HomeForumsEngineeringCodes,Standards&CertificationsEngineeringCodes,Standards&CertificationsNFPA(fire)CodeIssuesForum
Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?
6
thread184170610
OSN
7932
Therequiredfireflowcanbereducedupto75%ifthebuildingissprinkleredaccordingtotheIFC.
Doesthereducedfireflowrequirementincludewaterdemandforsprinklersystem?orjustforfiredepartmenthosestreams
only?
Ifnot,whatmethodshouldIusetogetthevaluetoaddthethereducedfireflowrequirementtoperformhydraulicmodel?
Thanks.
Greatpost! Report
WhicheditionoftheIFC?The2003IFCtookthecreditawayforsprinklersinmostbuildings.Itwasgivenback(correctly)inthe
06IFC.
Greatpost! Report
Ilookedatyourquestionagainandhaveconcludedyouaremixingappleswithzebras.
Fireflowversussprinklerdemandaretwocompletelydifferentdesigncriteria.Fireflowisbasedonthetypeofconstruction
andthebuildingarea.ItwascalculatedusingveryempiricalformulasthatwereformulatedbytheInsuranceServiceOfficein
the1950s.Basicallyfireflowisanestimationofhowmuchwaterdoesoneneedtocontrolafireinabuildingthatisnot
equippedwithsprinklers.
SinceyourquestionindicatedthattheIFCisbeingapplied,openyourbookandturntopage394(06edition).Assumea50,000
squarefootbuildingofTypeVA(combustiblewithnofireresistance)construction.Theprescribedfireflowis2,750GPM@20
PSIGresidualpressurefor2hours.
Letusassumethattheownerequipsthissame50,000squarefootbuildingwithaNFPA13compliantautomaticsprinkler
system.Iwillfurtherassumetheceilingheightislessthan14feetandthattheownerwillnotstorehazardousmaterials,
flammableorcombustibleliquids,orotherhighchallengecommodities.Theassumedbuildingwillhouseahaircareproducts
retailoutlet.BasedonthisIwouldmostlikelyclassifythebuildingasanOrdinaryHazardGroupIIoccupancyusingthe
requirementsinChapter5ofNFPA13.
NFPA13statesthatforanOrdinaryHazardGroupIIdesign,aminimumdischargedensityof0.19GPM/squarefootovera
1,500squarefootdesignareaisrequired.Thisequalsasprinklerdemandof285GPM.
IFCsectionB105.2inthe2006editionstatesintheexceptionthatthefireflowcanbereducedby75%butmustnotbeless
than1,500GPM@20PSI.
Soyourminimumfireflowwillbebasedonthebuildingarea,constructiontypeandifthebuildingisorisnotequippedwitha
NFPA13compliantautomaticsprinklersystem.Regardless,theIFCcorrectlygivesyouagreatdealofcreditifthebuildingis
sprinklered.Therefore,ifthebuildingissprinklered,yourminimumfireflowis1,500GPM@20PSI.Ifitisnotsprinkleredthe
fireflowis2,750GPM@20PSI.
http://www.engtips.com/viewthread.cfm?qid=170610 1/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
Yoursprinklerdemandquestioncannotbeansweredwithoutmoreinformationbecauseitsdesignisbasedonstorageheight,
commodity,roofheightandthelike.SeeChapter5ofNFPA13.
Iapologizeformyfirstanswer.Ishouldhavegonetobedratherthanprovideamorecomprehensiveresponsetothequestion
asIhavenowdone.
Greatpost! Report
Thankyoustookeyfpe.Iwaslookingatthe2003IFCandnowIdonothaveeitherthe06IFCorNFPA13handy.
FYI.Iworkforawaterdistrictandwegetfireflowrequirementsfromfiredepartments(usuallyjustonenumberi.e.2750gpm
at20psifor2hours).Then,we(useaconsultantto)performahydraulicmodeltodetermineavailablefireflowtocompare
withtherequirements,anddeterminewhatimprovementsareneededtomeettheflowrequirements.Now,Iamlookingfor
appropriatemethodstoanswerinquiriesforflow/pressureinformationfromfiresprinklerdesignersandwonderifIcoulduse
thehydraulicmodeltoanswerthesequestions.Afteralittleresearch,Ifoundoutthatthefireflowrequiredbyfiredepartment
may(not)includeademandforfiresprinkler.Then,Iwonderifthehydraulicmodelweusuallyrunisadequate.However,the
differencecouldbeacouplehundredgpm(+/).AndyesItrytoaddtheapplestothezebrastocoverallfireflow
requirements.
Then,Iconcludethatthefireflowrequirementof1,500gpm@20psiinyourcase(sprinklered)doesnotincludefiresprinkler
demand.
Also,Ishouldfindanappropriatedischargedensity(0.19inyourexample)andmultiplyitwiththedesignarea(1,500sq.ft.)to
getREASONABLEadditionalrequiredflowtoperformhydraulicanalysis(1500+285=1,785).Notethatattheverybeginning
oftheproject,weusuallydonotknowalotofdetailsaboutthebuildingi.e.proposedtenants,storageheight,etc.
Aresprinklerheadsstilldischargingwaterwhenthefiredeparmentarriveandstartthehosestreams?Frankly,Idonotknow
howtheyoperate.
Again,thankyoufortheinformation.ItisveryhelpfulandIwouldappreciateifyoucouldconfirmthatmyunderstandingis
rightorhavemoresuggestions.
Greatpost! Report
Hereismy$0.02,anditmaybeworthlessthanthat..
1stStookey:OHGrpIIis0.20/1500nobigdeal.ThatisperNFPA13:FIGURE11.2.3.1.5Density/AreaCurves.
And,asScottsaid,youfigurethe2completelyindependently.FireFlowistypicallyarequirementof1500@20psibasedon
IFCtables.Thisdoesnot,andisnotrequiredtoincludefiresprinklerdemand.
ThesprinklerdemandinthecaseofanOHGrpIIrequirement,wouldbeapproximately300gpmforsprinklers(0.2*1500)+
250gpmhoseallowanceifhydrantsaretakenfromthesupplyasisthecaseinmostinstallations.
Inordertodothefiresprinklersystemcalculations,thedesignerisgoingtowantastaticpressureinthelines,thenaresidual
pressureatsomeflowrate.Forexample,youmayhave80psistaticpressure,whiledroppingto50psiwhenflowing1500
gpm.Thatiswhatthesprinklerguywouldwanttodohis/hercalculations.
Ihopethatmakessomesenseandaddstoyourclarification.
Also,yes,sprinklerheadsarestilldischargingwhentheFDarrives.Thesprinklersthathaveactivatedduetoheat(NOTEVERY
SPRINKLERINTHEBUILDING)willbeflowingwateruntilthesupplyisexhaustedorthecontrolvalveonthesystemisshut
downessentiallyexhaustingthesupply.
Greatpost! Report
NTTT:
Justrememberthatfireflowisindependantofthesprinklerdemand.Generallyspeaking,fireflowis>sprinklerdemand.The
exceptionissomethinglikeaflammableliquidwarehouseoracetylenechargingplant.Thesecanhavesprinklerdemandson
http://www.engtips.com/viewthread.cfm?qid=170610 2/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
theorderof2,500to3,000GPM.Iamalsoawareofsomeaircraftrepairhangerswithhydraulicdemandsontheorderof
5,000GPM.Thesearefairlyrare.
TheexampleIused(andthanksTravisforcorrectingme)isprobablytypicalforabout75%ofthebuildingsyoumayseein
yourcommunity.Theother25%Iwouldestimaterequirelargersprinklerdemandsbecauseoftheirstorageheights.Usinga
conservativeNFPA13sprinklerdesignbasedontheuseofESFRsprinklers(125GPM/sprinklerx12sprinklers)+500gallons
forhosestreams,Icalculatedasprinklerdemandof2,285GPM.
SoTravis,haveyoufoundwhereyouaregoingtoshopforyourlittlepieceofTexastranquility?
Greatpost! Report
stookeyfpe&Travis:
Thankyouverymuch!
IthinkIamconfusedabouttheword"hosestreams"andhowyoucameupwith2,285gpm.Isit1500gpmfireflow+
0.19x1500sprinklerdemand+500hosestreams?
Waterusedtoextinguishfireinasprinkleredbuildingconsistsof:
1.Fireflow,forfirehosestreamsconnectedfromhydrantsaroundthebuilding?,obtainedfromIFCtable,2750gpmreduced
to1500gpmintheaboveexample.
2.Sprinklersandhoseallowanceboostingthesprinklersystem?,=(dischargedensityxdesignarea)+hoseallowance(250or
500gpm).
Thesetwoarecalculatedindependently.However,thewaterdistrictwantstoconfirmthattherewillbeadequateflowforall
demands(items1and2)andIbelievethattheFireMarshalwouldwanttoensurethateverythingiscoveredforfirefighting.
DoyouthinkwhatavailablefireflowFireMarshalwanttoseeinaWaterAvaialbilityCertificate?2285gpmor1500gpm?(The
Certificateisrequiredforpermitsi.e.building,fire,etc.)Whatdoyouseetypically?
Idonotknowaboutyourbackgroundbutifyouknowofsomething,pleaseletmeknow.Thankyou.
Greatpost! Report
NTTT:
Thestatedvalueiswrong.IrecalculateditandIcameupwith2,000gpm:
[(125GPM/Sprinkler)(12sprinklers)]+500GPMforhosestreamdemand=2,000GPM.
TheFireDepartmentwillalwayswantatleast1500GPM@20PSI.However,inthecasepresentedthesprinklerdesigner
wouldneedatleast2,000GPM@20PSI.
Myexperiencewithfireflowisthatitwillalsobedrivenbythetypeofdevelopment.Forexample:
Singleormultiplefamilydwellings:1,500GPMmax
Lightcommercial:1,500to2,000GPM
Industrialpark:2,000to3,500GPM
Again,Iapologizeforthematherror.
Greatpost! Report
stookey:
http://www.engtips.com/viewthread.cfm?qid=170610 3/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
MywifeisstillsurfingaroundfortheDFWarea.Sheissetonthatarea.IhavebeentryingtogethertolookaroundSan
AntonioandAustinareas.
Greatpost! Report
NTTT
Ithinkyouarestilltryingtoadd2thingsthatarenotadditive.
Ifyouhavethenonsprinkleredbuilding..sayanindustrialpark,youmusthaveaminimumflowatanyhydrantof20003500
gpmatstookeystatedabove.
Ifyouhavethesprinkleredbuilding,forexamplewithESFRheads,youwouldneedaround1750gpm(12headsflowingat1500
gpm+250gpmhoseallowance[StookeyitisjustmydaytocoveryourbackESFRonlyrequires250gpmhose])
Now,basedonmyunderstanding,hereishowthescenarioworksandmayhelpyouunderstand....
Fireoccursinanunsprinkleredbuilding.BythetimetheFDgetsthere,thefireisragingprettyheavyandtheFDwillbe
drawingalotofwaterfromthemunicipalsupplysayat3000gpmtoattackthefire.Thatiswherethefireflowscomeinto
play.
FireoccursinSPRINKLEREDbuilding.Let'sassumethereareESFRsprinklerstostaywiththeexampleabove.Bythetimethe
FDgetsthere,thefireissuppresedorcontainedtoarelativelysmallarea(1200sqftorless)andtheFDonlyneedstodrawa
smallamountofwater(tocompletethefinalknockdownonthefire).Thehoseallowancethatismentionedaboveaccountsfor
therelativelysmallamountofwaterthattheFDwillbetakingfromthesupplyinadditiontothedemandfromthe
sprinklers.So,inthiscasetherewouldbeabout1500gpmflowingfromthesprinklersandabout250gpmfortheFDtofinish
theattack.
Thescenariosare2completelydifferentsituationstotrysoshowhowthenumbersarereallyindependentofeachother.
Hopefullythathelpstoclearupsomeofthedifferencesforyou.
Greatpost! Report
Travis:
Goodjob.Ihadthosewordsinmyheadbutyoudidabetterjob.IthinkIwasspookedbymatherrorsandyoucorrectingme
onNFPA13(notetoselfreadthestandardbeforeposting).
YouwillliketheMetroplex.JustgravitatetowardsFortWorth.Ialwayslikedthatsideoftown.
Whenyoudecidetobeginthehunt,emailmeandIwillmakeatripupfromAustinsoIcanmeetyou.Wecanhaveourown
fireprotectionPat'sPubinFortWorth.AndbuddyIdohaveagreatsteakhouseinFortWorth.Bestinthestate...mytreat.
Heck,Iwillgiveyouastarjustsoyoucanremindmeaboutitnextyear.
ComehometoTexasbrother.Youwilldowellhere...
Greatpost! Report
IamworkingonahousingprojectinNYSwith89buildingswhicharemultifamilyresidentialinscope.Basedontheheightof
thebuildingsandthenumberofstairwells,themaximumfireflowforthestandpipeswouldbe1250GPM.Isthisaddedtothe
sprinklerdemand,hosestream,hydrantflows,orwhat.Inotherwords,whatisthemaximumfireflowrequiredforthisproject?
Isitthe1500GPMmentionedforresidentialprojects,oristhestandpipedemandanaddedfactor?Thankyouforyourinput.
Greatpost! Report
thebabe:
Asstatedabove,theyareallseparateentitiesandthewatersupplyneedstobesizedtosupplyeachindependently.
http://www.engtips.com/viewthread.cfm?qid=170610 4/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
1Sitefireflowrequirements:ThisisoftenfoundintheIFCorwhateverfirecodeyoufallunder.Itistypicallysomethinglike
1500gpm@20psiatanyhydrantonpropertyforaresidentialcomplex.
2Standpipes:Youneedtofigureoutifyouhavemanualorautomaticstandpipes.Ifautomatic,youneedtobeabletosupply
100psi@250atthetopmostoutlet,250atthenextoutletand250foreachadditionalstandpipetoatotalof1000gpmfora
sprinkleredbuilding.Ifitisamanualsystem,thenyoustillneedthesameflows,buttheFDpumpertruckwillprovidethe
pressure.Thiswillcoincidewiththesitefireflowrequirements,buttheyarenotaddititve.
3Sprinklersystem:Foraresidentialsystem,assumingNFPA13R,youflow4headsatamaxof20gpmeachforatotalof80
gallons.Witha13Rsystem,youthenfigureadomesticdemandtoaddtothecommonpointofdomestic/firelines.Thismay
beacouplehundredgallons,dependingonthedomesticfixturesandtheloadsasillustratedinNFPA13R.Remember,you
onlyhavetofigure1areain1buildinggoingoffatagivenpointintime.Youdonotcalculate4headsoneachfloorineach
buildingatonetime.
Again,eachoftheseareindependentandnotadditive.
Greatpost! Report
TheStateofNewYorkusestheNYUniformFireCode,whichisthe2003editionoftheIFC.Thestatedoesnotpostallofits
amendmentsonlinesoIamunsureiftheAppendixChapteronfireflowisadopted.
Ifyoucantellmetheconstructiontypeandtheheightandareaofthelargestbuildinginthecomplex,Icantellyouthe
requiredfireflow.
Travis,yousurearerackingupsomestars...
Greatpost! Report
Stookey:
IonlycareaboutgettingtotheLoneStar
LookslikeIwillbethereinJanforascoutingtrip.IwillletyouknowwhenIgetthedatesfirmedup.
Greatpost! Report
inresponsetostookeyfpe,thelargestbuildingwillbefourfloorswiththreestaircases,andatotalareaofapproximately
700,000sq.ft.alsototravismack:ialwaysthoughtstandpipeswere500GPMforthefirstand250eachadditionalwithamax.
of1250.thanksagainforyourinputandhelp.
Greatpost! Report
thebabe:
59.1.2*HydraulicCalculationProcedure.
Hydrauliccalculationsandpipesizesforeachstandpipeshallbebasedonproviding250gpm(946L/min)atthetwo
hydraulicallymostremotehoseconnectionsonthestandpipeandatthetopmostoutletofeachoftheotherstandpipesatthe
minimumresidualpressurerequiredbySection57.Commonsupplypipingshallbecalculatedandsizedtoprovidethe
requiredflowrateforallstandpipesconnectedtosuchsupplypiping,withthetotalnottoexceed1250gpm(4731L/min).
Iwasassuming250atthetopfloorand250atthenextfloordownforatotalof500gpmflowingthroughthemostremote
standpipe.
Idon'tknowifthatmakesmoresenseorjustmakesitmoreconfusing.
Greatpost! Report
http://www.engtips.com/viewthread.cfm?qid=170610 5/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
Babe:
Youdidn'tprovidemeaconstructiontype.However,yourbuildingareaandheighttellsmethatthebuildingissprinkleredin
accordancewiththe2003IBC,whichistheadoptedbuildingcodeinthestateofNewYork.Iamgoingtoassumethatitissteel
constructionandthesteelhasnofireresistance.
Basedonmydescriptionoftheconstruction,itisassignedasType2Bconstruction.Basedontheconstructiontypeandbuilding
areathefireflowis2,000GPMusingtherequirementsinTableB105.1andapplyinga75%reductioninfireflowbecausethe
buildingissprinklered.See2003IFC,sectionB105.2,exception.
Pleaseconfirmthetypeofconstructionandthatthebuildingwillbeprotectedthroughoutbyanautomaticsprinklersystem.If
not,yougotamuchlargerproblem.
Greatpost! Report
responsetostookeyfpe:thebuildingswillbeType2Aconstructionandwillbefullysprinklerprotected.isthemaxfiredemand
still2000GPM,andifso,howdoesthatbreakdown?(1000standpipe,250hosestream,etc.?)THANKYOU!
Greatpost! Report
Fireflowiscompletelydifferentthansprinklerdemand.Youaremixingthetwotogether.Lookcloselyatwhathasbewrittenin
thisthread.
Greatpost! Report
stookeyfpe:onnov.14,youindicatedthatthemaxfireflowdemandforamultifamilyres.developmentisalmostalways1500
GPM,butyouindicateamaxflowof2000forabuildingofType2Bconst.thatissprinklered.so,whatisadded?intheend,i
justwanttoknowwhatthemax.TOTALfireflowrequiredfromthewaterdistributionsystemwouldbeforthisproject.THANKS
AGAIN.
Greatpost! Report
IFC2003TableB105.1
RequiredFireFlowforTypeIIaconstructionwitharea>166,5001sqftis6000gpmfora4hourduration.Sinceyouhave
apts,IamassuminganRoccupancy.Therefore,youcanreducetheflowby25%to4500gpmasindicatedbyfootnoteAin
thesametable.
PerB105.2exception,youcanreduceby75%whereitisalighthazardoccupancyandprotectedthroughoutbyanautomatic
sprinklersystem.Therefore,youhave45004500*.75=1125.Theexceptionalsostatesthattheminimumfireflowshallnot
belessthan1500gpm.
PerIBC2003Table503,youareallowed24000sqftperfloorfortypeIIaconstruction.Youcanincreasethatanadditional
200%forasprinkleredbuildinginaccordancewithNFPA13,soyougetupto72ksqftperfloor.Itrustthearchitecthas
alreadytakenthefloorarealimitationsperbuildingintoaccount.
Goodluck.NowthatStookeyandIhavepointedyouintherightdirectionforallofthis,youshouldreallyresearchtheIBCand
IFCsectionsquotedandverifytheinformationforyourself.Afterall,youwillbetheengineerofrecordontheprojectand
needtohaveanunderstandingofwhatallofthismeans.Idon'twanttosoundmean,butIstillamnotsureyouunderstand
thefireflowvs.standpipevssprinklercalculationsbasedononeoftheresponsestoStookeyabove.
Goodluckandhaveagoodweekend.
Greatpost! Report
Howthesevaluesweredevelopedisinteresting.First,theirareanumberofmethodsforcalculatingfireflow.Thisincludesthe
NationalFireAcademymethod,theIowaStateMethodandtheISOmethod.ISO(InsuranceServicesOffice)methodisthe
basisforthetableinInternationalFireCode.
http://www.engtips.com/viewthread.cfm?qid=170610 6/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
ThevaluesIquotedonNovember14thareestimations.ThosevaluesarebasedonwhatIhaveseenoverthepast20some
oddyearsasafireprotectionengineer.Thevaluesthatarebindingarethosethatarepublishedintheadoptedfirecode.Sorry
ifImisleadyouitwasn'tmyintent.
Greatpost! Report
travismack&stookeyfpe:weusethenewyorkstatecodewhichis,ofcourse,basedontheIBC.don'tyethavetheIFC,butwill
certainlygetit.havebeendoingresearchasyousuggestandhaveabetterhandleonitatthistime.mythankstoboyhofyou
foryourinput.itwashelpfulandappreciated.wishyouagreatholidayseason.
Greatpost! Report
So,Travishasimpressedusasthegreatpoobahofsprinklerdesignandadamngoodexplaineroffireflow.I,aold,
whiteheadedAHJwillsitbackandhopemypalTravisfindshimselfaplacecalledTexas.
Thisthingcalledtheinternetisabsolutelyunique.
SoTravis,whendowemeet?
Babe,areyouhappywithouranswers?
Greatpost! Report
Stookey:
HowaboutFriday,Jan19.YouupfordinnerattheplaceyoumentionedinFortWorth?
Greatpost! Report
IstherearoomsizelimitationtoNOThaveafiresuppressionsprinkler?likeunder200sqft?
Joe
Greatpost! Report
All,
Thatsagreatthreadanditprovidesalotofinformationthatamyseemcounterintuitivetopeoplelikemyboss.
Ifthefireflowandthesprinklerdemandareindependent,whatcodefromIFCorNFPAcanIquotetoshowmybossthe
hydrantandsprinklerdemandsarenotadditive?
fyimyprojectisanewspaperpress.
Wouldreallyappreciateanyhelp.
RichardinAustin.
Greatpost! Report
Richard,
Thesprinklerdemandswilltypicallyincludeahoseallowance,andwillalsobeathigherpressurerequirementsthanthesite
firelines.Forexample,asprinklersystemmayneed300gpmat50psiatthebaseoftheriser,and550gpm@55psiatthe
citytap.Theextra250gpmisthehoseallowanceyouarerequiredtoaccountforincalculations.
Thesitefirelinedemandsarerequiredflowsat20psi.Sincemostwaterpurveyorsdon'tlikethewatermainpressurestofall
below20psi,thiswillinsurethattheFDhasadequatewatertogothroughtheFDpumpertruckwhilemaintainingthepressure
inthecitywatermains.
http://www.engtips.com/viewthread.cfm?qid=170610 7/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
Ican'tthinkoffthetopofmyheadwhereyouwillfindthequotetoshowtheyarenotadditive,butyouwillnotfindaquotethat
saystheyaren't.IfyouchecktheappendixBintheIFC,itindicatesthesitefireflowrequirements.Itdoesnotsaythatyou
arealsotoincorporatethesprinklerdemandtothese.
IhopeStookeychecksinonthis.SinceheistheresidentICCexpert,hecanlikelygiveyouabetterpointtolookintheI
codes.
Greatpost! Report
Atexeng:
YouareinAustin?SoamI.Getreadyforsomerain.
See2006IFCsectionB105.2,exception.
Greatpost! Report
Thanksstookey,
butthatisthereductioninfireflowforsprinkleredbuildings.Iamlookingforsomethinginprinttotellmethefireflowand
sprinklerflowareindependentandnotconcurrentuses.TheexceptiontoB105.2wouldleadmetobelievethatinorderto
reducethefireflowdemands,thesprinklerswouldhavetobesprinkling.
Itseemsmostofthecivilsiteengineersbelievethetwoshouldbemodeledconcurrently,butthemechanicalengineersItalkto
believethetwodemandsareindependentanddonothavetobemodeledtogether.
Greatpost! Report
Atxeng
YournotgoingtofindsuchaprovisionintheFireCode.IbelievetheclosestprovisionIcansendyoutoisthedefinitionoffire
flowinsectionB102.1.Fireflowisdefinedas:
Theflowrateofawatersupply,measuredat20poundspersquareinch(psi)(138kPa)residualpressure,thatis
availableforfirefighting.
Theimportantphraseis"firefighting."Thisismanualfiresuppressionoperationsinvolvinglayingofsupplyhoselinesand
deployingattackhoselinesforinteriorfirefightingoperations.Manualfirefightingisgenerallymoredemandingtoawater
supplywhencomparedtosprinklerdemand.Astandard11/2inchnozzleandattacklinecarriedonafiretruckdischargesa
minimumof150GPM.Conversely,asprinklerdesignedforanOrdinaryHazardGroupIIdensitydischargesabout20GPMusing
a100squarefootspacing.
Sprinklerdemandiscompletelydifferentinthatthedischargedensity(GPM)isbasedonthestoredhazardwithinthe
compartmentordesignarea.
SorrybuttheFireandBuildingcodesdon'talwaysprovideaclean,intuitiveexplanation.
Greatpost! Report
ThanksStookey,
fyiThesprinklerdemandisover2,200gpmat77psifortheoldpaperpress.
Greatpost! Report
Notthatitmatterstoanyoneelsebutme,butanyway....
IjusttalkedtothereviewerfortheFireDepartmentandshesaidthattheydonotcarewhatthefiresprinklerdemandis,they
justwanttoknowtheirlinehasenoughcapacityfortheirfireengines.Itoldhertheywillbothbedrawingoffthesameline,but
http://www.engtips.com/viewthread.cfm?qid=170610 8/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
itdidnotmakeanydifferencetoher.
Thankseveryonewhohelpedmeoutonthisone.
Greatpost! Report
anyrolledpaperstorage???ifsohowmanysqfeet
Greatpost! Report
Atexeng
Thatresponseisuncommon.Ifindalotoffirecodeofficialswholackaunderstandingofthedifferencebetweensprinkler
demandandfireflow.
Greatpost! Report
"...theydonotcarewhatthefiresprinklerdemandis,theyjustwanttoknowtheirlinehasenoughcapacityfortheirfire
engines...".
Thatmakessensewhenyouthinkaboutit.Sincethefirehydrantisthefirstfixtureonthelinecomingfromthedistribution
maininthestreet,thedepartmentwillbeabletodrawessentiallyallthewatertheyneedforthepumpertruck.Unfortunately,
theresultisthatthesprinklersystemwillgetwhateverisleftandmayfizzleoutduetothereducedpressureof20psi(possibly
lesssinceitisfartherdownthelineandsprinklersareathigherelevationthanthehydrant).Ifafraidthatifyouwantbothto
workatthesametime,youwillneedtomodelthembothsimultaneously.
Greatpost! Report
IwouldHOPEtheFireDepartmentwouldfollowNFPA13Eandpumpthefiredepartmentconnectiononthesprinklersystemat
150psi.Sinceafterallthesprinklersystemknowswherethefireisandthefiredepartmenthastofinditinthesmoke.Ifnot
wehaveaBIGproblem!
Greatpost! Report
Atex:
Youarenotconsideringtheefficacyoftheautomaticsprinklersystem.IfyoureviewtheNFPAdataforsprinklerperformance,
over90percentofthefiresarecontrolledby3orlesssprinklers.Evenifyouaredealingwithalargedemandlikeyourprinting
pressissueandyouareusinglargeflowsprinklers(let'sassume100GPM/sprinkler)theEnginecompanycanstillsupplythe
systemandtheirattacklines.
Greatpost! Report
"Thesprinklerdemandisover2,200gpmat77psifortheoldpaperpress."
Foraprintingpressthisisahugewaterdemand,whatisthesprinklerdesign?Anyflammableliquidusedonthepress?
Greatpost! Report
LCREPyouareassumingthefireisoninsideofthebuildingwherethe"sprinklerscanfindit".Ifontheoutsideofthe
building,sprinklersareessentiallyuseless.
Greatpost! Report
AccordingtotheMEP,
http://www.engtips.com/viewthread.cfm?qid=170610 9/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
"FireSprinklerSystem:Worstcasedesignflowdemandestimate:2214.9gpm@77.17psi(forexistingsystemZone1per
hydraulicinformationplacard)"
Idonotknowofanyflammableliquidsorrolledpaperinventory.
Greatpost! Report
morethanlikelyminimalflammables,butwouldaskthequestionaboutrolledpaperandisitbandedorunbanded.
Greatpost! Report
Atex:
Thissoundslikerolledpaperstorage.ThequestionIhaveistherolledpaperstorageseparatedfromthepress?Ifso,your
printingpresswillhaveafarsmallerdemandthantherolledpaperstorage.
ByseparatedImeanisa1houror2hourfirebarrierwithafiredoorseparatingtheprintingpressfromtherolledpaper
storage?
Atex,somethingisdrivingaverylargedischargedensity.AprintingpressatmostisanExtraHazardGroupIdensity(0.30
GPMovera2500squarefootdesignarea).Yougotsomethingelseinthebuildingthatneedstobeexamined.
Greatpost! Report
Idon'tknowStook,likeIsaid,theMEPgavemetheinformationforthesprinkler.ShouldI"stopthepresses"andfindout?My
scopeissiteengineering,butIdowanttomakesurethebuildingiscoveredintheeventofafire.
DidyouworkfortheAFDin1990?Youdon'treallynoticethingsuntilyouhaveareason,butIseemtobenoticingStookey
signaturesonsetsofplansaroundtheoffice.
Greatpost! Report
14yearsatAFD.That'smysignature.IhopeItreatedyoufairandrespectfully.
Sinceitisoutsideyourscopeyouhavenoobligation.YourresponsibilityisonlytogettheH2Otothesite.
Ithinkthequestionissolved.ItsoundsliketheMEPhasreviewedandevaluatedthehazardsandjustwantsyoutodeliverthe
GPMatagivenpressure.
Greatpost! Report
LookingForFlights?GetTheBestTravelRatesNow
Easy&HassleFreeBookings.OnlywithTajawal.BookYourFlightNow!Goto
tajawal.sa/Tajawal/Offers
Home>Forums>EngineeringCodes,Standards&Certifications>EngineeringCodes,Standards&Certifications>NFPA
(fire)CodeIssuesForum
Advertise
Copyright19982017ENGINEERING.com,Inc.Allrightsreserved.
Unauthorizedreproductionorlinkingforbiddenwithoutexpressedwrittenpermission.RegistrationonoruseofthissiteconstitutesacceptanceofourPrivacyPolicy.
http://www.engtips.com/viewthread.cfm?qid=170610 10/11
4/9/2017 Fireflowreqmntforsprinkleredbuildingincludesprinklerdemand?NFPA(fire)CodeIssuesEngTips
http://www.engtips.com/viewthread.cfm?qid=170610 11/11