Professional Documents
Culture Documents
energy recovery
in the Gulf
region climate
Il recupero di calore dall'aria espulsa nel
clima degli Emirati Arabi Uniti e del Qatar
The air to air energy recovery in the UAE and
Qatar climate
MICAELA RANIERI1, MICHELE VIO2
1
Rhoss, Irsap Group Codroipo (Ud)
2
HVAC Designer, Rhoss Irsap Group R&D consultant ,
SUMMARY
Air to air heat recovery is an essential aspect for air-conditioning systems in United
Arab Emirates (UAE), not only for the environmental condition but also for the features
of used HVAC systems.
Indeed, heat recovery units have to guarantee supply airs post-heating in addition
to reduce energy costs.
This paper compares energy performance of 10 different solutions.
Key words: air to air energy recovery, energy efficiency, HVAC systems
SUMMARY
The air to air energy recovery is a key aspect in the buildings climatization in the
UAE, not only for the climate, but also for the peculiarities of the used HVAC systems.
In fact, the heat recovery units must ensure the post-heating of supply air, in addition to
reducing energy costs
The paper compares the energy performance of 10 different solutions..
Key words: air to air energy recovery, energy efficiency, HVAC systems
1. INTRODUCTION
Exhaust airs heat recovery have an important effect on energy performance of air-
conditioning systems, especially in regions with extreme weather condition either warm-
er or colder than Mediterranean weather.
To the UAEs hot weather its added a more widespread of air conditioning system
with completely different features from Europeans type.
In the UAE there is an higher spread of all-air-conditioning systems and also they
are completely different from those which are utilized in the old country.
The air to air energy recovery in the UAE and Qatar climate
Furthermore, UAEs indoor condition are extremely different from ours. They are
used to having 22C 23C indoor temperature with 50% of relative humidity for all the
year, without take care of energy consumption with the use of outdoor air.
Therefore, the design of heat recovery system which utilize outdoor air have to be
considered carefully to optimize energy efficiency.
In Figure 1 there are no distinction between night and day values because usually
in UAE night temperatures arent too much lower than daily temperatures. The two dif-
ferent charts for daily and night temperatures havent been shown only for space reason.
Outdoor air temperature never decreases over 10C, with the exception of Doha where it
is reached 9C only for few hours per year during the night.
The air to air energy recovery in the UAE and Qatar climate
The most frequent average temperatures are included between 20C and 30C,
with a symmetrical extension on the two adjacent bands (10C-20C and 30C-40C)
and exceeding 40C for at least 1% or 2% of the time.
If we decide to do a comparison with a city like Bari of the south of Italy, the out-
door air temperature exceed 30C only for the 4% of the time, meanwhile for the 20%
of the time it never reachs 10C, for the 46% it is included between 10C and 20C, and
for the remaining 30% it is included between 20C and 30C (these values are extracted
from Enea and CTI data)
Figure 2: Trend of outdoor air relative humidity in Dubai, Abu Dhabi and Doha
The air to air energy recovery in the UAE and Qatar climate
For space reason Figure 2 shows annual average value without any distinction for
single month which values have been utilized during the following energy analysis.
This figure shows that during night hours and when outdoor air temperature is
higher than 30C Dubais weather is the dampest one. During night hours and until 35C
Abu Dhabis relative humidity becomes more similar to Dubais and it becomes higher
when outdoor air temperature decrease over 28C.
When outdoor air temperature exceeds 27C Dohas weather is drier.
Figure 3 shows the percentage of hours during the year when a certain specific
humidity occurs within interval of 5g/kg and it is useful to know the different problems
connected to the air conditioning in UAE.
It is incredible the amount of hours during the year that occur with an outdoor air
specific humidity higher than 15g/kg, which is rare even in the hottest Italian cities
(15g/kg correspond to 35C with 42% relative humidity or 30C with 56% relative hu-
midity).
Furthermore, if we consider that during all the year inside the buildings 23C and
50% relative humidity (x=8.7g/kg) are maintained against ours 26C and 55%
(x=11.6g/kg), it is clear that x between outdoor air and indoor air are often higher than
7 g/kg and they reach even 22g/kg, against the Italian maximum of 6 g/kg which is
reached only for few hours per year.
As an example, in Bari the specific humidity is lower than 10g/kg for about the
55% of the time, it is higher than 15g/kg for a percentage of hours lower than 1% and for
the remaining 45% it is included between 10 and 15g/kg (these values would be extract-
ed from Eneas and CTIs average years data).
been spread rotary heat recovery units made by different materials which are able to re-
duce potential contamination drastically with molecular sieve of 3.
Experiment made in SUVA (Swiss Accident Insurance Institute) have shown that
Carry Over decrease from 24% to 3% during summer season and from 36% to 4% dur-
ing winter season [Schreck, 2012]. These low values permit to extend rotary heat recov-
erys application. However, Carry Overs value isnt zero, therefore for those critical ap-
plications that require to avoid supply airs contamination alternative solution has to be
found.
4.2.1. Heat recovery for the supply airs post-heating from exhaust air
The heat recovery for the supply airs post-heating it is usually made by heat re-
covery sensible wheels in series and before the main heat exchanger, as it is shown in the
2a solution of Figure 5. In this way it is allowed the heat transfer from exhaust air to the
The air to air energy recovery in the UAE and Qatar climate
supply air after the cooling coil. For furthermore information look at the bibliography
[Vio, 2015, 314 to 321 slides].
4.2.2. Heat recovery for the supply airs post-heating from supply air
The heat recovery from the same supply air consists on the hydraulic combination
between two coils: one located after the main heat recovery unit and the other after the
cooling coil.
This kind of system is known as RAC (Run Around Coil) and it could be made
through hydraulic connection either as it is shown in 2b and 4b solution of Figure 5 or
through pipe connection that uses phase changing fluid. The second solution called
Horse Pipe Shoe for the typical horseshoes shape of the pipe connection around the
cooling coil its used in UAE but has a very low efficiency. For furthermore information
look at the bibliography [Vio, 2015, 301 to 313 slides].
Figure 4: Comparison between heat recovery for the post-heating from exhaust air and supply air
The air to air energy recovery in the UAE and Qatar climate
5. ENERGY ANALYSIS
Figure 4 shows energy power needed in punctual condition. Only an energy analy-
sis allows to consider all the different solutions.
perdite di carico
Soluzione Tipologia scambiatore efficienza scambiatore
totali [Pa]
solution 1 static heat recovery unit, either plate heat exchanger or twin recovery
coils, which has to be used when there is the necessity to avoid leakage
between exhaust air and supply air
solution 2 enthalpy wheel which is the most common solution that is adopted with
UAEs weather through series of two enthalpy wheels to improve total
efficiency
solution 3 series of two enthalpy wheels to improve total efficiency
solution 4 solution 1 with the addition of indirect adiabatic recovery
solution 5 double indirect adiabatic recovery [Vio, 2015, 72 to 73 slides] which is
made with the series of two solution 2s systems
6.1 Percentage of recovered energy in respect to the required energy for the sup-
ply airs treatment
Figure 7 shows the percentage of recovered energy in respect to the required ener-
gy for the supply airs treatment.
The air to air energy recovery in the UAE and Qatar climate
Figure 7: Percentage of recovered energy in respect to the required energy for the treatment
Dubais values are similar to Dohas: in Qatars capital where the weather is the
dampest of UEAs cities only sensible heat recovery units performance increase and la-
tent heat recovery units performance decrease. However, the second type is always the
one which has the best performance in both the areas as a consequence of high level of
outdoor air specific humidity.
It is possible to recovery more than 50% of supply airs cooling, which is impossi-
ble with Mediterranean weather conditions [Vio, 2015, 109 to 113 slides].
Solutions 3 and 5 increase the heat recoverys percentage with an higher complexi-
ty for series of heat recovery units.
Rotary wheels are the heat recovery units which gave the best results and it is
shown that RAC system is always a positive choice. When it is impossible to use enthal-
py wheels, adiabatic indirect heat recovery systems (solution 4 and solution 5) give bet-
ter performance than the only sensible hear recovery (solution 1)
Solution 3 and solution 5, which consider heat recoverys stages in series, improve
energy performance with an higher complexity than the other.
Figure 10: Solution 2as energy saving depending on ambient load line and chillers efficiency (Dohas weath-
er)
Figure 10 shows results for Dohas weather which however is similar to Dubais.
As it is shown, the use of RAC in combination to the enthalpy wheel (solution 2b)
is always more convenient than the use of sensible wheel for the post-heating (solution
2a). This convenience increases with the ambient load lines reduction and therefore
with the increase of latent endogenous load in comparison to the sensible load.
This result is explained with the higher temperature which is needed after the post-
heating.
The air to air energy recovery in the UAE and Qatar climate
After a certain point with the increase of ambient load line, air temperature after
the cooling coil starts to increase and air temperature after post-heating decreases.
The advantages that occur with the variation of chillers efficiency are almost the
same.
Solution 4b is the best choice when it is impossible to use enthalpy wheels. Energy
performances are always lower in UAEs weather (it is the opposite with Mediterrane-
ans) but they are always higher than the sensible heat recovery units performance.
These performance become closer to solution 2as performance as lower ambient load
lines values are and as higher chillers efficiency is.
CONCLUSION
United Arab Emirates have a particular weather, it is hot and damp simultaneously
and so completely different from Mediterraneans weather. Also the common types of
air-conditioning systems are different; therefore heat recovery units from exhaust air
have to be adopted.
The energy analysis has confirmed importance of enthalpy heat recovery units in
UAE. Meanwhile, it has shown the huge possibilities to improve the situation using heat
recovery systems for supply airs post-heating which are more efficient than the common
sensible wheel, like for example the heat recovery Run Around Coil with hydraulic con-
nections. It has shown that the performance increase over 10%.
BIBLIOGRAPHY
M. Vio, 2015: "Heat recovery on the exhaust air", Delfino edition, available for consul-
tation on the Aicarr website
T. Schreck, 2012: "Carry over Test in Eventus HM1 Molecular Sieve 3 vs. Silica Gel",
Eventus technical documentation
AiCARR, 2011, " AiCARR position paper on D.Lgs. 28/11 for the issue regarding the
renewable thermal sources, downloadable from AiCARR website.
THE AIR TO AIR
ENERGY RECOVERY
IN THE GULF REGION
CLIMATE