Problme no. 1
a) On divise le rseau en trois zones:
B1 T1 T2 B4
G1 B2 B3 M1
Ligne 1 500 MVA
345 kV, 200 km 15 kV
750 MVA Z = (6.4 + j70) X m = 0.2 pu
13.8 kV -4 S
750 MVA Y = j4.2 x 10 1000 MVA
X g = 0.2 pu 13.8kV / 345kV Y 345kV Y / 15kV 150 MW
Zeq1 80 Mvar
= (0.01 + j0.16) pu Z eq2 = (0.01 + j0.16) pu
Zone 3: VbaseLL3 = 15 kV
I base3 = 100 ( 3 15 ) = 3.849 kA Z base3 = ( 15 ) 100 = 2.25
2
Limpdance en pu du gnrateur:
X Gpu = 0.2 ---------- --------- = 0.0267 pu
13.8 2 100
13.8 750
Limpdance en pu du moteur:
X Mpu = 0.2 ------ --------- = 0.04 pu
15 2 100
15 500
Limpdance en pu du transformateur T1:
Z eq1pu = ( 0.01 + j0.16 ) ---------- --------- = 0.0013 + j0.0213 pu
13.8 2 100
13.8 750
Limpdance en pu du transformateur T2:
Z eq2pu = ( 0.01 + j0.16 ) ------ ------------ = 0.001 + j0.016 pu
15 2 100
15 1000
Limpdance srie en pu de la ligne 1:
( 6.4 + j70 )
Z pu = ------------------------------- = 0.0054 + j0.0588 pu
1190.3
Limpdance en pu de la charge ( la barre B4):
(------------
14 )
2
( 14 )
- + j -------------
2
150 80
Z ch = ----------------------------------------- = ( 0.581 + j1.089 ) pu
2.25
page 1
j0.0267 B1 T1 B2 Ligne 1 B3 T2 j0.04
B4
+ 0.0013 + j0.0213 0.0054 + j0.0588 0.0010 + j0.0160 +
Eg Em
- -
0.581 + j1.089
Charge Moteur
Gnrateur
1
I 1 = --- [ 34.64 0 + 28.867 270 + 23.09 90 ] = 11.547 j1.926 = 11.706 9.5
3
A
1
I 2 = --- [ I a + a I b + aI c ]
3
2
avec a = e
j 2 3
1
I 1 = --- [ 34.64 0 + 28.867 30 + 23.09 30 ] = 26.545 + 0.963 = 26.563 2.0 A
3
page 2
Problme no. 2
a) Conducteur ACSR Martin 54/19, r = 1.8085 cm, GMR = 1.46 cm, R (50C) = 0.0502 /km
Le rayon moyen gomtrique des faisceaux:
GMR
faisceau = 3 GMR
cond d2 = 3 1.46 502 = 15.3968 cm
La ligne est transpose. La distance moyenne gomtrique des conducteurs:
GMD =
3 D D 2D = 3 10 10 20 = 12.60 m
R
1 /km
0.0502
= ---------------- = 0.0167
3
C V
1 1 ( 1.2838 108 ) ( 288.68 103 )
q = ------------- = --------------------------------------------------------------------- = 3.706 10
6
C/m
1000 1000
page 3
q/3
d = 0.5 m d = 0.5 m
q/3 q/3
d = 0.5 m
Le champ lectrique la surface dun conducteur est la somme vectorielle des champs lectriques
crs par les trois conducteurs du faisceau:
( q 3) r
E rmax = -------------- 1 + 3 ---
20 r d
6
1.2354 10 1.8085
E rmax = ----------------------------------------------------------
12 - 1 + 3 ---------------- = 13048
50
V/cm
2 ( 8.854 10 )1.8085
kV/cm
E rmax = 13.048
On peut remarquer que la contribution des deux autres conducteurs est ngligeable cause de la
grande distance entre les conducteurs (d = 50 cm) par rapport au rayon du conducteur (r =
1.8085 cm)
page 4
Problme no. 3
a) Modle de ligne moyenne (circuit quivalent en pi nominal):
IS Z IR
Paramtres de transmission (ABCD):
+
A = D = 1 + YZ
+
-------
2-
VS Y/2 Y/2 VR
B=Z
- - C = Y 1 + YZ
-------
4 -
C = Y 1 + YZ
-------
- j0.881 10 3 ) ( 22 + j116.25 )- = 4.269 106 + j8.584 10 4 S
= j0.881 103 1 + (----------------------------------------------------------------------
4 4
page 5
La tension V R dsire: V R = 230 3 = 132.79 kV
V R 132.79 0 132.79
On a: V R = 132.79 0 et I R = --------
jX L - = --------------------------
jX L - = j ---------------
X L -
V S = 140 s
132.79- = 140
V S = AV R + BI R = A ( 132.79 ) + B j ---------------
On a la relation suivante:
X s
L
132.79- = 140
( 0.9488 + j0.0097 )( 132.79) + ( 22 + j116.25 ) j ---------------
X L
s
15437- j ---------------
( 125.99 + j1.29 ) + -------------- 2921.4- = 140
On dduit:
X L X L
s
VS VR A VR 2
Z - cos ( Z ) --------------------------
P R = -------------------------- Z - cos ( Z A )
P R = 230 230 0.95- cos ( 79.3 35 ) 0.9488
---------------------------------------- ( 230 0.95 )2- cos ( 79.3 0.6 )
-------------------------------------------------------
118.31 118.31
P R = 304 75 = 229 MW
page 6
Problme no. 4
a) La nature des barres du rseau:
j0.5
0.0054+j0.0588
j0.5
B4
0.0013+j0.0214
B3
Y11 Y 12 0 0 0 0
Y 12 Y 22 0 0 Y 25 0
0 0Y33 Y 34 0 0
La matrice Ybus:
0 0 Y 34 Y 44 Y 45 0
0 Y 25 0 Y 45 Y 55 Y 56
0 0 0 0 Y 56 Y 66
Les lments non-nuls sont donns:
1 1
Y 11 = ----------------------------------- Y 12 = Y 21 = -----------------------------------
0.002 + j0.032 0.002 + j0.032
1 1 1
Y 22 = ----------------------------------- + ----------------------------------------- + j0.5 Y 25 = Y 52 = -----------------------------------------
0.002 + j0.032 0.0054 + j0.0588 0.0054 + j0.0588
1 1
Y 33 = ----------------------------------------- Y 34 = Y 43 = -----------------------------------------
0.0013 + j0.0214 0.0013 + j0.0214
page 7
1 1 1
Y 44 = ----------------------------------------- + ----------------------------------------- + j0.5 Y 45 = Y 54 = -----------------------------------------
0.0013 + j0.0214 0.0054 + j0.0588 0.0054 + j0.0588
1 1 1
Y 55 = ----------------------------------------- + ----------------------------------------- + ----------------------------------------- + j0.5 + j0.5 + j0.5
0.0054 + j0.0588 0.0054 + j0.0588 0.0054 + j0.0588
1
Y 56 = Y 65 = -----------------------------------------
0.0054 + j0.0588
1
Y 66 = ----------------------------------------- + j0.5
0.0054 + j0.0588
c) Commentaires sur les rsultats de calcul de logiciel PowerWorld:
- Les tensions aux barres sont dans les limites acceptables (0.95, 1.05) except les barres B5 et
B6 o les tensions sont de 0.89 pu et 0.79 pu respectivement.
- Les transformateurs fonctionnent dans les limites permises.
- Les lignes fonctionnent dans les limites permises.
La ligne no. 1 est sous utilise (elle transport 37.5% de sa capacit)
La ligne no. 2 est sous utilise (elle transport 36.7% de sa capacit)
La ligne no. 3 est sous utilise (elle transport 47.7% de sa capacit)
Les pertes dans les quipements:
Transformateur T1 : 2.46 MW
Transformateur T2 : 2.36 MW
Ligne 1 : 7.17 MW
Ligne 2 : 8.17 MW
Ligne 3 : 10.81 MW
Les problmes et solutions
1) La tension la barre B5 (0.89 pu) est infrieure la valeur acceptable 0.95. On peut connecter
cette barre un banc de condensateurs afin daugmenter la tension.
2) La tension la barre B6 (0.79 pu) est infrieure la valeur acceptable 0.95. On peut connecter
cette barre un banc de condensateurs afin daugmenter la tension.
page 8