Pumps Head calculations

MASAA AC PLANT AT AGYAD PROJECT


PUMPS HEAD CALCULATIONS
pumps head calcul-PP-01-RF-01

0 1 (Schedule Q = 9.2 I/S , H= 21.8 mt)

Chilled Equivlent
Chilled Pipe Wall Cross Pipe
Pipe No. of Out side water length for Total head loss
Fittings type water size thickness sectional section
section fitting dia mm velocity fitting& length ft ft
flow Lps. mm mm. area m2 length m
m/s valves ft
Pipe 42.0
Tee branch 12 180
363.6 17.461
Elbow 90 6 45
SK 42.0 225
9.2 80 88.9 5.49 0.0047661 1.93
Check valve 1 1.990 NIBCO(Approved)
Globe valve 1 4.320 NIBCO (will submit)
Gate valve 4 0.720 NIBCO (will submit)

Suction Diffuser 1 2.700 Bell&Gossett(Resubmit)

Air Sep WATER PRESSURE DROP THROUGH AIR SEPARATOR (FT) 1.82 Wessels (Approved)
Gate valve 2 9.2 80 88.9 5.49 0.0047661 1.93 0 0.360
Pipe 70.0
Tee branch 2 30
306.0 14.695
1 2 Elbow 90 6 9.2 80 88.9 5.49 0.0047661 1.93 45
SK 70.0 75
Motorized valve 2 0.360
Pipe 28.0
2 3 Tee branch 2 6.9 80 88.9 5.49 0.0047661 1.45 30 122.4 3.450
SK 28.0 30
Pipe 28.0
3 4 Tee branch 2 4.6 80 88.9 5.49 0.0047661 0.97 30 122.4 1.628

SK 28.0 30
Pipe 38.0
Tee branch 2 30
4 5 2.3 80 88.9 5.49 0.0047661 0.48 155.4 0.573
Elbow 90 2 15
SK 38.0 45
Gate valve 2 2.3 80 88.9 5.49 0.0047661 0.48 0 0.023
Balance valve 1 2.3 80 88.9 5.49 0.0047661 0.48 0 0.246

CENT
WATER PRESSURE DROP FOR COIL OF COMPRESSOR CHILLER (FT),5000 TR 14.50 YORK (Approved)
CHILLER

SCROLL
WATER PRESSURE DROP THROUGH SCROLL CHILLER (FT), 60 TR 14.98 YORK (Resubmit)
CHILLER

TOTAL PRESSURE DROP FOR NETWORK (FT) 79.827

TOTAL PRESSURE DROP FOR NETWORK (MT) 24.3374

TOTAL PRESSURE DROP FOR NETWORK (MT) WITH SAFETY 25% 30.4218

Remarks
*Equivlent length for fitting from carrier standard.