You are on page 1of 6

DIESEL GENERATOR SET

STANDBY
528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT C18 ATAAC DIESEL ENGINE
Low Fuel consumption Utilizes ACERT Technology
Reliable, rugged, durable design
FULL RANGE OF ATTACHMENTS Field-proven in thousands of applications
Wide range of bolt-on system expansion worldwide
attachments, factory designed and tested Four-stroke-cycle diesel engine combines
Flexible packaging options for easy and cost consistent performance and excellent fuel
effective installation economy with minimum weight
Electronic controlled governor
SINGLE-SOURCE SUPPLIER
Fully prototype tested with certified torsional CAT GENERATOR
vibration analysis available Matched to the performance and output
characteristics of Cat engines
WORLDWIDE PRODUCT SUPPORT
Load adjustment module provides engine relief
Cat dealers provide extensive post sale support
upon load impact and improves load acceptance
including maintenance and repair agreements
and recovery time
Cat dealers have over 1,800 dealer branch stores
UL 1446 Recognized Class H insulation
operating in 200 countries
The Cat SOSSM program cost effectively detects CAT EMCP 4 CONTROL PANELS
internal engine component condition, even the Simple user friendly interface and navigation
presence of unwanted fluids and combustion Scalable system to meet a wide range of
by-products customer needs
Integrated Control System and Communications
Gateway
STANDBY 528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet Air cleaner

Cooling Package mounted radiator

Exhaust Exhaust flange outlet [ ] Industrial [ ] Residential [ ] Critical Mufflers

Fuel Primary fuel filter with integral water separator


Secondary fuel filters
Fuel priming pump
Generator Matched to the performance and output [ ] Oversize and premium generators
characteristics of Cat engines [ ] Permanent magnet excitation (PMG)
Load adjustment module provides engine relief upon [ ] Internal excited (IE)
load impact and improves laod acceptance and [ ] Anti-condensation space heaters
recovery time
IP23 protection
Power Termination Bus bar [ ] Circuit breakers, UL listed
[ ] Circuit breakers, IEC compliant

Control Panel EMCP 4 Genset Controller [ ] EMCP 4.2


[ ] EMCP 4.3
[ ] EMCP 4.4
[ ] Local and remote annuniciator modules
[ ] Load share module
[ ] Digital I/O module
[ ] Remote monitoring software
Mounting Rubber vibration isolators

Starting/Charging 24 volt starting motor [ ] Battery chargers


Batteries [ ] Oversize batteries
[ ] Jacket water heater
[ ] Heavy duty starting system
[ ] Charging alternator
General Paint - Caterpillar Yellow except rails and radiators The following options are based on regional and
gloss black product configuration:
[ ] Seismic Certification per Applicable Building Codes:
IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
[ ] UL 2200 package
[ ] EU Certificate of Conformance (CE)
[ ] CSA Certification
[ ] EEC Declaration of Conformity
[ ] Narrow, wide or skid base
[ ] Sound attenuated, weather protective or high
ambient weather protective enclosures
[ ] Single or dual wall integral fuel tanks
[ ] Single or dual wall sub-base fuel tanks
[ ] Integral & sub-base UL listed dual wall fuel tanks
[ ] Automatic transfer switches (ATS)

2 February 08 2013 14:32 PM


STANDBY 528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts

SPECIFICATIONS

CAT GENERATOR CAT EMCP 4 SERIES CONTROLS


Frame size.................................................................LC7024F EMCP 4 controls including:
Excitation..................................................Internal Excitation - Run / Auto / Stop Control
Pitch.............................................................................. 0.6667 - Speed and Voltage Adjust
Number of poles...................................................................4 - Engine Cycle Crank
Number of bearings...................................... Single bearing - 24-volt DC operation
Number of Leads.............................................................. 012 - Environmental sealed front face
Insulation....................... UL 1446 Recognized Class H with - Text alarm/event descriptions
tropicalization and antiabrasion Digital indication for:
- Consult your Caterpillar dealer for available voltages - RPM
IP Rating.........................................................Drip Proof IP23 - DC volts
Alignment.............................................................. Pilot Shaft - Operating hours
Overspeed capability........................................................150 - Oil pressure (psi, kPa or bar)
Wave form Deviation (Line to Line)................................. 2% - Coolant temperature
Voltage Regulator.............................. Single Phase Sensing - Volts (L-L & L-N), frequency (Hz)
Voltage regulation............Less than +/- 1/2% (steady state) - Amps (per phase & average)
Less than +/- % (w/ 3% speed change) - ekW, kVA, kVAR, kW-hr, %kW, PF (4.2 only)
CAT DIESEL ENGINE Warning/shutdown with common LED indication of:
- Low oil pressure
C18 ATAAC, I-6, 4-Stroke Water-cooled Diesel
- High coolant temperature
Bore........................................................ 145.00 mm (5.71 in)
- Overspeed
Stroke....................................................... 183.00 mm (7.2 in)
- Emergency stop
Displacement.........................................18.13 L (1106.36 in3)
- Failure to start (overcrank)
Compression Ratio....................................................... 14.5:1
- Low coolant temperature
Aspiration......................................... Air-to-Air Aftercooled
- Low coolant level
Fuel System.................................... Electronic unit injection
Programmable protective relaying functions:
Governor Type................ Caterpillar ADEM control system
- Generator phase sequence
- Over/Under voltage (27/59)
- Over/Under Frequency (81 o/u)
- Reverse Power (kW) (32) (4.2 only)
- Reverse reactive power (kVAr) (32RV)
- Overcurrent (50/51)
Communications:
- Four digital inputs (4.1)
- Six digital inputs (4.2 only)
- Four relay outputs (Form A)
- Two relay outputs (Form C)
- Two digital outputs
- Customer data link (Modbus RTU) (4.2 only)
- Accessory module data link (4.2 only)
- Serial annunciator module data link (4.2 only)
- Emergency stop pushbutton
Compatible with the following:
- Digital I/O module
- Local Annunciator
- Remote CAN annunciator
- Remote serial annunciator

3 February 08 2013 14:33 PM


STANDBY 528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts

TECHNICAL DATA

Open Generator Set - - 1500 rpm/50 Hz/400 Volts DM9822


Low Fuel Consumption

Generator Set Package Performance


Genset Power rating @ 0.8 pf 660 kVA
Genset Power rating with fan 528 ekW
Fuel Consumption
100% load with fan 135.0 L/hr 35.7 Gal/hr
75% load with fan 100.9 L/hr 26.7 Gal/hr
50% load with fan 69.5 L/hr 18.4 Gal/hr
Cooling System1
Air flow restriction (system) 0.12 kPa 0.48 in. water
Air flow (max @ rated speed for radiator arrangement) 373 m/min 13172 cfm
Engine Coolant capacity with radiator/exp. tank 54.8 L 14.5 gal
Engine coolant capacity 20.8 L 5.5 gal
Radiator coolant capacity 34.0 L 9.0 gal
Inlet Air
Combustion air inlet flow rate 34.2 m/min 1207.8 cfm
Exhaust System
Exhaust stack gas temperature 571.1 C 1060.0 F
Exhaust gas flow rate 102.4 m/min 3616.2 cfm
Exhaust flange size (internal diameter) 203 mm 8 in
Exhaust system backpressure (maximum allowable) 10.0 kPa 40.2 in. water
Heat Rejection
Heat rejection to coolant (total) 169 kW 9611 Btu/min
Heat rejection to exhaust (total) 504 kW 28662 Btu/min
Heat rejection to aftercooler 91 kW 5175 Btu/min
Heat rejection to atmosphere from engine 84 kW 4777 Btu/min
Heat rejection to atmosphere from generator 39.1 kW 2223.6 Btu/min
Alternator2
Motor starting capability @ 30% voltage dip 1376 skVA
Frame LC7024F
Temperature Rise 163 C 293 F
Lube System
Sump refill with filter 38.0 L 10.0 gal
Emissions (Nominal)3
NOx mg/nm3 3486.4 mg/nm
CO mg/nm3 507.4 mg/nm
HC mg/nm3 1.7 mg/nm
PM mg/nm3 4.7 mg/nm
1
For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2
Generator temperature rise is based on a 40 C (104 F) ambient per NEMA MG1-32. Some packages may have oversized generators
with a different temperature rise and motor starting characteristics.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel
with 35 API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

4 February 08 2013 14:33 PM


STANDBY 528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC,
2004/108/EC
Standby - Output available with varying load for the
duration of the interruption of the normal source power.
Average power output is 70% of the standby power
rating. Typical operation is 200 hours per year, with
maximum expected usage of 500 hours per year.

5 February 08 2013 14:33 PM


STANDBY 528 ekW 660 kVA
50 Hz 1500 rpm 400 Volts

DIMENSIONS

Package Dimensions
NOTE: For reference only - do not use for
Length Information not installation design. Please contact
Width available at this time. your local dealer for exact weight
and dimensions. (General
Height Dimension Drawing #3930335).

www.Cat-ElectricPower.com
Performance No.: DM9822
2013 Caterpillar
All rights reserved.
Feature Code: C18DF1E
Materials and specifications are subject to change without notice.
Gen. Arr. Number: 3921383 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the
Source: European Sourced "Power Edge" trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.
February 08 2013 21376158
6

You might also like