42TX 018 - 060

42MX 048 - 060


Direct Expansion Fan Coil
With Remote Control
(50/60 Hz)

Product Data
42TX/MX Direct Expansion fan coil units are available in 6 sizes with an airflow range from 300 CFM to 2000
CFM. Each unit is designed to occupy a minimum space. No complex system controls are required for Carrier
fan coil units. Piping, drain, and wiring connections are readily accessible and mounting holes and slots are pre-
drilled to save installation time and field labor expense.

Features/Benifits
x Standard wired control board kit to control
the unit functions, with additional remote
control.
x The drain pan is polyester powder coated
for extra protection.
x Piping connection are field exchangeable;
Standard right hand side.
x Direct drive forward curved centrifugal fan.
x 3 speed high efficiency motor.
x Standard galvanized sheet metal casing.
x Low unit height suitable for low false
ceiling application.
x Washable aluminum filter.
x Easy installation and maintenance.
x inch thickness internal insulation with
24 kg/m^3 density.
x Low noise level suitable for all application.
x Sweat connections for easy installation and
maintenance.
Carriers 42TX/MX direct expansion fan coils
are designed to cover low to medium range of
air handling requirements. They are compact
and ready to fit in the under ceiling
application. All units come with solid-state fan
controls, 1/2-in. insulation, quiet multi-speed
motors, and fully wet coils. Units can
accommodate factory installed heaters from 2
to 4kw. 42TX/MX are designed for ease of
service in under ceiling applications. A carton
CONTROL BOARD template for easy location of mounting
REMOTE CONTROL
hardware simplifies installation. Coils are
made of double wavy aluminum fins
mechanically bonded to copper tubes for
superior heat transfer.

42TX-MX - 03 PD 2013
Direct drive forward curved centrifugal fan attached board with the integrated thermostat , remote control
to 3-speed high efficiency motors. Galvanized sheet and washable Aluminum filters are standard feature.
metal casing protects against rust and drain pan is Piping connections position (RH/LH) is optional,
polyester powder coated for extra protection. also it is field interchangeable to suite various
Electrical heater is available option while the control applications.

Table of Contents
Page Page
Model Numbers & Nomenclature. 2 Fan Performance Data. 8
Physical Data 3 Typical Wiring Schematic 10
Combination Rating .. 4 Application Data. 16
Electrical Data 4 Control Board and Remote Control 17
Base Unit Dimensions. 5 Options & Accessories. 19
Detailed Performance Data. 6 Guide Specification... 20

Model Number Nomencalature


42TX - 018 - 3 2 1 C R E

Electronic Control
Connection side
R Right Hand Connection.
L Left Hand Connection.
Factory installed options
H With Heater
C Cool Only
Packiging
1 Standard

Design Series
42TX /MX

2 2nd Design Series

Voltage
3 208/230 V, 1 P, 60 Hz
7 220/240 V, 1 P, 50 Hz

Nominal cooling capacity


018 18,000 Btuh 036 36,000 Btuh
024 24,000 Btuh 048 48,000 Btuh
030 30,000 Btuh 060 60,000 Btuh

42 Series Low Height Fan Coils Energy Efficiency labels


TX Direct Expansion, Medium Static SASO 2663/2007
MX Direct Expansion, High Static Size 48-60 only

2
Physical Data 42TX
Model 42TX-18 42TX-24 42TX-30 42TX-36 42TX-48 42TX-60
CFM* 692 692 780 1181 1385 1572
Nominal Capacity (Tons)** 1.5 2 2.5 3 4 5
Motor HP 1/10 1/15 1/10
Input Watts @ Med Speed & 25 Pa ESP 70 80 80 130 146 160
Number of Motors, speeds 1, 3 Speed 2, 3 Speed
Evaporator Coil
Coil Material Grooved copper tubes/ Aluminum fins with double wavy fin
Coil Face Area, m^2 0.15 0.21 0.26 0.31 0.44 0.52
Number of Rows 3
Fin Denisty/ Inch 14
Coil Connection Type Sweat Type
Coil Connection Size (Suction,liquid) Inch 5/8, 3/8 3/4,3/8
Drain Diameter Inch 5/8
REFRIGERANT METERINGDEVICE AccuRater
Size 055 059 065 070 076 096
Blower Direct drive forward curved centrifugal fan
Blower Diameter / Width, mm 156/220 156/170 156/220
Filter Type Washable Aluminum Filter
Filter Qty. / Size (mm) 1/847x262 2/525x262 2/630x262 2/630x365 2/735x365
Unit Dimensions
Width, mm 1010 1220 1430 1430 1640
Depth, mm 590
Height, mm 275 375
Net Weight, kg 28 32 39 43 49 56

Physical Data 42MX


Model 42MX-48 42MX-60
CFM ( Nominal)* 1600 2000
Nominal Capacity (Tons)** 4 5
Motor HP 1/3 1/2
Number of Motors 1, 6 Speed 1, 5 Speed
Evaporator Coil
Coil Material Grooved copper tubes/ Aluminum fins with double wavy fin
Coil Face Area, m^2 0.44 0.52
Number of Rows 3

42TX /MX
Fin Density/ Inch 14
Coil Connection Type Sweat Type
Coil Connection Size (Suction,liquid)Inch 3/4 , 3/8
Drain Diameter 1 Inch
REFRIGERANT METERING DEVICE AccuRater
Size 076 096
Blower Direct drive forward curved centrifugal fan
Blower Diameter / Width, mm 2x180x240 3x180x240
Filter Type Washable Aluminum Filter
Filter Qty. / Size (mm) 2/630x365 2/735x365
Unit Dimensions
Width, mm 1430 1640
Depth, mm 656
Height, mm 375
Net Weight, kg 53 60
LEGEND
*CFM Cubic Feet Per MInute (Air Flow Rate Unit)

NOTES:
** Cooling Capacity based on: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.

3
Combination Ratings
COOLING ONLY
Nominal Outdoor
Indoor CAP. Outdoor Cap. Input
Cap. Unit Voltage CFM E.E.R.
Model Tons Model Btu/hr Watts
MBtuh
42TX-018-7 1.5 38HKR018DS 220-240 19,400 650 2.40 8.0
42TX-024-7 2 38HKC024DS 220-240 24,900 650 3.10 8.0
42TX-030-7 2.5 38HKC030DS 220-240 29,500 800 3.20 9.3
50Hz* 42TX-036-7 3 38HKC036DS 220-240 35,000 1100 4.00 8.8
42TX-048-7 4 38HKC048DS 400 45,000 1400 4.50 10.0
42TX-060-7 5 38HKC060DS 400 57,600 1550 5.70 10.0
42MX-048-7 4 38HKC048DS 400 46,700 1550 4.60 10.1
42MX-060-7 5 38HKC060DS 400 59,000 1800 6.00 9.8
42TX-018-3 1.5 38HKR018DS 230 19,000 650 2.30 8.1
42TX-024-3 2 38HKC024DS 230 23,000 650 2.60 8.8
42TX-030-3 2.5 38HKC030DS 230 30,500 800 3.70 8.2
42TX-036-3 3 38HKC036DS 230 35,000 1100 3.65 9.6
60Hz**
42TX-048-3 4 38HKC048DS 230 44,000 1400 4.51 9.7
42TX-060-3 5 38HKC060DS 230 56,500 1600 5.8 9.8
42MX-048-3 4 38HKC048DS 230 47,500 1633 5.00 9.5
42MX-060-3 5 38HKC060DS 230 58,300 1820 6.10 9.6

LEGEND
CFM Cubic Feet Per MInute
EER Energy Efficiency Ratio
*Air Conditioning, Heating and Refrigeration Institute.
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F
db air entering outdoor unit.
**as per SASO 2681/2007 Standard
Cooling Standard: 80.6F db, 66.2F wb indoor entering-air temperature and 95.0 F
db air entering outdoor unit.

Electrical Data
42TX Series
Voltage Fan
Condenser Control
Nominal Capacity Ton Power Supply
Input Min Max FLA

1.5
2 1.0
2.5 220-240/1/50 198 264
3 1.2
4 1.2
5 24 V 1.6
1.5
2 1.0
42TX /MX

2.5
208-230/1/60 198 264
3 1.5
4 1.5
5 2

42MX Series
Condenser Control Voltage Fan
Nominal Capacity Ton Power Supply
Input Min Max FLA
4 3.3
220/1/50 198 264
5 3.8
24 V
4 3
208-230/1/60 198 264
5 3.5
LEGEND
FLA Full Load Amps

4
Base Unit Dimensions 42TX/MX

42TX /MX

5
Detailed Performance Data
Matching 38HK with 42TX

Nom 75 85 95 105 115 120


Cap.
Mbtuh MBtuh MBtuh MBtuh MBtuh MBtuh MBtuh
CFM EWB Sen Kw Sen Kw Sen Kw Sen Kw Sen Kw Sen Kw
72 22.6 10.9 2.0 21.8 10.7 2.2 20.7 10.4 2.3 19.7 10.0 2.6 18.4 9.5 2.7 9.2 4.8 2.8
67 20.9 13.6 2.0 19.9 13.2 2.1 18.7 12.8 2.2 17.6 12.3 2.5 16.3 11.8 2.6 8.1 5.9 2.7
450
62 18.9 16.0 1.9 17.8 15.5 2.0 16.7 15.0 2.1 15.7 14.4 2.3 14.5 13.5 2.5 7.3 6.8 2.6
57 18.0 16.8 1.9 17.2 16.1 2.0 16.3 15.3 2.1 15.5 14.4 2.3 14.5 13.5 2.5 7.3 6.8 2.6
72 22.9 11.3 2.1 22.1 11.1 2.2 21.1 10.8 2.4 20.1 10.5 2.6 18.7 10.1 2.8 9.4 5.0 2.9
67 21.3 14.3 2.0 20.3 14.0 2.2 19.1 13.7 2.3 17.9 13.2 2.5 16.6 12.6 2.7 8.3 6.3 2.7
18 550
62 19.3 17.1 1.9 18.3 16.6 2.2 17.1 16.0 2.2 16.2 15.1 2.4 15.2 14.1 2.6 7.6 7.1 2.6
57 18.8 17.6 1.9 17.9 16.8 2.2 17.0 16.0 2.2 16.2 15.1 2.4 15.2 14.1 2.6 7.6 7.1 2.6
72 23.1 11.6 2.1 22.3 11.5 2.2 21.3 11.2 2.4 20.3 10.9 2.7 19.0 10.5 2.8 9.5 5.3 2.9
67 21.5 15.0 2.1 20.6 14.8 2.2 19.0 14.4 2.3 18.2 14.0 2.6 18.0 13.4 2.7 8.4 6.7 2.8
650
62 19.7 18.0 2.0 18.7 17.5 2.2 17.7 16.5 2.3 16.8 15.6 2.5 15.8 14.7 2.6 7.9 7.3 2.7
57 19.5 18.2 2.0 18.6 17.5 2.2 17.7 16.5 2.3 16.8 15.6 2.5 15.8 14.7 2.6 7.9 7.3 2.7
72 26.6 12.5 2.2 25.7 12.2 2.4 24.4 11.8 2.6 23.5 11.4 2.7 21.9 10.9 2.9 11.0 5.4 3.0
67 24.6 15.5 2.2 23.4 15.1 2.3 22.0 14.6 2.5 20.9 14.0 2.6 19.4 13.5 2.8 9.7 6.7 2.9
450
62 22.3 18.2 2.1 21.0 17.6 2.3 19.7 17.0 2.4 18.6 16.4 2.5 17.3 15.4 2.7 8.7 7.7 2.7
57 21.2 19.2 2.1 20.2 18.3 2.2 19.2 17.4 2.4 18.5 16.4 2.5 17.3 15.4 2.7 8.7 7.7 2.7
72 27.0 12.9 2.3 26.0 12.7 2.4 24.8 12.3 2.6 23.9 11.9 2.8 22.3 11.5 3.0 11.2 5.7 3.1
67 25.1 16.3 2.2 23.9 16.0 2.4 22.5 15.6 2.6 21.4 15.0 2.7 19.7 14.4 2.8 9.9 7.2 2.9
24 550
62 22.8 19.5 2.2 21.5 18.9 2.4 20.2 18.3 2.4 19.3 17.2 2.6 18.1 16.1 2.7 9.1 8.1 2.8
57 22.2 20.1 2.1 21.2 19.1 2.4 20.1 18.2 2.4 19.3 17.2 2.6 18.1 16.1 2.7 9.1 8.1 2.8
72 27.2 13.2 2.3 26.3 13.1 2.4 25.1 12.8 2.7 24.2 12.5 2.9 22.6 12.0 3.0 11.3 6.0 3.1
67 25.4 17.1 2.3 24.2 16.8 2.4 22.9 16.5 2.6 21.7 15.9 2.8 20.0 15.3 2.9 10.0 7.7 3.0
650
62 23.3 20.5 2.2 22.1 20.0 2.4 20.8 18.8 2.5 20.0 17.8 2.7 18.8 16.7 2.8 9.4 8.4 2.9
57 23.0 20.8 2.2 22.0 19.9 2.4 20.8 18.8 2.5 20.0 17.8 2.7 18.8 16.7 2.8 9.4 8.4 2.9
72 34.9 15.4 2.8 33.6 15.0 3.0 32.0 14.6 3.2 29.1 14.0 3.3 27.2 13.4 3.5 13.6 6.7 3.6
67 32.3 19.1 2.7 30.7 18.6 2.9 28.9 18.0 3.1 25.9 17.3 3.2 24.0 16.6 3.3 12.0 8.3 3.4
600
62 29.2 22.5 2.7 27.5 21.8 2.8 25.7 21.0 3.0 23.1 20.2 3.0 21.5 19.0 3.2 10.7 9.5 3.3
57 27.7 23.7 2.6 26.5 22.6 2.8 25.2 21.5 3.0 22.9 20.3 3.0 21.5 19.0 3.2 10.7 9.5 3.3
72 35.3 15.9 2.9 34.1 15.6 3.1 32.5 15.2 3.3 29.7 14.7 3.4 27.7 14.1 3.7 13.8 7.1 3.8
67 32.9 20.2 2.8 31.3 19.7 3.1 29.5 19.2 3.2 26.5 18.5 3.3 24.5 17.8 3.5 12.2 8.9 3.6
30 700
62 29.9 24.0 2.7 28.2 23.3 3.1 26.4 22.5 3.1 23.9 21.2 3.2 22.5 19.9 3.4 11.2 9.9 3.5
57 29.1 24.8 2.7 27.7 23.6 3.1 26.3 22.5 3.1 23.9 21.2 3.2 22.5 19.9 3.4 11.2 10.0 3.5
72 35.6 16.4 3.0 34.4 16.1 3.1 32.9 15.8 3.4 30.0 15.4 3.5 28.0 14.8 3.7 14.0 7.4 3.9
67 33.3 21.1 2.9 31.8 20.8 3.1 30.0 20.3 3.3 26.9 19.7 3.4 24.8 18.9 3.6 12.4 9.5 3.7
800
62 30.5 25.3 2.8 28.9 24.6 3.1 27.3 23.3 3.2 24.8 22.0 3.3 23.3 20.6 3.5 11.6 10.3 3.6
57 30.1 25.6 2.8 28.8 24.5 3.1 27.3 23.3 3.2 24.8 22.0 3.3 23.3 20.6 3.5 11.7 10.3 3.6
72 40.7 18.6 3.1 39.2 18.1 3.4 37.4 17.6 3.6 35.3 16.9 3.8 33.0 16.2 4.1 16.5 8.1 4.2
67 37.6 23.0 3.0 35.8 22.4 3.3 33.7 21.7 3.5 31.4 20.9 3.7 29.1 20.0 3.9 14.5 10.0 4.0
800
62 34.0 27.1 3.0 32.0 26.3 3.2 30.0 25.4 3.3 28.0 24.4 3.5 26.0 22.9 3.7 13.0 11.5 3.8
42TX /MX

57 32.4 28.5 2.9 30.9 27.3 3.1 29.3 25.9 3.3 27.8 24.5 3.5 26.0 22.9 3.7 13.0 11.5 3.8
72 41.2 19.2 3.2 39.8 18.8 3.4 38.0 18.3 3.7 35.9 17.8 3.9 33.5 17.1 4.2 16.8 8.5 4.3
67 38.3 24.3 3.1 36.5 23.8 3.4 34.4 23.2 3.6 32.1 22.3 3.8 29.6 21.5 4.0 14.8 10.7 4.1
36 950
62 34.9 29.0 3.0 32.9 28.1 3.4 30.8 27.2 3.4 29.0 25.5 3.6 27.2 24.0 3.8 13.6 12.0 4.0
57 33.9 29.9 3.0 32.3 28.5 3.4 30.7 27.1 3.4 29.0 25.6 3.6 27.2 24.0 3.8 13.6 12.0 4.0
72 41.6 19.7 3.3 40.2 19.5 3.4 38.4 19.0 3.7 36.4 18.6 4.0 33.9 17.9 4.3 17.0 8.9 4.4
67 38.8 25.5 3.2 37.1 25.1 3.4 35.0 24.5 3.6 32.6 23.7 3.9 30.0 22.8 4.1 15.0 11.4 4.2
1100
62 35.6 30.5 3.1 33.7 29.7 3.4 31.8 28.1 3.6 30.0 26.5 3.8 28.2 24.9 4.0 14.1 12.4 4.1
57 35.1 30.9 3.1 33.6 29.6 3.4 31.8 28.1 3.6 30.0 26.5 3.8 28.2 24.9 4.0 14.1 12.4 4.1

6
Detailed Performance Data
Matching 38HK with 42TX

75 85 95 105 115 120


Nom
Cap. Tot
Mbtuh Sys
MBtuh MBtuh MBtuh MBtuh MBtuh MBtuh Kw
CFM EWB Sen Kw Sen Kw Sen Kw Sen Kw Sen Kw Sen
72 51.1 24.3 3.9 49.3 23.7 4.2 47.0 23.0 4.4 45.3 22.1 4.7 42.3 21.2 5.0 21.2 10.6 5.2
67 47.3 30.1 3.8 45.0 29.4 4.0 42.3 28.4 4.3 40.4 27.3 4.5 37.4 26.2 4.8 18.7 13.1 4.9
1100
62 42.8 35.5 3.7 40.3 34.4 3.9 37.8 33.2 4.1 36.0 31.9 4.3 33.4 30.0 4.5 16.7 15.0 4.7
57 40.7 37.4 3.6 38.9 35.7 3.9 36.9 33.9 4.1 35.7 32.0 4.3 33.4 30.0 4.5 16.7 15.0 4.7
72 51.8 25.1 4.0 50.0 24.7 4.2 47.7 24.0 4.5 46.2 23.3 4.8 43.0 22.3 5.1 21.5 11.2 5.3
67 48.2 31.8 3.9 45.9 31.1 4.2 43.3 30.3 4.4 41.2 29.2 4.6 38.1 28.1 4.9 19.0 14.0 5.0
48 1250
62 43.8 37.9 3.8 41.4 36.8 4.2 38.8 35.6 4.2 37.2 33.4 4.4 35.0 31.4 4.7 17.5 15.7 4.8
57 42.6 39.1 3.7 40.6 37.3 4.2 38.6 35.4 4.2 37.2 33.4 4.4 35.0 31.4 4.7 17.5 15.7 4.8
72 52.3 25.8 4.1 50.5 25.5 4.2 48.3 24.9 4.6 46.7 24.3 4.9 43.6 23.4 5.2 21.8 11.7 5.4
67 48.8 33.3 4.0 46.6 32.8 4.2 44.0 32.1 4.5 41.8 31.0 4.7 38.6 29.8 5.0 19.3 14.9 5.1
1400
62 44.7 40.0 3.9 42.4 38.9 4.2 40.0 36.7 4.4 38.6 34.7 4.6 36.2 32.6 4.8 18.1 16.3 5.0
57 44.1 40.5 3.8 42.2 38.7 4.2 40.0 36.7 4.4 38.6 34.7 4.6 36.3 32.6 4.8 18.1 16.3 5.0
72 63.8 30.3 5.0 61.5 29.6 5.4 58.6 28.7 5.7 56.6 27.6 6.4 52.9 26.4 6.9 26.5 13.2 7.1
67 59.0 37.6 4.9 56.1 36.6 5.2 52.8 35.4 5.5 50.5 34.1 6.2 46.7 32.7 6.5 23.4 16.3 6.7
1300
62 53.4 44.3 4.7 50.2 42.9 5.0 47.1 41.4 5.3 45.0 39.8 5.9 41.8 37.4 6.2 20.9 18.7 6.4
57 50.8 46.6 4.7 48.5 44.5 5.0 46.0 42.2 5.2 44.6 40.0 5.9 41.8 37.4 6.2 20.9 18.7 6.4
72 64.6 31.3 5.1 62.4 30.8 5.5 59.5 29.9 5.8 57.7 29.0 6.6 53.8 27.8 7.0 26.9 13.9 7.3
67 60.1 39.7 5.0 57.3 38.8 5.5 54.0 37.8 5.7 51.5 36.5 6.4 47.6 35.0 6.7 23.8 17.5 6.9
60 1450
62 54.7 47.3 4.8 51.6 45.8 5.5 48.3 44.4 5.5 46.5 41.7 6.1 43.7 39.1 6.4 21.8 19.6 6.7
57 53.1 48.8 4.8 50.7 46.5 5.5 48.2 44.2 5.5 46.5 41.7 6.1 43.7 39.2 6.4 21.8 19.6 6.7
72 65.2 32.2 5.2 63.0 31.8 5.5 60.2 31.1 6.0 58.4 30.3 6.7 54.4 29.2 7.1 27.2 14.6 7.4
67 60.9 41.6 5.1 58.1 40.9 5.5 54.9 40.0 5.8 52.3 38.7 6.5 48.2 37.2 6.9 24.1 18.6 7.1
1600
62 55.8 49.8 5.0 52.8 48.5 5.5 49.9 45.8 5.7 48.2 43.2 6.3 45.3 40.6 6.7 22.6 20.3 6.9
57 55.0 50.5 4.9 52.6 48.3 5.5 49.9 45.8 5.7 48.2 43.2 6.3 45.3 40.6 6.7 22.7 20.3 6.9

Matching 38HK with 42MX


Evaporator CONDENSER AIR ENTERING Deg. F
Air 75 85 95 105 115 120
Nom
Cap. Tot
Mbtuh Capacity Tot Capacity Tot Capacity Tot Capacity Tot Capacity Tot Capacity Sys
MBtuh Sys MBtuh Sys MBtuh Sys MBtuh Sys MBtuh Sys MBtuh Kw
CFM EWB Tot Sen Kw Tot Sen Kw Tot Sen Kw Tot Sen Kw Tot Sen Kw Tot Sen
72 52.9 24.3 4.3 51.0 23.7 4.6 48.6 23.0 4.9 45.2 22.1 5.1 42.2 21.2 5.4 21.1 10.6 5.6
67 48.9 30.1 4.2 46.5 29.4 4.5 43.8 28.4 4.8 40.2 27.3 4.9 37.2 26.2 5.2 18.6 13.1 5.3
1250
62 44.2 35.5 4.1 41.6 34.4 4.3 39.0 33.2 4.6 35.9 31.9 4.7 33.3 30.0 4.9 16.6 15.0 5.1
57 42.1 37.4 4.0 40.2 35.7 4.3 38.1 33.9 4.5 35.5 32.0 4.6 33.3 30.0 4.9 16.7 15.0 5.1
72 53.6 25.1 4.4 51.7 24.7 4.7 49.4 24.0 5.0 46.0 23.3 5.2 42.9 22.3 5.5 21.4 11.2 5.7
67 49.8 31.8 4.3 47.5 31.1 4.7 44.8 30.3 4.9 41.1 29.2 5.0 37.9 28.1 5.3 19.0 14.0 5.4
48 1440
62 45.3 37.9 4.2 42.8 36.8 4.7 40.1 35.6 4.7 37.1 33.4 4.8 34.8 31.4 5.1 17.4 15.7 5.2

42TX /MX
57 44.1 39.1 4.1 42.0 37.3 4.7 39.9 35.4 4.7 37.1 33.4 4.8 34.8 31.4 5.1 17.4 15.7 5.2
72 54.1 25.8 4.5 52.2 25.5 4.7 49.9 24.9 5.1 46.6 24.3 5.3 43.4 23.4 5.6 21.7 11.7 5.8
67 50.5 33.3 4.4 48.2 32.8 4.7 45.5 31.8 5.0 41.7 31.0 5.1 38.5 29.8 5.4 19.2 14.9 5.6
1550
62 46.2 40.0 4.3 43.8 38.9 4.7 41.4 36.7 4.9 38.5 34.7 5.0 36.1 32.6 5.3 18.1 16.3 5.4
57 45.6 40.5 4.2 43.6 38.7 4.7 41.4 36.7 4.9 38.5 34.7 5.0 36.1 32.6 5.3 18.1 16.3 5.4
72 67.8 32.6 5.2 65.4 31.9 5.6 62.2 30.9 6.0 55.9 29.7 6.2 52.2 28.4 6.6 26.1 14.2 6.9
67 62.7 40.5 5.1 59.6 39.4 5.5 56.1 38.1 5.8 49.8 36.7 6.0 46.1 35.2 6.3 23.0 17.6 6.5
1450
62 56.7 47.7 5.0 53.4 46.2 5.3 50.0 44.6 5.6 44.4 42.8 5.7 41.2 40.3 6.0 20.6 20.2 6.2
57 53.9 50.2 4.9 51.5 47.9 5.2 48.9 45.5 5.5 44.0 43.0 5.7 41.2 40.3 6.0 20.6 20.2 6.2
72 68.7 33.7 5.4 66.3 33.1 5.7 63.3 32.3 6.1 56.9 31.3 6.3 53.1 30.0 6.7 26.5 15.0 7.0
67 63.9 42.7 5.2 60.8 41.8 5.7 57.4 40.7 6.0 50.8 39.3 6.2 46.9 37.7 6.4 23.5 18.9 6.6
60 1600
62 58.1 50.9 5.1 54.8 49.4 5.7 51.4 47.8 5.7 45.9 44.9 5.9 43.1 42.2 6.2 21.5 21.1 6.4
57 56.5 52.5 5.0 53.8 50.1 5.7 51.2 47.6 5.7 45.9 44.9 5.9 43.1 42.2 6.2 21.6 21.1 6.4
72 69.3 34.7 5.5 66.9 34.2 5.7 64.0 33.5 6.3 57.6 32.6 6.5 53.7 31.4 6.9 26.9 15.7 7.1
67 64.7 44.8 5.4 61.7 44.1 5.7 58.3 43.1 6.1 51.6 41.7 6.3 47.6 40.1 6.6 23.8 20.0 6.8
1800
62 59.2 53.7 5.2 56.1 52.2 5.7 53.0 49.3 5.9 47.6 46.6 6.1 44.7 43.7 6.4 22.3 21.9 6.6
57 58.4 54.4 5.2 55.9 52.0 5.7 53.0 49.3 5.9 47.6 46.6 6.1 44.7 43.7 6.4 22.4 21.9 6.6

Notes:
1. Net Capacities shown include a deduction for evaporator fan motor heat.
2. Formulas:
Leaving db= Entering - Sensible Heat Cap./(1.09 x CFM)
Leaving wb= wb corresponding to air leaving coil (hwb)
h wb leaving = hwb entering - Total Cap(Btuh)/(4.5 X CFM)
3. Direct Interpolation Permissible. Do not extrapolate.

7
Ex. Static Pres. inwg 0 0.05 0.1 0.15
Unit Size H M L H M L H M L H M L
012 592 498 408 553 448 370 515 398 332 467 353 278
018/024 692 586 548 666 555 497 640 524 447 603 466 373
030 780 691 607 756 642 552 732 592 497 682 527 443
036 1181 995 815 1106 895 740 1031 796 665 935 706 557
048 1385 1172 1096 1333 1110 995 1281 1048 893 1205 931 746
060 1572 1383 1214 1512 1283 1104 1452 1184 995 1363 1054 885

42TX Air Flow (CFM)


Ex. Static Pres. inwg 0.2 0.25 0.3
Unit Size H M L H M L H M L
012 423 318 229 368 258 308
018/024 541 421 294 434 318 329
030 607 464 373 524 383 453
036 846 637 457 736 517 617
048 1082 842 587 846 621 642
060 1214 927 746 1042 762 901

Fan Performance 42MX ENGLISH


42MX Air Flow (CFM)
Ex. Static Pres. inwg 0 0.1 0.2 0.3
Unit Size H M L H M L H M L H M L
048 1641 1398 1138 1531 1300 1069 1422 1211 995 1302 1108 914
060 2186 1940 1513 1956 1736 1336 1741 1518 1175 1492 1273 972

42MX Air Flow (CFM)


Ex. Static Pres. inwg 0.4 0.5
Unit Size H M L H M L
048 1163 983 796 984 790 609
060 1263 1047 742 955 757 455

H At High Fan Speed.


M At Medium Fan Speed.
L At Low Fan Speed.

SOUND PRESSURE 42TX/MX ENGLISH


External static Pressure dBA @ 0 inwg ESP dBA @ 0.1 inwg ESP dBA @ 0.2 inwg ESP
Motor Speed Hi Med Low Hi Med Low Hi Med Low
42TX012 48.5 46.5 44.5 47.5 45.0 43.5 46.5 43.5 42.0
42TX018 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TX024 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TX030 50.5 48.5 46.5 49.5 47.0 45.5 48.5 45.5 44.0
42TX036 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.0
42TX048 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.5
42TX060 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0

External static Pressure dBA @ 0 inwg ESP dBA @ 0.2 inwg ESP dBA @ 0.5 inwg ESP
Motor Speed Hi Med Low Hi Med Low Hi Med Low
42MX048 52.5 48.0 42.7 50.8 45.0 40.8 48.3 43.8 38.2
42MX060 57.3 50.5 43.3 56.1 49.2 42.5 53.2 46.4 40.0
Note: Assumes "standard room ", 3 meters from exit, no ducts, ducts will further reduce sound
3
/hr)
Ex. Static Pres. Pa 0 12.5 25 37.5
Unit Size H M L H M L H M L H M L
012 1005 846 694 940 761 629 875 676 564 794 600 473
018 1176 995 931 1132 943 845 1088 891 759 1024 791 634
024 1176 995 931 1132 943 845 1088 891 759 1024 791 634
030 1325 1174 1031 1284 1090 938 1243 1006 845 1158 896 752
036 2007 1690 1385 1879 1521 1257 1751 1352 1129 1589 1200 946
048 2353 1991 1862 2265 1886 1690 2177 1781 1518 2048 1582 1268
060 2671 2349 2062 2569 2180 1876 2467 2011 1690 2315 1791 1504

3
42TX Air Flow (m /hr)
Ex. Static Pres. Pa 50 62.5 75
Unit Size H M L H M L H M L
012 718 541 389 625 439 524
018 919 715 499 737 541 559
024 919 715 499 737 541 559
030 1031 788 634 890 651 769
036 1437 1082 777 1251 879 1048
048 1839 1430 997 1437 1055 1091
060 2062 1575 1268 1770 1295 1530

Fan Performance 42MX SI


42MX Air Flow (m3/hr)
Ex. Static Pres. Pa 0 25 50 75
Unit Size H M L H M L H M L H M L
048 2788 2374 1934 2601 2209 1816 2416 2057 1691 2212 1882 1552
060 3711 3294 2569 3322 2947 2268 2957 2578 1994 2534 2161 1651

3
42MX Air Flow (m /hr)
Ex. Static Pres. Pa 100 125
Unit Size H M L H M L
048 1976 1670 1352 1672 1342 1035
060 2154 1778 1260 1622 1285 773

H At High Fan Speed.


M At Medium Fan Speed.
L At Low Fan Speed.

Sound Pressure 42TX/MX SI


External static Pressure dBA @ 0 Pa ESP dBA @ 25 Pa ESP dBA @ 50 Pa ESP
Motor Speed Hi Med Low Hi Med Low Hi Med Low
42TX012 48.5 46.5 44.5 47.5 45.0 43.5 46.5 43.5 42.0
42TX018 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TX024 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TX030 50.5 48.5 46.5 49.5 47.0 45.5 48.5 45.5 44.0
42TX036 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.0
42TX048 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.5
42TX060 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0

External static Pressure dBA @ 0 Pa ESP dBA @ 50 Pa ESP dBA @ 125 Pa ESP
Motor Speed Hi Med Low Hi Med Low Hi Med Low
42MX048 52.5 48.0 42.7 50.8 45.0 40.8 48.3 43.8 38.2
42MX060 57.3 50.5 43.3 56.1 49.2 42.5 53.2 46.4 40.0
Note: Assumes "standard room ", 3 meters from exit, no ducts, ducts will further reduce sound
Typical Wiring Schematic
42TX /MX

10
Typical Wiring Schematic

42TX /MX

11
Typical Wiring Schematic
42TX /MX

12
Typical Wiring Schematic

42TX /MX

13
Application Data
FIELD SUPPLIED
TYPE L REFRIGERANT
TUBING
FEMALE SWEAT FIELD SUPPLIED
CONNECTIONS 24 V CONTROL
AT SERVICE VALVES WIRING

FIELD SUPPLIED
FIELD SUPPLIED WEATHERPROOF
FILTER DRIER FUSED DISCONNECT
AND WIRING PER NEC

FIELD SUPPLIED
CONDENSATE
DRAIN LINE
TO OPEN DRAIN

FIELD SUPPLIED
42TX /MX

FUSED DISCONNECT
AND WIRING PER NEC

REMOTE CONTROL
CONTROL BOARD

NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for a special installation.
4. Insulate condensate line if run above a conditioned space.

14
CONTROL BOARD & REMOTE CONTROL CONTROL BOARD & REMOTE CONTROL
h SPECIFICATIONS h FUNCTIONS

The controller is used to control (DX/CW) cooled ducted (1) ON/OFF KEY
split unit, supports the following functions: If you press this key, the systm will begin operation,
ModeCool, Dry, Fan, Heat, Auto Cool-Heat Press the key again, and operation stops. (You can
Indoor fan speedAuto, High, Medium, Low hear a receiving beep)
Sleep mode If you press this key immediately after turning off
Compressor protections:- (Not Applied for CW units) the system, the compressor will not operate for 3
- Comp 3 minutes restart protection minutes to prevent overloading.
- Indoor coil anti freeze Hardware setting
- Room sensor and indoor coil sensor failure A 2 way DIP switch is used to configure:
monitoring DIP Switch On Off
Non volatile memory keep system settings SW1 Cool Cool-Heat
Programmable On/Off timer SW2 Water System DX System
Random restart to minimize voltage dip during
compressor first cut in cycle upon power up. Note: In water cooled model, the following
functions are not available:-
Control Board - 3 min compressor protection
- Indoor coil sensor
- Indoor anti freeze
Error code

Fault Erro code
Room sensor fault E1
Indoor coil sensor fault E2
Comp fault E4

If multiple faults happen at the same


time, the corresponding error code will
be shown one after another.

(2) OPERATION MODE SELECTING KEY


Toggles the operation mode: Cool, Dry, Heat, or
Remote Control Handset Fan only
COOL Led Lights on when selecting COOL mode.
DRY Led Lights on when selecting DRY mode.
HEAT Led Lights on when selecting Heat mode.
FAN Led Lights on when selecting FAN mode.

42TX /MX
(3) SLEEP KEY
Press this key to set the SLEEP timer and then the
sleep led will light on.
To cancel the sleep timer press this key again.
- Sleep function for healthy sleep to control
automatically the room temperature and stop
automatically the operation of the air conditioner
after certain set off time.

- Sleep mode is valid in cool or heat mode and


invalid in Fan mode.

Fig. 10- Control Board & Remote Control

15
(4) KEY LOCK MODE
To activate key lock mode, hold down for 3 automatically turn off to stop cooling operation. In
seconds, temp. Down Key (5) and Mode Key (2). HEAT mode, if the room temperature is lower than the
In key lock mode, all keys are not valid except setting, the compressor for heat pump system will
ON/OFF Key (1) to turn ON/OFF the system automatically turn on to provide a heating effect. If the
> At Key Lock Mode: room temperature is higher than the setting, the
XHold down Temp Down and Sleep button for one compressor for heat pump system will automatically
second to enter into coil temperature display mode. turn off to stop heating operation.
Press Temp Up key to display indoor coil - In Dry mode, the fan speed runs automatically at low
temperature, High Fan LED flashes. With the same speed and compressor stopping and running is
sequence to exit coil temperature display mode. controlled by the difference between room and setting
Temperature display range is -9C to 78 C. temperatures and by continuous running time.
Y Hold down and FAN buttons for only - In Dry mode, the humidity reduced in the space to be
1 second (5 sec to toggle between C and F temperature) air-conditioned.
to activate temperature display setting and auto fan LED
flashes. Repeat the same sequence to cancel this function.
- In Fan mode, there will be no cooling or heating
Press or button to change the setting from effects; only the fans of indoor unit will run for
12. 1 means disable room temperature display and 2 ventilation.
means enable room temperature display.
Notes:
(5) FAN SPEED SELECTING KEY
(A) Temperature setting range is 16C to 30C or 60F
Toggles the fan speed: Auto, High, Medium, or Low
to 85F.
AUTO Led Lights on when selecting Auto fan speed.
For optimum operation set the temperature
HIGH Led Lights on when selecting High fan speed.
between 21-240 C (70-75F).
MED Led Lights on when selecting Medium fan speed.
(B) Hold down at the same time for about 5 seconds,
LOW Led Lights on when selecting Low fan speed.
Temp down and fan keys will toggle the temperature
setting from degree C to degree F and vice versa.
Note: Fan key is invalid in Dry mode.
(C) Press any temperature key will flash the current
(6) TEMPREATURE UP KEY
setting temperature for 4 seconds.
By pressing Temperature Up Key, the setting
Should there be no further key press, it will revert to
temperature increases by 1C with each press. For
room temperature display mode.
optimum operation set the temperature between 20-24
Room temperature display range is 0C to 50C or 32F
C (68-75F).
to 99F.
(7) TEMPREATURE DOWN KEY
By pressing temperature down key, the setting (D) Temp keys are invalid in Fan mode.
temperature decreases by 1C with each press.
(8) TIMER KEY Notes :
Upon count down of the number of set hours, the (A) The digital display show the number of hours
system will switch from OFF to ON or ON to OFF. previously set, only the Timer Led flashes.
42TX /MX

- OFF Timer Function to stop automatically, the air


conditioner after certain set OFF time. (B)If there be no further key press, it will revert
- ON Timer Function to start automatically, the air to normal mode.
0
conditioner after certain set ON time. (C)If Timer key is not released timer setting will
Timer setting is I HR to 24 HR. The timer led will increase automatically every 0.5-second.
light on when operating the Timer Function
First key press will flash the digital display and (9) DISPLAY SCREEN
Timer Led for 3 seconds. Displays the set temperature and displays also the
- If you set the desired room temperature, then system TIMER settings when adjusting it.
will maintain the room temperature as set. In COOL
mode, if the room temperature is higher than the (10) SENSOR
setting, the compressor will automatically turn on Receives the remote controllers signal.
provide a cooling effect. If the room temperature is
lower than the setting, the compressor will

16
Options & Accessories
ELECTRIC HEATER OPTION
A single heater element having capacity of 2.0 and 2.5 kw or two heater elements with a combined
capacity of 4.0 KW can be factory installed (Option); the electric heater is open type with thermal
protection and fuse for more safety. In case of electric heaters, a special quiet contactor is installed in
the electric box to minimize contactor noise when heater is energized and de-energized. Heater
capacities are available as shown in the following table:

Total Heating Capacity


Models Heaters noWatts/Heater KW
42TX018
12000 2
42TX 024
42TX030 12500 2.5
42TX036
42TX048
42TX060 22000 4
42MX048
42MX060

CONNECTION SIDE OPTION


Standard coil connection and electric box position is RH facing air flow direction while the optional
position is LH facing the air flow for both coil connection and electric box.
Customers can order this option directly from the factory also units are designed to be field
exchangeable if needed in the field.

CONTROL BOARD WIRE EXTENSION


Standard wire length for control board is 7.5m. optional extensions are available to enlarge the wire
up to 30 m. if extension are required, please contact your local Carrier dealer.

42TX /MX

h Factory Supplied, Field Installed.


h Easy installation
h Field Exchangeable Connections.
h Available for DX & Chilled Water Systems.
h Available for size 36-60.

17
Guide Specification
Carrier 42TX/MX

GENERAL be dynamically balanced with double inlet


SYSTEM DESCRIPTION forward curved type blower wheel.
The fan coil unit is designed for under F- Unit coil shall have aluminum fins
ceiling installation, electrically controlled mechanically bonded to seamless smooth
cooling and heating (option). Unit shall be copper tubes 3/8 inch with all joints brazed.
horizontal installation. Standard unit shall Unit coil shall be accessible for cleaning.
include washable permanent aluminum G- The coil connection shall be sweat type,
filter. Unit shall be designed for medium it shall be RH/LH exchangeable.
external static pressure up to 0.5 inch H- The unit fan motor shall have
water. permanently lubricated sleeve bearing and 3
speeds, the motor shall have overload
protection and B class insulation.
QUALITY ASSURANCE I- Unit shall have a wired control board
A- Unit shall be rated in accordance with with a built-in thermostat to be installed in
ARI standard. the airconditioned area and it shall have the
B- Unit shall be manufactured in facility following Features:
registered to ISO9001: 2000 standard. - Control Modes Cool, Dry, Fan,
Heat, Auto Cool-Heat and Sleep
PRODUCT mode.
- Compressor protections 3 minutes
A- The unit shall be factory assembled restart protection.
single piece cooling unit, with optional - Indoor coil anti freeze.
electric heat. - Failure monitoring for room sensor
B- Unit cabinet shall be constructed of and indoor coil sensor.
galvanized steel. The unit shall be insulated - Non volatile memory keep system
with polyester urethane insulation that is settings.
1/2 inch thickness & 24 kg/m^3 density, - Programmable On/Off timer.
Unit cabinet panels shall be single skin - Random Restart Time Delay to
C- Unit shall have a permanent washable minimize voltage dip during
aluminum filter. Filter shall be flame compressor first cut in cycle upon
retardant and easy accessible through an power up for multiple units operation.
access panel.
D- Units shall have external drain pan with J- Unit shall have a wireless remote control
42TX /MX

inch insulation, the drain pane shall be to control all the functiones of the control
galvanized steel coated with polyester board at a distance.
powder for extra protection. K- All electric parts shall be easy accessible
E- The unit fan wheel shall be directly for service.
connected to the motor. The fan wheel shall L- Unit control board shall be 220 V.

18
19
42TX /MX
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations