You are on page 1of 6

Selective Wave-Front Based Protection

Algorithm for MTDC Systems


N Johannesson*, S Norrga*, C Wikstrm
*KTH Royal Institute of Technology, Sweden, njohanne@kth.se, norrga@kth.se
ABB HVDC, Sweden, christian.wikstrom@se.abb.com

Keywords: HVDC power transmission, power transmission clearing is achieved. Achieving selective detection of DC line
protection, power transmission faults, circuit breakers. faults is, however, not straightforward since the low impedance
characteristics of the DC network provides a very small
Abstract electrical distance at the boundary of the protection zone in the
forward direction. The presence of current limiting reactors
Protection algorithms which can differentiate between installed in series with DC breakers increase the electrical
different faults is a necessity for the reliable operation of multi- distance between protection zones and does therefore enable
terminal HVDC systems with multiple DC breakers. For single-ended protection schemes to differentiate between faults
selective detection by single-ended line protection algorithms, at either side of this inductance where one is considered to be
current limiting reactors installed in series with the breaker at internal and one is external.
the opposite side of the line can be used for limiting the reach
in the forward direction. In this paper, a further development The principle of differentiating between remote internal faults
on the idea of basing the detection on the incident traveling and external faults by using a DC reactor is not new and has
wave is presented. The extraction of the incident wave is been used for many years in LCC HVDC schemes. However,
achieved by representing the frequency dependent the critical external faults in these systems are typically
characteristic admittance by a rational approximation. The commutation failures, during which the DC line protection at
main advantage over other single-ended protection methods is the rectifier should not operate [1].
that the incident wave is independent of the boundary The principle of using reactors for selective detection of faults
conditions at the terminal of the line. In this paper, this is has recently received further attention for applications in
illustrated by the simulation of both internal and external faults MTDC systems. Previously published methods for single-
during two different operation scenarios in a four-terminal ended algorithms typically rely on measured voltage, current,
MTDC system. Finally, the performance of the suggested their derivatives or combinations thereof [2][6]. The
protection algorithm is compared to other single-ended drawback of single-ended methods is that the selective
methods with regard to the protection margin. operation heavily relies on the protection setting. This setting
has to be determined by extensive time-domain simulations
1 Introduction where all imaginable operation scenarios are studied.

The ongoing transition towards renewable energy generation is In this paper, a detection method based the principle of using
challenging the structure and operation of existing power the incident wave is described. This idea has previously been
transmission systems. Therefore, an increasing share of HVDC presented for application in both AC [7] and HVDC [8]
transmission is expected in the future. For optimization of applications. The further development from previous work
investment cost and minimization of transmission losses, consists in adapting the technique for cables, in which the
multiple HVDC lines and converters might be connected characteristic impedance is strongly frequency-dependent, and
together on the DC side, thus forming a multi-terminal HVDC therefore cannot be accurately approximated by a constant. In
system (MTDC). Recent developments of DC breakers, the proposed method, this is achieved by using rational
capable of clearing DC faults within a few milliseconds since approximations, the same approach which is commonly used
their application allow for selective disconnection of DC faults. in time domain simulation programs. The main advantage of
basing the detection on the incident wave is that the incident
For maximum reliability of MTDC systems, the protection wave is independent of the boundary conditions at the terminal
zones should be as small as possible, ideally containing a single where the protection is located.
object such as a busbar or a DC cable. This type of
configuration is similar to those being used in AC transmission After presenting the relevant theory and explanation of the
systems and allow for disconnection of the only faulted object principle, the performance of the proposed method is
where the healthy parts of the system to continue their benchmarked against other methods in PSCAD/EMTDC
operation. simulations of a four-terminal MTDC model provided by the
authors of [9]. Remote internal and external faults are
The protection system in such configurations with multiple DC simulated during two different operation scenarios with and
breakers must be able to differentiate between different faults without one converter connected. The incident wave protection
such that the correct DC breakers operate and selective fault

1
is shown to give identical results in these two cases which is in A
Equivalent impedance x = A x=0 B
agreement with the theoretical discussion. of the network If

2 DC line protection I t=0 -


V 0
Zeq V + Vf
x +
2.1 Telegraphers equation and traveling waves
Measurements for I+
Due to the combination of fast dynamics associated with line protection
HVDC systems and the typical great geographical distance Figure 2 Internal cable fault and the traveling waves which
between terminals in HVDC systems, lumped line models do originate from the location of the fault.
not accurately describe the behaviour during faults in MTDC imaginary parts, which vary with frequency. In the time
systems. Instead, the distributed parameters of transmission domain, the wave which appears at the other end is therefore
lines must be considered where voltages and currents behave both delayed and distorted. The behaviour is conceptually
as waves which travel back and forth along the line. illustrated in Figure 1. As seen in (7), the amount of delay and
For a general transmission line with n conductors, the per-unit- severity of distortion depends on the length of the line , where
length series impedance (Z) and the per-unit-length shunt long lines of a given geometry result in greater distortion.
admittance (Y) consist of square matrices (n u n) where the off-
diagonal elements represent the coupling between conductors. 2.2 Waves originating from cable faults
At an arbitrary point x along the transmission line, the voltage During short-circuits, the voltage at the fault location collapses
(Vx) and current (Ix) are column-vectors of dimension (n u 1), from the pre-fault voltage to a low level. If the fault is assumed
Ix ex I  ex I (1) to be solid, the remaining voltage in the fault location can be
x  x  assumed to be strictly zero, and thus be represented by the
Vx  e V e V (2)
sudden connection of an ideal step voltage with opposite
where YZ is the propagation constant matrix, and I  I ,  
polarity but equal magnitude of the pre-fault voltage in the fault
V V are the forwards and backwards traveling waves of location.
currents and voltages, determined at the terminals of the line.
For easier explanation of the transients after a fault, the
Substitution of the solutions from (1)-(2) into the original superposition principle can be used, which allows for the short-
telegraphers equations reveal the relation between voltage and circuiting of all other sources than the step voltage which
current waves which allows for the voltage to be written in represent the fault. The advantage of using this approach is that
terms of the current waves, the circuit is initially at rest which means that all waves prior
x 
Vx  Y1
c e I ex I (3) to the application of the step voltage are zero. The equivalent
where Yc is the characteristic admittance matrix which is circuit for representing the cable fault using this approach is
calculated from the line parameters displayed in Figure 2 where the fault is located at the distance
A from the protection, located at the left side of the figure.
Yc YZ1 Y. (4) Note that in the general case with multiple conductors, all
Considering a transmission line of length where voltages and voltages, currents and waves are vectors.
currents are observed at both ends, i.e. at x 0 and x , the Once the fault is applied, at t 0, the voltage in the fault
relation between voltages and currents at both ends relate to location becomes Vf where the element which corresponds to
each other as the faulted conductor equals the voltage source. It should be
I YcV  2HI HI0 YcV0 (5) noted that the elements in Vf which correspond to the non-

I0 YcV0 2I HI YcV (6) faulted conductors are not necessarily strictly zero, depending
where the propagation function matrix H is calculated as on the coupling. For instance, in symmetrical monopoles where
the converter is connected between the two poles, and none of
H e . (7)
them is grounded, the healthy pole is known to experience
The interpretation of the results in (5)-(6) is that the wave overvoltage during asymmetrical faults. However, since this
which enters the transmission line at one end appears at the paper is concerned with the steep wave-fronts caused by the
other end as modified by the propagation function matrix. The sudden breakdown of voltage, this is neglected since the
propagation function matrix has in general both real and components which connect the two poles (inductance and
capacitance) result in that the voltages on the other conductors
I+ Attenuation/Distortion

change at a much slower rate compared to an ideal step.
I0 I HI+
Since the circuit is assumed to initially be at rest before the
Propagation delay () + + fault is applied, the negative direction waves (V, I) which
V0 V I-
travel from the protection location in the direction of the fault
HI- - x=0 x x= - are initially zero. Therefore, the voltage in the fault location
Figure 1 Traveling waves enters at one end and appear at the other becomes Vf which according to (2) results in a positive
influenced by the propagation matrix. direction non-zero voltage wave,

2
V Vf 0 t  2WA (8) During a fault beyond the reactor, as illustrated in Figure 3, the
where WA is the propagation time of the cable length A. The voltage at the line side of the reactor do not collapse
voltage wave which travel towards the protection is therefore instantaneously as during the internal fault. Instead, it depends
initially equal to the voltage in the fault location. on the relation between the characteristic impedance of the line
and the inductance of the reactor. The result is that the waves
Since the voltage and current waves in each direction always which are initiated in the positive direction have a limited slope
are accompanied by each other, the application of the fault of the wave-front. This is illustrated by the waves which enter
simultaneously initiates a current wave I, the cable at the right side in the figure. The dashed lines in the
I YcVf . 0 t < 2WA (9) figure are provided for comparison with the wave-shapes
Similarly as for the voltage, the current wave will initially be during the internal fault, which was discussed in the previous
equal to the current contribution from the cable into the fault. subsection.
Due to the polarity convention, the discharge current (If) As the waves propagate along the line, they are influenced by
illustrated in Figure 2 is of opposite direction to the current attenuation and distortion before they finally arrive at the
wave. terminal shown on the left side of the figure. Given the
The waves which originated at the fault location arrive at the difference between the wave-shapes of the internal and
end of the cable (x = A) a time interval WA later, and appear external faults, the line protection can be designed to
with an altered shape, determined by the propagation function differentiate between these two cases. However, even though
(HA). Once the waves arrive, they encounter the equivalent the waves which enter the line are clearly different, the waves
source impedance (Zeq) which results from the combination of which eventually arrive at the protection are much more
all equipment connected at that point (e.g. reactor, converter, difficult to distinguish between due to the low-pass
neighbouring cables, AC network etc). Since the voltage and characteristics of the propagation function (H). As the
current at the relaying point must fulfil the circuit laws propagation function is dependent on the length of the line, at
according to Zeq, and the incident waves are determined at the a certain length of cable, the difference between the waves
fault location, some of the incident waves are in the general which eventually arrive at the protection will not be significant
case reflected backwards in the negative direction. This implies enough for differentiating between them. In such cases, single-
that the voltage (V) and current (I), to be used for detection, ended protection schemes might not be able to reliably cover
are depending on the boundary conditions of the line. Since the the entire line length.
source impedance is a combination of all equipment at that
point, it is very likely that this will change during operation in 2.4 DC line protection setting
a MTDC systems. For instance, if a DC busbar has multiple
As single-ended DC line protection methods are not inherently
cables connected, the operators could switch any of the cables
selective, they require the setting to be coordinated such that
in or out of service at any time. This will change the source
its forward direction reach is limited such that the protection
impedance which results in a different behaviour of voltage
can operate with selectivity. In principle, the setting needs to
and currents, thus influencing protections based on them.
be determined from extensive numerical simulations where all
possible operation scenarios and events are covered. The
2.3 External disturbances setting can then be chosen be identifying the worst internal
For the DC line protection to be able to differentiate between and external case and then choosing a setting which makes the
remote internal faults and external disturbances in the forward protection to only operate when required. The principle is
direction, the two most crucial cases are faults on each of the illustrated in Figure 4 where the protection algorithm output
sides of the reactor at the remote end. One of which is internal during internal and external faults are compared.
and should be detected, whereas the other one is external and As illustrated in the figure, the protection setting could in
should not cause the line protection to operate. principle be chosen anywhere within the interval between the
x= x=0 two cases and operate with selectivity. However, the result of
If simulations cannot be assumed to be entirely accurate, and
some deviation always has to be anticipated if the protection is
I x to be applied in practice. Therefore, the margins are very
V important as they provide some indication of whether a
Zeq
External Fault
protection scheme will be reliable or not. As illustrated in the
t=0 t = A t=0 figure, applying a reduced setting will result in a more
+ dependable protection since it will be more sensitive. On the
HV V+
other hand, the probability that the protection might falsely
operate during an external fault, or other disturbance, is
HI + I+
increased. Similarly, increasing the setting will make the
protection less sensitive, but then risk that the protection does
not operate during actual internal faults. Thus, obtaining a
Figure 3 Waves which enter and arrive at the protection during
internal (dashed) and external faults (solid).

3
v are column-vectors of the measured currents and voltages at
0 the end of the line, respectively.
Protection output

Increased dependability For detection of the wave-front, the slope can be estimated as
-20
the difference over a pre-determined period of time (T),
Protection Setting
iTW (t) iTW (t)iTW (tT). (12)
-40
Internal Fault The calculated slope for each element in the vector iTW is then
Increased security
External Fault
separately compared with the setting threshold. If one or more
-60
elements exceed the threshold, an internal fault in the
5.1 5.105 5.11 5.115 5.12 conductors corresponding to those elements is detected. The
Time (s) algorithm is conceptually shown in Figure 5.
Figure 4 Principle of achieving selective detection by coordination
of the protection setting. The protection algorithm based on detection of the incident
proper setting involves a trade-off between security and wave is in principle directional since it is only sensitive to the
dependability. wave which travel in the direction toward the protection. For
application in practice, it might however be beneficial to
Even though the actual setting of a protection is a trade-off, the complement the operation with the detection of low voltage
width of the interval in which a setting can be chosen is a good and/or high current. In such a combination, the incident wave
indicator of how suitable different protection principles are for protection provide the selectivity and the presence of additional
a given main circuit. Alternatively, the protection margin can criteria ensure that a fault is actually present.
be considered as the ratio between the protection output during
internal and external faults as
3.2 Characteristic admittance
Algoritm output, Internal
m (10) As stated in the formulation of the algorithm in (11), a
Algoritm output, External
where the numerator is the most difficult internal fault to detect convolution between characteristic admittance and voltage is
and the denominator is the external disturbance during which required for extracting the incident current wave. Since the
the protection shall not operate. The resulting margin (m) is admittance is frequency-dependent, numerical time domain
dimensionless and a larger margin is better whereas a value of simulation tools often rely on frequency domain
1.0 would signify that the protection is not able to differentiate approximations in a form which can easily be transformed into
between internal and external faults. Calculating the protection the time-domain and implemented with a high computational
margin from the example in Figure 4 results in efficiency [10]. One of the commonly used forms is a series of
m = 6010 = 6.0 pu. rational approximations,
N
ci
3 Incident traveling wave protection f s  d (13)
sai
i 1
where the approximation is of the Nth order, d is a constant, ci
3.1 Protection algorithm
and ai are residues and poles, respectively.
As previously explained, the sudden breakdown of voltage at For the calculation of the incident wave, each element in the
the location of a fault on a transmission line initiates voltage characteristic admittance matrix (Yc) is fitted into the form
waves where the wave-front is a step function. Since external given in (13). In general, all elements of the matrix should be
faults in the forward direction result in a limited slope of the represented but in some cases the off-diagonal elements may
wave-front, detection of faults might be based on the slope of be neglected if they are close to zero, i.e. if the coupling
the incident wave. between conductors is very low. This is typically the case for
The voltage wave is accompanied by a current wave which is cables, which are surrounded by their separate shields.
related to the voltage wave by the characteristic impedance of For some special cases, when there exists a particular
the line. For cables, the characteristic impedance is typically symmetry in the configuration of the transmission line, it is
frequency-dependent and the current wave therefore has a convenient to perform the calculations of the waves in the
different shape than the voltage wave. The shape of the current modal domain rather than in the phase-domain since the
wave is more suitable for detection since it results in larger
margins between internal and external faults. I
DC Cable

Even though waves on a transmission lines cannot be V Relaying point Protection


measured directly, they can be calculated. For detection of the setting
incident current wave, the protection at the end of the cable DC Line
Protection iref a Operate
calculates the incident wave according to v(t) i(t) iTW (t) + b<a
+
iTW (t)
b

iTW (t) 0.5i (t)yc v (t) (11) s c- a
i
i
i
+
1
2 e-sT iTW(t-T)
Recursive convolution Delay Protection algorithm
where denotes time domain convolution, yc is the matrix with Figure 5 Block diagram which illustrates the method of the incident
impulse responses of the characteristic admittance and i and traveling wave protection.

4
Converter 1
Cable 12 100 km Converter 2 converter 1 is isolated by a disconnector. Consequently, the
disconnected converter does not contribute any fault current in
DC Line
Protection Case II, thus reducing the current through the current sensor
used by the protections.
Cable 13 200 km

Cable 24 150 km
Disconnector Since the cable configuration is symmetrical (2 cables which
Case I Closed
Case II - Opened are buried at the same depth with the same internal geometry),
the modal domain approach is used for the implementation of
the incident traveling wave protection. The two modal domain
Converter 3 Converter 4
Internal Fault
characteristic admittances (ground and pole mode) are realized
as 5th order rational approximations.
Cable 34 100 km
External Fault

Figure 6 Meshed MTDC system with four terminals. 5 Results


characteristic admittance matrix becomes diagonal, thus The resulting voltages and currents of the four simulations are
allowing for each mode to be considered as an independent shown in the two left subfigures of Figure 7. The right
single-phase conductor. However, this is typically only subfigure shows the incident current wave. The solid lines
practical in some situations where the transformation matrices show the results during Case I, i.e. with converter 1 connected
are real and constant, whereas the phase-domain approach is to the DC network. The figure reveals that the voltage is quite
more general. similar during the first couple of hundred microseconds,
whereas the current almost instantaneously deviates between
4 Time domain simulations Case I and Case II. The difference is mainly due to the pole
capacitor of the converter which being is disconnected together
For illustrating the performance of the incident traveling wave with converter 1 during Case II.
protection, time domain simulations have been performed in
As expected, the incident current wave is not noticeably
PSCAD/EMTDC of a four-terminal MTDC system as influenced by the changed impedance the waves encounter at
developed in [9]. The system is based on symmetrical the protection location. This is in agreement with the
monopoles with a rated voltage of 320 kV. The four previously discussed theory. The incident wave at the
converters are connected by DC cables with varying lengths, protection will in fact not differ until the reflected wave returns
according to the illustration in Figure 6. Each cable is equipped
to the fault location and is reflected back, i.e. until after 3WA
with a DC breaker at both ends, and the inductance of the
which for the 250 km long cable in these simulations
current limiting reactors is 50 mH.
corresponds to approximately 4.4 ms since the fault is located
The original cable model in [9] is based on a 1200 mm2 PEX at the very remote end of the cable.
cable with copper conductor which has a comparatively low
Internal Fault (Case I)
distortion for the lengths given in the original model. This 9
6.54 kVkA

Internal Fault (Case II)


makes the differentiating between internal and external faults 8 External Fault (Case I)
-1.13 kA
-1.13 kA
External Fault (Case II)
comparatively easy, with large protection margins. Therefore, 7
Protection margin [pu]

4.43 kVkA

the protected cable (Cable 14) was replaced by a model of a 6


-0.301 kA

250 km long cable with aluminium conductor. The aluminium 5


-0.243 kA
-58.1 kV

cable has larger distortion and thus makes the protection design
-59 kV

a bit more challenging. 3


0.909 kVkA
-0.0721 kA

-0.186 kA

-0.186 kA
0.527 kVkA
-17.8 kV

-0.0408 kA
-15.8 kV

For illustrating the influence of the source impedance on 2

protection performance, both internal and external faults were 1

simulated during two different operation scenarios, denoted as 0


+
'V 'I 'V 'I ' iTW
Case I and Case II. The difference being that in the latter,
Figure 8 Simulation results for each protection.
0.5 0.5
300 Internal Fault (Case I)
Incident traveling wave current [kA]

0 0
External Fault (Case I)
Internal Fault (Case II) -0.5
200 -0.5
External Fault (Case II)
DC Voltage [kV]

DC Current [kA]

-1
-1
100 -1.5
-1.5
-2
0 -2
-2.5
-3 -2.5
-100
-3.5 -3

-200 -4 -3.5
1.2 1.202 1.204 1.206 1.208 1.21 1.2 1.202 1.204 1.206 1.208 1.21 1.2 1.202 1.204 1.206 1.208 1.21
Time (s) Time (s) Time (s)

Figure 7 Simulation results during internal and external faults when converter 1 is connected (solid) and disconnected (dashed).

5
The differences in primary voltage and current due to the is and thereby also the probability that it will operate as
changed boundary conditions must be considered during the expected.
design of the DC line protections which relies on them for
Basing the detection on the incident wave, by combining the
detection. The results of a few different protection methods are
current with voltage and characteristic admittance of the cable,
shown in Figure 8. As previously discussed, the protection
makes the detection principle independent of the boundary
margin is a valuable performance indictor since it provides a
conditions at the terminal of the line. This has been
sense of how much deviations are allowed with regard to
demonstrated in this paper by considering two different
modelling errors and therefore also the probability of
operation scenarios, with and without one of the converters
successful operation in practice. Assuming that the protection
connected to the DC bus. If the protection is required to have
settings are not to be changed during different operation
the same setting, without changing settings depending on the
scenarios, which would increase the complexity, the settings
configuration, the incident traveling wave has the largest
must be chosen with regard to all possible scenarios in which
protection margin of the compared protection principles.
the protection should, respectively should not, operate. The
y-axis in Figure 8 is therefore normalized with regard to the
external fault which is the more severe of the two cases (Case I References
and Case II). Hence, the total protection margin for each
protection is the height of the lowest internal fault in the figure. [1] D. Naidoo and N. M. Ijumba, HVDC line protection
As already expected from the primary voltages and currents, for the proposed future HVDC systems, in Int. Conf.
the protections based on currents (I and VI) show the Power Syst. Technol., Singapore, 2004, vol. 2, pp.
largest deviations due to the disconnection of converter 1. This 13271332.
can be further illustrated by one extreme case where only a [2] L. Tang and B.-T. Ooi, Protection of VSC-multi-
single cable is connected to the bus such that there are no terminal HVDC against DC faults, in IEEE 33rd
contributors of fault current at all. Since the fault current will Annu. Power Electron. Spec. Conf., Cairns, 2002, vol.
be zero, so will also the derivative and the protection based on 2, pp. 719724.
current will fail to recognize the fault. This is perhaps a non- [3] A.-K. Marten, C. Troitzsch, and D. Westermann,
critical case since no equipment will be feeding the fault, but it Non-telecommunication based DC line fault
is still illustrative of the dependence on boundary conditions. detection methodology for meshed HVDC grids, in
11th Int. Conf. AC DC Power Transm., Birmingham,
2015.
6 Discussion [4] V. Pathirana, U. Gnanarathna, K. Nanayakkara, and J.
Since the voltage and current at the terminal of a line is subject Zhou, Protection Design Considerations for VSC
to the circuit laws at that point, incident waves originating from Based HVDC Grids, in CIGR Conf. Innov. Secur.
a fault will generally be reflected back onto the cable and travel Effic. Transm. Grids, Brussels, 2014, pp. 18.
back towards the fault. Basing the detection solely on voltage [5] J. Descloux, J.-B. Curis, and B. Raison, Protection
or current derivatives is therefore not actually a detection of the algorithm based on differential voltage measurement
traveling wave caused by the fault, but is instead a detection of for MTDC grids, in 12th IET Int. Conf. Developments
sum of both incident and reflected waves, where the reflected Power Syst. Protection (DPSP 2014), Copenhagen,
wave is a function of source impedance encountered by the 2014.
incident wave at the protection location. Particularly in MTDC [6] J. Wang, B. Berggren, K. Linden, J. Pan, and R. Nuqui,
systems, the operation conditions might change, thus changing Multi-Terminal DC System line Protection
the equivalent impedance. Requirement and High Speed Protection Solutions, in
CIGR Symp., Lund, 2015.
[7] A. T. Johns, New ultra-high-speed directional
7 Conclusion comparison technique for the protection of e.h.v.
Single-ended protection algorithms are not inherently selective transmission lines, IEE Proc. C Gener. Transm.
and therefore relies on proper protection settings in order to Distrib., vol. 127, no. 4, pp. 228239, Jul., 1980.
operate reliably. For MTDC system studies, where single- [8] G. Arnljotsson, Line Fault detection in HVDC
ended protection principles are used and the forward direction transmission based on the Travelling wave principal,
is limited by the presence of a current limiting inductance, M.S. thesis, ITN, Linkpings Universitet, 1999.
there will always be a slight difference between two of the most [9] W. Leterme et al., A new HVDC grid test system for
critical faults remote internal and external fault. This slight HVDC grid dynamics and protection studies in
difference will always make it possible to design a protection EMTP, in 11th Int. Conf. AC DC Power Transm.,
algorithm to differentiate between the two. However, for Birmingham, 2015.
application in practice, there will always be deviations from the [10] A. Semlyen and A. Dabuleanu, Fast and accurate
model used in the study, e.g. noise, unforeseen contingencies, switching transient calculations on transmission lines
uncertainty in parameters etc. It is therefore important to with ground return using recursive convolutions,
consider the margins of a protection before application in IEEE Trans. Power Appar. Syst., vol. 94, no. 2, pp.
practice since it will indicate how robust a protection principle 561571, Mar., 1975.

You might also like