You are on page 1of 7

1

Impact of Distributed Generation on Distance


Protection Performance - A Review
Viraj Pradeep Mahadanaarachchi, Student Member, IEEE, and Rama Ramakumar, Life Fellow, IEEE

The presence of DG provides an additional contribution to


Abstract-Early power systems were comprised of centrally the fault current, which is determined by factors such as size
dispatched conventional power generation facilities, delivering and type of DG, location of DG, interconnection transformer
power to customers via transmission and distribution networks. configuration, DG earthing arrangement etc, [2-4]. This
With the changes in utility structures, development in
additional fault current contribution could adversely affect the
technologies, increased attention on environmental concerns,
increase in electricity demand coupled with attractive advantages performance of line protection, primarily on existing distance
offered by small to medium generation sources have led to protection schemes. Distance protection is based on the
increasing use of Distributed Generation (DG). However, high measured current and voltage at the point of interest and
penetration of DG will have an adverse impact on the power distance relay operation and /or accuracy could be affected by
system operation & protection. In this paper an extended review factors such as changes in the power flow, current transformer
is done to identify the impact of fault current contribution from
saturation, capacitive coupled voltage transformer (CVT)
DG on the line protection performance. The disturbing factors
for proper operation of distance protection and further the transients, power swings etc,.
impact of fault currents on those disturbing factors are identified. In this paper, after a brief discussion of different types of
DG, the impact of DG on short circuit capacity is considered.
Index Terms - Capacitive coupled voltage transformer The impact of short circuit capacity on performance of line
transients, current transformer saturation, distributed distance protection is reviewed by considering the factors
generation, distance protection, fault currents, load flow. which disturb the distance protection performance.
I. INTRODUCTION
II. DISTRIBUTED GENERATION

T RADITIONALLY electric power systems have been


designed with large centrally dispatched generation
sources connected to high voltage networks, which deliver
Various efforts have been made to establish an universal
definition for Distributed Generation (DG) and still there are
some ambiguities among IEEE, work groups of CIGRE,
power through a distribution system. Power system protection International Energy Agency, etc,. However, small to medium
was based on unidirectional power flow from upper stream to size generators connected to the power system at distribution
down stream and the sole source of fault current contribution level or sub transmission level close to loads are called
is from upper stream bulk generation [1]. With the Distributed Generation, Embedded Generation (preferred
introduction of Distributed Generation (DG) in distribution term in UK), Dispersed Generation (preferred term in USA )
and sub transmission levels these assumptions will no longer or Decentralised Generation [5]. DG includes mostly
be valid since DG will result in bidirectional power flows and electrical energy provided by alternate sources of energy,
act as an additional source of fault currents [2]. beyond the conventional sources such as hydro electric, coal,
High penetration of DG will have an impact on short circuit oil, gas and nuclear [6]. DG can be in the form of wind
capacity, protection coordination, system transient stability, turbines, photovoltaic cells, micro turbines, fuel cells, other
voltage control and power quality, which can significantly types such as small gas turbines, diesel engines and gas fired
influence the proper operation and protection performance of internal combustion engines. Their ratings could vary from a
the power system [2-3]. In this paper, impact of DG on short few kW to a few MW.
circuit capacity and load flow behavior are taken into A. Wind Turbines
consideration as main disturbing factors for effective
Grid connected wind turbines (WT) as an effective DG
protection operation. source has developed dramatically in the recent past. WT can
be operated at nearly constant or variable speed and coupled
This work was supported by the Oklahoma State University Engineering to induction generators to produce power. Induction
Energy Laboratory and by the US-Egypt joint project on Extended Investigation generators are widely used in WT, and variable speed
of Wind Farm Protection Systems funded by the USDA. technology is preferred in almost all newer installations [7]. A
V. P. Mahadanaarachchi and R. Ramakumar are with the Department of squirrel cage induction generator could be connected to the
Electrical and Computer Engineering, Oklahoma State University, Stillwater,
OK 74078 USA (e-mail: pradeep.mahadanaarachchi@okstate.edu;
power system through a power electronic interface as shown
rama.ramakumar@okstate.edu). in the Figure 1 with full power conversion.

2008 IEEE.
2

converted to electrical energy. The dc power produced by the


fuel cell is converted into ac using a dc/ac inverter.
D. Micro turbines
Gas fired micro-turbines in the range of 25kW to 1MW can
be used to generate electricity. They are designed to combine
the reliability of on board commercial aircraft generators with
the low cost of automotive turbochargers. These micro-
Figure 1 Variable speed induction generator [7]
turbines run at high speeds (50,000-90,000 rpm) with air foil
Alternatively wound rotor induction machine can be used bearings. The ac generator is a high frequency generator that
as a doubly fed induction generator (DFIG), where the stator cannot be directly connected to the power system, and hence a
is directly connected to the system and the rotor is connected power electronic interface is used [8]. Generated voltage is
through a power electronic interface as shown in Figure 2. rectified first using a diode rectifier and dc/ac voltage source
type inverter is employed to obtain utility-grade ac for
injection into the grid as shown in Figure 4.

Figure 4 - Micro-turbine electrical system [7]

III. FAULT CURRENTS


Figure 2-Doubly fed induction generator [7]
There are several factors which determine the level of fault
This method is the preferred in new wind farms since it current contribution from DG.
requires a much smaller power electronic system and since it A. Number and size of DG
allows to support the power system in the event of a system
In a DG facility there can be a few or higher number of
disturbance.
generators. If there are more parallel connected generators,
B. Photovoltaic Systems they will present a lesser source impedance to the power
The photovoltaic (PV) module or array is an unregulated dc system and more fault current contribution in case of a fault in
power source, which has to be treated and conditioned before power system side or at DG collector system.
being connected to the power system. A dc/dc converter Further, depending on the size of generators, generator
(chopper) is used at the PV array output for maximum power transient/ subtransient impedance and their short circuit ratios
tracking (MPPT) as shown in Figure 3. i.e. for extracting (SCR), fault current contribution will be impacted.
maximum available power at a given insolation level, which
means maintaining the voltage as close as possible to the B. Types of DG
maximum power point [8]. Different types of generators are used in various DG
sources. In wind turbines induction generators (Doubly fed
Induction generators) are preferred and in small hydro
installations synchronous generators (Salient pole) are
preferred. In photovoltaic systems and in fuel cells power
electronic interface is used. Depending on the type of
generator/interface fault current contribution will vary.

a. Synchronous Generators
A Synchronous generator when subject to a three phase
fault at its terminals will contribute fault current as shown in
Figure 5. This will encompass a subtransient period, transient
period and a steady state period [9]. Since subtransient period
Figure 3-Grid connection of PV system [8]
(time constant) is comparatively small, transient period
(thereby transient reactance) will determine the fault current
C. Fuel Cells
contribution.
A fuel cell is an electrochemical energy conversion device,
where chemical energy in the fuel is directly and isothermally
3

as well as fault currents, which should be controlled. Fault


current contribution of inverter based DG is lesser when
compared with a similar synchronous generator. However
large amount of inverter based DG can have an impact on
transient fault currents.
C. Transformer Configuration
The selection of the interconnection transformer
configuration has a major impact on how the DG will interact
with the connected power system [12]. Figure 7 shows five
commonly used transformer connections. Here the High
Voltage (HV) terminal is the utility side and the Low Voltage
(LV) terminal is the DG side.

Figure 5 Synchronous generator short circuit current characteristics [9]


(ST-Sub-transient period, T-Transient period, S-Steady state period)

b. Induction Generators
Behavior of an induction generator under fault condition is
different from a synchronous generator since induction
generators do not have field windings to develop the required
electro-magnetic field in the machines air gap. A three phase
fault on the generator terminals will interrupt the reactive
power import, which is required to maintain the excitation of
the induction generator [10]. As shown in Figure 6, fault
Figure 7-Interconnection Transformer Connections [12]
current diminishes rapidly as the stored magnetic energy in
the machine decays. As a result the fault current contribution In first three connections, Delta(HV)/Delta (LV),
is limited to subtransient period. Delta(HV)/Grounded Wye (LV) and Ungrounded Wye (HV)
/Delta (LV), there is no connection to the ground in HV side
and thereby no source of earth fault current to interact with
utility side relaying. A ground fault at LV side of the
transformer will not be detected by utility side. With this
ungrounded connection, phase faults will have two sources of
fault currents. In last two connections, Grounded Wye
(HV)/Delta (LV) and Grounded Wye (HV)/ Grounded Wye
(LV), will have a source of earth fault current in HV side,
which increase the earth fault current level at utility side [12-
13]. Large number of DG facilities with several
interconnection transformers can make an impact to the phase
and ground fault contribution and there by maloperate the
existing protective devices.
D. Generator Earthing Arrangement
Figure 6 fault current of induction generator when a three phase fault applied For DGs connected to the power system through a step up
to its terminals (phase shown with minimum offset) [10] transformer, the stator winding of the generator and the
associate transformer winding (if not earthed) will form an
c. Power Electronic Interfaces isolated system that is not affected by the power system
Almost every DG (except small hydro based DG, diesel earthing system. This floating system can lead to overvoltage
engines etc.) will be interfaced to the power system through a conditions. In larger DGs neural of the generator is earthed
dc/ac inverter, normally a self commutated Pulse Width through a single phase distribution transformer with a
Modulated (PWM) inverter. This interface allows the DG resistive load on the secondary [14]. If the generator is not
scheme to configure and control functions such as reactive earthed, (as in some small DGs) DG side interconnection
power control, power system stabilization and power system transformer winding should be earthed. DGs directly
damping as can be implemented in ac synchronous generators connected to the power system with no step-up transformer,
through the excitation system [11]. are normally earthed through a resistance.
DC injection to the power system through the inverters can Depending on the earthing method (solidly, resistive or
create high frequency harmonic components in load currents inductive) used in DG facilities, fault loop impedance for
4

internal and through (external) faults could change. significantly alters the load flow and its direction. Further
Source to line impedance ratio (SIR, ZS/ZL) can be a critical
IV. DISTANCE PROTECTION PERFORMANCE parameter in appraising the protective relay behaviour when
Distance relays are used for primary and/or backup load flow is considered [17]. Since DG will have a clear
protection for phase faults and/or ground faults on impact on system SIR, and thereby distance protection
transmission, sub-transmission and distribution lines. Distance performance.
based schemes are also a very economical and simple B. Capacitive Coupled Voltage Transformer Transients
approach to protecting these lines. Distance relays operate by Capacitive coupled Voltage Transformers (CVT) provides
measuring the phase relationship between an operating an effective way of obtaining secondary voltages for HV and
quantity and a polarizing quantity [15]. Line drop EHV systems. However they create some problems for
compensated voltage is the operating quantity, which consists distance relay operation. During line faults, when the primary
of measured voltage, measured current and reach setting. voltage collapses, the energy stored in the stack capacitors
Polarizing quantity should remain unchanged and unaffected (C1 & C2) and the tuning reactor (L) of a CVT (as shown in
during a fault. Polarizing quantities for mho elements can be figure 8) needs to be dissipated.
positive sequence voltage, healthy or unfaulted phase voltage,
quadrature voltage (shifted leading 900) etc.
Distance protection should quickly detect and clear faults,
dependable when required to detect and isolate a fault/faulty
section, secure for external/out-of-zone faults and selective in
tripping decisions [16]. Voltage and Current inputs to distance
relays are taken from instrument transformers and it is very
important to select instrument transformers with proper
ratings and tolerable errors.
Distance protection performance could be affected from (i)
various dynamic system conditions such as changes in load
flow, stable and unstable power swings, mutual coupling of
transmission lines, sub-synchronous resonance, and (ii) Figure 8 Capacitive Voltage Transformer Circuit [18]
instrument transformer conditions such as current transformer
saturation, capacitive coupled voltage transformer transients. As a result CVT generates severe transients (with
These disturbing factors are further worsened by large significant magnitudes and for long duration) that affect the
deployment of distributed generation in distribution and sub- performance of protective relays. Due to these transients it
transmission lines. Increased in fault currents and changes in will be difficult to differentiate faults at the reach point and
load flow are the main adverse contribution from DG to affect faults within the protection zone [18]. This will be prominent
above factors and thereby the effective and efficient operation in systems with high Source Impedance ratios (SIR).
of distance protection. Static and microprocessor based relays are highly prone to
A. Load Flow these CVT transients, since they are designed for high speed
operation. Electromechanical relays can tolerate the
An ideal distance relay sees apparent impedance equal to unfavorable CVT transients due to their natural mechanical
the positive sequence impedance from the relay location to inertia, but with slower operation.
the fault location. The perfect behavior is affected by changes CVT transients can have a direct impact on (i) the transient
in load flow coupled with fault arc resistance/ground fault overreach (a relay operates during faults located out of its set
impedance. This will alter the measured impedance from reach) due to the under estimation of voltage, (ii) the speed of
actual positive sequence impedance, which can result in operation (slow tripping for in-zone faults under high SIRs)
overreach for line-end faults and incorrect directional action and (iii) directionality [19].
for close-in reverse faults [17]. More over, load flow causes a Distance relays calculate a lesser value than actual apparent
shift of the distance relay characteristics as plotted on an R-X impedance to the fault, due to the CVT transients, since CVT
diagram. transients will reduce the fundamental component of the fault
The type of relay characteristic and the polarizing quantity voltage. This can cause overreach of Zone 1 distance relay
used will determines the level of distance relay over reaching elements [20].
problem. When looking high resistance phase to ground faults A system with a higher SIR results in worse CVT transients
directly in front of the relay, first zone relay characteristics and hence DG will have direct contribution to CVT transients
which have large first quadrant coverage in the R-X diagram since increased penetration of DG will have an impact on the
should be selected to reduce relay maloperation. SIR of the connected system. Moreover, the shape of the CVT
In most protection application and setting calculations load transient is influenced by the fault initiation angle. CVT
flow is assumed as zero or not taken in to consideration in a transients will be worse for a fault at a voltage zero crossing.
detailed manner. But load flow can have an adverse impact on Parallel operation of large amount of DG with the power
real-time protective relay performance. This impact is further system will have an impact on fault initiation angle.
weighted with incorporation of DG, since large amount of DG
5

Relay manufacturers have used several methods to experience a minor tripping delay and a possible underreach
overcome CVT problem, which includes narrow band pass for faults near to the relay reach point and a limited impact on
filtering of the voltage (which effectively adds delay through longer set Zone 2 and Zone 3 distance elements.
filtering), reducing distance relay reach, and delaying the In early distance protection schemes, it was unlikely that a
distance relay tripping decision. These solutions have their distance relay would be subjected to CT saturation for remote
own disadvantages [21]. faults or faults near the Zone 1 reach point. CT saturation
With the increase in fault current contribution and change would occur for faults close to the relay terminals and this
in power flow introduced by DG will worsen the CVT will have a limited impact on distance relay operation [22].
transients and hence will have a direct impact on distance But with the power system growth and changes in complexity
protection performance. Further this impact is increased, since CT saturation has become a probable event. Moreover, with
relay settings are made based on system studies, which may high penetration of DG will change the system transient fault
not have considered the contribution from increased behavior and can create greater probability of CT saturation.
deployment of DG in to the system over the time.
D. Power Swings
C. Current Transformer Saturation Power swings are variations in power flow that occur when
Secondary current from Current transformers (CT) are the the internal voltages of generators at different locations of the
current input to the protective relays. Protective relay power system slip relative to each other. While mechanical
accuracy and performance are directly related to the steady power input to generators remains almost unchanged, sudden
state and transient performance of the CTs [21]. The changes in electric power in an interconnected power system
performance of CTs and its errors during short circuit can happened due to power system faults, line switching,
conditions are very important with regard to protective generator disconnection, loss or application of large blocks of
devices in power networks. load. These system disturbances can cause oscillations in
CT output is affected drastically when the CT operates in machine rotor angles which can lead to severe power flow
the non-linear region of its excitation characteristics. swings. Depending on the nature and degree of the
Operation in this region is initiated by (i) large asymmetrical disturbance, and the power system control actions, for a stable
primary fault currents with a decaying dc component, (ii) power swing, the system may remain stable and return to a
Residual magnetism left in the core from an earlier new equilibrium state. Severe disturbances will lead to
asymmetrical fault, or field testing if the CT has not been unstable power swings, which can lead to large separation of
demagnetized properly, (iii) large connected burden combined generator rotor angle and thereby loss of synchronism which
with high magnitudes of primary fault currents [21-22]. is known as out of step (OOS) conditions [24].
CT saturation causes severe waveform distortions in the Power swings can cause the load impedance to enter in to
secondary currents supplied to the protective relays. In the relays operating characteristic, which under steady state
extreme cases secondary current can be zero. Protective conditions is not with in the relays operating characteristic.
relays are designed to operate before the time period of the This will be similar to a load encroachment problem in
transient disturbance during a system fault. However large CT distance relaying. Relay operation during power swings may
transient errors may delay or prevent relay operation [21-22]. cause undesirable tripping of lines or the other power system
A current waveform associated with CT saturation is shown in elements. Therefore, for transient power swings, distance
figure 9. relay elements should be temporary prohibited from
operating.
In modern relays, a power swing block (PSB) function is
available to prevent distance relay element maloperation
during power swings and differentiate power swings from
faults. And an out of step trip (OST) function to isolate
faulted sections, and maintain stability and continuity.
Faults developed during a power swing should be detected
and cleared with a high priority. In protective relays Rate of
change of the positive sequence impedances is used in PSB
and OST functions to differentiate a stable power swing from
a fault. During a power swing, this rate is slower since it takes
certain time for rotor angle to advance due to the system
inertia. On the other hand the rate is very fast during a system
Figure 9 Waveforms of saturated CT [23]
(E-induced emf, -flux in the core) fault.
Depending on the DG size and voltage level they are
Saturation of the CT also causes a phase shift between the connected to the system, the location of the swing centre will
unsaturated waveform and the saturated waveform, which can be determined (location of the swing center is given in [24
result in distance element under reach or overreach [22]. sec. 5.2]). Normally the swing center is located in the step up
According to the work done in [21], CT saturation will have transformer or in the Generator in the case of a small DG.
an impact on distance relay Zone 1 elements, which will When large number of DG is connected to the system the
6

swing center may move out onto the distribution feeder. Then Moreover, the specific impact on different types of distance
feeder protective relays should be equipped with power swing relay characteristics such as mho, quadrilateral and, for
protection and feeder breaker with OOS switching capability numerical and electromechanical relays using appropriate
[24]. There is a significant impact on power swings from high relay models will be analyzed and verified.
penetration DG and thereby on existing distance relaying.
VI. CONCLUDING REMARKS
E. Subsynchronous Resonance
Subsynchronous Resonance (SSR) is an electrical power Grid connected Distributed Generation has experienced a
system condition where the electrical network exchanges rapid growth in the recent past and is expected to have an
energy with a turbine generator at one or more of the natural exponential expansion in the future. Though DG has
frequencies of the combined system below the synchronous significant economic and environmental benefits, increased
frequency of the system [25]. SSR can be steady state (self penetration of DG will impose significant technical barriers
excitation) or transient (transient torques). For self-excitation for the efficient and effective operation of the bulk power
can be involved with rotor electrical dynamics (Induction system. Increased fault current contribution and load flow
generator effect) or with rotor electrical and mechanical changes are two of the major impacts on the utility system,
dynamics (torsional interaction). Transient torques can be due and these will affect the existing protective relaying,
to the system disturbances resulting from switching in the especially overcurrent and distance protection. In this paper
network which can excite oscillatory torques on the generator distance protection performance is studied by identifying the
rotor [25-26]. salient factors which will maloperate or disturb the proper
Previously the effect of SSR has been identified in series distance relay operation. Further, work carried out by various
compensated long transmission lines with large synchronous researchers has been reviewed to assess the impact of DG on
generators. Also SSR may occur in small private power distance relay disturbance factors.
systems with faulty induction machines [26]. With large Finally, planned future strategies are highlighted to evaluate
number of induction generators connected to the power and verify the DG impact on distance protection by modeling
system, SSR can be a significant issue, which can impact the and simulation.
transient fault current behavior.
VII. ACKNOWLEDGMENT
The authors gratefully acknowledge the contributions of
F. Other Possible Factors
J. B. Ekanayake for his valuable comments from his
Mutual coupling of transmission line will have a major experience in distributed generation field.
impact on the zero sequence impedance on a double circuit
transmission line. This impact is considered in distance relays VIII. REFERENCES
and accordingly compensated when commissioning, based on
[1] M. Begovic, A. Pregelj, A. Rohatgi and D. Novosel, "Impact of renewable
system conditions. When DG is added to the system and when distributed generation on power systems, " in proc. of the 34th Hawaii
the penetration levels grew high, there can be a change in International Conference on System Sciences, 2001.
mutual coupling and thereby an impact on distance relaying. [2] WS5 P01 Steering group, "The contribution to distribution network fault
However this is a less probable scenario when compared with levels from the connection of distributed generation," KEMA consulting
report for the department of trade and industrys new & renewable Energy
other disturbing factors. programme, May 2005.
Ferroresonance is also another probable factor which is [3] N. Nimpitiwan, G.T. Heydt, "Consequences of Fault Current Contributed
normally initiated after some type of switching event such as by Distributed Generation," Power System Engineering Research Center
load rejection, fault clearing, transformer energization, single Publication No. 06-21, Jun.2006.
[4] N. Nimpitiwan, G.T. Heydt, "Fault current issues for market driven power
phase switching or loss of system grounding [27]. Further systems with distributed generation," Power System Engineering Research
ferroresonance can occur due to DG going in to islanding Center, Pub. No.04-08, Apr. 2004.
mode with a captive load [28]. Impact of ferroresonance on [5] G. Pepermans, J. Driesen, D. Haeseldonckx, R. Belmans and W.
distance relay performance is not specifically discussed in Dhaeseleer, "Distributed generation: definition, benefits and issues,"
Energy Policy ,vol. 33, iss. 6, Apr. 2005, pp. 787-798.
literature. [6] P. Dondi, D. Bayoumi, C. Haederli, D. Julian and M. Suter ," Network
integration of distributed power generation," in Journal of Power Sources,
V. FUTURE STRATEGIES vol. 106, iss. 1-2, 1 Apr. 2002, pp 1-9.
[7] G. Joos, B. T. Ooi, D. McGillis, F. D. Galiana and R. Marceau "The
The impact of DG will be modeled and simulated in a potential of distributed generation to provide ancillary services," in Proc.
power system modeling software, PSCAD/EMTDC using a 2000 IEEE Power Engineering Society Summer Meeting.
standard power system model (eg. IEEE 14 bus [8] CIGRE Technical brochure on "Modeling new forms of generation and
storage," TF 38.01.10, Nov. 2000.
configuration). Initially the increase in fault current
[9] C. H. W. Lackey, Fault Calculations, Oliver & Boyd Ltd, 1951, pp 123-
contribution and load flow changes are verified through 133.
incorporating DG in different buses. To assess the impact [10] T. Burton, D. Sharpe, N. Jenkins E. Bossanyyi, Wind Energy Hand Book,
from different types of DG, DG models for wind, solar, fuel John Wiley, 2001, pp 590-592.
cells etc, will be employed. This modeling exercise will be [11] L. Gertmar, P. Karlsson, O. Samuelsson,"On dc injection to ac grids from
distributed generation," ISBN: 90-75815-08-5, 2005.
extended to evaluate the impact of distance relay operation by
considering the disturbance factors mentioned in this paper.
7

[12] Working group D3,"Impact of distributed resources on distribution relay Indian Institute of Technology, Kharagpur, India, and
protection," Line protection subcommittee of the Power System Relay the PhD degree from Cornell University, Ithaca, NY,
Committee of the IEEE Power Engineering Society, Aug. 2004. all in Electrical Engineering.
[13] W. Hartmann, "Interconnection transformer winding arrangement After a decade (total) of service on the
implications for distributed generation protection," Blackwith Electric Co., faculty of the Coimbatore Institute of Technology,
Inc. Coimbatore, India, he joined Oklahoma State
[14] N. Jenkins, R. Allan, P. Crossley, D. Kirschen and G. Strbac, Embedded University, Stillwater, in 1967, where he has been a
Generation, IEE, 2000. Professor since 1976.In addition, he has been the
[15] E. O. Schweitzer III and J. B. Roberts, "Distance relay element design, Director of the OSU Engineering Energy Laboratory
presented at the 46th Annual Conf. for Protective Relay Engineers, College since 1987. In 1991, he was named the PSO/Albrecht
Station, TX, Apr. 1993. Naeter Professor of Electrical and Computer Engineering. His research interests
[16] J. M. Gers and E. J. Holmes, Protection of Electricity Distribution are in the area of energy conversion, energy storage, power engineering, and
Networks, IEE, 1998. renewable energy. He has been a consultant to several national and
[17] G. E. Alexander, J.G. Andrichak, W. Z. Tyska and S. B. Wilkinson, supranational organizations in the field of energy and has organized and
"Effect of load flow on relay performance," presented at the 39th Annual presented short courses on renewable energy topics and engineering reliability.
Conf. for Protective Relay Engineers, College Station, TX, Apr. 1986. His contributions are documented in over 150 publications, which include four
[18] D. Hou and J. Roberts, "Capacitive Voltage Transformers: Transient U.S. patents, contributed chapters in four books and seven hand books, and
Overreach concerns and solutions for distance relaying," presented at the technical papers in various journals, transaction, and national and international
Canadian Conf. on Electrical and Computer Engineering, 1996. conference proceedings. He is the author of the text book Engineering
[19] B. Kasztenny, "Distance relays and capacitive voltage transformers- Reliability Fundamentals and Applications (Englewood Cliffs, NY, Prentice-
problems and solutions," General Electric Company. Hall, 1993).
[20] B. Kasztenny, D. Sharples, V. Asaro and M. Pozzuoli, "Distance relays Dr. Ramakumars past and present leadership activities in the IEEE
and capacitive voltage transformers-balancing speed and transient Power Engineering Society include chairing the Awards Committee of the
overreach," GE pub. GER-3986.Apr. 2000. Technical Council, the award Subcommittee of the Power Engineering Education
[21] D. Tziouvaras, "The effect of conventional instrument transformer Committee, the Energy Development Subcommittee of the Energy Development
transients on numerical relay elements," Schweitzer Engineering and Power Generation Committee, the Working Group on Renewable
Laboratories, tech. paper no. 6119, 2001. Technologies, and the Fellows Working Group of the Power Engineering
[22] J. Mooney, "Distance element performance under conditions of CT Education Committee. He is a member of the American and International Solar
saturation," SEL Schweitzer Engineering Laboratories, tech. paper no. Energy Societies, the American Society for Engineering Education, and the
6299, 2007. IEEE Industry Applications Society. He is a Registered Professional Engineer in
[23] A. R. Van C. Warrington, Protective Relays, Their theory and practice, the State of Oklahoma.
vol. 1, John Wiley, 1962.
[24] Working group D6, "Power swing and out of step considerations on
transmission lines," Power System Relaying Committee of the IEEE Power
Engineering Society, Jul.2005.
[25] P. Kundur, Power System Stability and Control, McGraw-Hill, 1994.
[26] F. Joswig and S. Kulig, "Subsynchronous resonance in turbine generators
caused by faulty induction machines," University of Dortmund, Germany,
[online] Available : www-mal.e-technik.uni-
dortmund.de/paper/upload/paper_31.pdf
[27] D.A.N. Jacobson, "Examples of ferroresonance in a high voltage power
system," Presented in Power Engineering Society General meeting, Jul.
2003.
[28] V. P. Mahadanaarachchi, R. Ramakumar, "Challenges and issues of wind
farm protection," in Proc. of the 40th Annual Frontiers of Power Conf.,
Stillwater, OK, Oct. 2007, pp XI-1-7.

IX. BIOGRAPHIES
Viraj Pradeep Mahadanaarachchi (S07) was born in Sri Lanka on
September 10, 1978. He received the B.Sc. degree in Electrical Engineering
from the University of Moratuwa, Sri Lanka in 2004.
His working experience is on Manufacturing and
Designing of high voltage protection and control
panel boards at Cruickshank Ceylon, Sri Lanka, and
on Protection Testing and Condition Monitoring of
power plants at Generation Asset Management
Branch, Ceylon Electricity Board, Sri Lanka, as an
Electrical Engineer. Presently he is working on
protection aspects of wind farms, as a Graduate
Research Assistant at Oklahoma State University,
Stillwater.
His research interests are Power System
Protection & Stability, Condition Monitoring of high voltage equipments, Grid
integration and impact of Distributed Generation.

Dr. Rama Ramakumar (M62, SM75, F94, LF02) received the B.E. degree
from the university of madras, Madras, India, the M.Tech. degree from the

You might also like