You are on page 1of 2

July, 2007 HAP System Design Load v4.

34 Page 1 of 2
Patch Update
Release Sheet
HAP System Design Load v4.34 replaces v4.31

UPDATE DESCRIPTION
HAP System Design Load v4.34 includes the following change:
Publishing Equipment Sizing Requirements for use in E-CAT. Carrier is enhancing features for sharing data
between engineering programs like HAP and its Electronic Catalog (E-CAT) software. Part of this work involves
improvements to how sizing data generated by HAP is shared with E-CAT. In v4.34 there is a new "Publish
Equipment Sizing Requirements" option on the Project Menu and on the toolbar. When you've finished your
HVAC system design and are ready to select equipment, use this "Publish" option to make data available in
E-CAT. Once you "Publish" the requirements, the data appears automatically in E-CAT and can be used for
selections. Or, after "Publishing", a customer can use the "Send E-mail" option to automatically archive the
project and e-mail it to a sales engineer for assistance with selections. The "Publish" feature replaces the
traditional method of printing out sizing requirements and then manually entering them into equipment selection
software. To take full advantage of these features, HAP System Design Load v4.34, X Builder Framework
v1.02m, WSHP Builder v4.15 and Packaged RTU Builder v1.09L need to be installed on your computer. For
more information on how to use the new integration features, see the link on the top of the E20-II or E-CAT
downloads page.
In addition, the following problems in v4.31 were corrected in v4.34:
Minimum Zone Airflow Calculations with User-Defined Sizing. If you selected the "User-Defined" sizing
option in air system inputs for a VAV system, minimum zone airflows sometimes differed from results for the
same air system using the "Computer-Generated" sizing option. With "computer generated" sizing, the software
sets the minimum zone airflow for a VAV terminal using the minimum zone airflow specified in inputs or the
zone ventilation airflow requirement, whichever is larger. With "user-defined" sizing, the system ventilation
airflow rate is directly defined by the user and a zone-by-zone ventilation calculation is not performed so zone
ventilation airflow cannot dictate the minimum setting for the VAV terminal. As a result, minimum zone airflow
for VAV terminals could sometimes be smaller using the "user-defined" sizing option than with "computer-
generated" sizing. HAP has been revised so minimum zone airflow calculation for VAV terminals will be the
same for both "user-defined" and "computer-generated" scenarios - considering both the user specified minimum
airflow and the zone ventilation requirement.
Error 91 While Importing gbXML. While importing data from a gbXML file, the program halted due to the
error message "Error 91 Object variable or With block variable not set in GenerateFloorData.". This only
happened in specific situations related to the content of the gbXML file.
Error 13 While Importing gbXML. While importing data from a gbXML file, program halted due to the error
message "Error 13 Type Mismatch in GenerateDoorAssemblyData.". This only happened in specification
situations related to the content of the gbXML file.
Further details on program additions and problem corrections are provided in section 1.2 (Whats New in HAP?) in
the programs on-line help system.

Carrier Software Systems


Syracuse, NY, USA
1-800-253-1794
software.systems@carrier.utc.com
July, 2007 HAP System Design Load v4.34 Page 2 of 2
Patch Update
Release Sheet

INSTALLATION PROCEDURES
The HAP System Design Load v4.34 patch install can only be run on a computer which already contains HAP System
Design Load v4.30 or v4.31.
Use the following procedure to install the HAP System Design Load v4.34 patch update:
Download the e20p-sdl434.exe file from the internet site and save it in a folder on your hard disk.
Run Windows Explorer and double-click on the e20p-sdl434.exe file. This launches the patch installer.
Follow the instructions which appear on your screen. For the destination drive, you must choose the drive used
when you originally installed HAP System Design Load v4.30 or v4.31.
Note 1: HAP System Design Load v4.34 requires X-Builder Framework v1.20n (or later). This software
can be downloaded from the Carrier web site.
Note 2: For network installations, repeate the previous steps from each workstation running HAP System
Design Load. This is necessary to install software components in the Windows folder on C: drive of each
workstation.
Use the following procedure to run HAP System Design Load v4.34:
From the Windows Desktop, press the Start button and choose the Programs option.
Choose the Carrier E-CAT and E20-II Programs group on the Programs Menu and then double click on the
HAP System Design Load v4.34 item in this group.
Minimum computer requirements:
Hard Disk Space: Minimal additional space required.
Random Access Memory (RAM): At least 64 megabytes.
Display Monitor: VGA with at least 800 x 600 and 256 colors.
Operating Systems: Windows 98, 2000, XP, NT (service pack 4 or later).
X-Builder Framework v1.02n or later.

PREVIOUS VERSION INFORMATION


1. Data created with HAP System Design Load v4.30 and v4.31 is compatible with v4.34. No data conversion is
necessary.
2. Data from HAP v3.2, and from HAP System Design Load v4.0 thru v4.2 projects can be converted for use in
v4.34 using options on the Project Menu. Please refer to section 1.5 in the on-line help system for details

PROGRAM DOCUMENTATION
The HAP Quick Reference Guide has not been changed. The current edition has a publication date of 9/2003.
The programs on-line help system provides complete documentation for the program. This includes a copy of the
Quick Reference Guide material plus detailed discussions of program inputs, reports and calculation procedures.

Carrier Software Systems


Syracuse, NY, USA
1-800-253-1794
software.systems@carrier.utc.com