still indicates that there is high lube Alarm on high lube oil reservoir level.
pump pressure.
There are two main lube oil pumps of MBV30 - Lift Oil Control
which one must be running prior to This system has been designed to provide lift
starting. Which lube oil pump is to the rotor during turning gear operation. It is
running depends on which lube oil required in order to be on turning gear (low or
pump has been selected. If the lube high speed). In the event the unit drops off
oil pump which is selected isn't turning gear with the unit hot, rotor bow may
running, an alarm is generated. occur. To prevent rotor damage, the turning
When all of the above conditions are gear operation is prevented for a period of 24
met, a GT start is permitted. hours. After this time, it is the operators
There are two vapor extractors of responsibility to ensure the lift oil system is
which one must be running prior to running and that a manual check is done to
starting. Which vapor extractor is ensure that the rotor is free to rotate before
running depends on which extractor restoring turning gear operation and removing
has been selected. If the vapor the rotor lock from the control system.
extractor which is selected isn't The following conditions generate an alarm:
running, an alarm is generated.
Low pressure.
An alarm is also generated and the GT is
tripped whenever there isn't adequate lube oil Lift oil system failure.
pressure. Two pressure switches and one
pressure transducer are monitored to MBX00 Common Hydraulic
determine if low lube pressure exists (2 out of Control
3). The starter is permitted to be run as long
Hydraulic supply pressure is monitored as
as there is adequate lube oil pressure. If
part of the ready to start conditions and
either pressure switch or pressure transducer
alarms on low pressure.
deviates from the other two, an alarm is
generated indicating sensing device failure. There are two hydraulic pumps. Which
hydraulic pump is running depends on which
The following conditions generate an alarm:
hydraulic pump has been selected. If the
The engine is not permitted to start hydraulic pump which is not selected is
unless the temperature of the oil in running, an alarm is generated.
the reservoir is 70 F (21 C) or
above. MBX01 Hydraulic Supply
The lube oil temperature reaches 145 System Monitoring
F (63 C). Hydraulic supply temperature is monitored
The engine unloads when the lube oil and there are alarms on both high and low
temperature reaches 150 F (66 C). temperature.

The engine trips when the lube oil Hydraulic supply pressure is monitored and
temperature reaches 155 F (68 C). alarms on high pressure.
The hydraulic reservoir level is monitored and
MBV20W - Water Cooled Lube Oil alarms on a low or extra low level. There are
The control valve that controls the lube oil also alarms on high hydraulic pump filter DP
temperature is a fully automatic, 3-way fluid and high hydraulic recirculation filter DP.
control valve for mixing applications. The valve The hydraulic system cooling fan and tank
is supplied with the temperature element heater are controlled based on temperature.
assemblies factory-set to the nominal Both the cooling fan and heater must be in
temperature setting 110 F (43.33 C)