You are on page 1of 32

Cahier technique no 214

Energy efficiency:
benefits of variable
speed control
in pumps, fans and compressors

J. Schonek
Cahiers Techniques is a collection of documents intended for engineers
and technicians, people in the industry who are looking for more in-depth
information in order to complement that given in product catalogues.
Furthermore, these Cahiers Techniques are often considered as helpful
tools for training courses.
They provide knowledge on new technical and technological developments
in the electrotechnical field and electronics. They also provide better
understanding of various phenomena observed in electrical installations,
systems and equipments.
Each Cahier Technique provides an in-depth study of a precise subject in
the fields of electrical networks, protection devices, monitoring and control
and industrial automation systems.
The latest publications can be downloaded from the Schneider Electric
internet web site :
http://www.technical-publications.schneider-electric.com
Please contact your Schneider Electric representative if you want either a
Cahier Technique or the list of available titles.

The Cahiers Techniques collection is part of the Schneider Electrics


Collection technique.

Foreword
The author disclaims all responsibility subsequent to incorrect use of
information or diagrams reproduced in this document, and cannot be held
responsible for any errors or oversights, or for the consequences of using
information and diagrams contained in this document.

Reproduction of all or part of a Cahier Technique is authorised with the


prior consent of the Scientific and Technical Division. The statement
Extracted from Schneider Electric Cahier Technique no. ..... (please
specify) is compulsory.
no 214
Energy efficiency:
benefits of variable
speed control
in pumps, fans and compressors

Jacques Schonek

A graduate of the ENSEEIHT engineering school with a doctorate in


engineering from the University of Toulouse, J. Schonek took part in
the development of Telemecanique variable-speed drives from 1980 to
1995.
He was subsequently in charge of studies in the field of Harmonic
Filtering and then Electrical Distribution architectures.
He is presently in charge of developing solutions for the Water
segment of Schneider Electric.

CT 214 EDITION - mai 2008


Glossary

Energy efficiency: Useful power:


Optimum use of electrical energy, including The power transferred to a fluid drawing a certain
reduced consumption and cost and improved quantity of energy per unit time. Also referred to
availability. as the output power.
Variable speed drive (VSD): Mechanical power:
A device used to control the speed of a machine. The mechanical power transferred to a machine
Frequency converter: (pump, fan, compressor) such that it can deliver
A device used to adjust the frequency of the a certain useful power to the fluid. Also referred
power supplied to a motor and thus control its to as the shaft power.
speed. Electrical power:
Soft starter: Power drawn by the electric motor driving the
A device used to limit the inrush current when a machine. Also referred to as the input power.
motor is started and to control its acceleration. Head loss:
Pump: Additional power that must be transferred to the
A device used to raise or move a fluid. fluid to overcome the various forces that oppose
the flow.
Centrifugal pump:
A pump in which the liquid is put into motion by a Booster:
circular movement. A device used to maintain a certain pressure in a
fluid circuit, whatever the required flow rate.
Fan:
A device used to displace air. Water hammer:
A sudden variation of the pressure in a circuit
Compressor:
following an excessively fast drop in the flow rate
A device used to increase the pressure of a
due to the closing of a valve or the stopping of a
volume of gas.
pump.
Flow rate:
Cavitation:
The quantity of a fluid conveyed per unit time.
A phenomenon involving the formation and
Head: sudden collapse of vapour bubbles in a pump
The pressure at a given point in a circuit, following a drop in the inlet pressure of the liquid.
expressed as the height of a column of liquid.

Cahier Technique Schneider Electric n 214 / p. 2


Energy efficiency:
benefits of variable speed control in
pumps, fans and compressors

A large proportion of the electricity produced around the world is used to


raise, move or pressurise liquids and gases with machines such as pumps,
fans and compressors.

Given the increasing importance of controlling energy consumption, special


attention must be paid to the way these machines are operated and the
energy savings that can be achieved through variable speed control.

These different aspects will be dealt with in this Cahier Technique


publication, both from the qualitative and quantitative standpoint. Variable
speed drives are among the front-ranking solutions proposed by Schneider
Electric to increase Energy efficiency.

Sommaire
1. Introduction p. 4
2. Centrifugal pumps p. 5
2.1 General aspects p. 5
2.2 Fundamental characteristics p. 6
2.3 Operating point p. 8
2.4 Varying the flow rate at a fixed speed p. 9
2.5 Variable speed operation p. 12
3. Fans p. 20
3.1 General aspects p. 20
3.2 Fixed-speed operation p. 21
3.3 Variable-speed operation p. 23
4. Compressors p. 27
4.1 General aspects p. 27
4.2 Variable-pressure operation p. 28
4.3 Variable-speed operation p. 28
5. Conclusion p. 29
Appendix 1: Bibliography p. 29

Cahier Technique Schneider Electric n 214 / p. 3


1. Introduction

Electrical energy consumed by pumps, fans and Valves, taps and gates are the most commonly
compressors represents a signicant proportion used devices.
of the electricity used around the world. It is However substantial energy savings can be
estimated that in industrial processes and obtained by using variable speed drives to
building utilities, 72 % of electricity is consumed control the ow rate or pressure in pumps, fans
by motors, of which 63 % is used to drive uid and compressors as opposed to the above
ow in pumps, fans and compressors. physical or mechanical means. In pumping
Numerous industrial sectors have pumping, applications, the most signicant savings are
ventilation and compression needs. For achieved with centrifugal pumps.
example: The aim of this document is to describe how
b In the Water sector, for lifting, irrigation, centrifugal pumps, fans and compressors
distribution, treatment, etc. function in different operating modes, and
b In the Oil and Gas sector, for extraction, to quantify the energy savings that speed
transport, rening, liquefaction, etc. control can generate. Other advantages of this
b In buildings, for heating, ventilation, air technique in terms of Energy Efciency are also
conditioning, etc. reviewed.
Traditional methods of controlling ow rate or
pressure involve varying the effective cross-
section of the pipe or circuit through which the
uid ows.

Cahier Technique Schneider Electric n 214 / p. 4


2. Centrifugal pumps

2.1 General aspects

Centrifugal pumps cover a very wide spectrum Figure 2 shows a centrifugal pump driven by a
in terms of power, ow rate and pressure. They three-phase asynchronous squirrel-cage motor,
are used in a host of applications, notably in the the most common type of electric motor used.
water sector. This is the most widespread type These motors operate at a xed speed when
of pump. connected directly to the power grid, but are
The principle involves actuating an impeller perfectly suited to operation at variable speeds
that transfers mechanical energy to the uid, when powered via a frequency converter.
which is then converted into potential energy
(represented by the pressure) and kinetic energy
(represented by the ow rate).
Figure 1 shows the main parts of a simple
single-impeller centrifugal pump:
b the pump body, which comprises the inlet and
outlet manifolds,
b the impeller, which is xed to the drive shaft.

Outlet Outlet

Impeller

Fig. 2. Centrifugal pump driven by an electric motor.

Inlet

Different centrifugal pump congurations have


been developed to cover a wide range of ow
Volute rates and pressures. In particular, the pressure
can be increased by placing several pumps in
series. Figure 3 shows an example of a multi-
Fig.1. The main parts of a centrifugal pump. stage pump.

Fig. 3. Multi-stage centrifugal pump.

Cahier Technique Schneider Electric n 214 / p. 5


2.2 Fundamental characteristics

A pumps fundamental role is to deliver a In the case of water: = 1000 kg/m3


certain quantity of uid in a given time at a A pumps Total Dynamic Head (TDH)
given pressure. The major parameters used in represents the pressure differential the pump
pumping are therefore flow rate and head. creates in the uid between the inlet and the
The ow rate (or discharge) Q represents the outlet, expressed as the uid column height. The
volume of uid transported per unit of time and is TDH varies according to the ow rate. The curve
expressed in m3/s. representing TDH as a function of ow rate is
The head (H) represents the pressure at a given characteristic of each pump.
point of the circuit, expressed as the height of a There is a different TDH curve for every pump
uid in a vertical column (in m). drive speed.
Relationship between the head and the The Maximum Total Dynamic Head (TDHmax)
pressure: Pr = gH sometimes refered to as shut off head
Pr: pressure (Pa) corresponds to the maximum pressure the pump
: density of the uid (kg/m3) can exert on the uid, at a ow rate of zero. This
g: acceleration due to gravity (9.81 m/s2) corresponds to the maximum uid column height
H: head (m) the pump can maintain, as illustrated in figure 4.

TDHmax

Fig. 4. Illustration: Maximum Total Dynamic Head.

Cahier Technique Schneider Electric n 214 / p. 6


The useful power (Pu) transferred to the uid is T D H max
given by the formula: Pu = gHQ (in W)
The mechanical power (P) supplied to the Hn
pump takes into account the pumps efficiency
, i.e.
TDH
P=(1/)Pu =(1/)gHQ

The pumps efficiency varies with the ow 0


rate. It is zero when the TDH or ow rate are 0
zero. This is the case because no power is
transferred to the uid.
The nominal operating point, or Best Efciency
Point (BEP), is dened as the point at which the
pumps efciency is at its maximum.

Figure 5 represents variations in TDH, efciency 0


and power as a function of ow rate, for a typical 0
centrifugal pump
Pn

0
0 Qn Q (m3/s)

Fig. 5. Characteristic curves of a typical centrifugal pump.

Cahier Technique Schneider Electric n 214 / p. 7


2.3 Operating point

The distribution circuit to which the pump is tted pressure that needs to be exerted on the uid to
is characterised by: overcome friction in the conduits.
b the water column height between the suction A simplied distribution circuit is represented in
point and the point at which the uid is used figure 6.
(total geometric height Z),
b the head loss, corresponding to the additional

Fig. 6. Simplified distribution circuit.

The head loss R is proportional to the square The operating point of the pump tted to the
of the ow rate. This results in a curve that circuit is determined by the intersection of the two
is characteristic of the distribution circuit, as curves characterising the pump and the circuit,
represented in figure 7. as indicated in figure 8.
In this case, the useful power supplied by the
pump to the uid (equal to gHQ) is proportional
to the shaded area.
H (m)

H (m)
R
Pump
Circuit
Z

0
0 Q (m3/s)

Fig. 7. Characteristic curve of a distribution circuit.


0
0 Q (m3/s)

H: head at the pump


Z: water column height (static head) Fig. 8. Operating point of a pump in a circuit.
R: head loss (dynamic head)

Cahier Technique Schneider Electric n 214 / p. 8


2.4 Varying the flow rate at a fixed speed

In most applications, the fluid flow rate to be Using a bypass circuit


supplied varies over time, according to the needs The principle involves returning some of the
of users. pumped fluid back to the source, using a bypass
When using a fixed-speed pump, different valve. This allows the flow rate to be closely
methods can be applied. controlled but presents the drawback of low
Some of the most common solutions are outlined energy efficiency.
below. In figure 10, point A is the operating point
Use of valves downstream from the pump relating to the nominal flow rate Qn. The optimal
This aim here is to reduce the effective cross- operating point for this circuit at a reduced flow
section of the pipe downstream from the pump. rate Qr would be point C. The bypass valve
This results in an increase in head loss in the located downstream from the pump makes
circuit, which translates into an increase in the practically no difference to its operating point.
pressure at the pump outlet and dissipation of The shaded area therefore represents the power
energy in the fluid. lost with this type of operation.
In figure 9, point A is the operating point at the This type of operation allows a low flow rate
nominal flow rate Qn. Point B is the operating to be achieved without running the risk of
point at the reduced flow rate Qr. The circuits increasing the pump outlet pressure to an
optimal operating point at flow rate Qr would be excessive degree.
point C. The shaded area therefore represents
the power lost with this type of operation.

H (m) H (m)

A
A

C C

0 0
0 Qr Qn Q (m3/s) 0 Qr Qn Q (m3/s)

Fig. 9. Varying the flow rate using a downstream valve. Fig. 10. Varying the flow rate using a bypass valve.

Cahier Technique Schneider Electric n 214 / p. 9


Intermittent operation Parallel pumping
This operating conguration is commonly used When the ow rate in a circuit needs to vary to a
to ll storage tanks such as water towers. The great degree, it is a good idea to place several
pump is selected so that it operates at an optimal pumps in parallel. This conguration, which
level of efciency for the water height in the is illustrated in figure 11, makes it possible to
circuit considered and the maximum ow rate operate pumps as close as possible to their
required. The pump is switched on during the optimal level of efciency.
periods at which electricity is cheapest.
The drawback of this method is that operating the
pump at its maximum ow rate means the head
loss in the circuit is also at a maximum.

P1

P2

P3

Pa

Fig. 11. Pumps in parallel.

If, for example, three identical pumps are H (m)


installed in parallel, the resulting TDH curve is
plotted point by point by adding together the
corresponding ow rates at a given head.
In a given circuit, there are therefore three
possible operating points, depending on the
number of pumps in operation, as represented in
figure 12.

Note that Q1+2 < 2 Q1. 0


This is due to the increase in system resistance 0 Q1 Q1+2 Q1+2+3 Q (m3/s)
(friction).
Fig. 12. Combination of identical pumps in parallel.

Cahier Technique Schneider Electric n 214 / p. 10


Intermediate operating points can be obtained
by using a lower-powered auxiliary pump, as
illustrated in figure 13.
H (m)

Increasing
demand

H (m)
P
max

P
min
1P 2P 3P
0
0 Q (m3/s)

Fig. 14. Operation of a booster pump as the flow rate


0 increases.
0 Qa Q1 Q1+a etc... Q (m3/s)

Fig. 13. Using an auxiliary pump. Conversely, falling demand translates into an
increase in head losses, resulting from the
closing of taps downstream, and an increase in
Following the same principle, it is quite common the pressure.
for a low-powered "jockey pump" to be used to When the maximum pressure is attained, a
maintain the circuit at a minimum pressure when pump must be switched off. This operation is
the main pumps are not in operation. illustrated in figure 15.
Note that parallel operation of pumps with
different pumps curves may lead to stability
problems and design of such a system should be
veried by a hydraulics engineer.
Booster function
Pumps placed in parallel generally include a H (m)
pressure regulation system, so as to maintain
the pressure in the circuit between a minimum Decreasing
and maximum value. demand
An increase in demand results in a reduction in
head losses, resulting from the opening of taps P
downstream, and a reduction in the pressure. max
When the minimum pressure is attained, an
P
additional pump must be put into operation. This min
operation is illustrated in figure 14. 1P 2P 3P
0
0 Q (m3/s)

Fig. 15. Operation of a booster pump as the flow rate


decreases.

Cahier Technique Schneider Electric n 214 / p. 11


2.5 Variable speed operation

The fundamental characteristics of a centrifugal Similarly, the characteristic P(Q) curve can be
pump are linked directly to its rotational speed. If plotted point by point, with the homologous
we consider the pump on its own (without taking points being located on a cubic curve, as shown
into account the water column height), at a in figure 17.
rotational speed N other than the nominal speed Nn: Varying the flow rate in a given circuit
b the ow rate Q is proportional to (N/Nn), We saw above that it is possible to vary the ow
b the total dynamic head TDH is proportional to (N/Nn)2, rate of a pump operating at a xed speed using a
b the power P is proportional to (N/Nn)3 valve placed downstream. This type of operation
Note that these pumps afnity laws are is illustrated in figure 9.
aproximation but are legitimate on a wide range Figure 18 illustrates the power reduction
of speed variation. achieved when the ow rate is varied by altering
the pumps rotational speed. The useful power
supplied by the pump is proportional to the
shaded rectangular areas, therefore one can
observe a signicant reduction in power in the
HMT variable speed conguration.

Nn

Nn x 0.8
H (m)

0
0 Q (m3/s)

Fig. 16. Characteristic curves of a centrifugal pump at


two different speeds .

0
0 Q (m3/s)
Based on the characteristic curve at the nominal
speed, the characteristic TDH(Q) curve at a
different speed can be plotted point by point, H (m)
with the homologous points being located on a
parabola, as shown in figure 16.

P (W)

Nn
0
0 Q (m3/s)

Nn x 0.8
Fig. 18. Variation of the flow rate at a constant speed
and with variable speed.

0
0 Q (m3/s)

Fig. 17. Characteristic P(Q) curves of a centrifugal


pump at two different speeds.

Cahier Technique Schneider Electric n 214 / p. 12


Varying the rotational speed makes it possible Taking Hn as the TDH at the pumps nominal
to use the pump at its highest level of efciency operating point, one can dene the following
at all times. In this case, the rectangular shaded different types of circuits:
areas are therefore directly proportional to the
power drawn by the pump. In this example, b Z = 0: circuit with head losses alone
the way the power drawn varies is illustrated in b Z = 0.85 Hn: typical water supply
figure 19. (the geometric height is a
preponderant factor)
b Z = 0.5 Hn: intermediate value

The top graph of figure 20 shows that to obtain


H (m) a similar reduction in the ow rate from Qn to
Qr, the decrease in pump speed will be different
depending on the type of circuit. This results in
different curves for power as a function of ow
rate, as shown in the bottom graph of the gure.
The greater the decrease in speed, the greater
the reduction in power.

0
0 Q (m3/s)

P (W) H (m)

Hn

0
0 Q (m3/s)

Fig. 19. Variation of power with variable speed.

Variation of power in different types of 0


circuits 0 Q (m3/s)
The variation in the power drawn by the pump
P (W)
as a function of the ow rate depends on the
characteristics of the circuit to which it is tted. Pn
The parameter to be taken into account is the
ratio between the head at the pumps nominal
operating point and the head Z at a ow rate of
zero (see figure 7).

0
0 Qr Qn Q (m3/s)

Fig. 20. Variation of power for different types of circuits.

Z=0
Z = 0.5 Hn
Z = 0.85 Hn

Cahier Technique Schneider Electric n 214 / p. 13


Example of a power reduction calculation
Let us consider a motor-driven pump with an
installed power of 100kW tted to a circuit with
head Z equal to half the pumps nominal TDH P (%)
(Z = 0.5 . Hn). 100
We wish to compare the energy consumed 94
at 80% of the nominal ow rate when the
pump is driven at its nominal speed with that 66
consumed at a reduced speed. A valve is placed
downstream to reduce the ow rate at the
nominal speed.

Motor efciency: mot = 0.95 at the nominal speed 0


0 20 40 60 80 100 Q (%)

mot = 0.93 at 80% of the


nominal speed Fig. 21. Power variation.

Variable speed drive efciency: vsd = 0.97

The power drawn in each case is presented by


the curves above and specied in figure 21.

At a ow rate of 80 % of the nominal ow rate,


the power drawn at the nominal speed is equal to
94 % of the nominal power.
At this same ow rate, the power drawn at
reduced speed is equal to 66% of the nominal
power.

Electrical power at the nominal speed:

1 1
P f = Pn. ---------- . P( Q) = 100. ------------ . 0.94 = 98.9 kW
mot 0.95

Power at reduced speed:

1 1 1 1
P r = Pn . ---------- . ---------- . P( Q) = 100. ------------ . ------------ . 0.66 = 73.1 kW
mot vsd
0.93 0.97

The difference in power consumption is 25.8kW,


which represents an energy saving of 226 MWh
per year for continuous operation, and therefore
a saving of 11,300 per year, assuming a cost of
0.05/kWh.

Cahier Technique Schneider Electric n 214 / p. 14


Eco8 software
This Schneider Electric software application
makes it possible, for general cases, to estimate
the energy savings that can be achieved H (m)
by varying the speed, as opposed to more
traditional techniques such as throttling the ow Pump at
by downstream valves or the use of bypass nominal speed
circuits.
Hn

Z = Hn/2
Circuit Pump at
reduced speed

0
0 Qn/2 Qn Q (m3/s)

Fig. 23. Characteristic curves of the pump and the


circuit.

Let the desired ow rate be equal to half the


Fig. 22. Eco8 software application. nominal ow rate. In the case of a xed-speed
pump, this requires intermittent operation at
nominal power, with a duty cycle of .
Power reduction compared to intermittent
operation The average power required will therefore be
given by:
The intermittent use of a xed-speed pump was
discussed above as a possible solution for the Pavg = k () Hn Qn
adjustment of the average ow rate in a circuit.
We will now provide an example of the savings
The coefcient k takes into account the pumps
that can be achieved by varying the speed.
efciency, which is assumed to be optimal at the
Let us consider a circuit with head Z at a ow nominal operating point (Hn, Qn).
rate of zero is equal to half the pumps nominal
When operating at reduced speed, the power
TDH, i.e. Z = 0.5 Hn
will be given by:
The head in the circuit as a function of ow rate
is given by: Pr = k . H . Qn/2

H = Z + k1 . Q2 (1) We can use the same coefcient k if we assume


that the pump operates at reduced speed at its
If Qn is the pumps nominal ow rate, we obtain: optimal level of efciency.
The head H can be calculated using equation (3)
Hn = Z + k1 Qn2 with Z = 0.5 Hn with Q = Qn / 2.
0.5 Hn Thus, we obtain:
then k1 = (2)
Qn2
Pr = (5 / 8) . k . () . Hn . Qn
Substituing k1 in quation (1) leads to :
Therefore: Pr = 0.62 . Pavg

( Q
H = 0.5 Hn 1 + ------
Q ( ))
n
2
(3) The use of a pump operating at reduced speed
therefore allows the power drawn to be reduced
by almost 40 % in this example, without taking
into account energy losses in the motor and
variable speed drive.

Cahier Technique Schneider Electric n 214 / p. 15


Variable speed parallel pumping The most commonly used conguration involves
The operation of the multi-pump conguration varying the speed of one pump and operating
presented above (see figure 11) can be the others at a xed speed. The use of a
signicantly improved through variable speed. variable-speed pump allows the entire range to
be covered (H,Q), as illustrated in figure 24.

H (m)

0
0 QV Q1 Q1+2 Q1+2+3 Q (m3/s)

Fig. 24. Using a variable-speed pump.

The use of a variable-speed pump makes it Comparison of different solutions


possible to maintain the pressure in the circuit In the following example, different options are
at a set value. If the pressure drops or rises compared for ow reduction:
compared to the set value, an acceleration or b Throttling
deceleration command is sent to the variable b One pump running at variable speed (lead
speed drive. If the pumps maximum or minimum pump) and other pumps running at xed speed,
speed are attained, one of the xed-speed b All pumps running at variable speed
pumps is started or stopped depending on the Let us consider a conguration with 3 identical
case. motor-driven pumps in parallel, each one with a
The variable-speed pump makes it possible power at 100% ow equal to 100kW. The circuit
to prevent large pressure differences, such as static head Z is equal to half of the Total Head Hn
those represented in gures 14 and 15. of the circuit (Z = 0.5 Hn).
This system also allows a reduction in the A comparison of the different options is made
number of motor starts and stops by preventing at 70% of the total capacity, i.e. 210% of the
the large pressure or ow rate uctuations that nominal ow of one single pump.
occur when a xed-speed pump is started or The pumps characteristics are represented on
stopped. This reduces stress on the motors and figure 25, for different values of rotating speed.
the risk of water hammer.

Cahier Technique Schneider Electric n 214 / p. 16


P (kW)
P (kW)

Fig. 26 : Using one variable-speed lead pump.

Fig. 25 : Pump and circuit characteristics.

With throttling, the power of each pump running of one single pump, only one pump running at
at full speed is reduced to 85 kW. The total full speed is necessary.
power is then equal to 255 kW. The flow delivered by the lead pump is then
The operation with one lead pump at reduced equal to 210 - 130 = 80% of the nominal flow.
speed is illustrated on figure 26. As a For this flow and head, the pump is running at
consequence, the flow of a pump running at full approximately 87% of its nominal speed, and
speed is increased to 130%, with an increase the absorbed power is around 66 kW.
of the absorbed power (around 7%). As the For this option, the total power is then equal to
requested total flow is 210% of the nominal flow 107 + 66 = 173 kW.

Cahier Technique Schneider Electric n 214 / p. 17


P (kW)

Fig. 27 : Using three variable-speed lead pumps.

With all three pumps running at the same It can be concluded that the use of variable
reduced speed, their speed must be adjusted to speed brings a significant total power reduction.
85% of the nominal speed. The power of each In the example presented here, the lead pump
pump is reduced to 60 kW. solution has the better efficiency, but the pump
The total power for this option is then equal to running at full speed must have a higher power
3 x 60 = 180 kW. rating.

Cahier Technique Schneider Electric n 214 / p. 18


Other advantages of variable speed b Less risk of water hammer and cavitation:
In addition to the advantages already these phenomena, which arise as a result of
mentioned, the use of variable speed enables rapid variations in pump speed, are avoided
greater exibility in the design and running of thanks to the gradual acceleration and
installations. In particular it allows: deceleration made possible by the variable
b The elimination of valves to adjust the speed drive,
maximum ow rate: if the pump is oversized, b The replacement of two-speed motors and
operation at reduced speed makes it possible to other obsolete speed control devices that offer
avoid the energy losses caused by a ow rate low efciency.
throttle valve. b Pump impeller life is related to impeller tip
b The reduction of noise and vibrations: the use speed. As such reducing motor speed will
of a variable speed drive means that the pump improve impeller reliability
does not have to be used for extended periods b Speed control allows the pump to operate
at a xed speed that may cause resonance in at high efciency. Operation away of BEP will
pipes. reduce bearing and seal life.

Fig. 28. Schneider Electrics Altivar 61 range of variable speed drives.

To power such variable speed motors, Schneider Additionnal pump control cards are available
Electric offers the Altivar 61 range of variable for even better control or for more complex
speed drives specially designed for pumping applications.
applications.

Cahier Technique Schneider Electric n 214 / p. 19


3. Fans

3.1 General aspects

Fans are machines designed to propel a There are many different fan congurations.
gaseous uid with a low compression ratio. Figure 29 presents two examples of these: a
They are therefore governed by the same uid centrifugal or radial fan, and a propeller or axial
mechanics laws that apply to centrifugal pumps, fan.
resulting in numerous analogies between the two
types of machines.

Fig. 29. Examples of a centrifugal fan (left) and a propeller fan (right) together with their drive motors.

The pressure differential created by the fan can


be expressed in the form of a uids geometric
height, as is the case for pumps. Figure 30 H
shows the rate at which head H and power P, in
the case of a centrifugal fan, vary as a function
of the ow rate Q, at a constant rotational speed.

0
0 Qn Q (m3/s)

Fig. 30. Typical characteristic curves of a centrifugal fan.

Cahier Technique Schneider Electric n 214 / p. 20


In most cases, the outlet circuit exhibits no
notable pressure differential (the circuits inlet
H (m)
and outlet are both at atmospheric pressure).
The shape of the circuits characteristic curve
can be explained by head losses that are
Fan
proportional to the square of the ow rate. The
circuits H(Q) curve is therefore a parabola
passing through the origin. The operating point Hn
of the fan tted to the circuit is determined by the
intersection of the two curves characterising the
fan and the circuit, as indicated in figure 31.
The area to the left of the characteristic curves Circuit
peak must be avoided, as it presents the risk
of instability, which would lead to ow rate and
pressure oscillations, as well as abnormal noise 0
and considerable mechanical stress. 0 Qn Q (m3/s)

Fig. 31. Operating point of a fan in a circuit.

3.2 Fixed-speed operation

Different types of mechanical devices are used


to vary the ow rate of fans operating at a xed
speed.
Devices placed downstream from the fan
The principle involves placing a device into the
air conduit to control the circuits head losses.
Depending on the size of the conduit, the device
can be either a valve or a single or multi-leaf
damper.
This method is the simplest way of varying the
ow rate, but its energy efciency is low. This
is illustrated in figure 33, which shows that the
ow rate can be varied by modifying the circuits
characteristics. For the two operating points
represented, the useful power values, which are Fig. 32. Example of a multi-leaf damper.
proportional to the shaded rectangular areas,
are very close. At low ow rates, a signicant
proportion of the energy is dissipated in the uid. H (m)

0
0 Q (m3/s)

Fig. 33. Adjusting the flow rate with a device placed


downstream .

Cahier Technique Schneider Electric n 214 / p. 21


Devices placed upstream from the fan a reduced ow rate the fan does not produce
The aim of these devices is to alter the fans superuous pressure.
characteristic curve, so as to displace the Different technologies have been developed,
operating point while leaving the circuits including wicket gates, buttery valves, dampers
characteristic curve unchanged. Energy and guide vanes.
efciency is signicantly improved, because at

Fig. 34. Examples of devices placed upstream: multi-leaf damper (left), guide vanes (right).

With all these devices, the fans characteristic Other devices


curves are altered as indicated in figure 35. b With propeller fans (axial), the ow rate
The useful power values are proportional to the can be adjusted by varying the angle of the
shaded rectangular areas, and we can observe vanes. Because of its mechanical complexity,
a signicant reduction in power at a low ow this technique is only used for large fans. This
rate. This alteration of the characteristic curves method is highly energy efcient
is accompanied by a smaller loss in efciency b The ow rate can also be adjusted using
than that caused by simply placing a damper at a bypass circuit, but this is uneconomical as
any point on the circuit. energy consumption is constantly at a maximum,
regardless of the effective ow rate.
Remarks:
In many cases, fans are oversized to obtain a
H (m) maximum ow rate that is greater than the useful
ow rate. Dampers are therefore installed to
reduce the ow rate or the speed of the air at
the outlet, and adjusted when the installation is
put into operation. This results in constant head
losses that reduce overall energy efciency.
Another drawback of xed-speed operation is
that the noise level is always at a maximum.

0
0 Q (m3/s)

Fig. 35. Adjusting the flow rate with a device placed


upstream.

Cahier Technique Schneider Electric n 214 / p. 22


3.3 Variable-speed operation

The fundamental characteristics of a fan are


linked directly to its rotational speed. If we
consider the fan in isolation, at a rotational speed
N other than the nominal speed Nn: P (W)
b the ow rate Q is proportional to (N/Nn), Nn
b the head H is proportional to (N/Nn)2,
b the power P is proportional to (N/Nn)3
Based on the characteristic curve at the nominal
speed, the characteristic H(Q) curve at a
different speed can be plotted point by point,
with the homologous points being located on a Nn x 0.8
parabola, as shown in figure 36.

0
0 Q (m3/s)
H(m)
Nn Fig. 37. Characteristic P(Q) curves of a fan at two
different speeds.

Nn x 0.8
H (m)

0
0 Q (m3/s)

Fig. 36. Characteristic curves of a fan at two different


speeds.

0
0 Q (m3/s)
Similarly, the characteristic P(Q) curve can be
plotted point by point, with the homologous Fig. 38. Varying the flow rate by varying the speed of
points being located on a cubic curve, as shown the fan.
in figure 37.
Figure 38 illustrates the shifting of the fans
characteristic curves at different rotational
speeds and the resulting ow rate in a given P (W)
circuit.
Varying the rotational speed makes it possible
to always use the fan at its highest level
of efciency. This means that the shaded
rectangular areas are directly proportional to the
power drawn by the fans.
Speed variation is therefore the method that
offers the greatest energy efciency. Figure 39
compares the variations in power resulting from 0
the three main methods of varying the ow 0 Q (m3/s)
rate: device placed downstream, device placed
upstream, variable speed. Fig. 39. Power versus flow rate for the different
methods.
Downstream
Modulation
Upstream
On-Off
Var. Speed
speed

Cahier Technique Schneider Electric n 214 / p. 23


Examples of power reduction calculations
Let us consider a centrifugal fan with a nominal
Downstream
Modulation
power of 100kW.
Upstream
On-Off
The fan is slightly oversized, which means that
Var. Speed
speed
the maximum ow rate in the circuit must be P (%)
adjusted to 90% of the fans nominal ow rate to
100
limit the speed of the air at the circuits outlet.
85
In a 24-hour cycle, a ow rate of 90% is required
77
over a 12-hour period (daytime), and a ow rate
of 50% is required over the remaining 12-hour
46
period (night time).
We wish to compare the different adjustment
methods. 18
Motor efciency: 0
b mot = 0.95 at the nominal speed 0 50 90 100 Q (%)
b mot = 0.94 at 90% of the nominal speed
b mot = 0.89 at 50% of the nominal speed Fig. 40. Variation in power drawn.

Variable speed drive (VSD) efciency: vsd = 0.97

The power drawn by this fan using the different At reduced speed, the formula takes into account
adjustment methods is illustrated by the curves the efciency of the variable speed drive:
shown previously in figure 39 and detailed in 1 1
figure 40. P r = Pn . ---------- . ---------- . P( Q)
mot vsd
The general power calculation formula at the
nominal speed is as follows:
The table below shows the results of the power
1 calculation for the different methods, in kW:
Pf = Pn . ---------- . P( Q)
mot

Setting: kW at 0.9 x Qn kW at 0.5 x Qn


Downstream 105 89
Upstream 80 48
Variable speed 84 21

The energy consumed is calculated by downstream, and 5,100 compared with control
multiplying the power by the operating time, for using a device placed upstream.
each period (day and night): 12 hrs/day x 365 The Eco8 software application presented above
days = 4,380 hrs/year, assuming that the fan is allows this type of calculation to be performed
running constantly. for all cases (selection of the engine power,
Assuming a cost of 0.05/kWh, the use of control of the upstream or downstream ow rate,
variable speed allows annual savings of 19,600 denition of the operating speed).
compared with control using a device placed

Setting: kWh
Downstream 852 947
Upstream 562 484
Variable speed 460 661

Cahier Technique Schneider Electric n 214 / p. 24


Fans operating in parallel Flow rate Q1 represented in figure 41 can be
Gaseous uids can be propelled at high ow obtained either by operating fan 1 alone at
rates by placing fans in parallel. Generally, its nominal speed, or by operating both fans
identical fans are used. The resulting together at reduced speed. This type of operation
characteristic curve is obtained from the sum of is illustrated in figure 42, which represents the
the ow rates at equal pressure, as illustrated in characteristic curve of both fans operating at the
figure 41. same time at the reduced speed Nr.
We can see that in a given circuit, as a result of
the quadratic increase in head loss as a function
of ow rate, the resulting ow rate with two fans
is not double the ow rate obtained with a single
fan.

H (m) H (m)
1 1+2 1 1+2

Hn Hn

Nn
1+2

Nr

0 0
0 Q1 Q1+2 Q (m3/s) 0 Qr Qn Q (m3/s)

Fig. 41. Characteristic curve of two fans operating Fig. 42. Operation of two fans at reduced speed.
in parallel.

Cahier Technique Schneider Electric n 214 / p. 25


In the example represented, the reduced speed
is equal to approximately 2/3 of the nominal To obtain a ow rate equal to half the maximum
speed Nn. Each fan therefore absorbs power ow rate, three fans can be operated at the
equal to (2/3)3 times the nominal power Pn of a nominal speed or all six fans can be operated at
fan. half the nominal speed.
The total power is therefore given by:
3
In the rst case, the power will be:

( )2
Pt = 2. ---------- .Pn 0.6
3
. .Pn
P1 = 3. Pn

In the second case, the power will be:


Operating two fans at reduced speed therefore
brings about an energy saving of 40% compared 3
with a single fan operating at the nominal speed.
( )
1
P2 = 6. ---------- .Pn = ----------
2 4 n
P1
3 . P = ----------
4
-

The energy saving achieved is even greater with


a multiple-fan conguration operating under a
Therefore, this is another example of energy
head that is very low or even zero.
consumption being substantially reduced when
variable speed drives are used to adjust fans.
For example, let us consider a conguration
where six fans with nominal unit power Pn are
To control the speed of fans, Schneider Electric
placed in parallel, with no signicant outlet
offers the Altivar 21 range of variable speed
pressure.
drives, which is particularly well suited to
heating, ventilation and air conditioning (HVAC).

Fig. 43. Schneider Electrics Altivar 21 range of variable speed drives.

Cahier Technique Schneider Electric n 214 / p. 26


4. Compressors

4.1 General aspects

A compressors fundamental role is to increase b Aeration in wastewater treatment facilities.


the pressure of a gas from the suction pressure Requirements in terms of ow rate and pressure
to the discharge pressure. vary greatly, which is why different technologies
Air and gas compression has numerous have been developed. The most common are:
applications in industry. These include: b Centrifugal compressors,
b The production of mechanical energy for b Screw compressors,
different types of actuators (screw guns, b Piston compressors,
pneumatic jacks, etc.), b Vane compressors,
b The production of industrial gases through b Turbochargers.
liquefaction (nitrogen, oxygen, natural gas, etc.),
b Air conditioning and refrigeration,

Fig. 44. Example of a screw compressor.

In general, the torque developed increases with Pressure


the speed, but the starting torque can sometimes
Compressor
be high, as is the case with piston compressors.
As we saw above with pumps and fans, the
compressors operating point depends on the Pn
characteristics of the uid circuit, as illustrated
in the following gure (for a centrifugal Circuit
compressor).

0
0 Qn Q (m3/s)

Fig. 45. Operating point of a centrifugal compressor.

Cahier Technique Schneider Electric n 214 / p. 27


4.2 Variable-pressure operation

To cater for uctuations in system demand, systems, because of its low energy efciency.
all compressors are coupled with a pressure b Partial or total load shedding by shutting
regulation device. The main adjustment the compressors suction ap or valve. The
methods, which are suited to the characteristics compressor operates at reduced or zero load,
of different technologies, are recalled below: thus reducing the electrical power drawn.
b Starting and stopping the compressor. b Placing several units in parallel. The number
Intermittent operation is suited to low-power of compressors in operation can be adjusted on
devices that can be started frequently with demand.
no unacceptable drawbacks. During phases b Varying the compressor speed. This method is
of operation, the compressor operates at its the most energy efcient.
optimum level of efciency.
b Recirculating or evacuating excess ow. This
operating method is only applicable to low-power

4.3 Variable-speed operation

Varying a compressors speed is a method


well suited to most technologies. It presents a Modulation
number of major advantages: On-Off
b Gradual start up: no current peaks, reduced P (%) Var. Speed
mechanical stress,
b Precise pressure regulation: the compressors 100
speed and therefore ow rate can be adjusted 80
on demand, which reduces the amplitude of
pressure uctuations and the size of the buffer 60
tanks required,
b Optimum efciency: operating without head 40
losses in the circuit allows energy losses to be 20
reduced.
Speed variation is also well suited to 0
compressors operating in parallel. In general, 0 20 40 60 80 100 Q (%)
only one of the compressors is driven at variable
speed, while the others operate on an on-off Fig. 44. Comparison of compressor control methods.
basis.
The gure below shows typical power variation
curves, when using different ow control
methods.

Cahier Technique Schneider Electric n 214 / p. 28


5. Conclusion

The use of variable speed in hydraulic machines surges, are greatly reduced by the gradual and
such as pumps, fans and compressors is the controlled acceleration and deceleration of
key way of reducing energy consumption the motor. The life expectancy of equipment is
in numerous industrial and commercial therefore extended. In addition, the management
installations. of the process is signicantly improved and
The energy savings are particularly signicant if simplied, because it is possible to nely adjust
reduced ow rates are used on a frequent basis. the uid ow rate and pressure.
The sums invested in variable speed drives An in-depth discussion of the operation of
are paid back very quickly and subsequently pumps, fans and compressors was beyond the
generate considerable savings. scope of this document. Nevertheless, the key
As well as energy savings, variable speed principles have been presented, together with
drives bring many other advantages to these examples that illustrate the extent of the energy
applications. Thus, mechanical constraints, savings that can be achieved through the use of
such as water hammer, cavitation and torque variable speed drives.

Appendix 1: Bibliography

b Technical booklets of the International Water b "Systmes de compression et de rfrigration"


Ofce, Limoges, France (Compression and refrigeration systems)
technical guide, Hydro-Qubec, Montreal,
b "Entrainements lectriques vitesse variable" Canada
(Variable speed drives), Promthe, Schneider
Electric b "Energy Efciency Guide Book", Bureau of
Energy Efciency, India
b "Improving pumping system performance", US
Department of Energy b "Energy savings with electric motors and
drives", AEA Group, UK
b "Systmes de ventilation" (Ventilation systems)
technical guide, Hydro-Qubec, Montreal,
Canada

Cahier Technique Schneider Electric n 214 / p. 29


Schneider Elctric de Colombia S.A. Schneider Electric de Colombia S.A.
Principal BOGOT D.C., Carrera 102 A No. 25 D - 40
Agencia Eje Cafetero
MANIZALES Carrera 24 No. 20 - 48 Of. 10-01
Tel.:57 (1) 4269700 Edificio Confamiliares
Fax: 57 (1) 4269740 - 57 (1) 4269738 Tel/Fax: 57 (6) 8973435
Centro de Atencin Clientes
Agencia Antioquia Agencia Occidente
Bogot: 4269733 Resto del Pais: 01900 33 12345 MEDELLN Calle 10 Sur No. 50FF - 28 Of. 309 CALI Calle 19 Norte No. 2N - 29 Edificio Torre de Cali
Tel.: 57 (4) 3616730 - 57 (4) 3621191 Piso 36 Of. 3601-A Tel.: 57 (2) 6536414 - 57 (2) 6536515
cacschneider@co.schneider-electric.com Fax: 57 (4) 2856568 57 (2) 6536539 Fax: 57 (2) 6536540
www.schneider-electric.com.co Agencia Costa Norte Agencia Oriente
BARRANQUILLA Calle 77B No. 57 - 141 Of. 309 BUCARAMANGA Carrera 28 No. 41 - 19
Tel.: 57 (5) 3530465 - 57 (5) 3530468 - 57 (5) 3530447 Tel.: 57 (7) 6343169 Fax. 57 (7) 6450762
Fax. 57 (5) 3530429

Toda la informacin presentada se encuentra protegida por las normas de propiedad intelectual. Cualquier copia
o reproduccin sin autorizacin se encuentra prohibida y ser sancionada de conformidad con la legislacin vigente.
Publicado por Schneider Electric de Colombia S.A.. Todos los derechos reservados

You might also like