In recent years a number of failures of transformers and reactors have occurred due to copper sulphide formation in the windings.
The failures affected different classes of interaction. Sometimes increased corrosivity is, at least partly, the same bivalent sulphur
equipment [1, 2, 3, 4, 5, 6]. They involved is seen in the traditional meaning of the compounds that act as peroxide scavengers
mostly equipment operating at elevated word, i.e. with blackening of copper and (and in that role suppress the oxidation of oil)
average temperature, although (with some silver sur faces. This may be a serious that may also have corrosive effects. They
exceptions) within accepted temperature problem in some cases. However, the larger may possibly, under some conditions, be
limits, and were normally without warning problem seems to be the precipitation of corrosive in themselves, but there is the more
from commonly used oil tests, including DGA. semiconductive copper sulphide in or on likely possibility that more aggressive sulphur
Several different oils were involved. All oils organics, such as mercaptans, are formed
the solid insulation, something which cuses
fulfilled present IEC and ASTM specifications during operation.
significant deterioration to its dielectric
when new but, at least in some cases, the
properties. In some cases growth of copper Accessibility of copper is also an important
oils changed during operation, turning
sulphide is found starting at the innermost factor. Conductors without enamel are clearly
corrosive and causing growth of Cu2S. Today
layer of covering paper on the conductors, more vulnerable to growth of copper sulphide
there are no reliable and universally known
eventually growing through several layers. from the inside, but even with enameled
and accepted methods to identify units at
In other cases copper sulphide is found conductors copper may be available
risk or oils that may cause problems, nor
deposited on the outside of the conductors elsewhere to be dissolved, transported
diagnostic techniques to identify already
paper wrapping, or on spacers. Examples are and eventually precipitated as sulphide. All
affected equipment. There is so far quite
chemical reactions proceed at a higher rate
a low level of general understanding shown in Figs. 1 - 3.
when the temperature increases, and there
of the phenomena which include the
The details of the chemical reactions leading certainly appears to be some correlation
influence of transformer materials, temporal
to these phenomena are not yet well known. with temperature, but sulphide formation is
development, temperature dependence,
Some active sulphur containing compounds not always observed in the areas with highest
service conditions, impact of design, etc..
are obviously needed. There are several temperature, nor are there usually any signs
Some mitigation techniques, namely the
possible sources of such compounds, of very high temperature (such as low DP
addition of metal passivators, have been tried
including contamination from unsuitable values of paper) where the sulphide has been
with apparent success, but more knowledge
materials and handling of the oil, but it formed. A low oxygen content of oil seems to
of possible side effects and long term stability
is already clear that some oils contain promote sulphide formation. Such conditions
of these is needed.
are found primarily in sealed units, and
significant amounts of potentially reactive
Copper sulphide formation unsealed units with uninhibited oil, especially
sulphur. Generally sulphur compounds have
working at high and constant load.
There seem to be several different been considered important for the oxidation
manifestations of the copper - sulphur stability of oils. There are indications that it Which units are at risk