You are on page 1of 9

the practical effects of inrush will be

Transformer Magnetizing Inrush Currents greatly reduced and may even be absent
altogether.
The effects of inrush currents ard volt
and Influence on System Operation age dips on other system equipment are
most pronounced in the case of fuses and
some types of relays but may also in
L F. BLUME G. CAMILLI S. B. FARNHAM H. A. PETERSON fluence the behavior of motors, starting
FELLOW AIEE FELLOW AIEE MEMBER AIEE MEMBER AIEE
contactors, and lighting circuits.
In applying fuses in series with trans

W HEN a transformer is energized, a with the system voltage dips which it formers, care should be taken to select
transient current, known as magne may produce, can have an important fuses which are large enough so that
tizing inrush current, generally flows for a bearing not only on the application of the they will not be damaged by the trans
short period of time until normal flux transformers themselves, but also on former inrush current, but on the other
conditions are established. Under most 'fuses, relays, contactors, motors, or other hand the fuses selected should not be un
practical system conditions, this current system equipment which is influenced by necessarily large so that inadequate pro
transient is of little consequence. How the inrush current or the resulting system tection to the transformers and system
ever, in very rare cases a combination of voltage dips. results. Although it is often the practice
circumstances may be obtained which It is the purpose of this paper to dis to apply fuses on the basis that their nor
results in this'inrush being of such con cuss the mechanism by which inrush mal current ratings should be approxi
sequence as to impair momentarily the currents are produced, the results of mately equal to some multiple of the
proper operation of the system. Because tests and calculations, and studies made transformer full-load current, this oc
of the numerous factors bearing upon this with the miniature-system analyzer. Fac casionally results in unnecessary fuse
general problem, an investigation has tors that determine the significance of blowing because the normal fuse rating
been made to determine the effects of inrush current from the standpoint of does not in any way reflect its character
transformer inrush currents under a wide system operation and methods for re istics in the short-time-high-current part
variety of system conditions. ducing the inrush current or mitigating of the range. For example, current
That transformers may require a large its effects are also discussed. limiting fuses inherently have limited
initial transient magnetizing current ability to withstand current surges,
when connected to a voltage source has Effects of Inrush Current on while other fuses are available that have
long been recognized.l ~3 Explanations of System Equipment specially designed characteristics to per
the nature of this initial inrush current, mit them to withstand relatively large
together with oscillograms obtained from The magnetizing inrush currents of overcurrents for short periods. Hence.
tests on a few specific transformers, have transformers may, in extreme cases, ap since inrush phenomena are usually asso
been published. No information, how proach in magnitude the currents which ciated with the first few seconds or less
ever, has been found in the technical result from short circuits across their after transformers are energized, this is
literature defining the parameters which secondary terminals. Calculations and the part of the fuse-characteristic curve
determine the variations in the transient measurements indicate that, on typical that should be examined, and the fuse
inrush current among individual trans systems, inrush currents may cause the applied on this bais.
formers, or indicating how the inrush voltage level of one phase at the trans A series of tests, to which later re
current may be affected by the design former terminals to drop as much as 20 ference is made, has indicated that there
and connections of the transformers per cent momentarily. Fortunately, is a simple criterion for selecting fuses
themselves or by the characteristics of the however, even these momentary currents which will be adequate to withstand the
electric systems to which they are applied. and voltage dips occur only very infre inrush current, namely, that the fuses
A working knowledge of these factors quently, as transformers generally are selected should have such character
is made increasingly important by ad not switched often; and, when they istics that they will carry without damage
vances in the art of transformer design are energized, only the pyramiding of 12 times the normal transformer full-load
and manufacture. A particularly im several critical factors, which are dis current for one tenth of a second.
portant advance is the trend toward the cussed later, can produce disturbances Where transformers are expected to be
use of improved silicon steel. The use of as severe as those obtainable under care loaded above their nameplate kilovolt-
this steel offers several distinct advan fully controlled test conditions. In this ampere ratings in accordance with pub
tages, namely. paper, the emphasis is placed on the lished guides for transformer operation4 '
extreme values of inrush current and the
1. Permits operation at higher flux densi resultirg system disturbances, because
ties without increasing core loss, exciting these define the upper limit of the prob
current, or core temperature.
lem. However, in many actual cases,
2. Permits a saving of steel and copper,
both critical materials, in that less actual Paper 4 4 - 1 0 , recommended by t h e A I E E com
mittees on electrical machinery and p o w e r trans
material is required for a given design. mission and distribution for presentation a t t h e
3. Reduces the size and weight of trans A I E E winter technical meeting, N e w Y o r k , N . Y . ,
January 2 4 - 2 8 , 1944. Manuscript s u b m i t t e d
formers per kilovolt-ampere capacity. N o v e m b e r 10, 1943: made available for printing
December 17, 1943.
The attainment of these advantages, L. F. B L U M E and G. CAMTLLI are in t h e power-
transformer-engineering division o f t h e General
however, has been accompanied by a Electric C o m p a n y a t Pittsfield, M a s s . S. B .
tendency to increase the initial transient F A R N H A M a n d H. A . P E T E R S O N are in t h e central-
Figure 1. Flux and voltage relation at instant
station-engineering division of the General Electric
inrush current. This current, together C o m p a n y a t S c h e n e c t a d y , N . Y. of switching

366 Blume, CamiUi, Farnham, PetersonMagnetizing Inrush Currents AIEE TRANSACTIONS


tends in some measure to defeat the pur
pose of the differential relays, since in
sulation failures in transformers have
been known to occur at the instant
of energizing, particularly in the case of
transformers that have been standing idle
for long periods of time
Harmonic-restrained differential relays
offer another solution to the problem.9
In these relays the restraining forces
are produced by harmonic components
of current; and since typical inrush-cur
rent wave forms are rich in harmonic
content, relay operation is prevented so
long as the differential current is of this
type. Full sensitivity of operation, how
ever, is retained for protecting the trans
formers if faults should develop during
the transient inrush period. For parallel
operation of transformers, one harmonic-
Figure 2. Effect of circuit resistance during restraint relay must be used with each
first cycle after switching in at instant of transformer bank in order to insure cor
voltage zero rect relay operation.10
Induction-type inverse-time overcur-
the fuses selected must necessarily be of rent relays, as normally used for overload
sufficient rating to meet the increased and short-circuit protection of power
load-carrying requirements, and will, transformers, are not likely to be caused
to operate by magnetizing inrush cur Figure 3. Effect of source reactance on
therefore, almost certainly be large
rents, except possibly when used for voltage wave shape
enough so that there is no possibility of
being damaged by inrush current. The protecting transformers having unusually Single-phase miniature-system transformer 101.5
fusing of potential transformers con severe inrush-current requirements, and volts at source, base ohms = 4 5 0 ohms, 3 per
stitutes a special problem and has been then only if the relays are adjusted for cent exciting current. Effect of system im
covered elsewhere.6 It has been found minimum pickup and fastest time-lever pedance on inrush current, and voltage wave
setting. Instantaneous plunger-type shape. Transformer d-c resistance, 5.57 ohms.
also that, where fused transformers are
overcurrent relays similarly used oc Saturation curve A of Figure 1 2
exposed to the effects of lightning surges,
the fuse ratings must be greater than a casionally might be caused to operate
System Times Normal Voltaae Across Transformer
certain minimum value to avoid being by the inrush current. Reactance Crest Current
(Per Cent) Inrush Primary Secondary
damaged by the lightning current.7 With correctly applied motors and
Nearly all large or important power startirg equipment; difficulties resulting 0 26.5 116-1 118-1
transformers are protected in event of from the system voltage dips produced 1.18 21.0 116-2
2.36 18.0 116-3 118-2
internal faults by percentage differential by transformer inrush current are not 2.93......17.0 116-4
relays and circuit breakers which operate likely to occur. The starting contactors 5.86
11.4
11.5
7.2
116-6
116-8
118-3
118-4
to isolate the transformers from all normally used with small and medium-
sources of power if the currents in then- size motors are held in their closed posi
windings differ by more than a predeter tion by magnet coils connected across the
mined per cent from one another. Since source of supply voltage. These contactors step or to stall when the system voltage
magnetizing inrush currents flow in the are designed to remain closed until the drops materially. With correctly ap
transformer primary windings orly, the voltage falls to 60 per cent or less of plied motors, troubles of this nature are
differential relays may respond as for rated value and hence are unaffected by not likely to occur unless the transformer
transformer internal faults, thereby trip the voltage dips resulting from trans inrush current is sufficient to lower the
ping the breakers immediately after they former magnetizing inrush currents, since voltage at the motor terminals approxi
have been closed. Although the relays the system voltage during the inrush mately 20 per cent, which, as already
used for transformer applications are period usually does not drop to this low stated, is about the maximum voltage
made inherently less sensitive than those level even momentarily. Large motors drop that may be expected to result from
used for differential protection of busses are usually provided with undervoltage this cause.
or
generators, in recognition of the in protective relays which may be adjusted The switching of transformers of ap
rush problem, this is not always sufficient to cause the motors to be disconnected preciable size is seldom done directly on
t0
prevent false operation. A remedy from the system at any predetermined low-voltage lighting circuits, and hence
sometimes used to prevent such false drop in voltage. These relays, however, light flicker from this cause is rarely a
peration consists in temporarily reduc- are normally of the time-delay type and problem. However, if transformers are
,n
g further the sensitivity of the differ therefore are not caused to operate by switched at a substation which supplies
ential relays or making them entirely the transient voltage dips produced by lighting circuits, this may cause lamp
ineffective for a few seconds or until the connecting transformers to the system. flicker over the entire area served by the
l
nrush current has had an opportunity to However, the motors themselves, may, substation. This will be particularly
decay. Unfortunately, however, this if heavily loaded, tend to pull out of true in the case of single-phase circuits or

1944, VOLUME 63 Blume, Camilli, Farnkam, PetersonMagnetizing Inrush Currents 367


Figure 4. Effect of IIOi
impedance on magnitude of
100
inrush currents

Residual of magnitude and <qo 90i


polarity to give maximum in
rush current. Instant of closing
IS
3 S ;
controlled to give maximum
inrush. Source voltage normal s
as denned by Figure 12. oat 6 0
H tu
Single-phase transformer, as
suming 3 per cent normal ex ou, 5 10 15
2
ce
citing current. Base ohms S Y S T E M REACTANCE I N PER C E N T
O N T R A N S F O R M E R BASE
4 5 0 ohms. Saturation curve A
of Figure 1 2 Figure 5. Effect of source reactance on
system rms voltage
Residual of rnasnitude and polarity to give
maximum inrush current. Instant of closing
controlled to give maximum inrush. Source
voltage normal as defined by Figure 12.
X M PER CENT ON TRANSFORMER BASE
Single-phase transformer, assuming 3 per cent
normal exciting current. Base ohms = 450
certain three-phase circuits (for example, 2. The value of residual magnetism and its ohms. Saturation curve A of Figure 12
four-wire with wye-connected transform sign with respect to the first half cycle of
the alternating flux. 1. Curve A of Figure 12
ers) where the inrush associated with any
2. Curve B of Figure 12
one phase is not modified by the presence 3. Saturation or maximum flux-carrying
of the other phases. As stated pre capacity of the iron.
viously, however, the switching of trans 4. Total impedance of the circuit through It follows from this elementary con
formers is generally so infrequent an which the current flows. sideration that if the transformer is
occurrence that the resulting voltage dips energized by closing the primary switch!
PHYSICAL EXPLANATION
are not a serious problem. On the other at the instant a corresponding to the
hand, if the switching is done frequently, Under normal steady-state conditions zero point of the voltage wave, and, if it is
the light flicker resulting even from small corresponding to a voltage wave E, a flux presumed that there is no residual flux,
voltage dips may become objectionable wave in quadrature with the voltage the maximum peak flux corresponding to
through repetition. exists ignoring the negligible resistance the impressed voltage E will become 2
drop of the primary winding for exciting one-half cycle after the closing of the
Inrush-Current Phenomena current. Starting from a, Figure 1, switch. The flux curve is shown in
corresponding to the negative maximum Figure 1, a'b'.
It is well known that when a trans point of the flux wave and the zero If the core at the instant of closing the
former is connected to a circuit, the cur point of the voltage wave, the flux at a switch possessed a residual flux (^) the
rent taken by it generally will not as has a value ( 0max) and, in one-half final maximum peak flux becomes
sume immediately its final or normal cycle, increases through zero and reaches
wave form and magnitude. a maximum value of (-|-<i>max) at b. So
The magnitude, as well as the number From this it is evident that residual may
* ( <^maz) ~2*
of cycles of the transient, depends on : increase or decrease the maximum peak
1. The point of the voltage wave at the is the change in flux necessary to produce value of the flux.
moment of the closing of the switch. the electromotive force E. Not all of the flux is carried by the core.
The core can carry only a flux (&)
corresponding to its saturation; the rest
Table I. Relative Magnetizing Inrush Currents for Various Transformer Connections is carried by space. The flux that is
carried by space and has its return path
Three Single-Phase Transformers Three-Phase Transformer through the air is :
Transformer Connection
Simultaneous Sequential Simultaneous Sequential
Primary Secondary Switching Switching Switching Switching 2 ax "f" #sat = \ (1)

The current to produce this flux is


^ \ OR ^f 26 X normal 26 X normal 13 X normal 14.5 X normal

jL \ S 26 X normal 29 X normal. . . . 13 X normal 14.5 X normal

where Lx is the air-core inductance of the


| 1 ^ OR | 20 X normal 20 X normal 11.0 X normal 11.0 X normal
winding under consideration.
I \y^ 20 X normal 20 X normal. . . . 11.0 X normal 11.0 X normal
Theoretically the current wave cor
responding to the flux wave can be cal
\ S \y R I 20
* x norma1
3 t X normal. . . 15.5* X normal. . . 15.5* X normal
culated with the aid of the hysteresis
loop (or average magnetization) cun<?
V^ \ ^ 20* Xnormal. . .30f X normal. .. 15.h% X normal. . . 15.5$ X normal of the core. But hysteresis loops or
magnetization curves cannot be obtain
* Based on normal phase current; equals 11.5 based on normal line current. very easily for very high densities afl
t Based on normal phase current; equals 17.3 based on normal line current.
X Based on normal phase current; equals 9.0 based on normal line current. generally are not available. The pea*

368 Blume, Camilli, Farnham, PetersonMagnetizing Inrush Currents AIEE TRANSACTION


71
Curve Residual of masni-
tude and polarity to give maxi
5 35

~
/ mum inrush. Source voltage
normal as defined by Figure 1 2 .
/
1 30 Single-phase transformer, as
suming three per cent normal
39 |/
J exciting current. Base ohms
= 4 5 0 ohms
?
/ Curve BNo residual
5 2 0 /
50C /
DO
2.
/
SMTCMNG ANGLE - DEGREES
20 40 60 80 100 120 140
PER CENT VOLTS Figure 7. Maximum crest inrush current versus switching angle

Figure 6. Effect of system voltage on maxi


mum crest inrush current This formula is only approximate and the d-c component is not reduced greatly
Residual of magnitude and of polarity to give is offered not for the calculation of the by a small variation from a voltage zero.
maximum inrush. Closing at voltage zero. entire wave but only for its peak. 1 In fact, assuming no residual flux, ii
Source voltage normal as defined by Figure 12. Since, as explained heretofore, the 0 = 30 degrees, the crest value of the
Single-phase transformer, assuming 3 per cent inrush peak is determined by the air-core flux is still 1.866 which is only a slight
normal exciting current. Base ohms = 450 ohms inductance of the excited winding and reduction from the maximum of two foi
since generally the higher-voltage winding 0=0.
has higher percentage inductance, there The transient inrush current for typical
value of the current, however, can be fore, exciting a transformer through its transformers is shown in Figures 15 and
approximated fairly closely as follows: higher-voltage winding leads to smaller 16. It is characterized by being almost
With reference to equations 1 and 2 the inrush current. This is particularly entirely unidirectional, rising abruptly to
maximum flux density which iron mole true of concentric transformers in w7hich its maximum value in the first half cycle
cules can add to a given magnetic field is the higher voltage is generally the outer and thenceforth decaying until normal
estimated as 130 kilolines per square solenoid, the lowTer-voltage winding the steady-state magnetizing current is
inch. At densities greater than this inner. reached.
value the field behaves as if the medium The mechanism by which this decay
were entirely air, with no iron present. TIME OF SWITCHING AND RATE OF DECAY
is accomplished is illustrated in Figure 2.
In the present case, the maximum peak OF THE INRUSH CURRENT
It will be noted that the inrush current
flux is equal to (& +25 ) Ac, Ac has modified the impressed voltage on
The flux wave, a'b' of Figure 1 is sinu
being the cross-sectional area of the core. the terminals of the transformer by a
soidal and offset. It can be resolved
Of this, then, something like 130 Ac small value equal to the voltage drop
into two components: a sinusoidal a-c
kilolines will be carried by the iron, the produced by the series resistance R.
component and a d-c component which
rest ( r e 8 +23 m a x -130) A, by space As Examination of the resultant voltage
eventually decays -The general equation
which is the space occupied by the core curve shows that the effect of this drop is
for the transformer flux can be expressed
legs plus the space between the core legs
as followTs : to decrease the area of the positive volt
and the excited winding. age wave and to increase the area of the
The ampere-turns necessary to produce negative voltage wave, thus making the
4>=(<2>* + 4>maxeOS0) -R I idt-
(B^+2Bma3L-130) Ac/As kilolines den J o voltage applied to the transformer asym
sity in space will ordinarily be so large <*W cos M+0) (5) metrical. As the transformer flux is
that it may be considered as adequate to strictly proportional to the areas of the
where
Produce the 130 kilolines density in the impressed voltage, it is evident that
iron molecules in parallel with the flux = residual flux at the instant imme under these conditions, the positive flux
m space; and, therefore, the inrush cur diately preceding energizing the generated in each cycle in the trans
rent for the saturated range of the wave transformer
c #max = maximum value of steady-state flux former is less than the negative flux gener
an be calculated in terms of the air-core ated by an amount equal to
inductance of the winding and the space R = resistance of circuit through which
magnetizing current flows

-X
-2
flux.
= instantaneous value of flux at any = I Ridt
Briefly, if Bs is the flux density in space, time
= the phase angle measured from the
ft A
c where is the flux change per cycle.

^J {Bn*+2Bmmx-13Q) kilolines per instant of zero voltage at which the


transformer is energized From this it is evident that the flux and
square inch (3) corresponding inrush immediately begin
an
d, therefore, if the length of the sole- Since the flux controls the inrush cur to decay an amount which is largely a
noi
d is h inches, and the turns in series n, rent from the preceding expression, it will function of the resistance of the circuit
the maximum instantaneous current be seen that the maximum crest inrush and that the decay will continue until
'max will be current will be obtained when 0=0, x, the magnetizing current of the trans
27 . . . which leads to the well-known former becomes symmetrical, that is, to
, )00, lQ*hAe{Br~+2Bmmx-13Q) conclusion that closing the switch at a normal value of the magnetizing current.
3.2n Z2nAs voltage zero results in the maximum in I t might appear that the core loss also
(4) rush. It should be noted, however, that may be a factor influencing the rate of

1944, VOLUME 63 Blume, Camilli, Farnkam, PetersonMagnetizing Inrush Currents 369


decay of the inrush current If the source reactance and system rms voltage as might be assumed from familiarity
eddy-current losses are considered this at the transformer terminasl during the with normal exciting-current character
may be partially true during the first inrush period is shown in Figure 5. istics. In this connection, it seems prob
few cycles when the rate of decay is able that the few cases of trouble which
highest and appreciable eddy currents SYSTEM VOLTAGE LEVEL have been experienced from inrush cur
might be induced thereby. So far as the It is well known that the normal ex rents of transformers installed at points
hysteresis loss is concerned, its influence citing current of a transformer varies of relatively high system voltage have
is for all practical cases absent. essentially linearly with applied voltage been caused as much by the low system
up to the point where saturation of the reactance viewed from these points as by
Factors Affecting the Magnitude iron begins to take place. Increasing the the relatively high operating voltage level.
of Inrush Currents voltage beyond this point produces more
than a proportionate increase in the ex SWITCHING ANGLE
SOURCE IMPEDANCE
citing current. In the case of maximum It has been pointed out that when a
Impedance between the transformer transient inrush current, however, there transformer is energized at a zero peint
and the source of sustained voltage acts is a linear relation between maximum on the voltage wave, the maximum in
to reduce the magnitude of the peak peak inrush current and applied voltage rush current will be obtained. As the
inrush currei t. Simultaneously a reduc which prevails over a wide range of ap switching angle is varied in either direc
tion in voltage at the transformer ter plied voltage, both above and below the tion from a voltage zero the crest inrush
minals takes place. This is illustrated rated voltage of the transformer. This current is reduced. Figure 7 shows the
by means of oscillograms shown in Figure is indicated by Figure 6 which shows relation between crest inrush current
3. Figure 4 indicates the reduction in the results of tests on a miniature-system and angle of switching, as obtained from
the peak inrush current for a typical single-phase transformer. The straight- tests on a miniature single-phase trans
modern single-phase transformer, as the line relationship is explained by the fact former. Figure 7 also indicates the
source impedance is increased. that under the conditions of residual flux effect of residual flux. The upper curve
A study of Figure 4 in connection with and switching angle which produce the shows the inrush current for the condition
the corresponding voltage wave shapes maximum inrush current, the iron is com of maximum residual of the polarity to
shown on oscillograms of Figure 3 reveals pletely saturated. Hence the transformer produce the maximum flux. The lower
the fact that when inrush currents are of impedance which limits the inrush current curve is for the condition of no residual
the highest magnitude (no system im is essentially the resultant of the air-core flux. If a residual of opposite polarity
pedance), the voltage distortion is at its reactance of its windings as previously exists, then the current resulting from
least. Generally in practical systems pointed out. Under maximum inrush switching at voltage zero will be still
there will be some external impedance conditions, this remains constant over a lower.
which will tend to reduce the inrush range of applied voltage extending up Since any instant of closing may be
current below the maximum that could ward from approximately 60 per cent of realized in practice, the effect of switching
be obtained if the transformer were con rated transformer voltage. angle and the resulting inrush current
nected to an infinite bus. Thus, if the While large initial inrush currents are on system rms voltage becomes of in
transformer is small as compared to the most frequently encountered in trans terest in determining the range of varia
system, which will be the more common formers connected at system locations tion of system voltage for various switch
case, relatively high inrush currents may where the voltage is relatively high, as ing angles. This effect is shown in
be obtained. However, with a system for example at generating stations or Figure 8. In connection with Figures 7
reactance of 1.18 per cent on the trans close to substation busses, it is important and 8, it is recognized that for relatively
former base, for example, the system to note that the relation between inrush high voltages and for slow rates of con
voltage as shown in oscillogram 116-2, and voltage is essentially a linear one; tact travel, prestriking may occur before
Figure 3, is not seriously affected even not second or third power relationship mechanical closing of the switch contacts
though the inrush current is 21 times takes place. Hence the probability of
normal full-load current for the trans closing at a voltage zero is reduced.
former. The general effect of source Figure 8. Effect of switching angle on sys
impedance on system voltage indicated tem rms voltage THREE-PHASE SWITCHING
by these oscillograms is in good quanti Residual of magnitude and polarity to give In energizing a three-phase trans
tative agreement with some unpublished maximum inrush. Source voltage normal as
former, the inrush current will generally
results based on calculations made by defined by Figure 1 2 . Single-phase trans
former, assuming 3 pzr cent normal exciting
be quite different in the three phases.
Edith Clarke. The relationship between Furthermore, modification may be intro
current. Base ohms = 450 ohms
duced by the nonsimultaneous closing
1. 5.5 per cent of all poles of the switch.
system reactance. In order to get a clear picture of the
curve A, Figure 1 2 effect of switching angle on inrush in the
2. 5.5 per cent case of a three-phase core-type miniature
system reactance system transformer, tests were made using
curve B, Figure 1 2 a delta-connected winding. All poles
3. 2.75 per cent were closed simultaneously, and the in
system reactance stant of closing the switches was varied
curve A, Figure 1 2 throughout a 360-degree range. The
4. 2.75 per cent results are shown in Figure 9.
BEFCRE VOLAGE ZERO system reactance The winding currents are seen to line
dT 60 40 20 w
0 20
SWITCHNG ANGLE - DEGREES
40 60 80
curve B, Figure 1 2 up properly with the instant of closing as

370 Blame, Camilli, Farnham, PetersonMagnetizing Inrush Currents A I E E TRANSACTIONS


4-.-
Tcurrent in top leg | 40
.- A
Mcurrent in middle/ delta as
leg ; currents
)

ffoc

yU
30
Lcurrent in l o w e r ! S3
I!
leg /
Aline current 7L
nl-f 1
Bline current LM tZ 0 K> KX> 1000
Cline current=AfT **" O CAPACITOR KVA IN PER CENT OF TRANS
FORMER MAGNETIZING KiLOVOLT-AMPERES
Delta currents should be multi
plied by y/3 to become times Figure 1 1 . Effect of capacitor on maximum
normal delta currents transformer magnetizing inrush currents

Three-phase transformer delta- Transformer de-energized under normal opera


connected operated under nor ting flux-density conditions leaving the capaci
mal conditions as indicated in tor at normal voltage to discharge through the
Figure 1 2 . N o external impedance. Three transformer each time before the transformer
per cent exciting current assumed, base ohms was again energized at an instant controlled
should be expected; that is, each winding
= 1 0 0 ohms. Three phases closed simultane to give maximum inrush. Saturation curve A
behaves as if it were a single-phase unit. of Figure 1 2 w i t h transformer operating at
ously. W h e n phase c voltage is a maximum,
However, the line currents are deter switching angle is 9 0 degrees 1 1 0 volts
mined by the sums of two winding cur
Curve ALast half-cycle of current in trans
rents. This sum can never be greater Figure 9 . Effect of closing angle on maxi
mum crest inrush currents former before switch was opened of same
than the arithmetical sum of the two
polarity as first half-cycle of inrush current
winding currents and never less than the
difference. The polarity of the maximum Curve BLast half-cycle of current in trans
former before switch was opened of opposite
crest will be that of the greater of the two or for three-phase banks of single-phase
polarity to the first half-cycle of inrush current
winding currents. As the instant of transformers.
closing is varied, passing through that Table I also shows that sequential
instant which causes two winding cur switching in a three-phase transformer that winding, it follows that the winding
rents to be equal, the polarity of the maxi increases the inrush by about ten per having the greatest air-core reactance
mum peak line current will suddenly cent only for the wye-grounded primary should have the lowest inrush. For the
reverse as shown in this figure. with secondary either delta or wye. For single-phase miniature-system units, it
other connections, there is no increase was found that the inrush currents < ould
SEQUENTIAL SWITCHING due to sequential switching. be cut in half by energizing the winding
In three-phase switching it is possible For single-phase banks, the wye-con farthest from the core rather than the
and likely that all poles of the breaker do nected primary gives no increase due to winding nearest the core. Thus, other
not close at exactly the same instant. sequential switching for any condition things being equal, for concentric wind
In order to show what the maximum except when the secondary is delta-con ings, there is some practical merit in
possible inrush currents would be as nected. For this case an increase of energizing transformers on the high-
compared to those obtained for simul about ten per cent was observed. For the voltage side, since that winding, ordinarily
taneous closing for all possible trans delta-connected primary, the increase in being farthest from the core, will gener
former connections, Table I has been magnitude of inrush current was 50 per ally have an appreciably higher air-core
prepared. cent with the secondary either wye or reactance.
The results presented here show that delta.
based on normal line currents, the wye- In connection with Table I it should be Characteristics Affecting the
grounded transformer with delta second- pointed out that substantial reduction in Duration of Inrush Current
an- gives the highest inrush while the inrush-current magnitudes can be ob
lowest is obtained with the delta-con tained by energizing the winding farthest In the case of transformers connected
nected primary winding, with the second from the core. Since the absolute ceiling to systems having negligible source re
ary either wye or delta. This is true for on magnetizing inrush crest current is sistance, the transient inrush currents
either three-phase core-type transformers determined bv the air-core reactance of decay at a rate determined by the re
sistance of the transformers themselves.
Tests on representative power trans
1 1 1 1


formers, both single-phase and three-
^ , *, I
1 phase, indicate that for ratings in the
neighborhood of 1,000 kva, the crest
*
E tin wt
1! Figure 10. Effect of resistor
inrush current decays to approximately
^Ic 1 half its initial peak value in ten cycles.
V switching on inrush currents.
With larger transformers, the rate of de
1 Single-phase transformer. cay is slower, the inrush current some
Source voltage normal as de
times lasting a second or more in extreme
fined by curve A, Figure 1 2 .
cases. Conversely, smaller transformers
Residual of polarity to give
generally have higher rates of decay.
Ie! maximum inrush. Time lag is
interval between closing Sx The inrush current of a typical small
w R i>2JZ\

M R-2221 and St. For any given time distribution transformer, for example,
\ v V. R5&5X ! lag, the inrush given by these may be only approximately 20 per cent
|--> curves is the maximum possible of its initial crest value after ten cycles.
> 0 0 1250 MO 2C
TIME VU\_ (JEGREE!'
K> 2 iK> 3! 960 for the conditions specified Transformers having relatively high losses

I9
44 VOLUME 63 Blume, Camilli, Farnham, PetersonMagnetizing Inrush Currents 371
^ . __JL-"
A

0 200
TIMES NORMAL CREST EXCITING CURRENT

Figure 12. Saturation curves for miniature-


system transformers

Constants are for 6 0 cycles per second


A. Single-phase transformer. Base voltage
(normal) 100 volts rms. Magnetizing reac
tance x m = 15,000 ohms at 1 0 0 volts rms
B. Same as A but less abrupt saturation
C. Three-phase core-type transformer. Aver Figure 14. Hysteresis loop for modern silicon
age of three legs. Average magnetizing steel as used in typical power transformer
reactance, x m = 10,000 ohms at 100 volts rms.
Base voltage (normal) = 100 volts rms

it is apparent that if this resistance be


will in general have faster rates of decay comes so high as to limit appreciably the
than those which are more efficient. flow of normal magnetizing current it will
Resistance in the circuit between the again lose its effectiveness. The impor
transformer terminals and the source of tant conclusion to be drawn from this is
sustained voltage not only reduces the that breakers equipped with resistors
maximum initial inrush current that can useful in preventing switching over
be obtained but hastens its rate of decay voltages on opening may also be helpful
where only one transformer is involved in reducing inrush currents on closing.11
and aids in restoring normal voltage wave
shape more quickly. Source reactance MEANS OF REDUCING RESIDUAL FLUX
does not alter the rate of decay of inrush Since one of the factors tending to in
currents for practical cases. crease inrush currents is the residual
The effect of system resistance in Figure 13. Hysteresis loops for single-phase magnetism, it follows that any means ol
causing circulating magnetizing currents miniature-system transformers
reducing it would have some merit.
to flow when one transformer is energized Saturation curve A of Figure 1 2 . 25-ohm The possibility of mechanical jarring, for
oh the same bus with another which is resistor in series to give voltage d r o p for instance, was tried and found to have
already energized has been investigated. amplifier to oscillograph only slight effect.
The summary of that investigation is The possibility of using a capacitor con
60-Cycle
included in reference 10. Oscillosram Rms nection in parallel with the transformer to
Number Voltage
cause a damped oscillation to occur when
Means for Reducing Magnitude 94-1 110 the switch is opened has been suggested
94-3 102
of Inrush Currents 94-5 90 as a means for eliminating the residual.
Following the opening of the switch, the
SWITCHING WITH RESISTANCE oscillation theoretically should cause an
The use of resistance as an intermediate degrees the inrush current is approxi alternating current to flow in the trans
step in closing a switch to reduce the in mately cut in half for practical values of former winding decreasing in ampUtude
rush current was investigated with the resistance. For time intervals up to with time, thus gradually reducing the
miniature system. The results are shown about 200 electrical degrees, the value of area of the traversed hysteresis loop until,
in Figure 10. In these tests, the interval resistance (for reasonable values) is not when the current oscillation has died
between the instant of closing Si and the nearly so important as the time interval. away, no residual remains.
instant of closing S2 was varied through For greater values of time interval the Such an arrangement was tried, and
360 electrical degrees. For each value resistance is practically the sole deter results as shown in Figure 11 were ob
of this interval, the synchronous switch mining factor, although the magnitude tained. These results show that capaci
was adjusted to give the maximum in of inrush current is so low for any interval tors can eliminate the residual magne
rush for the particular value of resistance greater than 200 degrees that a wide tism and that there is a minimum size of
being used. Thus for the given trans range of resistance values will accomplish capacitor that can do this. Smaller
former, and for the resistance used, the the desired result. Thus, if the time capacitors cause the circuit to be more
curve shows the maximum peak inrush interval between closing Si and S2 is than critically damped rather than os
current that can be obtained, correspond 200 degrees or more, maximum inrush cillatory so that the current flowing in
ing to any interval between the closing currents can be reduced to half value th transformer due to the capacitor dis
of the switches. by using a resistor of ten per cent ohms charge just after the switch is opened does
It is significant that for relatively short on the transformer base. A higher re not oscillate at all. In fact, the amplitude
intervals on the order of 180 electrical sistance is even more effective, although of the current never reaches that re-

372 Blume, Catnilli, Farnham, PetersonMagnetizing Inrush Currents AIEE TRANSACTIONS


core is 7.0 ohms and of the winding far
\ \ r\ thest from the core, 24.0ohntsr Thesatura-

v v tion characteristic shown in Figure 12,


curve C, was obtained with the trans
former connected in delta, currents being
measured in the transformer windings
and not in the line. In the line, the
third harmonic and multiples thereof do
not flow. Consequently, the apparent
saturation is much less abrupt when line
currents are used.
quired to bring the residual to zero. Figure 15. Oscillogram showing inrush current For the single-phase transformers satu
However, as the capacitance is increased, transient in 833-kva single-phase transformer rating as in Figure 12, curve A, the
the crest current during discharge in Upper traceTransformer terminal voltage hysteresis loops are as shown in oscillo-
creases without oscillation until a value is Center traceTransformer current grams 94-1, 94-3, 94-5, Figure 13. For
reached which is just high enough to Lower traceSource voltage excitations of the order of 100 volts, the
eliminate the residual. This optimum hysteresis loop is such as to yield residual
value corresponds to capacitor kilovolt accordance with the foregoing results flux of the order of 50 to 60 per cent.
amperes of from 40 to 50 per cent of the could be of some practical value in par Thus, while the saturation characteristic
transformer magnetizing kilovolt- tially reducing transformer inrush cur appears to be similar to that of new silicon
amperes. rents. steels, the residual is somewhat less than
An increase in capacitance beyond this that associated with such steels. The
optimum value causes the crest current Miniature-System and Test Data residual in these units is more on the
during capacitor discharge to exceed that order of that for transformers using the
MINIATURE-SYSTEM TRANSFORMERS old types of sheet steel. However, this
required for eliminating the residual.
Thus, a residual of opposite polarity is The saturation curves for the minia does not invalidate the qualitative results
introduced and reaches a maximum when ture-system transformers are shown in obtained, although direct numerical
the capacitor kilovolt-amperes equal the Figure 12. These have Mumetal cores checks cannot be made in some cases.
transformer magnetizing kilovolt-am in order to give the desired abruptness of A hysteresis loop for typical modern-
peres. In this area, the discharge begins saturation. When operating at 100 volts power-transformer steel, indicating ap
to be oscillatory so that, as the capaci rms, the saturation characteristics cor proximately 80 per cent residual, is shown
tance is increased, the first oscillation respond very nearly to those of some of in Figure 14 for comparison.
of current due to discharge from the the" newer silicon strip steels when used
TESTS ON ACTUAL TRANSFORMERS
capacitor reverses the residual, but the at an assumed density of 100 kilolines
COMPARISON WITH CALCULATED VALUES
second oscillation reverses this. Con per square inch. At 100 volts, tiie ex
sequently, as the capacitance is increased, citing impedance of the single-phase units (a). Single-Phase Transformer. This
a value is reached which causes this is 15,000 ohms. Their leakage reactance unit was a 60-cycle core-type design
second oscillation to reduce the residual is 25 ohms at 60 cycles, and their average rated 833 kva. The core steel was of the
to zero. Further increase of capacitance d c resistance is* approximately 5.5 new high-permeability high-saturation
causes similar phenomena involving more ohms for the winding nearest the core type, and the unit was energized from a
reversals during discharge, which result and 11.0 ohms for the outside winding. 2,300-volt winding. The calculated peak
in a number of values of capacitance Curve A of Figure 12 is the saturation inrush current was 14 times peak full-
which can reduce the residual to zero. curve for these units while curve B is load current based on an assumed 75
Subsequent tests revealed that the for another transformer identical in per cent residual and a core saturation
effectiveness of the capacitor was rela every respect except for less abrupt flux of 130 kilolines per square inch.
tively unchanged by the amount of saturation.
residual in the practical range. This For the three-phase core-type units, Figure 16. Oscillogram showing inrush current
suggests that a capacitor selected in the resistance of the windings nearest the transients in three-phase 750-lcva transformer

C> 3 77/6 2 lr?ros6 G

ry r\ r\ r\ r\ r\ r\

's;. J\ I \ /\ A

1944, VOLUME 63 Blume, Camilli, Farnham, PetersonMagnetizing Inrush Currents 373


Figure 1 7 . Calcu and the slowest rate of decay. Although
lated inrush charac the maximum-crest inrush currents of the
teristics of single- several sizes of transformers tested
phase transformers
ranged from 11 to 20 times their normal
Excitation o n l o w - full-load crest currents, and the intervals
voltage side required for these transient currents to
decay to normal value extended from 33
to 120 cycles, it was found that for each
transformer tested the total Pt in it?
magnetizing inrush was numerically al
eooo eooo most the same as if ten times normal full
TRANSFORMER KVft
load current had been flowing for 0.1
The maximum measured inrush cur of the fusible element, very little being second. This leads to a rather simple
ent obtained in 30 trials was 11 times dissipated elsewhere during the short criterion for selecting fuses which will
the peak full-load current. The oscillo- interval involved. Hence, the following safely withstand transformer magnetiz
gram for this test is shown in Figure 15. equation may be written, applying to the ing inrush currents. When what ap
The switch was not closed exactly at fuse during the inrush period. pears to be a reasonable margin in ex
voltage zero but nearly enough to zero cess of the actual Pt in the transformer
so that the maximum inrush should not Pt~K inrush is allowed, it is suggested that
be appreciably greater, based on the fuses be selected on the basis that at the
where
earlier considerations in this paper. 0.1-second point on their characteristic
/=current in the fuse, in amperes curves, they be capable of carrying at
(b). Three-Phase Transformer. This / time in seconds least 12 times the transformer normal full
unit was a 50-cycle core-type water- A' = a constant, depending on the size and load current. It will be apparent by
cooled design rated 750 kva. It was ex material of the fusible element referring to the equation PtK that any
cited from its 3,000-volt windings which
The Pt of any given fuse may be deter other pair of corresponding figures be
were delta-connected. The calculated
mined from the manufacturer's published sides 12 and 0.1 could have been used.
inrush was 12.5 times peak-line full-load
characteristics, usually given in curve These values, however, have the ad
current based upon 75 per cent residual
form, and plotted on logarithmic co vantage of being round numbers which
and core saturation of 130 kilolines per
ordinates so that this portion is rep are easily remembered, and at the 0.1-
square inch. second point, most fuses adhere closely
The maximum inrush current obtained resented as a straight line. It is only
to the straight-line characteristic. Fuses
in 20 trials was 10.35 times peak-line full- necessary then to know the Pt corre
selected on the basis outlined may be
load current. This is shown in the os- sponding to the transformer magnetiz
expected to be amply large for the
cillograms of Figure 16. ing inrush current, in oder to select a
majority of applications, since it is un
(c). Generalized Calculated Values of fuse which will withstand it safely.
likely that actual inrush currents will be
Inrush Currents. A more comprehen While the /*/ representing the inrush for
as severe or prolonged as those obtained
sive summary of calculated inrush cur any specific transformer is of course a
under the carefully controlled test condi
rents is shown in Figures 17 and 18. function of both the magnitude of the
tions, and where the testing source was
This summary includes numerous de first current loop and the rate of decay,
so much larger than the transformer as
signs and is of help in showing the prac neither of which is usually known with
to be practically an infinite bus. Further
tical limits between which the maximum out a rather exhaustive study of the trans
more, the transformers tested were of a
inrush current will likely fall for various former and the system to which it is con
design that is considered fairly representa
voltage levels and for various kilovolt- nected, a series of tests has indicated
tive of modern transformer designs with
ampere sizes Generally, calculations that the total Pt of the inrush may be
regard to the severity of inrush current
tend to give too high a value as indicated approximated with sufficient accuracy to be expected.
by the foregoing examples. Conse for purposes of fuse application. In
quently, actual maximum values will these tests, for which the authors are
generally be slightly less than the values indebted to H. C. Stewart of the General Conclusions
indicated by these bands. In the afore Electric Company, oscillograms were
taken of the inrush currents of represen 1. The inrush currents associated with
mentioned test cases, part of the dis transformer energizing do not, in the vast
crepancy between calculated and test tative samples from a complete line of majority of cases, produce any system dis
results is attributable to the fact that transformers, under conditions designed turbances. This is true even for trans
generator source used in the test was not to produce the greatest inrush current formers utilizing the modern steels and de-
actually an infinite bus, while calcula
tions were based upon the source being
an infinite bus. These calculations also
indicate that for typical 25-cycle and 60-
cycle transformers, there is no appreciable
difference in the peak inrush currents.
Figure 18. Calcu
TBSTS TO DETERMINE HEAT GENERATED
lated inrush charac
IN FUSES DURING INRUSH PERIOD teristics of three-
Essentially all of the heat developed phase transformers
in a fuse during the transient inrush Excitation on l o w - Sboc
period goes into raising the temperature voltage side

374 Blume, Camilli, Farnham, PetersonMagnetizing Inrush Currents A I E E TRANSACTIONS

You might also like