You are on page 1of 6

X International Symposium on

Lightning Protection
9th-13th November, 2009 Curitiba, Brazil

COMPARISON OF LOW FREQUENCY RESISTANCE AND LIGHTNING


IMPULSE IMPEDANCE ON TRANSMISSION TOWERS
William A. Chisholm1, Emanuel Petrache2, Fabio Bologna3
1
Kinectrics/UQAC, Canada W.A.Chisholm@ieee.org
2
Kinectrics, Canada Emanuel.Petrache@kinectrics.com
3
EPRI, USA fbologna@epri.com

Abstract A new field instrument, the Zed-Meter, has been the geometric resistance, and for transmission tower
developed to test the low-current lightning impulse footings the geometric resistance is dominant.
impedance Z of transmission tower footings and ground
electrodes. Surge impedance of test leads provided effective In order to understand the response of the transmission
reaction electrodes for the measurements, even when
tower to lightning surges, a new test method [5][6] was
ungrounded on frozen soil. Cross-calibration studies were
carried out using a variety of low-frequency measurements proposed and developed. This test method used a
of footing resistance Rf to establish the ratio Z : Rf for compact current impulse source and distributed leads as
compact and distributed electrodes. reaction antennas to measure the transient impedance Z of
transmission tower ground electrodes in-situ.
1 INTRODUCTION
This paper describes refinements of the test method [6] to
It has been traditional to measure low-frequency improve repeatability and then reports the results obtained
resistance Rf of transmission tower structures using low from Zed-Meter tests on 70 different transmission
currents and to use this resistance in estimates of structures, ranging in low frequency resistance from
transmission lightning performance. The measured 0.1 to 200 .
values of Rf can be adjusted for ionization and impulse
effects [1] to give: 2 PREVIOUS STUDIES
Low-current transient impedance Z;
High-current transient impedance ZI . Many researchers have carried out studies of the impulse
response of ground electrodes. Generally, experiments
Theoretically [2][3] and experimentally, a number of have been carried out on isolated electrodes. Analysis has
factors affect the ratios Z : Rf and ZI : Rf, including: considered either compact or distributed electrodes.
The contribution of ground plane surge response
and series inductance of distributed electrodes, 2.1 Impedance versus time for rods
which tend to increase the ratio Z : Rf ;
Reductions in the soil resistivity with increasing Bellaschi [7] applied lightning impulses in the range of
frequency, and the effect of displacement current 0.6 to 9 kA to driven rods. A high-voltage impulse
in the soil dielectric, which both tend to reduce generator, with a plan view in Fig. 1, was used.
the ratio Z : Rf ;
Ionization when local electric field gradients The typical voltages and currents were measured with a
exceed 150-300 kV/m in soil, increasing the voltage divider (VD) and cathode ray oscilloscope
apparent size of small electrodes and reducing (CRO). Some typical results for driven rods are shown in
the ratio ZI : Rf as current increases. Fig. 2. For currents in the range 1.5 to 6.5 kA in
waveforms AF, AX and BJ, the voltage and current
Recent work [4] has suggested that, while ionization can waveforms were similar, suggesting that an instantaneous
play an important role in the response of small electrodes ratio ZI(t)=v(t)/i(t) was constant for the 6x13 s or
such as a single driven rod, for the typical 5 to 50 m 12x50s test waves used in this work. The ground
dimensions of transmission tower foundations and ground around the test rod exploded in waveform BT, giving a
electrodes the role of ionization is limited. A recent sharp reduction in the ZI (t) ratio after 15 s.
analysis suggests that, for extensive electrodes, the
ionization effect reduces the contact resistance but not

329
in close agreement. Later at 10-25 s, there is a broad
minimum of ZI (t)=27 s for 60 kA and 22 at 120 kA.
Simplified [1] and detailed [8] modelling also suggest that
surge currents of more than 100 kA are needed to cause
ionization effects in large foundations.

2.3 Impedance versus time for buried horizontal wires

Modeling of the response of buried horizontal wires


(counterpoise) to surges started with the work of Bewley
[11]. Other tests of the transition from an initial surge
impedance to low-frequency resistance of 30.5-m buried
Fig. 1 Layout for laboratory tests of impulse ionization [7] wire can be found in Fig. 4 [3].

Fig. 2 Typical waveforms showing impulse ionization of


2.7 m vertical steel rods [7]
Fig. 4 Transient impedance of 30.5-m counterpoise in six soil
The ratio ZI to 60-Hz resistance Rf of 2.7-m vertical steel types for high-voltage impulse tests (adapted from [3])
rods decreased from 0.85 (1 kA) to 0.55 (10 kA) as a
result of ionization effects. Similar tests were carried out The modeling in Fig. 4 assumed an initial impedance of
[8][9] at currents up to 50 kA, confirming the behaviour 70-90 that fell or rose to levels close to the low-
and extending the understanding of how ionization
frequency resistance with time constants of 0.5-3 s.
reduces the impedance ZI of compact electrodes.
Fig. 5 shows a recent test method [12] that uses a local
2.2 Impedance versus time for foundations
impulse source of approximately 1 kV to provide impulse
current of 2-6 A into driven-rod and buried-wire
Recently, Yasuda et al [10] reported test results as ZI (t) in
electrodes. A multiple-rod auxiliary electrode is located
Fig. 3 for high-current impulses applied to the foundation
30 to 60 m away as a return path for the injected current
of a 500 kV tower in soil of high resistivity.
from the floating generator.

Fig. 3 ZI (t) for 500-kV transmission tower footing at two


levels of impulse current, adapted from [10]
Fig. 5 Experimental setup of Visacro and Rosado [12] for
At the early time (3-5 s) of interest in calculating testing impulse response of ground electrodes
flashover performance, the measured values of ZI (t) are

330
The electrode under test provides the ground reference for The Zed-Meter test methods were co-developed with a
the oscilloscope, and potential to remote earth is series of numerical simulations [6] using the NEC-4
measured on a lead oriented at 90. A typical result for computer program [14] for frequency-domain analysis of
an 18-m buried wire is shown in Fig. 6. antennas in soil of finite conductivity. Numerical
simulations were carried out of a steel lattice transmission
tower with four footings, equipped with a single overhead
groundwire. A Fourier transform provided the frequency
spectrum of the time-domain pulse input. The NEC-4
computer program was used to compute the potential rise
from tower base to remote potential lead at each
frequency, considering the influence of the currents in the
reaction lead, tower and OHGW. An inverse Fourier
transform then gave the time-domain voltage and current
waveforms.

The NEC-4 program confirmed a finding from initial field


tests of the Zed-Meter, which was that the Z(t) results
Fig. 6 Transient impedance v(t)/i(t) of 18-m horizontal were relatively insensitive to the lead orientation. For
electrode in 300 m soil from setup of Fig. 5 [12] example, Fig. 7 shows that Z(t) decays slowly from 7 to
5 in the time from 100 to 700 ns, with a medain value
The location of the impulse source and the measurement of 6 from 450 to 650 ns.
equipment together at the electrode, rather than separated
as shown in [13], is an important advantage in testing Z(t)
because the rise time of the test signal degrades with
distance along a horizontal line near ground [6].

3 ZED-METER METHOD

The Zed-Meter is a test instrument optimized for


measuring the transient impedance Z(t) of ground
electrodes. The original test method [5] used the sheath
of a 60-m coaxial cable to achieve a surge impedance of
400 with a two-way propagation time longer than
440 ns as a current reaction electrode. With a 200-V
pulse, a tower base current of about 0.5 A was measured
using a wideband current transformer. Transient voltage
was measured from tower base to a remote potential lead,
which was also 60 m long and oriented at 90 to the Fig. 7 Z(t) profile for test leads at 90 orientation
current reaction lead.
The rise in impedance after 750 ns in Fig. 7 corresponds
The R&D program leading to the present configuration to the return of a reflection from the end of the current
included: reaction lead, which terminates the period for which the
Adapting a commercial impulse source with reaction wire can be treated as constant surge impedance.
appropriate safety certifications for human and The drop in impedance at 1.5 s in Fig. 6 corresponds to
animal contacts; the falling edge of the applied voltage pulse in the model.
Extension of pulse width from 440 ns to cover a
longer time of interest of 1.5 s or more; It was anticipated that leads oriented at right angles would
Validation of the constant surge impedance of have a minimum of coupling. In fact, the orientation of
test leads, in 180 and 90 dipole configuration, leads at 180 led to a faster settling time to constant
fed from the center and grounded or open at impedance, as shown in Fig. 8. This lead orientation
remote ends; along the right-of-way is also more practical for most
Development of automated averaging and measurements, as the rights of way are maintained for
analysis critera for Z(t) waveforms to report Z; easy physical access and the adjacent property may be
Crosss-checks of Z with measurements of Rf; private. This was adopted as the reference configuration.
Packaging of instrument and test leads.

331
be higher than the surge impedance of the reaction leads
(444 ). The initial surge impedance is measured with a
2% relative standard deviation. After the slow reflections
from the terminations, the instrument eventually reaches a
second stable reading.

Two separate field studies [15][16], carried out in frozen


conditions at temperatures as low as -20C, established
that it was completely unnecessary to terminate the test
leads in driven rods or other auxiliary electrodes,
provided that Z(t) was analyzed prior to the arrival of
reflections from the open ends.

Fig. 8 Z(t) profile for test leads running along transmission


right-of-way (ROW) at 180 orientation

In both of these cases, a median impedance taken over the


200-ns range from 450 to 650 ns gave satisfactory results,
measured by a low standard deviation over time and using
surge currents into both the reaction lead and tower.

4 ZED-METER RESULTS

The Zed-Meter is normally used as a three-terminal


device, with connections to the current reaction lead, the
Fig. 10 Zed-Meter test: 300-m diople, open ends, frozen soil
tower under test and the remote potential lead. It can be
[15]
used as a two-terminal device by connecting two leads
together. The two-terminal results show principles of
In Fig. 10, the 300-m test leads over frozen soil provided
operation, while the three-terminal results give the desired
constant 660- surge impedance from 300 ns to 2.5 s.
values of Z for the transmission towers.
When used to test the input impedance of buried wires
4.1 Two-terminal measurements with the Zed-Meter
against the combined impedance of all other tower
foundation and guy electrodes in parallel [16], the Zed-
In two-terminal mode, the Zed-Meter is well suited for
Meter gave an impedance profile Z(t) that decayed with
measuring the input impedance of dipole leads laid on the
time as shown in Fig. 11.
ground [6], with a typical result in Fig. 9.

Fig. 11 Zed-Meter test: Four, radial 38-m wires with Rf =26-


Fig. 9 Zed-Meter test: 90-m terminated diople

Normally, if the leads are terminated with a temporary


driven rods (totaling 944 in Fig. 9), the resistance will

332
In this case, an L/Rf time constant of 0.3 s corresponds
to an equivalent series inductance of 8 H for the four
buried wires in parallel.

4.2 Three-terminal measurements with the Zed-Meter

Generally, when the Zed-Meter was used in three-


terminal mode to measure the impedance of transmission
towers [16], Z(t) was relatively constant after 300 ns, as
shown in Fig. 12.

Fig. 14 Zed-Meter measurement of 230-kV H-frame tower


with sixteen guy wires

In some cases, Rf was measured after isolating the


overhead groundwires (OHGW) from the structure. In all
of these field tests, the measured values of Z did not
change appreciably (within observation error), because
the parallel impedance of the OHGW was significantly
greater than the measured values of Z in each case

Three 500-kV towers with high values of Rf (163, 102


Fig. 12 Zed-Meter measurement of isolated 500-kV lattice
and 208 ) also had isolated overhead groundwires. The
tower with Rf = 23
towers behaved as parallel capacitance [16], given by
tower travel time divided by tower surge impedance.
With adequate test lead length and a low-impedance
connection to the tower, the relative standard deviation of
the measurements decreased below 10% at times greater 4.3 Comparing Zed-Meter and low-frequency results
than 300 ns, and stayed at this level until 1100-1400 ns.
Low-frequency resistance was measured on many of the
In general, the profiles of Z(t) were constant over this
towers at the same time that Zed-Meter tests were
time as in Fig. 12 or increased slightly from 500 ns to
performed. The test methods included traditional fall-of-
1000 ns as in Fig. 13.
potential measurements; tests of individual leg resistance
using a 30-cm clamp-on current transformer; tests of
isolated tower resistance using an oblique probe method,
taking a voltage profile on a traverse at 60 to the current
lead and calculating both Rf and local soil resistivity.
Fig. 15 and Fig. 16 show the relations between Rf and Z.

Fig. 13 Zed-Meter measurement of 161-kV steel pole with


0.22-m radius and 175 m soil resistivity, Rf = 40

Some measurements, in particular on towers with


multiple guy wires, did not settle quickly to constant
values of Z. The worst examples were H-frame 230-kV
towers with sixteen guy wires [16]. The test results in Fig.
Fig. 15 Comparison of Zed-Meter results at 500 and 1000 ns
14 show significant oscillation and high relative standard
with Rf for compact electrodes
deviation up to about 700-750 ns.

333
Fig. 15 shows that impedances read out at 500 ns and resistivity and type of electrode. Generally, Z<Rf for the
1000 ns were highly correlated, but significantly lower, tested towers with compact electrodes and high soil
than the Rf measurements taken at the same time in test resistivity, and Z>Rf for distributed electrodes in
campaigns. Towers with compact (local foundation) agreement with previous findings and modelling.
electrodes in Fig. 15 had Z<Rf with good correlation for
all but the lowest values of Rf<3 and Z<7. 6 REFERENCES

In contrast, Fig. 16 shows that all ten distributed [1] W. A. Chisholm and W. Janischewskyj, "Lightning surge
electrodes with buried wire length greater than 40 m had response of ground electrodes", IEEE Transactions on
Power Delivery, vol. 4, n. 2, pp. 1329-1337, Jan. 1989.
Z>Rf at 500 ns, and only two of these ten had Z<Rf at
[2] S. Visacro. A comprehensive approach to the grounding
800 ns. The four towers treated with four, 38-m radial response to lightning currents. IEEE Transactions on
wires tended to behave more like compact electrodes, Power Delivery, vol. 22, n. 1, pp. 381-386, Jan. 2007.
with Z<Rf at 800 ns. [3] S.S. Devgan and E.R. Whitehead, Analytical Models for
Distributed Grounding Systems, IEEE Transactions on
Power Apparatus and Systems vol. PAS-92, n. 5, pp. 1763-
1770, Sept. 1973.
[4] CIGRE Working Group C4.406, Performance of trans-
mission line grounding electrodes for lightning currents.
Electra, in press
[5] W. A. Chisholm, J. Williamson, S. Burnett and G. Hodges,
"Recent Progress in Design and Test Methods for
Transmission Line Ground Electrodes", VII International
Symposium on Lightning Protection, Curitiba, Nov. 2003.
[6] E. Petrache, W.A. Chisholm and A. Phillips, "Evaluating the
transient impedance of transmission line towers", IX
International Symposium on Lightning Protection, Foz do
Iguau, Brazil, Nov. 2007.
[7] P.L. Bellaschi, Impulse and 60-Cycle Characteristics of
Fig. 16 Comparison of Zed-Meter results at 500 and 1000 ns Driven Grounds, Transactions of the American Institute of
with Rf for distributed electrodes [16] Electrical Engineers, vol. 60, n. 3, pp. 123-128, Mar. 1941.
[8] A.C. Liew and M. Darveniza, Dynamic model of impulse
The results in Fig. 16 suggest that distributed electrodes characteristics of concentrated earths, Proceedings of the
IEE, vol. 121, n. 2, pp. 123135, 1974.
have high initial impulse impedance, as has been reported
[9] A. Phillips and J.G. Anderson, High Current Impulse
in many previous studies. Testing of Full-Scale Ground Electrodes, Technical Report
1006866, EPRI, Palo Alto, California. 2002.
5 CONCLUSION [10] Y. Yasuda, S. Kondo, T. Hara, J. Ikeda, Y. Sonoi and
Y. Furoka, Measurement of Soil-Ionization Characteristics
With an optimum placement of surge source, it is possible of Grounding and its Analysis using Dynamic Grounding
to inject fast-rising surge currents into the base of Model, IEEJ Transactions on Power and Energy, vol.
transmission tower foundations and ground electrodes 123B, n. 6, pp. 718-724, Jun 2003.
using the surge impedance of a wire on the surface of the [11] L.V. Bewley, Theory and Tests of the Counterpoise,
Transactions of the American Institute of Electrical
earth for the return path, rather than the resistance of an
Engineers, vol. 53, n. 8, pp. 1163-1172, Aug. 1934.
auxiliary remote electrode. In some cases, tests with no [12] S. Visacro and G. Rosado, Response of Grounding
auxiliary electrodes at all over frozen soil gave Electrodes to Impulsive Currents: An Experimental
satisfactory results as long as reaction wire length was Evaluation, IEEE Transactions on Electromagnetic
sufficiently long. Compatibility, vol. 51, n. 1, pp. 161-164, Feb. 2009.
[13] CIGRE Working Group C4.2.02, Methods for measuring the
For many tested transmission tower foundation earth resistance of transmission towers equipped with earth
electrodes, the settling time to a constant ratio of voltage wires, CIGRE Brochure 275, Jun. 2005.
to current was on the order of 300 ns. Settling time was [14] G.J. Burke, Numerical Electromagnetics Code NEC-4
Method of Moments, Lawrence Livermore National
increased for guyed structures and for lines with insulated
Laboratory UCRL-MA-109338, 1992.
overhead groundwires. Close agreement between current [15] W.A. Chisholm, Zed-Meter Trials at Manitoba Hydro,
into reaction lead and current into the tower was a good Proving the Concept and Equipment in Frozen Soil, EPRI,
indicator that oscillations had decayed to acceptable Palo Alto, CA and Manitoba Hydro: 2008.
levels. [16] W. A. Chisholm, Summary of Zed-Meter Field Tests:
Transient Imedance of Transmission Line Grounds, EPRI,
The ratio of measured transient impedance Z to low- Palo Alto, CA: 2006. Product ID 1012314.
frequency resistance Rf varied, depending on soil

334

You might also like