You are on page 1of 4

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by user number 1329 Project: Drevsj asylskermottak


F Infrastruktur AS Address: Hyttveien 21. 2443 Drevsj
Nittedalsgata 7 Number: 13860
2000 Lillestrm Area ref: Loft
Hordaland Hazard: NS-EN 12845 OH1. preaction
Norway Authority: EN 12845 Rules
Source: 254.4 l/min @ 2.844 bar
Tel:+4790021746 Fax: Printout: 30-april-14 at 08:14

Project Data and Design Parameters


Project name : Drevsj asylskermottak
Area reference : Loft
Address / location : Hyttveien 21. 2443 Drevsj
Project number : 13860
Installation number(s) : 1
Drawing number(s) : ---
Issue no / date : ---
Designers reference : Terje L
Project Data File : \\afnooslfs1\Prosjekt\13800\13803U~1\138031~1\05TE
Hazard classification : NS-EN 12845 OH1. preaction
Design authority : EN 12845 Rules
Insurance company : ---
Specified density of discharge : 4.08 mm/min (l/min/m2)
Assumed maximum area of operation : 40.00 m2
Number of operating sprinkler heads : 4
Maximum area covered per head : 10.00 m2
Highest head / nozzle above source : 7.15 m
Number of pipes in system : 12 from 25 to 65 mm
Pressure loss equation used : Hazen-Williams
Fluid : Water (Preaction)
Pipe Data Table : EN_12845.PDT
Maximum fluid velocity : 4.21 m/s in pipe 180 190
Volume of pipework and fittings : 0.03 m3
Elbows are welded for : 65 mm and above
Comment : Beregnes NS-INSTA 900, type 3, 4 hoder utlst
Checked by & Date :

Source duty = 254.4 l/min @ 2.844 bar at node no 100

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 2
Submitted by user number 1329 Project: Drevsj asylskermottak
F Infrastruktur AS Address: Hyttveien 21. 2443 Drevsj
Nittedalsgata 7 Number: 13860
2000 Lillestrm Area ref: Loft
Hordaland Hazard: NS-EN 12845 OH1. preaction
Norway Authority: EN 12845 Rules
Source: 254.4 l/min @ 2.844 bar
Tel:+4790021746 Fax: Printout: 30-april-14 at 08:14

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A r e a|Density mm/min|Pressure bar|Heights|Pipe
no | no | mm | factor| l/min | m2 |Req.d Actual| Min Actual| m | no
1 190 15.0 80.00 71.7 10.000 4.08 7.17 0.50 0.804 7.150 9
2 200 15.0 80.00 67.2 10.000 4.08 6.72 0.50 0.705 7.150 10
3 210 15.0 80.00 59.0 10.000 4.08 5.90 0.50 0.543 7.150 11
4 220 15.0 80.00 56.6 10.000 4.08 5.66 0.50 0.500 7.150 12

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 3
Submitted by user number 1329 Project: Drevsj asylskermottak
F Infrastruktur AS Address: Hyttveien 21. 2443 Drevsj
Nittedalsgata 7 Number: 13860
2000 Lillestrm Area ref: Loft
Hordaland Hazard: NS-EN 12845 OH1. preaction
Norway Authority: EN 12845 Rules
Source: 254.4 l/min @ 2.844 bar
Tel:+4790021746 Fax: Printout: 30-april-14 at 08:14

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
1 100 65mm GMW 254.4 1.000 Up 1.00 0.000 2.844 -0.803
110 68.50 120 1.2 0 0 PD 90.0 802.0 1.000 1.943 -0.098
2 110 65mm GMW 254.4 0.100 Up 3.00 1.000 1.943 -0.008
120 68.50 120 1.2 0 0 BV 90.0 2.8 1.100 1.925 -0.010
3 120 65mm GMW 254.4 0.100 Up 3.30 1.100 1.925 -0.009
130 68.50 120 1.2 0 0 SV 90.0 2.8 1.200 1.906 -0.010
4 130 50mm GMW 254.4 1.100 Up 1.10 1.200 1.906 -0.011
140 52.81 120 1.9 0 0 90.0 9.9 2.300 1.787 -0.108
5 140 50mm GMW 254.4 3.600 Up 3.60 2.300 1.787 -0.036
150 52.81 120 1.9 0 0 90.0 9.9 5.900 1.399 -0.353
6 150 50mm GMW 254.4 0.500 Up 0.50 5.900 1.399 -0.005
160 52.81 120 1.9 0 0 90.0 9.9 6.400 1.345 -0.049
7 160 50mm GMW 254.4 2.606 0 4.11 6.400 1.345 -0.041
170 52.81 120 1.9 1 0 0.0 9.9 6.400 1.304 +0.000
8 170 50mm GMW 254.4 0.750 Up 2.25 6.400 1.304 -0.022
180 52.81 120 1.9 1 0 90.0 9.9 7.150 1.208 -0.074
9 180 32mm GMW 254.4 5.150 270 6.15 7.150 1.208 -0.405
190 35.80 120 4.2 1 0 0.0 65.8 7.150 0.804 +0.000
10 190 32mm GMW 182.7 2.756 270 2.76 7.150 0.804 -0.098
200 35.80 120 3.0 0 0 0.0 35.6 7.150 0.705 +0.000
11 200 25mm GMW 115.5 2.756 270 2.76 7.150 0.705 -0.162
210 27.14 120 3.3 0 0 0.0 58.8 7.150 0.543 +0.000
12 210 25mm GMW 56.6 2.756 270 2.76 7.150 0.543 -0.043
220 27.14 120 1.6 0 0 0.0 15.7 7.150 0.500 +0.000

Maximum flow rate error at nodes : 0.00153 L/min


Maximum pressure drop error at nodes : 0.00000 bar
Maximum pressure drop error in loops : 0.00000 bar
Overall head flow balance error : 0.00100 %

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 4

180 110
160
150
140
130
120
170 100

190

200

210

220

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email info@canutesoft.com Web www.canutesoft.com
Program FHC

You might also like