Professional Documents
Culture Documents
ATA 24-00
Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
Drain Plug ......................................................................................16
TABLE OF CONTENT Overfill Bleed Plug ..........................................................................16
24-00 Electrical Power General.............................................................3
Charge Pressure Port.....................................................................16
Introduction ..........................................................................................3
Integrated Drive Generator ................................................................18
AC Generators. ....................................................................................5
(No. 1 and No. 4 Engines) Data .........................................................18
Auxiliary Power Unit Generator. ...........................................................5
BAe146 APU Generator.....................................................................20
External AC Ground Supply. ................................................................7
Introduction ........................................................................................20
Essential and Emergency AC Supplies ................................................9
BAe146 APU Generator Oil Monitoring ..............................................22
Standby Generator...............................................................................9
BAe146 Maintenance Panel...............................................................24
Static Inverter.......................................................................................9
RJ series APU Generator. .................................................................26
DC Power ..........................................................................................11
Introduction ........................................................................................26
Aircraft Batteries ................................................................................13
Generator Control Units (GCU's) ........................................................28
External DC Ground Supply ...............................................................15
introduction ........................................................................................28
Indicators and controls .......................................................................17
Generator Control Units .....................................................................30
24-21 Engine Driven Generators .........................................................2
GCU Operation ..................................................................................32
Introduction ..........................................................................................2
Examples of Generator Control Unit ..................................................34
IDG Operation......................................................................................4
BITE tests. .........................................................................................34
Constant Speed Drive Unit (CSD) ........................................................6
GCU BUILT-IN-TEST EQUIPMENT (BITE) ....................................34
CSD Operation ....................................................................................6
24-23 Essential AC Generation (Standby Generator)..........................3
CSD Operation Continued ...................................................................8
Introduction ..........................................................................................3
IDG Components ...............................................................................10
Standby Generator Operation ..............................................................5
Oil Filter ..........................................................................................10
Emergency AC Generation ..................................................................7
Chip detector ..................................................................................10
Static Inverter Operation ......................................................................9
Sight Glasses .................................................................................10
Standby Inverter ................................................................................11
Automatic Disconnection ................................................................10
Data ...............................................................................................11
Scavenge Filter ..............................................................................10
26 Volt AC Supplies ...........................................................................13
Temperature Control Valve ............................................................10
Transformer Operation.......................................................................15
Oil Coolers .........................................................................................12
Test Supplies .....................................................................................17
Oil Temperature Switch .....................................................................12
Galley Power Supplies. ......................................................................19
Drive Hi temp. ....................................................................................14
General ..............................................................................................19
GEN OFF LINE ..................................................................................14
Description.........................................................................................19
IDG Oil System. .................................................................................16
Ground operation ...............................................................................19
Oil-in-Oil-out Ports ..........................................................................16
Flight operation ..................................................................................19
Pressure Fill Adapter and Cap........................................................16
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
24-40 External AC Power. .....................................................................3
Introduction ..........................................................................................3
External AC Power Operation ..............................................................5
External Power Monitor Unit .............................................................5
24- 51 AC Power Distribution...............................................................3
Introduction. .........................................................................................3
AC. System Control .............................................................................5
Three Phase Contactors ......................................................................7
AC Busbar Supply and Transfer System ..............................................9
Connecting to Busbars. ......................................................................11
DC power distribution ...........................................................................3
Description and Operation ...................................................................3
Transformer Rectifier Unit TRU ............................................................5
TRU Operation.....................................................................................7
TRU Operation continued: ...................................................................9
Normal 28 Volt DC Output (+Bus) ......................................................11
Cold Start, 26 Volt DC Output.........................................................11
Protection Circuitry .........................................................................11
Battery Supplies .................................................................................13
Nickel Cadmium Battery .................................................................13
Battery No Charge Monitor (MOD00757B) .........................................15
MOD HCM01048 C and D ..............................................................15
Battery Control ...............................................................................15
DC Power Indication and Busbar Warnings .......................................17
DC Power Indication and Busbar Warnings .......................................19
External DC Ground Supply ...............................................................21
ATA 24-00
Page 2 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
24-00 ELECTRICAL POWER
GENERAL
INTRODUCTION
The Electrical Power system is comprised of AC and DC power sources.
The AC system consists of:
Two engine-driven Integrated Drive AC Generators (IDGs)
One Auxiliary Power Unit driven AC-Generator (APU GEN)
One Standby Generator and
One AC external power input
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: ELECTRICAL SYSTEM
ATA 24-00
Page 4 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
AC GENERATORS.
The primary AC power is obtained from the output of three engine driven
generators, fitted on No. 1 and No. 4 engines, and a third generator on
the Auxiliary Power Unit (APU).
The AC power system normally operates as a two-generator system. No.
1 engine generator supplying AC BUS l, No. 4 generator supplies AC
BUS 2 with automatic transfer of busbar supply in the event of generator
failure. If both generators fail, the third generator on the APU can be
used to energise the AC busbar system.
On the ground or in flight, the APU is used to supply air for air
conditioning, and it`s AC generator can supply the AC and DC busbars.
The generator output can be used for main engine start, and it is
essential to minimise busbar loads (50 amps) for engine start or when
using bleed air for air conditioning, especially in `hot-and-high' airfields.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: ENGINE AND APU GENERATORS
ATA 24-00
Page 6 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 3: EXTERNAL AC GROUND SUPPLY.
ATA 24-00
Page 8 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
STANDBY GENERATOR
During normal operating conditions the ESS AC BUS and EMERG AC
BUS are supplied from AC BUS 1, which is powered from engine driven
generator No. 1. If all the engine driven generators fail, the ESS AC BUS
and EMERG AC BUS can be energised from the output of the
hydraulically driven STANDBY GENERATOR which can supply an output
of 5 kVA.
STATIC INVERTER
Control switches for STBY Generator and Inverter are located together
on the pilot's overhead panel ELECIRIC selection. The switches have
three positions and are labelled ARM-OFF-OVRIDE, therefore, provided
that the standby and emergency power systems are ARM, transfer of
power supplies during abnormal conditions is achieved automatically.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 4: STANDBY GENERATOR AND STATIC INVERTER.
ATA 24-00
Page 10 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
DC POWER
An Ext D.C. supply can be use to start engines and or the APU but
cannot be connected to the D.C. busbar system.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 5: TRANSFORMER RECTIFIER UNITS.
ATA 24-00
Page 12 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
AIRCRAFT BATTERIES
The aircraft batteries are fitted in the front equipment bay and will
maintain the emergency AC and DC services for approximately 30
minutes per battery. Battery stowage is provided with venting of battery
gasses to atmosphere, where NI-CAD batteries are fitted.
In the extreme condition, when all generated power fails, the main aircraft
24 volt battery will maintain power to the EMERG DC BUS services. This
busbar will supply power to operate a standby static inverter and its
single phase. 250 VA output at 400 Hz will automatically supply the
EMERG AC BUS service.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 6: AIRCRAFT BATTERIES
.
ATA 24-00
Page 14 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
EXT DC can be used to start the aircraft main engines and also the APU
if required.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 7: EXTERNAL DC GROUND SUPPLY.
ATA 24-00
Page 16 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 8: ELECTRICAL INDICATIONS
APU GEN
BAe146 only FAIL
ATA 24-00
Page 18 Electrical General
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: INTEGARTED DRIVE GENERATOR
ATA 24-21
Page 2 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
IDG OPERATION
Each generator consists of a permanent magnet generator (PMG), an
exciter generator and a main generator combined in one assembly. The
electrical power developed in the PMG supplies the excitation current for
the exciter generator.
The PMG stator output is rectified and regulated by a generator control
unit (GCU) and applied to the exciter stator. The exciter armature
develops 3 phase AC power that is rectified by a rotating diode bridge
circuit, and the resultant DC supply is applied to the rotor of the main
generator.
Output power is developed in the start wound stator of the main
generator.
The main generator phase windings and the star point (neutral) are
brought out to terminal studs to facilitate connection to the external
circuit. The neutral stud is externally connected to earth. The PMG and
exciter generator stator windings are brought out to a multi-pole
connector.
The generator also accommodates a 3-phase current transformer that
forms part of a current protection network for the load lines between the
generator and the associated 3-phase contactor (A1 A2 or E1). The
current transformer winding terminations are brought out to the multi-pole
connector.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: GENERATOR SCHEMATIC
ATA 24-21
Page 4 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 3: CONSTANT SPEED DRIVE UNIT (CSD)
ATA 24-21
Page 6 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
If the input speed is less than 6000 r.p.m., speed must be added to the The governor is a spring-biased, flyweight operated control valve which
input to maintain a constant output speed of 12 000 r.p.m. To achieve hydraulically controls the position of the control cylinder piston. The
this, oil is ported from the governor to the control cylinder and the rotating sleeve in the governor, driven by the output gear, is responsive
pressure acting against the control cylinder piston changes the angular to output speed variations, and the flyweights pivoted on this sleeve
position of the variable wobbler via the control arm. Oil, pressurized by move a valve stem, located within the sleeve, against the bias of a
the variable unit pistons moving into the cylinder block as a result of the spring. During steady state operation, supply pressure is reduced to the
repositioned variable wobbler, is ported to the fixed unit pistons. The required control pressure by orificial action at the edges of the stem
fixed unit is rotated in a direction opposite to that of the variable unit and control land. Depending on valve stem position, charge oil is ported to
the fixed unit ring gear being in mesh with the fixed unit, will rotate in a the control piston or control oil is drained to the transmission case.
direction opposite to that of the carrier shaft, thereby adding to the output
speed.
When the input speed is above 6000 r.p.m., speed must be subtracted
from the input to maintain a constant output speed of 12 000 r.p.m. To
achieve this, the oil ported from the governor is reduced, and a spring
within the control cylinder repositions the control cylinder piston.
This movement positions the variable wobbler via the control arm so that
its face is parallel with the face of the fixed wobbler plate. This parallel
positioning causes oil to be pressurized in the variable unit and ported to
the fixed unit pistons located on the side of the fixed wobbler that will
result in the fixed unit rotating in the same direction as the variable unit.
The fixed unit ring gear will then rotate in the same direction as the
variable unit, thereby reducing the output speed.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 4: CONSTANT SPEED DRIVE COMPONENTS.
ATA 24-21
Page 8 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
IDG COMPONENTS
OIL FILTER SCAVENGE FILTER
Fitted in the CSD charging circuit and will filter out contamination that Located at the IDG oil out line and is used to filter the oil before it enters
may be in the oil entering the CSD from the external oil cooling system. If the temperature control valve and oil coolers. If the filter element
the filter element becomes contaminated a pressure differential indicator becomes contaminated the pressure differential indicator button will
will operate a spring-loaded magnetic plunger to release a red indicator operate.
button. The filter assembly also includes a bypass valve.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 5: IDG COMPONENTS.
ATA 24-21
Page 10 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
OIL COOLERS
The oil coolers are mounted on the engine gas generator cooling
assembly and uses fan duct air to effect cooling of the oil. This surface
type oil cooler assembly consists of two oil cooler panels connected in
series; each cooler consists of a core assembly with oil inlet and outlet
ports and manifolds.
The core assembly consists of a contoured plate with fins on the outside
of the contour and finned oil passage on the opposite side. The oil inlet
port is bracket mounted on the inlet pan at one end of the cooler and the
outlet port is similarly mounted at the other end of the cooler.
The coolers are coupled to each other and to the external system by
connectors which utilise O-rings to provide the necessary sealing.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 6: OIL COOLER CIRCUIT.
.
ATA 24-21
Page 12 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
DRIVE HI TEMP.
Drive Hi temp will illuminate when the oil temperature reaches 157C.
If the temperature continues to increase because of lack of action there is
an automatic disconnect of the IDG/Engine gearbox drive at 179C.
(The connection between the IDG and the Gearbox is held together by a
spring loaded Dog clutch. When the solder melts the teeth pull back and
the IDG is disconnected).
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 7: GENERATOR INDICATIONS.
ATA 24-21
Page 14 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
DRAIN PLUG
The oil drain plug is a self-closing valve, which accommodates a
magnetic chip detector plug and O-ring. When the chip detector is
installed the valve is open, but closes on removal of chip detector thereby
preventing oil spillage.
The oil is drained by opening the valve with a flexible drain line
(TEDECO-D-7670 A) or by removing the valve.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 8: IDG OIL PORTS
ATA 24-21
Page 16 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
Disconnect (Overheat)
Oil Temp 179 degrees C (354 degrees F)
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 9: IDG OIL FLOW
ATA 24-21
Page 18 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
The APU incorporates the same type of generator as the main engines. Should both engine driver generators fail in flight, the APU generator will
automatically power Channel 1 to ensure ESS AC and EMERG AC
The APU is fitted in the rear fuselage, to provide independence from busbars remain energised, irrespective of AC bustle switch positions.
ground power sources, and also can be operated during airborne In flight with the APU shutdown, the APU can only be started from the
conditions. DC output of TRU No. 1. The APU generator may only be used up to
On the ground or in flight, the APU is used to supply air for air 25,000 ft on limited power output.
conditioning, and the AC generator can supply the AC and DC busbars.
The generator output can be used for main engine start, and it is The lubricating oil is cooled by a fan, assisted oil cooler; the fan is driven
essential to minimise busbar loads (50 amps) for engine start or when from the APU and is augmented by blast air in flight.
using bleed air for air conditioning, especially in `hot-and-high' airfields. On the ground the A.C. bustie switch must be in the AUTO position
for the APU generator to supply both AC 1 and AC 2 busbars.
Power for APU starter motor is supplied from main aircraft battery supply, If the switch is in the OPEN position the generator will only supply
No. 1 TRU or external DC ground supply. Controls and indications are channel one that is AC bus two and the ground service bus.
provided on the pilots overhead panel.
During take-off and landing the APU will be operating, providing bleed air
for air conditioning, and its AC generator is available to supply the AC
and DC busbar systems, should a single or double engine failure occur.
On the ground the APU generator can provide power to both CHANNEL
1 and CHANNEL 2, but can only power one channel in flight, priority is
given to Channel 1.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 10: APU GENERATOR.
ATA 24-21
Page 20 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
The APU generator oil is monitored for low pressure and high
temperature (this is separate from the APU oil system). If either is
detected an APU DRIVE FAIL (A) indication is given on the overhead
electrical panel, accompanied by the amber APU light on the CWP.
On the maintenance panel located above the electrical bay entry door
two dolls eye indicators APU GEN OIL HI TEMP and APU EMERG
SHUT DOWN, will turn white if the APU generator oil temperature is high.
If the oil pressure is low, the roof panel indications are the same but only
the APU EMERG SHUT DOWN, dolls eye indicator will turn white
If the aircraft is on the ground, after 20 2 seconds, the APU shuts
down.
In flight the APU will continue running and the pilot will follow his
procedures.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 11: BAE146 OIL TEMP AND PRESSURE SENSORS
ATA 24-21
Page 22 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
APU EMERGENCY SHUT DOWN and APU HIGH TEMP, both energize
if the temp is high but only the APU EMERGENCY SHUT DOWN will
energize if it is due to an oil low pressure.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 12: BAE146 MAINTENANCE PANEL
ATA 24-21
Page 24 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
RJ SERIES APU GENERATOR.
INTRODUCTION
The APU incorporates the same type of generator as the main engines. Should both engine driver generators fail in flight, the APU generator will
automatically power Channel 1 to ensure ESS AC and EMERG AC
The APU is fitted in the rear fuselage, to provide independence from busbars remain energised, irrespective of AC bustle switch positions.
ground power sources, and also can be operated during airborne In flight with the APU shutdown, the APU can only be started from the
conditions. DC output of TRU No. 1. The APU generator may only be used up to
On the ground or in flight, the APU is used to supply air for air 25,000 ft on limited power output.
conditioning, and the AC generator can supply the AC and DC busbars.
The generator output can be used for main engine start, and it is The lubricating oil is cooled by a fan, assisted oil cooler; the fan is driven
essential to minimise busbar loads (50 amps) for engine start or when from the APU and is augmented by blast air in flight.
using bleed air for air conditioning, especially in `hot-and-high' airfields.
Power for APU starter motor is supplied from main aircraft battery supply,
No. 1 TRU or external DC ground supply. Controls and indications are
provided on the pilots overhead panel.
During take-off and landing the APU will be operating, providing bleed air
for air conditioning, and its AC generator is available to supply the AC
and DC busbar systems, should a single or double engine failure occur.
On the ground the APU generator can provide power to both CHANNEL
1 and CHANNEL 2, but can only power one channel in flight, priority is
given to Channel 1.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 13: APU GENERATOR.
ATA 24-21
Page 26 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
Each generator is protected and its voltage is regulated by a generator All transient faults, except for under-frequency, require the generator to
control unit (GCU). If the generators are switched ON their output is be RESET. After an over-current/out of balance current fault the
controlled in conjunction with the automatic power transfer system. automatic power transfer system can be reset on the ground.
System protection is provided for:
The APU generator will only come on line if the APU generator is
- over-voltage operating satisfactorily at governed speed.
- under-voltage
- over-frequency If engine 1 or 4 fire handle is pulled out to its full extent the respective
- under-frequency generator is isolated.
- negative phase sequence
- feeder and busbar earth fault.
- overcurrent/out of balance current
If a GCU senses a fault it will disconnect its generator from the busbar
system. For all faults, except under-frequency, the generator is also de-
energized and in the case of busbar overcurrent the automatic transfer of
the other generator (APU or ENG) is inhibited.
Overcurrent >160A <194A inhibits the bus tie contactor after a time
delay. >194A also de-energizes the generator after a time delay.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 14: GENERATOR CONTROL UNIT.
ATA 24-21
Page 28 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
The GCU protection circuits are only active during fault conditions; it is
therefore necessary to test these circuits periodically in order to ascertain
their continued serviceability.
The GCU incorporates built in test equipment (BITE) for this purpose.
The BITE consists of a two level, 12 way rotary selector switch, which is
used in conjunction with a push button TEST switch to inject +15V or
earth signals into each protection circuit in turn.
If the selected protection circuit is serviceable, the test signal should
cause the generator to trip the OFF LINE warning light of the associated
generator to illuminate.
There are two fuses mounted in holders which can be accessed from the
front of the unit, with fuse 2 having a RED fail LED indicator.
The power supply for the GCUs is derived from the permanent magnetic
generator inside the main generator.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 15: GENERATOR CONTROL UNIT
ATA 24-21
Page 30 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
GCU OPERATION
The internal circuitry of the GCU's is powered by the PMG of the The BFR effects overriding control over transfer contactors B 1, B2, D 1
associated generator and is therefore inherently independent from the and D2, bustie contactors C1, C2, and E1, E2 contactors.
rest of the aircraft system. The PMG output is distributed to two power The BFR is a latching relay with a trip coil and a reset coil.
supply circuits within the GCU. One circuit provides 15V and 30V DC
power supplies, which drive the GCU control, regulation and protection The trip coil is operated by the protection circuitry and causes the
circuits. The other power circuit provides DC excitation power for the contacts to open the reset coil is operated by a BUS RESET switch and
exciter generator. causes the contacts to close. The BUS RESET switch is installed in the
GCU and is therefore not accessible in flight. Consequently, if the BFR
The GCU exercises control over its associated generator and 3 phase trips as a result of an in-flight bus fault, the GCU cannot be reset until the
contactors by six integral relays designated `Generator Control Relay' aircraft lands. This prevents transfer of major busbar faults, an event that
(GCR), Power Ready Relay (PRR), Bus Fault Relay (BFR), Transfer would result in total loss of primary AC power
Relay (T'R), Lock Out Relay (LOR) and Under Frequency Relay (UFR).
The coils of these relays are energised from the PMG derived power The TR is controlled by the generator control switch, to connect or
supply and controlled by the GCU protection circuitry. disconnect the generator to the AC busbar system.
The GCR effects on/off control of the exciter generator-stator and the The LOR enables the GCR to operate during fault conditions, and isolate
PRR; the GCR therefore serves as an automatic generator control switch a faulty generator from the busbar system and remain isolated until fault
and is complementary to the manual generator control switch on the roof is isolated or rectified.
panel.
The PRR provides inhibit control over generator protection circuits during The UFR not only provides fault protection but also effects automatic on-
engine start, and effect control over line contactors A1, A2, and transfer line and off-line switching of the generator during the engine spool-up
circuit contactors B 1, B2, and in the case of the APU GCU, contactors and shut-down by control of PRR.
E1 and E2.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 16: GENERATOR CONTROL UNIT SCHEMATIC
ATA 24-21
Page 32 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
DIFFERENTIAL CURRENT On generator control unit, set rotary selector switch to OC. Press and
hold TEST switch.
On generator control unit, set rotary selector switch to DP. Press and - On panel 211-50-03:- After approximately 4 seconds, AC voltmeter
release TEST switch. reads low voltage.
- On panel 211-50-03:- AC voltmeter reads low voltage. Associated AC BUS OFF annunciator on.
GEN OFF LINE annunciator on. Release TEST switch.
On generator control unit, press and release BUS RESET switch.
On panel 211-50-03, set GEN switch to OFF/RESET and back to ON. - On panel 211-50-03:- - AC voltmeter reads low voltage.
- On panel 211-50-03 :- AC voltmeter reads within the green sector. GEN OFF LINE annunciator on.
Frequency meter reads 400Hz 12. Associated AC BUS OFF annunciator off.
OVER VOLT On panel 211-50-03, set GEN switch to OFF/RESET and back to ON.
- On panel 211-50-03:-
On generator control unit, set rotary selector switch to OV. Press and AC voltmeter reads within green sector.
release TEST switch. Frequency meter reads 400Hz 12.
- On panel 211-50-03:- AC voltmeter reads low voltage. GEN OFF LINE annunciator off.
GEN OFF LINE annunciator on. Associated AC BUS OFF annunciator off.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 17: GENERATOR CONTROL UNIT TESTS
ATA 24-21
Page 34 Generators
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: STANDBY GENERATOR
ATA 24-23
Page 2 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
When all engine-driven generators fail, AC BUS 1 OFF and AC BUS 2 If an engine driven generator is reinstated AC BUS 1 and AC BUS 2 are
OFF annunciators light and MWS operate. The AC bus fail relays would energised. The AC bus 1 and AC bus 2 relays would operate, and de-
be de-energised and through their relaxed contacts a supply from energise the standby generator control relay.
EMERG DC BUS is connected to the standby generator switch. The relay contacts would relax and connect a supply from EMERG DC
If the switch is set in its ARM position the standby generator relay is BUS to energise the selector solenoid valve to close, which would cut off
energised. the hydraulic fluid pressure and shutdown standby generator.
At the same time the green hydraulic system isolation valve will be
The selector valve is de-energised open and allows the GREEN actuated to the OPEN position and restore hydraulic pressure to the
hydraulic system pressure to operate the standby generator hydraulic green services.
motor. At the same time the green system isolation valve will be actuated AC BUS 1 would now supply power to the essential and emergency
to the close position and cut off fluid pressure to all other green services, busbars and air conditioning would revert to recirculation mode.
thereby avoiding a pressure drop that could cause standby generator
output to fail.
The air conditioning would operate in the fresh air mode to provide the
cooling. The hydraulic motor will not rotate the generator and the GCU
regulator will build up its output.
When its output is controlled at the correct value the GCU contactor
control circuit will operate in conjunction with the STBY GEN switch in the
ARM or OVRIDE position. An output signal will light the white STBY GEN
ON annunciator and energise the AC and DC supply contactors. The
STBY GEN/AC BUS 1 contactors will change over and connect the ESS
AC BUS to the standby generator output.
NOTE: To bypass the AC Bus 1 and AC Bus 2 fail relays, the standby
generator can be operated by setting the STBY GEN switch to its
OVRIDE position.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: GENERATOR SCHEMATIC
ATA 24-23
Page 4 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
EMERGENCY AC GENERATION
A standby static inverter rated at 250VA is fitted in the front equipment
bay, and can operate automatically in the event of failure of essential
busbar supplies to the EMERG AC BUS. This will maintain electrical
supplies to those services, which are necessary to complete the flight in
safety.
A three-position switch provides control of the standby inverter. It is
labelled STBY INV, ARM-OFF-OVRIDE. Indication is provided by an
amber EMERG AC OFF annunciator, and its output can be monitored on
the AC voltmeter and frequency meter. The control switch and indications
are located on the pilots overhead ELECTRIC panel.
The inverter input is supplied from EMERG DC BUS via a remote control
circuit breaker, and supported from the main aircraft battery. The inverter
will convert the DC input to provide a single phase 115/26 volt AC supply
at a constant frequency of 400Hz.
The inverter case is finned and embodies vent holes to promote cooling
by natural convection, and mounted on the front end plate is a single
connector with a polarising key, which provides both input and output
connections to the inverter. When using AC power during engine start the
ESS AC BUS provides power to the ESS AC START BUS for engine
instrumentation. If AC power is not available, and DC ground supply is
being used for engine start, the standby inverter will be in operation. The
inverter output which normally supplies the EMERG AC BUS will also
supply the ESS AC START BUS via the operated contacts of an engine
start control relay and the relaxed contacts of the essential AC bus fail
relay.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 3: STANDBY STATIC INVERTER.
ATA 24-23
Page 6 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 4: EMERGENCY AC GENERATION SCHEMATIC.
ATA 24-23
Page 8 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
STANDBY INVERTER
DATA
Efficiency 79%
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 5: ELECTRICAL DIAGRAM.
ATA 24-23
Page 10 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
26 VOLT AC SUPPLIES
Two 250VA transformers, coded XM3 and XM4 are located on the left
side of the front equipment bay, and convert 115 VAC to provide 26 VAC
supplies for instrumentation.
Transformer XM4 input is fed from A phase of ESS AC BUS, and the
transformer output supplies the 26VAC EMERG BUS and the 26VAC
ESS BUS.
The 26VAC EMERG BUS can also be supplied from the 26VAC output of
the standby inverter, which would automatically come into operation if the
ESS AC BUS- supplies fail.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 6: 26VAC SUPPLIES.
.
ATA 24-23
Page 12 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
TRANSFORMER OPERATION
Transformer XM4 26 VAC output derived from ESS AC BUS supplies the
26V EMERG BUS via the contacts of the energised inverter relay. The
transformer output also supplies the YELLOW and GREEN HYD PRESS
INDS and the 26V ESS AC BUS.
The 26VAC ESS BUS supplies are muted via an avionic master
switching relay (RB6) in its de-energised fail-safe state. If the ESS AC
BUS supplies fail, the inverter relay (XE5) is de-energised, and the
standby inverter will automatically come into operation and maintain 26V
AC to the 26V AC EMERG BUS services.
NOTE:
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 7: 26VAC SUPPLIES.
ATA 24-23
Page 14 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
TEST SUPPLIES
To facilitate the use of test equipment on the aircraft, 28v and 115v AC
test sockets are provided, on the flight deck and left hand console panel
and in the electrical equipment bay, on the outboard edge of No 2 AC
panel.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 8: TEST EQUIPMENT SUPPLIES
ATA 24-23
Page 16 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
GROUND OPERATION
With AC1 and AC2 busbars powered using an external AC or APU power
supply, and the GALLEY/SHED switch, on panel 211-50-03, set to
GALLEY, all galleys will be supplied. During engine start, the start control
relays are energized and inhibit the earth paths for the RCCB's. The
RCCB's relax and power to the galleys is inhibited. After the start is
completed and the START MASTER switch is selected OFF, the start
control relays relax and power is restored to the galleys.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 9: GALLEY LOAD SHED SCHEMATIC
ATA 24-23
Page 18 Emerg. and Essential Power
BAe146 AVRO 146RJ Maintenance Training Manual
If the AC bustie switch on the roof panel is selected to AUTO the Ext AC
power when connected to the aircraft will supply all the aircraft electrical
power.
If the switch is selected to OPEN only the AC 2 and ground service
busbar will be supplied from the Ext AC power.
Revision: September 2012 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: EXTERNAL A.C. POWER CONTROL
ATA 24-40
Page 2 External A.C.
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: September 2012 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: EXT A.C. THEORETICAL DIAGRAM
ATA 24-40
Page 4 External A.C.
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: A.C. POWER DISTRIBUTION
ATA 24-51
Page 2 A.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
The AC power system operates as a two-generator system, No. 1 The generator outputs are fed to their control unit (GCU) which contains
generator supplying AC BUS 1 and No. 4 generator supplying AC BUS 2. the voltage, current and frequency sensing circuits necessary to effect
Power for essential (ESS AC BUS) and emergency (EMERG AC BUS) regulation, control and protection of the generator and busbar supply.
AC busbar services are normally supplied from AC BUS 1. Within each GCU the outputs derived from the sensing circuits, and relay
switching, will control the automatic transfer circuit and associated
However, each generator has sufficient capacity to supply the total generator line contact (GLC) in conjunction with the associated generator
busbar system, since each generator can supply 110 AMP continuously, control switch.
140 AMP for 2 hrs. / 165 AMP 5 minutes or 220 AMPS for 5 seconds.
Each generator switch has three positions labeled OFF/RESET - OFF
Normally both generators operate as two separate isolated channels, but LINE - ON. If the generator switch is selected to its ON position, the
in the event of generator failure a pre-selected automatic transfer circuit system is automatically controlled by the GCU transfer circuitry and
will ensure that all busbar are supplied from a single power source. engine start system.
If a single generator fails or both No. 1 and No. 4 generators fail, the APU
generator can be used to energise the busbar system on the ground, in
flight the APU will only power 1 channel.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: A.C. SCHEMATIC DIAGRAM
ATA 24-51
Page 4 A.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 3: THREE PHASE CONTACTORS
ATA 24-51
Page 6 A.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
The AC busbars AC BUS 1, AC BUS 2, ESS AC BUS and EMERG AS To simplify functional description, the contacts are given alpha codes:
BUS are normally fed from the generators as follows:
A 1 or A2 Generator line 1 contactor or 2
No. 1 generatorAC BUS l, ESS AC BUS and EMERG AC BUS
No. 4 generatorAC BUS 2, and GROUND SERVICE BUS B 1 or B2 Bus transfer contactor 1 or 2
On the ground, an external AC supply or APU generator can be used to C 1 or C2 Bustie contactors 1 or 2
energise all the busbars, and during flight conditions the APU generator
can also be used to energise a channel with a failed generator. D1 or D2 Auxiliary Supply Contactors 1 or 2
If all engine-driven generators fail, a standby generator will supply the E1 Auxiliary generator line contactor
ESS AC BUS and EMERG AC BUS. If all generators fail, a standby
inverter will maintain power to the FMERG AC BUS. E2 External power contactor
Transfer of power sources for the normal busbars AC BUS 1 and AC
BUS 2 is achieved through five 3-phase contactors in conjunction with
generator control units and BUSTIE AC AUTO-OPEN switch.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 4: A.C. BUSBAR TRANSFER
ATA 24-51
Page 8 A.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
CONNECTING TO BUSBARS.
Transfer of the main power sources is achieved through the five 3 phase
contactors.
It is very important in this system that two power sources cannot power
the same bus.
Each twin contactor assembly includes a mechanical interlock, to ensure
that both contactors cannot close simultaneously.
Below shows the automatic power transfer priorities for the powering of
busbars:
1) Gen 1 1) Gen4
2) APU Gen 2) APU Gen
3) Ext AC 3) Ext AC
4) Gen 4 4) Gen 1.
1) Gen 1 1) Gen4
2) Ext AC 2) Ext AC
3) APU Gen 3) APU Gen
4) Gen 4 4) Gen 1.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 5: OPERATION
ATA 24-51
Page 10 A.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
In the unlikely event of failure, of all generated power, the main aircraft
battery or batteries will maintain electrical power to the EMERG DC BUS
services.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 1: D.C. POWER DISTRIBUTION
ATA 24-30
Page 2 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 2: TRU LOCATION
ATA 24-30
Page 4 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
TRU OPERATION
When the AC busbars are energised provided the TR 1 and TR2 circuit DC busbar system, TRU No. 1 feeds DC BUS 1 and TRU No. 2 feeds
breakers (0.5 amp) on the pilot's overhead panel are in the reset position, DC BUS 2.
the remote controlled circuit breaker (RCCB) will operate to close and
connect AC BUS 1 and AC BUS 2 to their respective TRU's. With battery No. 1 fitted and connected, power is available direct to APU
start, and to the primary BATT 1 BUS services. The BATT 1 Bus supply
Each TRU input is connected to its main transformer input star winding, is connected to BATTRY 1 master switch via a battery inhibit relay.
via a current transformer protection circuit and a tap change contactor.
The transformer output winding in star and delta will step down the AC When the BATTERY 1 switch is selected on, the battery contactor is
voltage to supply a full wave rectifier bridge, which converts the reduced energised, its main contacts close to connect the BATT 1 BUS supply to
AC voltage to supply a 28 volt DC output at 150 amps continuously. the EMERG DC BUS, its auxiliary contacts complete the battery no
charge detector supply direct from No. 1 battery.
The TRU output is supplied direct from the rectifier bridge for engine
start, or to the DC busbar via a 325 amp fuse and ammeter shunt circuit. With DC BUS 1 energised, DC 1 auto cut-out will close and connect DC
BUS 1 supply to energise EMERG DC BUS.
However, during cold engine start the tap change contactor is energised Since DC BUS 1 supply is likely to be above the battery supply, the main
which changes the ratio of primary transformer windings to secondary aircraft battery will receive a recharge from EMERG DC BUS, indicated
windings, which provide a greater DC output at 36 volts for engine cold on the battery ammeter. When the DC selector switch is set to BATT 1
start. If during engine start, the TRU input supplies fail or TRU overheats; position, battery terminal voltage will also be indicated.
the protection circuit relay will de-energise, to trip the RCCB and
disconnect the TRU AC input, and also terminate engine start by The auxiliary contacts of the operated DC 1 auto cut-out connect a
interrupting the operating signal to the engine start selected containers. supply signal from DC BUS 1 to the EMERG/ESS auto cut-out with the
DC bustle switch at open, the EMERG/ESS auto cut-out closes to link
The normal TRU 28 VDC output is connected to the TRU auto cut-out, EMERG DC BUS to ESS DC BUS.
and when its voltage/current relay coil senses 23 volts, supplied from the
TRU output via CB3, cold start relay and the switched contacts of the Now that ESS DC BUS is energised, a second (No. 2 channel) supply
voltage/current relay, to energise and close the main contactor. The TRU signal to energise the EMERG/ESS auto cut-out is completed, via the
output is now connected to the relaxed contacts of the standby generator DC contactor.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 3: TRU SCHEMATIC
ATA 24-30
Page 6 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 4: TRU SCHEMATIC
ATA 24-30
Page 8 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
The protection circuit board monitors the TRU input by using a current Operating Temperature Range - 40 to +60C
transformer. The power rectifiers are mounted on heat-sinks, which
sense temperature by a thermal switch. Power supplies for the protection Weight 41 lbs.
circuit board are obtained from the main transformer three phase output,
which is rectified on the protection circuit board.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 5: D.C. PANEL LOCATION
ATA 24-30
Page 10 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
BATTERY SUPPLIES
A 24 volt, 25 AH Lead Acid Battery or batteries (MOD HCM40028A) are Temperature sensing is provided by two integral thermostats, colour
located in the front equipment bay, and during extreme emergency coded black and red. A hot condition will operate the black thermostat at
conditions will maintain electrical power to the EMERG DC BUS services. 57C, and an overheat condition will operate the red thermostat at 71C.
NOTE: Nickel-Cadmium type battery (MOD HCM40024A) or batteries Electrical power connection is provided by an Elcon quick release
(MOD HCM400248) can be fitted to suit customer requirements. connector, also on the front face is a connector for the temperature
sensing thermostats.
The 24V 25 AH battery consists of two 12V sealed mono-blocs enclosed
Ventilation piping is fitted to the main aircraft battery where NICAD
in a polyester bonded fibreglass container. Each mono-bloc incorporates
batteries are fitted and extends from the battery vent bottle located in the
a resealing safety valve and has two tin-plated brass terminals. Each
nose gear bay. Battery venting is effectively accomplished when the
multiple strip connectors join the mono-blocs to each other and to the
aircraft is pressurised.
main battery connector.
The sealed battery works on gas recombination principle, the lack of free
The battery is mounted in a pressurised section of the aircraft, and the
electrolyte means the battery required no external venting and is
gases are piped from the outlet to a battery vent bottle located in the
maintenance free with respect to topping-up.
nose wheel bay. A non-return valve is fitted at the battery inlet, thus
Electrical connection to supply battery power to the aircraft system is
preventing gases entering the aircraft when charging is carried out on the
provided by an Elcon quick release connector.
ground when the pressure differential is negligible.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 6: BATTERY SCHEMATIC
ATA 24-30
Page 12 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 7: BATTERY CONTROL AND NO CHARGE
ATA 24-30
Page 14 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
An ELECTRIC system control and monitoring panel is located on the left Also on the ELECTRIC panel is the annunciator amber warning lights for
side of the pilot's overhead panel. This panel includes system control the DC busbars, DC BUS 1 OFF, DC BUS 2 OFF, ESS DC BUS OFF
switches, meters and indicators for control and monitoring of the and EMERG DC OFF.
electrical power system.
The Annunciators are supplied from the Warning Light Busbar via the
DC power indication is provided by a voltmeter, an ammeter for each associated busbar fail relay, which is energised from the respective
TRU and the main aircraft battery or batteries. busbar via a Zener diode.
The voltmeter and ammeters are switched across the output lines for the The contacts of the fail relays also control system functions for engine
battery or batteries. DC ground supply, standby generator and TRU's via cold start, APU start and emergency lights, EMERG LTS ON indication.
a rotary switch which is panel annotated with the various power source The Warning Light Busbar supply is derived from two power sources,
positions. EMERG DC BUS or DC BUS 2. The busbars, relays, diodes, fuses and
The voltmeter and ammeters are integrally illuminated and controlled by circuit breakers are all located in the front equipment bay on No. 1 and
the overhead panel INSTS DIM switch. No. 2 DC panels.
The battery ammeter circuit utilises a battery shunt, and each sensing
line is fuse protected. The battery shunt and fuses are located on the
right side of the front equipment bay on No. 1 DC panel.
Each TRU incorporates its own ammeter shunt and circuit breaker
protection, indented CB 1 and CB 2, and is directly connected to its
ammeter, but its output voltage is switched by the DC voltage selector
switch. The DC ground supply contactor and indicating circuit protection
fuse are located on the right side of the front cargo compartment.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 8: D.C. INDICATION
ATA 24-30
Page 16 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
The Annunciators are supplied from the Warning Light Busbar via the
associated busbar fail relay, which is energised from the respective
busbar via a Zener diode.
The contacts of the fail relays also control system functions for engine
cold start, APU start and emergency lights, EMERG LTS ON indication.
The Warning Light Busbar supply is derived from two power sources,
EMERG DC BUS or DC BUS 2. The busbars, relays, diodes, fuses and
circuit breakers are all located in the front equipment bay on No. 1 and
No. 2 DC panels.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 9: D.C. INDICATION
ATA 24-30
Page 18 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
EXT DC can be used to start the aircraft main engines and also the APU
if required.
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 10: EXTERNAL DC CONNECTION
ATA 24-30
Page 20 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
FIGURE 11: M.E.L. EXAMPLE
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited
FIGURE 12: M.E.L. EXAMPLE
ATA 24-30
Page 22 D.C. Power Distribution
BAe146 AVRO 146RJ Maintenance Training Manual
Revision: Nov. 2013 Swiss Aviation Training Ltd. FOR TRAINING ONLY
Issue: 01 Reproduction prohibited