. K. Epp and A.-A. Edris, The
application of segmentation and grid shock absorber concept for reliable
In each of CBG, LBG and LBM schemes, is minimum power grids, in 12th Int. Middle-East Power System Conf., Aswan,
for ring topology while for rest of the topologies; the values of 2008, pp. 34-38.
are approximately equal. The highest value of is 400 [8] L.C Azimoh, K. Folly, SP Chowdhury, S. Chowdhury and A. Haddad,
for ring topology in CBM scheme [Fig. 3]. Investigation of voltage and transient stability of HVAC network in
hybrid with VSC-HVDC and HVDC Link, in 45th International UPEC
conf., Cardiff, Wales, 2010, pp. 1-6.
[9] X. H. Fang and J. H. Chow, BTB DC link modeling, control, and
application in the segmentation of AC interconnections, in IEEE Power
& Energy Society General Meeting (PES), Calgary, AB, 2009, pp. 1-7.
[10] R.G. Roshanagh, S.N. Ravadanegh, A way to evaluate segmentation:
An examination of AC line elimination in a parallel AC/DC
transmission system, in 21st ICEE conf., Mashhad, 2013, pp. 1-4.
[11] Umar T. Shami, Rehan Naeem, M. Sufyan chaudhary, Analysis of
Different Power Grid Segmentation And Transmission Schemes For
Power System Security Improvement, Technical journal UET Taxila,
vol. 20 , no. 1 , pp. 39 - 49 , 2015.
[12] M. Bucher, R. Wiget, G. Andersson, and C. Franck, Multiterminal
HVDC networks: What is the preferred topology?, IEEE Trans. Power
Del., vol. 29, no. 1, pp. 406413, Feb. 2014.

Fig. 3. Relationship between rotor angle disturbance and HVDC


schemes

You might also like