Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
45 B12-11-RTU-100 / P2 B12-11-SC-01 Solar System Controller - System 1 Electrical Room M50 (30-37) 1 B12-11-RTU-100
84 B12-11-NAV 1 - JB / P1 B12-11-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-11-NAV 1 - JB
85 B12-11-NAV 2 - JB / P1 B12-11-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-11-NAV 2 - JB
86 B12-11-NAV 3 - JB / P1 B12-11-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-11-NAV 3 - JB
87 B12-11-NAV 4 - JB / P1 B12-11-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-11-NAV 4 - JB
88 B12-11-NAV 4 - JB / P2 B12-11-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-11-NAV 4 - JB
60 B12-13-NAV 1 - JB / P1 B12-13-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-13-NAV 1 - JB
61 B12-13-NAV 2 - JB / P1 B12-13-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 2 - JB
62 B12-13-NAV 3 - JB / P1 B12-13-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 3 - JB
63 B12-13-NAV 4 - JB / P1 B12-13-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 4 - JB
64 B12-13-NAV 4 - JB / P2 B12-13-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-13-NAV 4 - JB
60 B12-15-NAV 1 - JB / P1 B12-15-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-15-NAV 1 - JB
61 B12-15-NAV 2 - JB / P1 B12-15-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 2 - JB
62 B12-15-NAV 3 - JB / P1 B12-15-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 3 - JB
63 B12-15-NAV 4 - JB / P1 B12-15-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 4 - JB
Page : 2 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
64 B12-15-NAV 4 - JB / P2 B12-15-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-15-NAV 4 - JB
60 B12-17-NAV 1 - JB / P1 B12-17-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-17-NAV 1 - JB
61 B12-17-NAV 2 - JB / P1 B12-17-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 2 - JB
62 B12-17-NAV 3 - JB / P1 B12-17-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 3 - JB
63 B12-17-NAV 4 - JB / P1 B12-17-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 4 - JB
64 B12-17-NAV 4 - JB / P2 B12-17-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-17-NAV 4 - JB
23 C24-P2-RTU-100 / P2 C24-P2-SC-01 Solar System Controller - System 1 Electrical Room M50 (30-37) 1 C24-P2-RTU-100
61 C24-P2-NAV 1 - JB / P1 C24-P2-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 C24-P2-NAV 1 - JB
62 C24-P2-NAV 2 - JB / P1 C24-P2-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 2 - JB
63 C24-P2-NAV 3 - JB / P1 C24-P2-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 3 - JB
64 C24-P2-NAV 4 - JB / P1 C24-P2-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 4 - JB
65 C24-P2-NAV 4 - JB / P2 C24-P2-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 C24-P2-NAV 4 - JB
Page : 3 of 268
Document N
Rev No.: C1
Re-Issued F
To
Size Length Voltage
Runs NOC Cable Spec. Drg. No.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
RTU Cabinet TIC Room M50 (30-37) 1 1 2C 70 30 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 60 Fire Resistant, XLPE, CU 600/1000 -
600/100
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
Page : 4 of 268
Document N
Rev No.: C1
Re-Issued F
To
Size Length Voltage
Runs NOC Cable Spec. Drg. No.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU -
0
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000 -
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU 600/1000 -
600/100
Remote Telemetry Unit TIC Room M50 (30-37) 1 1 2C 70 30 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 60 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
600/100
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU -
0
Page : 5 of 268
Drum MCT
Remarks
No. No.
B12-11-MCT-E01
- C1###
MCT-101
C1
- B12-11-MCT-E04 ###
- - ###
- - ###
- - ###
- B12-11-MCT-E04 ###
- B12-13-MCT-E04 C1
###
- -
###
- -
###
- -
###
- B12-13-MCT-E04
###
- B12-15-MCT-E04
###
- -
###
- -
###
- -
###
Page : 6 of 268
Drum MCT
Remarks
No. No.
- B12-15-MCT-E04
###
- B12-17-MCT-E04 ###
- - ###
- - ###
- - ###
- B12-17-MCT-E04 ###
C24-P2-MCT-E01
- ###
MCT-101
- C24-P2-MCT-E04 ###
- - ###
- - ###
- - ###
- C24-P2-MCT-E04 ###
Page : 7 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
3 B12-13-BC-DCDB-01 / P1 DDP-BC-1 Portable Boost Charger - 01 Main Deck M50 (41-46) 1 B12-13-BC-DCDB-01
4 B12-13-BC-DCDB-01 / P2 DDP-BC-2 Portable Boost Charger - 02 Main Deck M50 (41-46) 1 B12-13-BC-DCDB-01
5 B12-13-SC-01 / P1 B12-13-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-13-SC-01
6 B12-13-SC-02 / P1 B12-13-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-13-SC-02
7 B12-13-SC-03 / P1 B12-13-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-13-SC-03
8 B12-13-SC-04 / P1 B12-13-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-13-SC-04
SOLAR PANEL
Page : 8 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
9 B12-13-SC-01 / P2 B12-13-AJB-01 AJB-01 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-13-SC-01
10 B12-13-SC-01 / P3 B12-13-AJB-02 AJB-02 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-13-SC-01
11 B12-13-SC-01 / P4 B12-13-AJB-03 AJB-03 for 9 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-13-SC-01
12 B12-13-SC-02 / P2 B12-13-AJB-04 AJB-04 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-13-SC-02
13 B12-13-SC-02 / P3 B12-13-AJB-05 AJB-05 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-13-SC-02
14 B12-13-SC-03 / P2 B12-13-AJB-06 AJB-06 for 9 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-13-SC-03
15 B12-13-SC-03 / P3 B12-13-AJB-07 AJB-07 for 6 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-13-SC-03
16 B12-13-SC-04 / P2 B12-13-AJB-08 AJB-08 for 3 Nos Solar Module - System 4 Heli Deck CG-1015 1 B12-13-SC-04
BATTERY BANK
17 B12-13-BR-01 / P1 B12-13-BR-01 Battery Bank For Solar Power - System 1 Battery Room M63 (53-61) 1 B12-13-SC-01
18 B12-13-BR-02 / P1 B12-13-BR-02 Battery Bank For Solar Power - System 2 Battery Room M63 (53-61) 1 B12-13-SC-02
19 B12-13-BR-03 / P1 B12-13-BR-03 Battery Bank For Solar Power - System 3 Battery Room M63 (53-61) 1 B12-13-SC-03
20 B12-13-BR-04 / P1 B12-13-BR-04 Battery Bank For Solar Power - System 4 Battery Room M50 (37-41) 1 B12-13-SC-04
Page : 9 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 1
21 B12-13-RTU-100 / P1 B12-13-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-13-RTU-100
22 B12-13-RTU-100 / P2 B12-13-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-13-RTU-100
29 B12-13-CCTV-100 / P1 B12-13-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-13-CCTV-100
Page : 10 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 2
30 B12-13-LG-341-04 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-341-04
31 B12-13-LG-440-06 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-440-06
32 B12-13-LG-450-07 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-450-07
33 B12-13-LG-451-07 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-451-07
34 B12-13-LG-490-07 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-490-07
35 B12-13-LG-900-08 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-900-08
36 B12-13-LG-920-08 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-LG-920-08
B12-13-HIPPS-310-
37 B12-13-HIPPS-310-13 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
B12-13-HIPPS-310-
38 B12-13-HIPPS-310-13 / P2 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
39 B12-13-M900/P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-13-M900
40 B12-13-SW-01 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-13-SW-01
41 B12-13-JBL-01 / P1 B12-13-SW-01 Electrical room lighting switch Electrical Room M20 (18-21) 1 B12-13-JBL-01
Page : 11 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
42 B12-13-LF-01 / P1 B12-13-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-13-LF-01
43 B12-13-LF-02 / P2 B12-13-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-13-LF-02
44 B12-13-SW-02 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-13-SW-02
45 B12-13-JBL-02 / P1 B12-13-SW-02 Telemetry room lighting switch TIC Room M20 (18-21) 1 B12-13-JBL-02
46 B12-13-LF-03 / P1 B12-13-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-13-LF-03
47 B12-13-LF-04 / P2 B12-13-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-13-LF-04
48 B12-13-SW-03 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-13-SW-03
49 B12-13-JBL-03 / P1 B12-13-SW-03 Battery room lighting switch Battery Room M20 (18-21) 1 B12-13-JBL-03
50 B12-13-LF-05 / P1 B12-13-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-13-LF-05
51 B12-13-LF-06 / P2 B12-13-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-13-LF-06
52 B12-13-SW-04 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-13-SW-04
53 B12-13-JBL-04 / P1 B12-13-SW-04 Shelter Room lighting switch Shelter Room M20 (18-21) 1 B12-13-JBL-04
54 B12-13-LF-07 / P1 B12-13-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-13-LF-07
55 B12-13-LF-08 / P2 B12-13-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-13-LF-08
Page : 12 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
56 B12-13-SW-05 / P1 B12-13-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-13-SW-05
57 B12-13-LF-09 / P1 B12-13-SW-05 Toilet Room lighting switch Portable Toilet M20 (14-18) 1 B12-13-LF-09
SYSTEM 3
58 B12-13-F&G-100 / P1 B12-13-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-13-F&G-100
59 B12-13-F&G-100 / P2 B12-13-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-13-F&G-100
Page : 13 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 4
60 B12-13-NAV 1 - JB / P1 B12-13-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-13-NAV 1 - JB
61 B12-13-NAV 2 - JB / P1 B12-13-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 2 - JB
62 B12-13-NAV 3 - JB / P1 B12-13-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 3 - JB
63 B12-13-NAV 4 - JB / P1 B12-13-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-13-NAV 4 - JB
64 B12-13-NAV 4 - JB / P2 B12-13-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-13-NAV 4 - JB
69 B12-13-NAV 2- JB / C1 B12-13-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 B12-13-NAV 2 - JB
70 B12-13-NAV 3 - JB / C1 B12-13-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 B12-13-NAV 3 - JB
Page : 14 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
71 B12-13-NAV 4 - JB / C1 B12-13-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 B12-13-NAV 4 - JB
72 B12-13-NAV 1 - JB / C1 B12-13-NAV 4 - JB NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 B12-13-NAV 1 - JB
THERMISTOR CABLE
73 B12-13-SC-01 / C1 B12-13-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-13-SC-01
74 B12-13-SC-01 / C2 B12-13-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-13-SC-01
75 B12-13-SC-01 / C3 B12-13-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-13-SC-01
76 B12-13-SC-02 / C1 B12-13-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-13-SC-02
77 B12-13-SC-02 / C2 B12-13-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-13-SC-02
78 B12-13-SC-03 / C1 B12-13-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-13-SC-03
79 B12-13-SC-03 / C2 B12-13-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-13-SC-03
80 B12-13-SC-04 / C1 B12-13-BR-04 Battery Bank For Solar Power - System 4 Battery Room M20 (14-18) 1 B12-13-SC-04
Page : 15 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 1
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 2
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 3
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 4
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Portable Boost Charger - 01 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
Portable Boost Charger - 02 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 1 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 2 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 3 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 4 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Page : 28 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 30 Fire Resistant, XLPE, AL 600/1000
Page : 29 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
CCTV Cabinet TIC Room M40 (30-37) 1 1 2C 50 30 Flame Retardant, XLPE, CU 600/1000
Page : 30 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Illumination Level Gauge 1 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 2 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 3 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 4 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 5 Cellar Deck M20 (14-18) 1 1 2C 6 30 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 6 Sub-Cellar Deck M20 (14-18) 1 1 2C 6 60 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 7 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Above Shelter
Illumination Level Gauge 8 - 1 - - - - - -
Room
HIPPS Supply 1 TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
HIPPS Supply 2 TIC Room M40 (30-37) 1 1 2C 50 45 Flame Retardant, XLPE, CU 600/1000
CO2 Snuffing System Main Deck M20 (18-21) 1 1 2C 10 50 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting switch Electrical Room M20 (18-21) 1 1 2C 10 25 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting junction box Electrical Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Page : 31 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 8 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting switch TIC Room M20 (18-21) 1 1 2C 10 45 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting junction box TIC Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room lighting switch Battery Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Battery room lighting junction box Battery Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 20 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting switch Shelter Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting junction box Shelter Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Page : 32 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Toilet Room lighting switch Portable Toilet M20 (14-18) 1 1 2C 6 40 Flame Retardant, XLPE, CU 600/1000
Toilet Room light Fixture Portable Toilet M20 (14-18) 1 1 2C 6 3 Flame Retardant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 1 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 2 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Page : 33 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
Page : 34 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 35 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Drum MCT
Drg. No. Remarks
No. No.
C1
Page : 48 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-13-MCT-E01
###
- - B12-13-MCT-E01
###
- - B12-13-MCT-E01
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E03
###
- - B12-13-MCT-E03
###
- - B12-13-MCT-E04
###
B12-13-MCT-E06
- -
B12-13-MCT-E01 ###
B12-13-MCT-E06
- -
B12-13-MCT-E02 ###
B12-13-MCT-E06
- -
B12-13-MCT-E03 ###
B12-13-MCT-E06
- -
B12-13-MCT-E04 ###
Page : 49 of 268
Drum MCT
Drg. No. Remarks
No. No.
B12-13-MCT-E01
- -
MCT-101 ###
B12-13-MCT-E01
- -
MCT-101 ###
- - -
- - -
- - -
- - -
- - -
- - -
Drum MCT
Drg. No. Remarks
No. No.
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - B12-13-MCT-E02
###
- - - Deleted
###
B12-13-MCT-E02
- -
MCT-103 ###
B12-13-MCT-E02
- - C1
MCT-103 ###
- - B12-13-MCT-E02
###
- - -
###
- - -
###
Page : 51 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
###
- - -
###
B12-13-MCT-E02
- -
MCT-101 ###
- - -
###
- - -
###
- - -
###
B12-13-MCT-E02
- -
B12-13-MCT-E06 ###
- - -
###
- - -
###
- - -
###
B12-13-MCT-E02
- - B12-13-MCT-E06
B12-13-MCT-E07 ###
- - -
###
- - -
###
- - -
###
Page : 52 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-13-MCT-E02
###
- - -
###
B12-13-MCT-E03
- -
MCT-102 ###
B12-13-MCT-E03
- -
MCT-102 ###
Page : 53 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-13-MCT-E04
###
- - -
###
- - -
###
- - -
###
- - B12-13-MCT-E04
###
- - -
###
- - -
Shileded 2C X 2.5 Sqmm ###
Cable provided
Page : 54 of 268
Drum MCT
Drg. No. Remarks
No. No.
Shileded 2C X 2.5 Sqmm
Cable provided
- - -
###
- - -
###
B12-13-MCT-E06
- -
B12-13-MCT-E01
B12-13-MCT-E06
- -
B12-13-MCT-E01
B12-13-MCT-E06
- -
B12-13-MCT-E01
B12-13-MCT-E06
- -
B12-13-MCT-E02
B12-13-MCT-E06
- -
B12-13-MCT-E02
B12-13-MCT-E06
- -
B12-13-MCT-E03
B12-13-MCT-E06
- -
B12-13-MCT-E03
B12-13-MCT-E06
- -
B12-13-MCT-E04
Page : 55 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
3 B12-15-BC-DCDB-01 / P1 DDP-BC-1 Portable Boost Charger - 01 Main Deck M50 (41-46) 1 B12-15-BC-DCDB-01
4 B12-15-BC-DCDB-01 / P2 DDP-BC-2 Portable Boost Charger - 02 Main Deck M50 (41-46) 1 B12-15-BC-DCDB-01
5 B12-15-SC-01 / P1 B12-15-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-15-SC-01
6 B12-15-SC-02 / P1 B12-15-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-15-SC-02
7 B12-15-SC-03 / P1 B12-15-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-15-SC-03
8 B12-15-SC-04 / P1 B12-15-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-15-SC-04
SOLAR PANEL
Page : 68 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
9 B12-15-SC-01 / P2 B12-15-AJB-01 AJB-01 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-15-SC-01
10 B12-15-SC-01 / P3 B12-15-AJB-02 AJB-02 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-15-SC-01
11 B12-15-SC-01 / P4 B12-15-AJB-03 AJB-03 for 9 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-15-SC-01
12 B12-15-SC-02 / P2 B12-15-AJB-04 AJB-04 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-15-SC-02
13 B12-15-SC-02 / P3 B12-15-AJB-05 AJB-05 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-15-SC-02
14 B12-15-SC-03 / P2 B12-15-AJB-06 AJB-06 for 9 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-15-SC-03
15 B12-15-SC-03 / P3 B12-15-AJB-07 AJB-07 for 6 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-15-SC-03
16 B12-15-SC-04 / P2 B12-15-AJB-08 AJB-08 for 3 Nos Solar Module - System 4 Heli Deck CG-1015 1 B12-15-SC-04
BATTERY BANK
17 B12-15-BR-01 / P1 B12-15-BR-01 Battery Bank For Solar Power - System 1 Battery Room M63 (53-61) 1 B12-15-SC-01
18 B12-15-BR-02 / P1 B12-15-BR-02 Battery Bank For Solar Power - System 2 Battery Room M63 (53-61) 1 B12-15-SC-02
19 B12-15-BR-03 / P1 B12-15-BR-03 Battery Bank For Solar Power - System 3 Battery Room M63 (53-61) 1 B12-15-SC-03
20 B12-15-BR-04 / P1 B12-15-BR-04 Battery Bank For Solar Power - System 4 Battery Room M50 (37-41) 1 B12-15-SC-04
Page : 69 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 1
21 B12-15-RTU-100 / P1 B12-15-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-15-RTU-100
22 B12-15-RTU-100 / P2 B12-15-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-15-RTU-100
29 B12-15-CCTV-100 / P1 B12-15-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-15-CCTV-100
Page : 70 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 2
30 B12-15-LG-341-04 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-341-04
31 B12-15-LG-440-06 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-440-06
32 B12-15-LG-450-07 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-450-07
33 B12-15-LG-451-07 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-451-07
34 B12-15-LG-490-07 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-490-07
35 B12-15-LG-900-08 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-900-08
36 B12-15-LG-920-08 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-LG-920-08
B12-15-HIPPS-310-
37 B12-15-HIPPS-310-13 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
B12-15-HIPPS-310-
38 B12-15-HIPPS-310-13 / P2 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
39 B12-15-M900/P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-15-M900
40 B12-15-SW-01 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-15-SW-01
41 B12-15-JBL-01 / P1 B12-15-SW-01 Electrical room lighting switch Electrical Room M20 (18-21) 1 B12-15-JBL-01
Page : 71 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
42 B12-15-LF-01 / P1 B12-15-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-15-LF-01
43 B12-15-LF-02 / P2 B12-15-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-15-LF-02
44 B12-15-SW-02 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-15-SW-02
45 B12-15-JBL-02 / P1 B12-15-SW-02 Telemetry room lighting switch TIC Room M20 (18-21) 1 B12-15-JBL-02
46 B12-15-LF-03 / P1 B12-15-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-15-LF-03
47 B12-15-LF-04 / P2 B12-15-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-15-LF-04
48 B12-15-SW-03 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-15-SW-03
49 B12-15-JBL-03 / P1 B12-15-SW-03 Battery room lighting switch Battery Room M20 (18-21) 1 B12-15-JBL-03
50 B12-15-LF-05 / P1 B12-15-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-15-LF-05
51 B12-15-LF-06 / P2 B12-15-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-15-LF-06
52 B12-15-SW-04 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-15-SW-04
53 B12-15-JBL-04 / P1 B12-15-SW-04 Shelter Room lighting switch Shelter Room M20 (18-21) 1 B12-15-JBL-04
54 B12-15-LF-07 / P1 B12-15-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-15-LF-07
55 B12-15-LF-08 / P2 B12-15-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-15-LF-08
Page : 72 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
56 B12-15-SW-05 / P1 B12-15-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-15-SW-05
57 B12-15-LF-09 / P1 B12-15-SW-05 Toilet Room lighting switch Portable Toilet M20 (14-18) 1 B12-15-LF-09
SYSTEM 3
58 B12-15-F&G-100 / P1 B12-15-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-15-F&G-100
59 B12-15-F&G-100 / P2 B12-15-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-15-F&G-100
Page : 73 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 4
60 B12-15-NAV 1 - JB / P1 B12-15-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-15-NAV 1 - JB
61 B12-15-NAV 2 - JB / P1 B12-15-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 2 - JB
62 B12-15-NAV 3 - JB / P1 B12-15-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 3 - JB
63 B12-15-NAV 4 - JB / P1 B12-15-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-15-NAV 4 - JB
64 B12-15-NAV 4 - JB / P2 B12-15-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-15-NAV 4 - JB
69 B12-15-NAV 2- JB / C1 B12-15-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 B12-15-NAV 2 - JB
70 B12-15-NAV 3 - JB / C1 B12-15-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 B12-15-NAV 3 - JB
Page : 74 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
71 B12-15-NAV 4 - JB / C1 B12-15-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 B12-15-NAV 4 - JB
72 B12-15-NAV 1 - JB / C1 B12-15-NAV 4 - JB NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 B12-15-NAV 1 - JB
THERMISTOR CABLE
73 B12-15-SC-01 / C1 B12-15-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-15-SC-01
74 B12-15-SC-01 / C2 B12-15-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-15-SC-01
75 B12-15-SC-01 / C3 B12-15-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-15-SC-01
76 B12-15-SC-02 / C1 B12-15-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-15-SC-02
77 B12-15-SC-02 / C2 B12-15-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-15-SC-02
78 B12-15-SC-03 / C1 B12-15-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-15-SC-03
79 B12-15-SC-03 / C2 B12-15-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-15-SC-03
80 B12-15-SC-04 / C1 B12-15-BR-04 Battery Bank For Solar Power - System 4 Battery Room M20 (14-18) 1 B12-15-SC-04
Page : 75 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 1
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 2
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 3
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 4
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Portable Boost Charger - 01 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
Portable Boost Charger - 02 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 1 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 2 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 3 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 4 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Page : 88 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 30 Fire Resistant, XLPE, AL 600/1000
Page : 89 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
CCTV Cabinet TIC Room M40 (30-37) 1 1 2C 50 30 Flame Retardant, XLPE, CU 600/1000
Page : 90 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Illumination Level Gauge 1 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 2 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 3 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 4 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 5 Cellar Deck M20 (14-18) 1 1 2C 6 30 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 6 Sub-Cellar Deck M20 (14-18) 1 1 2C 6 60 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 7 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Above Shelter
Illumination Level Gauge 8 - 1 - - - - - -
Room
HIPPS Supply 1 TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
HIPPS Supply 2 TIC Room M40 (30-37) 1 1 2C 50 45 Flame Retardant, XLPE, CU 600/1000
CO2 Snuffing System Main Deck M20 (18-21) 1 1 2C 10 50 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting switch Electrical Room M20 (18-21) 1 1 2C 10 25 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting junction box Electrical Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Page : 91 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 8 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting switch TIC Room M20 (18-21) 1 1 2C 10 45 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting junction box TIC Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room lighting switch Battery Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Battery room lighting junction box Battery Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 20 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting switch Shelter Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting junction box Shelter Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Page : 92 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Toilet Room lighting switch Portable Toilet M20 (14-18) 1 1 2C 6 40 Flame Retardant, XLPE, CU 600/1000
Toilet Room light Fixture Portable Toilet M20 (14-18) 1 1 2C 6 3 Flame Retardant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 1 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 2 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Page : 93 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
Page : 94 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 35 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Drum MCT
Drg. No. Remarks
No. No.
C1
Page : 108 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-15-MCT-E01
###
- - B12-15-MCT-E01
###
- - B12-15-MCT-E01
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E03
###
- - B12-15-MCT-E03
###
- - B12-15-MCT-E04
###
B12-15-MCT-E06
- -
B12-15-MCT-E01 ###
B12-15-MCT-E06
- -
B12-15-MCT-E02 ###
B12-15-MCT-E06
- -
B12-15-MCT-E03 ###
B12-15-MCT-E06
- -
B12-15-MCT-E04 ###
Page : 109 of 268
Drum MCT
Drg. No. Remarks
No. No.
B12-15-MCT-E01
- -
MCT-101 ###
B12-15-MCT-E01
- -
MCT-101 ###
- - -
- - -
- - -
- - -
- - -
- - -
Drum MCT
Drg. No. Remarks
No. No.
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - B12-15-MCT-E02
###
- - - Deleted
###
B12-15-MCT-E02
- -
MCT-103 ###
B12-15-MCT-E02
- - C1
MCT-103 ###
- - B12-15-MCT-E02
###
- - -
###
- - -
###
Page : 111 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
###
- - -
###
B12-15-MCT-E02
- -
MCT-101 ###
- - -
###
- - -
###
- - -
###
B12-15-MCT-E02
- -
B12-15-MCT-E06 ###
- - -
###
- - -
###
- - -
###
B12-15-MCT-E02
- - B12-15-MCT-E06
B12-15-MCT-E07 ###
- - -
###
- - -
###
- - -
###
Page : 112 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-15-MCT-E02
###
- - -
###
B12-15-MCT-E03
- -
MCT-102 ###
B12-15-MCT-E03
- -
MCT-102 ###
Page : 113 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-15-MCT-E04
###
- - -
###
- - -
###
- - -
###
- - B12-15-MCT-E04
###
- - -
###
- - -
Shileded 2C X 2.5 Sqmm ###
Cable provided
Page : 114 of 268
Drum MCT
Drg. No. Remarks
No. No.
Shileded 2C X 2.5 Sqmm
Cable provided
- - -
###
- - -
###
B12-15-MCT-E06
- -
B12-15-MCT-E01
B12-15-MCT-E06
- -
B12-15-MCT-E01
B12-15-MCT-E06
- -
B12-15-MCT-E01
B12-15-MCT-E06
- -
B12-15-MCT-E02
B12-15-MCT-E06
- -
B12-15-MCT-E02
B12-15-MCT-E06
- -
B12-15-MCT-E03
B12-15-MCT-E06
- -
B12-15-MCT-E03
B12-15-MCT-E06
- -
B12-15-MCT-E04
Page : 115 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
3 B12-17-BC-DCDB-01 / P1 DDP-BC-1 Portable Boost Charger - 01 Main Deck M50 (41-46) 1 B12-17-BC-DCDB-01
4 B12-17-BC-DCDB-01 / P2 DDP-BC-2 Portable Boost Charger - 02 Main Deck M50 (41-46) 1 B12-17-BC-DCDB-01
5 B12-17-SC-01 / P1 B12-17-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-17-SC-01
6 B12-17-SC-02 / P1 B12-17-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-17-SC-02
7 B12-17-SC-03 / P1 B12-17-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-17-SC-03
8 B12-17-SC-04 / P1 B12-17-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 B12-17-SC-04
SOLAR PANEL
9 B12-17-SC-01 / P2 B12-17-AJB-01 AJB-01 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-17-SC-01
10 B12-17-SC-01 / P3 B12-17-AJB-02 AJB-02 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-17-SC-01
Page : 128 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
11 B12-17-SC-01 / P4 B12-17-AJB-03 AJB-03 for 9 Nos Solar Module - System 1 Heli Deck CG-1015 1 B12-17-SC-01
12 B12-17-SC-02 / P2 B12-17-AJB-04 AJB-04 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-17-SC-02
13 B12-17-SC-02 / P3 B12-17-AJB-05 AJB-05 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 B12-17-SC-02
14 B12-17-SC-03 / P2 B12-17-AJB-06 AJB-06 for 9 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-17-SC-03
15 B12-17-SC-03 / P3 B12-17-AJB-07 AJB-07 for 6 Nos Solar Module - System 3 Heli Deck CG-1015 1 B12-17-SC-03
16 B12-17-SC-04 / P2 B12-17-AJB-08 AJB-08 for 3 Nos Solar Module - System 4 Heli Deck CG-1015 1 B12-17-SC-04
BATTERY BANK
17 B12-17-BR-01 / P1 B12-17-BR-01 Battery Bank For Solar Power - System 1 Battery Room M63 (53-61) 1 B12-17-SC-01
18 B12-17-BR-02 / P1 B12-17-BR-02 Battery Bank For Solar Power - System 2 Battery Room M63 (53-61) 1 B12-17-SC-02
19 B12-17-BR-03 / P1 B12-17-BR-03 Battery Bank For Solar Power - System 3 Battery Room M63 (53-61) 1 B12-17-SC-03
20 B12-17-BR-04 / P1 B12-17-BR-04 Battery Bank For Solar Power - System 4 Battery Room M50 (37-41) 1 B12-17-SC-04
SYSTEM 1
21 B12-17-RTU-100 / P2 B12-17-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-17-RTU-100
22 B12-17-RTU-100 / P1 B12-17-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-17-RTU-100
Page : 129 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
29 B12-17-CCTV-100 / P1 B12-17-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 B12-17-CCTV-100
SYSTEM 2
30 B12-17-LG-341-04 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-341-04
31 B12-17-LG-440-06 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-440-06
32 B12-17-LG-450-07 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-450-07
33 B12-17-LG-451-07 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-451-07
34 B12-17-LG-490-07 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-490-07
35 B12-17-LG-900-08 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-900-08
Page : 130 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
36 B12-17-LG-920-08 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-920-08
B12-17-LG-700-10 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-LG-700-10
37 B12-17-HIPPS-310-13 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1 B12-17-HIPPS-310-13
38 B12-17-HIPPS-310-13 / P2 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1 B12-17-HIPPS-310-13
39 B12-17-M900/P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-17-M900
40 B12-17-SW-01 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-17-SW-01
41 B12-17-JBL-01 / P1 B12-17-SW-01 Electrical room lighting switch Electrical Room M20 (18-21) 1 B12-17-JBL-01
42 B12-17-LF-01 / P1 B12-17-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-17-LF-01
43 B12-17-LF-02 / P2 B12-17-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 B12-17-LF-02
44 B12-17-SW-02 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-17-SW-02
45 B12-17-JBL-02 / P1 B12-17-SW-02 Telemetry room lighting switch TIC Room M20 (18-21) 1 B12-17-JBL-02
46 B12-17-LF-03 / P1 B12-17-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-17-LF-03
47 B12-17-LF-04 / P2 B12-17-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 B12-17-LF-04
48 B12-17-SW-03 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-17-SW-03
Page : 131 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
49 B12-17-JBL-03 / P1 B12-17-SW-03 Battery room lighting switch Battery Room M20 (18-21) 1 B12-17-JBL-03
50 B12-17-LF-05 / P1 B12-17-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-17-LF-05
51 B12-17-LF-06 / P2 B12-17-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 B12-17-LF-06
52 B12-17-SW-04 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 B12-17-SW-04
53 B12-17-JBL-04 / P1 B12-17-SW-04 Shelter Room lighting switch Shelter Room M20 (18-21) 1 B12-17-JBL-04
54 B12-17-LF-07 / P1 B12-17-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-17-LF-07
55 B12-17-LF-08 / P2 B12-17-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 B12-17-LF-08
56 B12-17-SW-05 / P1 B12-17-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 B12-17-SW-05
57 B12-17-LF-09 / P1 B12-17-SW-05 Toilet Room lighting switch Portable Toilet M20 (14-18) 1 B12-17-LF-09
SYSTEM 3
58 B12-17-F&G-100 / P1 B12-17-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-17-F&G-100
59 B12-17-F&G-100 / P2 B12-17-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 B12-17-F&G-100
Page : 132 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 4
60 B12-17-NAV 1 - JB / P1 B12-17-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-17-NAV 1 - JB
61 B12-17-NAV 2 - JB / P1 B12-17-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 2 - JB
62 B12-17-NAV 3 - JB / P1 B12-17-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 3 - JB
63 B12-17-NAV 4 - JB / P1 B12-17-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 B12-17-NAV 4 - JB
64 B12-17-NAV 4 - JB / P2 B12-17-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 B12-17-NAV 4 - JB
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
69 B12-17-NAV 2- JB / C1 B12-17-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 B12-17-NAV 2 - JB
70 B12-17-NAV 3 - JB / C1 B12-17-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 B12-17-NAV 3 - JB
71 B12-17-NAV 4 - JB / C1 B12-17-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 B12-17-NAV 4 - JB
72 B12-17-NAV 1 - JB / C1 B12-17-NAV 4 - JB NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 B12-17-NAV 1 - JB
THERMISTOR CABLE
73 B12-17-SC-01 / C1 B12-17-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-17-SC-01
74 B12-17-SC-01 / C2 B12-17-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-17-SC-01
75 B12-17-SC-01 / C3 B12-17-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 B12-17-SC-01
76 B12-17-SC-02 / C1 B12-17-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-17-SC-02
77 B12-17-SC-02 / C2 B12-17-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 B12-17-SC-02
78 B12-17-SC-03 / C1 B12-17-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-17-SC-03
79 B12-17-SC-03 / C2 B12-17-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 B12-17-SC-03
Page : 134 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
80 B12-17-SC-04 / C1 B12-17-BR-04 Battery Bank For Solar Power - System 4 Battery Room M20 (14-18) 1 B12-17-SC-04
Page : 135 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 1
81 B12-17-AJB-01 / P1 SP-SYS I - 01 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-01
82 SP-SYS I - 02 / P1 SP-SYS I - 01 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 02
83 SP-SYS I - 03 / P1 SP-SYS I - 02 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 03
84 B12-17-AJB-01 / P2 SP-SYS I - 03 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-01
85 B12-17-AJB-01 / P3 SP-SYS I - 04 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-01
86 SP-SYS I - 05 / P1 SP-SYS I - 04 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 05
87 SP-SYS I - 06 / P1 SP-SYS I - 05 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 06
88 B12-17-AJB-01 / P4 SP-SYS I - 06 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-01
Page : 136 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
89 B12-17-AJB-01 / P5 SP-SYS I - 07 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-01
90 SP-SYS I - 08 / P1 SP-SYS I - 07 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 08
91 SP-SYS I - 09/ P1 SP-SYS I - 08 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 09
92 B12-17-AJB-01 / P6 SP-SYS I - 09 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-01
93 B12-17-AJB-01 / P7 SP-SYS I - 10 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-01
94 SP-SYS I - 11 / P1 SP-SYS I - 10 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 11
95 SP-SYS I - 12 / P1 SP-SYS I - 11 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 12
96 B12-17-AJB-01 / P8 SP-SYS I - 12 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-01
97 B12-17-AJB-02 / P9 SP-SYS I - 13 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-02
Page : 137 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
98 SP-SYS I - 14 / P1 SP-SYS I - 13 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 14
99 SP-SYS I - 15 / P1 SP-SYS I - 14 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 15
100 B12-17-AJB-02 / P10 SP-SYS I - 15 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-02
101 B12-17-AJB-02 / P11 SP-SYS I - 16 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-02
102 SP-SYS I - 17 / P1 SP-SYS I - 16 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 17
103 SP-SYS I - 18 / P1 SP-SYS I - 17 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 18
104 B12-17-AJB-02 / P12 SP-SYS I - 18 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-02
Page : 138 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
105 B12-17-AJB-02 / P13 SP-SYS I - 19 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-02
106 SP-SYS I - 20 / P1 SP-SYS I - 19 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 20
107 SP-SYS I - 21 / P1 SP-SYS I - 20 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 21
108 B12-17-AJB-02 / P14 SP-SYS I - 21 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-02
109 B12-17-AJB-02 / P15 SP-SYS I - 22 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-02
110 SP-SYS I - 23 / P1 SP-SYS I - 22 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 23
111 SP-SYS I - 24 / P1 SP-SYS I - 23 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 24
112 B12-17-AJB-02 / P16 SP-SYS I - 24 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-02
Page : 139 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
113 B12-17-AJB-03 / P17 SP-SYS I - 25 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-03
114 SP-SYS I - 26 / P1 SP-SYS I - 25 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 26
115 SP-SYS I - 27 / P1 SP-SYS I - 26 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 27
116 B12-17-AJB-03 / P18 SP-SYS I - 27 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-03
117 B12-17-AJB-03 / P19 SP-SYS I - 28 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-03
118 SP-SYS I - 29 / P1 SP-SYS I - 28 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 29
119 SP-SYS I - 30 / P1 SP-SYS I - 29 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 30
120 B12-17-AJB-03 / P20 SP-SYS I - 30 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-03
121 B12-17-AJB-03 / P21 SP-SYS I - 31 SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 B12-17-AJB-03
Page : 140 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
122 SP-SYS I - 32 / P1 SP-SYS I - 31 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 32
123 SP-SYS I - 33 / P1 SP-SYS I - 32 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 SP-SYS I - 33
124 B12-17-AJB-03 / P22 SP-SYS I - 33 SOLAR PANEL - SYSTEM I Terminal Detail (-) Heli Deck - 1 B12-17-AJB-03
System 2
125 B12-17-AJB-04 / P1 SP-SYS II - 01 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-04
126 SP-SYS II - 02 / P1 SP-SYS II - 01 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 02
127 SP-SYS II - 03 / P1 SP-SYS II - 02 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 03
128 B12-17-AJB-04 / P2 SP-SYS II - 03 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-04
Page : 141 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
129 B12-17-AJB-04 / P3 SP-SYS II - 04 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-05
130 SP-SYS II - 05 / P1 SP-SYS II - 04 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 05
131 SP-SYS II - 06 / P1 SP-SYS II - 05 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 06
132 B12-17-AJB-04 / P4 SP-SYS II - 06 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-05
133 B12-17-AJB-04 / P5 SP-SYS II - 07 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-04
134 SP-SYS II - 08 / P1 SP-SYS II - 07 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 08
135 SP-SYS II - 09 / P1 SP-SYS II - 08 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 09
136 B12-17-AJB-04 / P6 SP-SYS II - 09 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-04
137 B12-17-AJB-05 / P1 SP-SYS II - 10 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-05
Page : 142 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
138 SP-SYS II - 11 / P1 SP-SYS II - 10 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 11
139 SP-SYS II - 12 / P1 SP-SYS II - 11 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 12
140 B12-17-AJB-05 / P2 SP-SYS II - 12 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-05
141 B12-17-AJB-05 / P3 SP-SYS II - 13 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-05
142 SP-SYS II - 14 / P1 SP-SYS II - 13 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 14
143 SP-SYS II - 15 / P1 SP-SYS II - 14 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 15
144 B12-17-AJB-05 / P4 SP-SYS II - 15 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-05
145 B12-17-AJB-05 / P5 SP-SYS II - 16 SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 B12-17-AJB-05
146 SP-SYS II - 02 / P1 SP-SYS II - 16 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 17
Page : 143 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
147 SP-SYS II - 03 / P1 SP-SYS II - 17 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 SP-SYS II - 18
148 B12-17-AJB-05 / P6 SP-SYS II - 18 SOLAR PANEL - SYSTEM II Terminal Detail (-) Heli Deck - 1 B12-17-AJB-05
System 3
149 B12-17-AJB-06 / P1 SP-SYS III - 01 SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 B12-17-AJB-06
150 SP-SYS III - 02 / P1 SP-SYS III - 01 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 02
151 SP-SYS III - 03 / P1 SP-SYS III - 02 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 03
152 B12-17-AJB-06 / P2 SP-SYS III - 03 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 B12-17-AJB-06
Page : 144 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
153 B12-17-AJB-06 / P3 SP-SYS III - 04 SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 B12-17-AJB-06
154 SP-SYS III - 05 / P1 SP-SYS III - 04 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 05
155 SP-SYS III - 06 / P1 SP-SYS III - 05 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 06
156 B12-17-AJB-06 / P4 SP-SYS III - 06 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 B12-17-AJB-06
157 B12-17-AJB-06 / P5 SP-SYS III - 07 SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 B12-17-AJB-06
158 SP-SYS III - 08 / P1 SP-SYS III - 07 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 08
159 SP-SYS III - 09 / P1 SP-SYS III - 08 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 09
160 B12-17-AJB-06 / P6 SP-SYS III - 09 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 B12-17-AJB-06
161 B12-17-AJB-07 / P1 SP-SYS III - 10 SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 B12-17-AJB-07
Page : 145 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
162 SP-SYS III - 11 / P1 SP-SYS III - 10 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 11
163 SP-SYS III - 12 / P1 SP-SYS III - 11 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 12
164 B12-17-AJB-07 / P2 SP-SYS III - 12 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 B12-17-AJB-07
165 B12-17-AJB-07 / P3 SP-SYS III - 13 SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 B12-17-AJB-07
166 SP-SYS III - 14 / P1 SP-SYS III - 13 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 14
167 SP-SYS III - 15 / P1 SP-SYS III - 14 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 SP-SYS III - 15
168 B12-17-AJB-07 / P4 SP-SYS III - 15 SOLAR PANEL - SYSTEM III Terminal Detail (-) Heli Deck - 1 B12-17-AJB-07
System 4
169 B12-17-AJB-08 / P1 SP-SYS IV - 01 SOLAR PANEL - SYSTEM IV Terminal Detail (+) Heli Deck - 1 B12-17-AJB-08
Page : 146 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
170 SP-SYS IV- 02 / P1 SP-SYS IV - 01 SOLAR PANEL - SYSTEM IV Terminal Detail (-) Heli Deck - 1 SP-SYS IV - 02
171 SP-SYS IV - 03 / P1 SP-SYS IV - 02 SOLAR PANEL - SYSTEM IV Terminal Detail (-) Heli Deck - 1 SP-SYS IV - 03
172 B12-17-AJB-08 / P2 SP-SYS III - 03 SOLAR PANEL - SYSTEM IV Terminal Detail (-) Heli Deck - 1 B12-17-AJB-08
Page : 147 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Portable Boost Charger - 01 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
Portable Boost Charger - 02 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 1 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 2 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 3 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 4 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Page : 148 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 30 Fire Resistant, XLPE, AL 600/1000
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 30 Flame Retardant, XLPE, CU 600/1000
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
Page : 149 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
CCTV Cabinet TIC Room M40 (30-37) 1 1 2C 50 30 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 1 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 2 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 3 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 4 Cellar Deck M20 (14-18) 1 1 2C 6 25 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 5 Cellar Deck M20 (14-18) 1 1 2C 6 30 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 6 Sub-Cellar Deck M20 (14-18) 1 1 2C 6 60 Flame Retardant, XLPE, CU 600/1000
Page : 150 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Illumination Level Gauge 7 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 8 Above Shelter Room M20 (14-18) 1 1 2C 6 55 Flame Retardant, XLPE, CU 600/1000
HIPPS Supply 1 TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
HIPPS Supply 2 TIC Room M40 (30-37) 1 1 2C 50 35 Flame Retardant, XLPE, CU 600/1000
CO2 Snuffing System Main Deck M20 (18-21) 1 1 2C 10 50 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting switch Electrical Room M20 (18-21) 1 1 2C 10 25 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting junction box Electrical Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 8 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting switch TIC Room M20 (18-21) 1 1 2C 10 45 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting junction box TIC Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room lighting switch Battery Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Page : 151 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Battery room lighting junction box Battery Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 20 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting switch Shelter Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting junction box Shelter Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Toilet Room lighting switch Portable Toilet M20 (14-18) 1 1 2C 6 40 Flame Retardant, XLPE, CU 600/1000
Toilet Room light Fixture Portable Toilet M20 (14-18) 1 1 2C 6 3 Flame Retardant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 1 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 2 TIC Room M40 (30-37) 1 1 2C 50 30 Fire Resistant, XLPE, CU 600/1000
Page : 152 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 35 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 45 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 50 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 35 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 4 MPPT-1 (TB4
Electrical Room M20 (14-18) 1 1 1P 1.5 30 Fire Resistant, Twisted pair, CU
18,19)
Page : 155 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 10 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM I Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
Page : 163 of 268
ELECTRICAL CABLE SCHEDULE - B12-17 PLATFORM
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM II Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM III Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
SOLAR PANEL - SYSTEM IV Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
SOLAR PANEL - SYSTEM IV Terminal Detail (+) Heli Deck - 1 1 1C 4 2 Fire Resistant, XLPE, CU 600/1000
Drum MCT
Drg. No. Remarks
No. No.
B12-17-MCT-E05
- -
B12-17-MCT-E01
B12-17-MCT-E05
- -
B12-17-MCT-E02
B12-17-MCT-E05
- -
B12-17-MCT-E03
B12-17-MCT-E05
- -
B12-17-MCT-E04
- - B12-17-MCT-E01
- - B12-17-MCT-E01
Page : 168 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-17-MCT-E01
- - B12-17-MCT-E02
- - B12-17-MCT-E02
- - B12-17-MCT-E03
- - B12-17-MCT-E03
- - B12-17-MCT-E04
B12-17-MCT-E06
- -
B12-17-MCT-E01
B12-17-MCT-E06
- -
B12-17-MCT-E02
B12-17-MCT-E06
- -
B12-17-MCT-E03
B12-17-MCT-E06
- -
B12-17-MCT-E04
B12-17-MCT-E01
- -
MCT-101
B12-17-MCT-E01 C1
- -
MCT-101
Page : 169 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - - C
1
- - -
- - -
- - -
- - -
- - -
- - B12-17-MCT-E02
- - B12-17-MCT-E02
- - B12-17-MCT-E02
- - B12-17-MCT-E02
- - B12-17-MCT-E02
- - B12-17-MCT-E02
Page : 170 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-17-MCT-E02
- - B12-17-MCT-E02 Deleted
B12-17-MCT-E02
- -
MCT-103
B12-17-MCT-E02
- -
MCT-103
- - B12-17-MCT-E02
- - -
- - -
- - -
- - -
B12-17-MCT-E02 C1
- -
MCT-101
- - -
- - -
- - -
B12-17-MCT-E02
- -
B12-17-MCT-E06
Page : 171 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
- - -
- - -
B12-17-MCT-E02
- - B12-17-MCT-E06
B12-17-MCT-E07
- - -
- - -
- - -
- - B12-17-MCT-E02
- - -
B12-17-MCT-E03
- -
MCT-102
B12-17-MCT-E03
- -
MCT-102
Page : 172 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - B12-17-MCT-E04
- - -
- - -
- - -
- - B12-17-MCT-E04
Drum MCT
Drg. No. Remarks
No. No.
- - -
- - -
Shileded 2C X 2.5 Sqmm Cable
- - -
- - - C1
B12-17-MCT-E06
- -
B12-17-MCT-E01
B12-17-MCT-E06
- -
B12-17-MCT-E01
B12-17-MCT-E06
- -
B12-17-MCT-E01
B12-17-MCT-E06
- -
B12-17-MCT-E02
B12-17-MCT-E06
- -
B12-17-MCT-E02
B12-17-MCT-E06
- -
B12-17-MCT-E03
B12-17-MCT-E06
- -
B12-17-MCT-E03
Page : 174 of 268
Drum MCT
Drg. No. Remarks
No. No.
B12-17-MCT-E06
- -
B12-17-MCT-E04
Page : 175 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
3 C24-P2-BC-DCDB-01 / P1 DDP-BC-1 Portable Boost Charger - 01 Main Deck M50 (41-46) 1 C24-P2-BC-DCDB-01
4 C24-P2-BC-DCDB-01 / P2 DDP-BC-2 Portable Boost Charger - 02 Main Deck M50 (41-46) 1 C24-P2-BC-DCDB-01
5 C24-P2-SC-01 / P1 C24-P2-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 C24-P2-SC-01
6 C24-P2-SC-02 / P1 C24-P2-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 C24-P2-SC-02
7 C24-P2-SC-03 / P1 C24-P2-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 C24-P2-SC-03
8 C24-P2-SC-04 / P1 C24-P2-BC-DCDB-01 48V , Boost Charger DCDB - 01 Electrical Room M50 (41-46) 1 C24-P2-SC-04
SOLAR PANEL
Page : 188 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
9 C24-P2-SC-01 / P2 C24-P2-AJB-01 AJB-01 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 C24-P2-SC-01
10 C24-P2-SC-01 / P3 C24-P2-AJB-02 AJB-02 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 C24-P2-SC-01
11 C24-P2-SC-01 / P4 C24-P2-AJB-03 AJB-03 for 12 Nos Solar Module - System 1 Heli Deck CG-1015 1 C24-P2-SC-01
12 C24-P2-SC-02 / P2 C24-P2-AJB-04 AJB-04 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 C24-P2-SC-02
13 C24-P2-SC-02 / P3 C24-P2-AJB-05 AJB-05 for 9 Nos Solar Module - System 2 Heli Deck CG-1015 1 C24-P2-SC-02
14 C24-P2-SC-03 / P2 C24-P2-AJB-06 AJB-06 for 9 Nos Solar Module - System 3 Heli Deck CG-1015 1 C24-P2-SC-03
15 C24-P2-SC-03 / P3 C24-P2-AJB-07 AJB-07 for 6 Nos Solar Module - System 3 Heli Deck CG-1015 1 C24-P2-SC-03
16 C24-P2-SC-04 / P2 C24-P2-AJB-08 AJB-08 for 3 Nos Solar Module - System 4 Heli Deck CG-1015 1 C24-P2-SC-04
BATTERY BANK
17 C24-P2-BR-01 / P1 C24-P2-BR-01 Battery Bank For Solar Power - System 1 Battery Room M63 (53-61) 1 C24-P2-SC-01
18 C24-P2-BR-01 / P2 C24-P2-BR-01 Battery Bank For Solar Power - System 1 Battery Room M63 (53-61) 1 C24-P2-SC-01
19 C24-P2-BR-02 / P1 C24-P2-BR-02 Battery Bank For Solar Power - System 2 Battery Room M63 (53-61) 1 C24-P2-SC-02
Page : 189 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
20 C24-P2-BR-03 / P1 C24-P2-BR-03 Battery Bank For Solar Power - System 3 Battery Room M63 (53-61) 1 C24-P2-SC-03
21 C24-P2-BR-04 / P1 C24-P2-BR-04 Battery Bank For Solar Power - System 4 Battery Room M50 (37-41) 1 C24-P2-SC-04
SYSTEM 1
22 C24-P2-RTU-100 / P1 C24-P2-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 C24-P2-RTU-100
23 C24-P2-RTU-100 / P2 C24-P2-SC-01 Solar System Controller - System 1 Electrical Room M50 (30-37) 1 C24-P2-RTU-100
30 C24-P2-CCTV-100 / P1 C24-P2-SC-01 Solar System Controller - System 1 Electrical Room M40 (30-37) 1 C24-P2-CCTV-100
Page : 190 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 2
31 C24-P2-LG-341-04 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-341-04
32 C24-P2-LG-440-06 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-440-06
33 C24-P2-LG-450-07 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-450-07
34 C24-P2-LG-451-07 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-451-07
35 C24-P2-LG-490-07 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-490-07
36 C24-P2-LG-900-08 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-900-08
37 C24-P2-LG-920-08 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-LG-920-08
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
C24-P2-HIPPS-310-
38 C24-P2-HIPPS-310-13 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
C24-P2-HIPPS-310-
39 C24-P2-HIPPS-310-13 / P2 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M40 (30-37) 1
13
40 C24-P2-M900/P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 C24-P2-M900
41 C24-P2-SW-01 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 C24-P2-SW-01
42 C24-P2-JBL-01 / P1 C24-P2-SW-01 Electrical room lighting switch Electrical Room M20 (18-21) 1 C24-P2-JBL-01
43 C24-P2-LF-01 / P1 C24-P2-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 C24-P2-LF-01
44 C24-P2-LF-02 / P2 C24-P2-JBL-01 Electrical room lighting junction box Electrical Room M20 (18-21) 1 C24-P2-LF-02
45 C24-P2-SW-02 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 C24-P2-SW-02
46 C24-P2-JBL-02 / P1 C24-P2-SW-02 Telemetry room lighting switch TIC Room M20 (18-21) 1 C24-P2-JBL-02
47 C24-P2-LF-03 / P1 C24-P2-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 C24-P2-LF-03
Page : 192 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
48 C24-P2-LF-04 / P2 C24-P2-JBL-02 Telemetry room lighting junction box TIC Room M20 (18-21) 1 C24-P2-LF-04
49 C24-P2-SW-03 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 C24-P2-SW-03
50 C24-P2-JBL-03 / P1 C24-P2-SW-03 Battery room lighting switch Battery Room M20 (18-21) 1 C24-P2-JBL-03
51 C24-P2-LF-05 / P1 C24-P2-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 C24-P2-LF-05
52 C24-P2-LF-06 / P2 C24-P2-JBL-03 Battery room lighting junction box Battery Room M20 (18-21) 1 C24-P2-LF-06
53 C24-P2-SW-04 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (18-21) 1 C24-P2-SW-04
54 C24-P2-JBL-04 / P1 C24-P2-SW-04 Shelter Room lighting switch Shelter Room M20 (18-21) 1 C24-P2-JBL-04
55 C24-P2-LF-07 / P1 C24-P2-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 C24-P2-LF-07
56 C24-P2-LF-08 / P2 C24-P2-JBL-04 Shelter Room lighting junction box Shelter Room M20 (18-21) 1 C24-P2-LF-08
57 C24-P2-SW-05 / P1 C24-P2-SC-02 Solar System Controller - System 2 Electrical Room M20 (14-18) 1 C24-P2-SW-05
Page : 193 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
58 C24-P2-LF-09 / P1 C24-P2-SW-05 Toilet Room lighting switch Portable Toilet M20 (14-18) 1 C24-P2-LF-09
Page : 194 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
SYSTEM 3
59 C24-P2-F&G-100 / P1 C24-P2-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 C24-P2-F&G-100
60 C24-P2-F&G-100 / P2 C24-P2-SC-03 Solar System Controller - System 3 Electrical Room M40 (30-37) 1 C24-P2-F&G-100
SYSTEM 4
61 C24-P2-NAV 1 - JB / P1 C24-P2-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 C24-P2-NAV 1 - JB
62 C24-P2-NAV 2 - JB / P1 C24-P2-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 2 - JB
63 C24-P2-NAV 3 - JB / P1 C24-P2-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 3 - JB
64 C24-P2-NAV 4 - JB / P1 C24-P2-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 C24-P2-NAV 4 - JB
65 C24-P2-NAV 4 - JB / P2 C24-P2-SC-04 Solar System Controller - System 4 Electrical Room M50 (30-37) 1 C24-P2-NAV 4 - JB
Page : 195 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
70 C24-P2-NAV 2- JB / C1 C24-P2-NAV 1 - JB NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 C24-P2-NAV 2 - JB
71 C24-P2-NAV 3 - JB / C1 C24-P2-NAV 2 - JB NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 C24-P2-NAV 3 - JB
72 C24-P2-NAV 4 - JB / C1 C24-P2-NAV 3 - JB NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 C24-P2-NAV 4 - JB
73 C24-P2-NAV 1 - JB / C1 C24-P2-NAV 4 - JB NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 C24-P2-NAV 1 - JB
Page : 196 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
THERMISTOR CABLE
74 C24-P2-SC-01 / C1 C24-P2-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 C24-P2-SC-01
75 C24-P2-SC-01 / C2 C24-P2-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 C24-P2-SC-01
76 C24-P2-SC-01 / C3 C24-P2-BR-01 Battery Bank For Solar Power - System 1 Battery Room M20 (14-18) 1 C24-P2-SC-01
77 C24-P2-SC-02 / C1 C24-P2-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 C24-P2-SC-02
78 C24-P2-SC-02 / C2 C24-P2-BR-02 Battery Bank For Solar Power - System 2 Battery Room M20 (14-18) 1 C24-P2-SC-02
79 C24-P2-SC-03 / C1 C24-P2-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 C24-P2-SC-03
80 C24-P2-SC-03 / C2 C24-P2-BR-03 Battery Bank For Solar Power - System 3 Battery Room M20 (14-18) 1 C24-P2-SC-03
81 C24-P2-SC-04 / C1 C24-P2-BR-04 Battery Bank For Solar Power - System 4 Battery Room M20 (14-18) 1 C24-P2-SC-04
Page : 197 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Page : 198 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 1
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Page : 202 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 2
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Page : 209 of 268
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 3
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
System 4
Project : DAMAN DEVELOPMENT PROJECT - PHASE 2 (C24-P2, B12-11, B12-13, B12-15 & B12-17)
Client : OIL & NATURAL GAS CORPORATION LTD
From
No. Cable No.
Equipment No. Description Location Gland1 Qty1 Equipment No.
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Portable Boost Charger - 01 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
Portable Boost Charger - 02 Main Deck - 1 1 4C 25 300 Flame Retardant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
48V , Boost Charger DCDB Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 1 Electrical Room M50 (41-46) 1 1 2C 120 20 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 2 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 3 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Solar System Controller - System 4 Electrical Room M50 (41-46) 1 1 2C 120 15 Fire Resistant, XLPE, CU 600/1000
Page : 214 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M50 (37-41) 1 1 2C 120 55 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 3 Electrical Room M50 (37-41) 1 1 2C 120 70 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 80 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 1 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 2 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Page : 215 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Solar System Controller - System 3 Electrical Room M63 (53-61) 1 1 2C 240 35 Fire Resistant, XLPE, AL 600/1000
Solar System Controller - System 4 Electrical Room M50 (37-41) 1 1 2C 120 35 Fire Resistant, XLPE, AL 600/1000
Remote Telemetry Unit TIC Room M40 (30-37) 1 1 2C 50 30 Flame Retardant, XLPE, CU 600/1000
Remote Telemetry Unit TIC Room M50 (30-37) 1 1 2C 70 30 Fire Resistant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
TIC Cabinet TIC Room M20 (14-18) 1 1 2C 6 5 Flame Retardant, XLPE, CU 600/1000
CCTV Cabinet TIC Room M40 (30-37) 1 1 2C 50 25 Flame Retardant, XLPE, CU 600/1000
Page : 216 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Illumination Level Gauge 1 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 2 Cellar Deck M20 (14-18) 1 1 2C 6 15 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 3 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 4 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 5 Cellar Deck M20 (14-18) 1 1 2C 6 20 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 6 Sub-Cellar Deck M20 (14-18) 1 1 2C 6 60 Flame Retardant, XLPE, CU 600/1000
Illumination Level Gauge 7 Cellar Deck M20 (14-18) 1 1 2C 6 50 Flame Retardant, XLPE, CU 600/1000
Above Shelter
Illumination Level Gauge 8 - 1 - - - - - -
Room
Page : 217 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
HIPPS Supply 1 TIC Room M40 (30-37) 1 1 2C 50 25 Flame Retardant, XLPE, CU 600/1000
HIPPS Supply 2 TIC Room M40 (30-37) 1 1 2C 50 25 Flame Retardant, XLPE, CU 600/1000
CO2 Snuffing System Main Deck M20 (18-21) 1 1 2C 10 50 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting switch Electrical Room M20 (18-21) 1 1 2C 10 20 Flame Retardant, XLPE, CU 600/1000
Electrical room lighting junction box Electrical Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Electrical Room light Fixture Electrical Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting switch TIC Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Telemetry Room lighting junction box TIC Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Page : 218 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Telemetry Room light Fixture TIC Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room lighting switch Battery Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Battery room lighting junction box Battery Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 15 Flame Retardant, XLPE, CU 600/1000
Battery room light Fixture Battery Room M20 (18-21) 1 1 2C 10 20 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting switch Shelter Room M20 (18-21) 1 1 2C 10 40 Flame Retardant, XLPE, CU 600/1000
Shelter Room lighting junction box Shelter Room M20 (18-21) 1 1 2C 10 2 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Shelter Room light Fixture Shelter Room M20 (18-21) 1 1 2C 10 10 Flame Retardant, XLPE, CU 600/1000
Toilet Room lighting switch Portable Toilet M20 (14-18) 1 1 2C 6 40 Flame Retardant, XLPE, CU 600/1000
Page : 219 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Toilet Room light Fixture Portable Toilet M20 (14-18) 1 1 2C 6 2 Flame Retardant, XLPE, CU 600/1000
Page : 220 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Fire & Gas Detection Panel Supply - 1 TIC Room M40 (30-37) 1 1 2C 50 25 Fire Resistant, XLPE, CU 600/1000
Fire & Gas Detection Panel Supply - 2 TIC Room M40 (30-37) 1 1 2C 50 25 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 1 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 2 - JB Cellar Deck M50 (30-37) 1 1 2C 70 60 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M50 (30-37) 1 1 2C 70 40 Fire Resistant, XLPE, CU 600/1000
Page : 221 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
NAV AIDS Lantern 2 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 60 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 3 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 4 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
NAV AIDS Lantern 1 - JB Cellar Deck M20 (14-18) 1 1 2C 2.5 40 Fire Resistant, XLPE, CU 600/1000
Page : 222 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Page : 224 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Page : 228 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Page : 235 of 268
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
To
Size Length Voltage
Runs NOC Cable Spec.
(Sq.mm) (Mtrs) (V)
Description Location Gland2 Qty2
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
- - C24-P2-MCT-E01
- - C24-P2-MCT-E01
- - C24-P2-MCT-E01
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E03
- - C24-P2-MCT-E03
- - C24-P2-MCT-E04
C24-P2-MCT-E06
- -
C24-P2-MCT-E01
C24-P2-MCT-E06
- -
C24-P2-MCT-E01
C24-P2-MCT-E06
- -
C24-P2-MCT-E02
Page : 241 of 268
Drum MCT
Drg. No. Remarks
No. No.
C24-P2-MCT-E06
- -
C24-P2-MCT-E03
C24-P2-MCT-E06
- -
C24-P2-MCT-E04
C24-P2-MCT-E01
- -
MCT-101
C24-P2-MCT-E01
- -
MCT-101
- - -
- - -
- - -
- - -
- - -
- - -
Drum MCT
Drg. No. Remarks
No. No.
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - C24-P2-MCT-E02
- - - Deleted C1
Page : 243 of 268
Drum MCT
Drg. No. Remarks
No. No.
C24-P2-MCT-E02
- -
MCT-103
C24-P2-MCT-E02
- -
MCT-103
- - C24-P2-MCT-E02
- - -
- - -
- - -
- - -
C24-P2-MCT-E02
- -
MCT-101
- - -
- - -
Page : 244 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
C24-P2-MCT-E02
- -
C24-P2-MCT-E06
- - -
- - -
- - -
C24-P2-MCT-E02
- - C24-P2-MCT-E06
C24-P2-MCT-E07
- - -
- - -
- - -
- - C24-P2-MCT-E02
Page : 245 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
Page : 246 of 268
Drum MCT
Drg. No. Remarks
No. No.
C24-P2-MCT-E03
- -
MCT-102
C24-P2-MCT-E03
- -
MCT-102
- - C24-P2-MCT-E04
- - - C1
- - -
- - -
- - C24-P2-MCT-E04
Page : 247 of 268
Drum MCT
Drg. No. Remarks
No. No.
- - -
- - -
Shileded 2C X 2.5 Sqmm
Cable provided
- - -
- - -
Page : 248 of 268
Drum MCT
Drg. No. Remarks
No. No.
C24-P2-MCT-E06
- -
C24-P2-MCT-E01
C24-P2-MCT-E06
- -
C24-P2-MCT-E01
C24-P2-MCT-E06
- -
C24-P2-MCT-E01
C24-P2-MCT-E06
- -
C24-P2-MCT-E02
C24-P2-MCT-E06
- -
C24-P2-MCT-E02
C24-P2-MCT-E06
- -
C24-P2-MCT-E03
C24-P2-MCT-E06
- -
C24-P2-MCT-E03
C24-P2-MCT-E06
- -
C24-P2-MCT-E04
Page : 249 of 268
Drum MCT
Drg. No. Remarks
No. No.
Page : 250 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Page : 254 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Page : 261 of 268
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Drum MCT
Drg. No. Remarks
No. No.
Electrical
Used Purchased
- 734 -
CG-1015 277 -
M20 40 -
M20 (14-18) 276 218
M20 (18-21) 176 220
M32 0 -
M40 (30-37) 66 78
M50 (30-37) 54 67
M50 (37-41) 51 111
M50 (41-46) 78 94
M63 (53-61) 50 58
B12-17 C24-P2
Count - Qty2 Gland1 Count - Qty1 Gland2 Count - Qty2 Gland1
49 - 94 - 48 -
46 CG-1015 8 CG-1010 46 CG-1015
4 M20 4 M20 4 M20
27 M20 (14-18) 28 M20 (14-18) 28 M20 (14-18)
17 M20 (18-21) 17 M20 (18-21) 17 M20 (18-21)
7 M40 (30-37) 7 M40 (30-37) 7 M40 (30-37)
5 M50 (30-37) 5 M50 (30-37) 5 M50 (30-37)
9 M50 (37-41) 1 M50 (37-41) 9 M50 (37-41)
6 M50 (41-46) 6 M50 (41-46) 6 M50 (41-46)
3 M63 (53-61) 3 M63 (53-61) 3 M63 (53-61)
(empty) (empty) (empty)
173 Total Result 173 Total Result 173 Total Result
Count - Qty1 Gland2 Count - Qty2
99 - 51
8 CG-1010 48
4 M20 4
27 M20 (14-18) 27
17 M20 (18-21) 17
6 M40 (30-37) 6
6 M50 (30-37) 6
1 M50 (37-41) 9
6 M50 (41-46) 6
4 M63 (53-61) 4
(empty)
178 Total Result 178