AIR CIRCUIT BREAKERS

AIR CIRCUIT BREAKERS


Crompton Greaves LH Series Air Circuit Breakers employ the latest state of the art
technology and fully conform to IEC /Indian standards. The range extends from 200A to
4000A for AC & DC applications. The ACBs are designed for high degree of
standardisation in Panel building, total operator safety and economical maintenance.

1 Next Page
RANGE

SIZE II III IV V
RATINGS ( A) 200 1600 2500 4000
400 2000 3200
630
800
1000
1250
NO. OF POLES 3P / 4P 3P / 4P 3P / 4P 3P

Fixed Fixed Fixed Fixed


EXECUTION
Drawout Drawout Drawout Drawout

Manual Manual Manual Manual


MECANISM
Electrical Electrical Electrical Electrical
RELEASE Thermal Thermal Thermal Thermal
Magnetic Magnetic Magnetic Magnetic
STATIC STATIC STATIC

BREAKING
CAPACITY
50 KA 65KA 80A 80KA
lic = lcu AT 415V
AC 3 Ph

2 Back - Next Page


THERMAL MAGNETIC PROTECTION
OVERLOAD PROTECTION
Overload protection is provided through CT operated continuous, variable bimetallic overload
unit. By adjusting the CT tapsand varying the setting of overload unit, current setting can be
varied from approximately 25% to 100% ( For exact details, refer technical data sheet ).

SHORT CIRCUIT PROTECTION :

Short circuit protection is provided through an armature type direct acting magnetic release.
During short circuit fault, the armature is instantaneously attracted, in-turn tripping the ACB
through delatching of trip shaft. This design ensures faster tripping time (less than 2 cycles).
Short circuit pick up level is adjustable continuously by knobs provided on the front of the ACB.
For 4000A ACB trippping is through series trip coil & is fixed at 5 times the CT TAP set current.

TIME DELAYED SHORT CIRCUIT TRIP (OPTIONAL) :

To achive discrimination when used as an incomer, a time delayed S/C trip can be provided. This
consists of a S/C release fitted with microswitch and RS unit supplied separately. RS unit
provides the time delay and is available in two versions - with fixed time delay ( 0.04 sec. ) and
with adjustable time delay ( 0.04 to 0.46 sec. ) During fault, the S/C release operates the micro
switch activating the RS unit. The RS unit trips the ACB through the tripping coil after the set time
delay.

EARTH FAULT PROTECTION ( OPTIONAL) :

Earth Fault Protection is also offered as an optional feature. This protection is achieved through
Earth Fault ( E/F ) relay. The E/F relay senses the earth fault and gbives a trip command to the
ACB through shunt trip. The sensitivity of the E/F relay is adjustable between 10% and 40% of the
ACB rating. The E/F telay is available in both versions - 3 phase 3 wire and 3 phase 4 wire. As a
standard, LED trip indication is provided on the E/F relay.

FAULT ANALYZER :

LH series thermal magnitic ACBs upto 3200A are fitted with mechanical trip indications for
overload, phase to ground fault, two phase or two phase to ground fault and three Phase or three
Phase to ground fault. Electrical indication facility for O/L trip is also provided as standard.
Electrical indication facility for phase to ground fault, two phase or two phase to ground fault and
three phase or three phase to ground fault can be provided on request. LH 4000 ACBs are
provided with mechanical trip indications for overload, short circuit & ;facility for O/L trip
electrical indication as standard feature.
Electrical indication facility for AC under voltage trip is available on entire range of ACBs on
request.

STATIC PROTECTION
Air Circuit Breakers with static protection come with a Solid Protection Relay - The CSR. The relay
comes as an integral part of LH series ACBs from 200 Amp to 3200 Amp. and does not require any
external supply for tripping ACB during fault.

3 Back - Next Page


TYPES OF CSR RELAYS :

SPECIFICATION SUITABLE FOR PROTECTION REMARKS


SYSTEM O/L S/C E/F
TYPE
CSR I 3 Phi - 3W A A NA --
NCT & ICT supplied loose
CSR II 3 Phi- 4W A A A
with the Breaker.
ICT supplied loose with
CSR III 3 Phi - 3W A A A the
Breaker.

TECHNICAL SPECIFICATIONS :

Input Scaling (O/L Setting) In 0.5, 0.6, 0.7, 0.8, 0.9, & 1.0 times of rated currunt
S/C pick up level setting 2 In, 3 In, 4 In, 5 In, 6 In & 8 In
S/C time delay Inst., 0.2, 0.4, 0.6, 0.8, & 1.0 Sec
IDMT characterists' selection 4, 8, 12.5, 16, 21, & 25 seconds at 6 In.
Earth Fault ( E/F ) settings 0.2, 0.3, 0.4, 0.5, & 0.6 times In (max.)
E/F time delay Inst. 0.2 , 0.4, 0.6, 0.8 & 1.0 Sec.

4 Back - Next Page


TECHNICAL DATA : REFERENCE IS : 13947 ( PART - 2 ) : 947 2

FRAME 800 1000 1250 1600 2000 2500 3200 4000


SPECIFICATION
No of Poles 3 or 4 3 or 4 3 or 4 3
Rated enclosed Thermal Current (A) 800 1000 1250 1600 2000 2500 3200 4000
(DEGREE CENTIGRADE) 40 800 1000 1250 1600 2000 2500 3200 4000
45 800 1000 1250 1600 2000 2500 3200 4000
50 790 920 1140 1570 1850 2360 3000 3840
55 780 850 1050 1440 1700 2200 2730 3600
60 770 820 970 1330 1550 2020 2480 3500
65 760 800 900 1200 1400 1800 2200 3400
70

Rated Insulation Voltage (V) Ui 1000 1000 1000 1000


AC 1200 1200 1200 1200
DC

Rated S/C Breaking Capacities forAC


Ics (Service) & icu (Ultimate) at 415V 50 kA 65 kA 80 kA 80 kA
Power Factor Cos pie 0.25 0.20 0.20 0.20
Rated S/C Breaking Capacities for DC * 30 kA 38 kA 38 kA 38 kA
Ics (Service) & Icu (Ultimate) 220V 25 kA 33 kA 33 kA 33 kA
At L/R = 15 ms 440V
Rated Making Capacity (Peak) Icm AC 105 kA 143 kA 176 kA 176 kA
415V

Rated Short Time Withstand Current Icw 1 50 kA 60 kA 65 kA 65 kA


sec.

Total Making Time 30 ms 30 ms 30 ms 30 ms


Total Breking Time 38 ms 38 ms 40 ms 40 ms
Mechanical Life (No. of Ops.) 8000 6000 6000 5000
Electrical Life (No. of Ops) 3000 3000 1500 1500
MOTORISED MECHANISM ( AC / DC )
220 / 240 V 220 /240 V 220 / 240 V 220 / 240 V
Operating Voltage
40 W 40 W 40 W 40 W
Motor Power
0.8 A 0.8 A 0.8 A 0.8 A
Current
8 - 16 Sec. 8 -16 Sec. 8 -16 Sec. 8 -16 Sec.
Total Charging Time
SHUNT TRIP / CLOSING RELEASE
400 VA 400 VA 400 VA 400 VA
AC Inrush
250 W 250 W 250 W 250 W
DC Inrush
15 - 20 ms 15 - 20 ms 15 - 20 ms 15 - 20 ms
Opening Time Delay (ms)
UNDER VOLTAGE RELEASE
150/ ( 66 ) VA 150/ ( 66 ) VA 150/ ( 66 ) VA 150/ ( 66 ) VA
AC - Inrush / ( Hold on )
185 / ( 5.5 ) W 185 / ( 5.5 ) W 185 / ( 5.5 ) W 185 / ( 5.5 ) W
DC - Inrush / ( Hold on )
20 - 30 ms 20 - 30 ms 20 - 30 ms 20 - 30 ms
Opening Time Delay (ms)
* 3 POLES IN SERIES (ONLY WITH S/C PROTECTION UP TO 3200 A).

5 Back - Next Page


OVERLOAD / SHORT CIRCUIT SETTINGS : For ACB with Thermal Magnetic Protection

Magnetic Magnetic
O / L Range S / C Setting S/C
Frame CT Taps
(A) ( Standard ) ( Optional )
( kA ) ( kA )
LH 800 400 - 630 - 800/5 200 - 400 3-6-9 i) 1.2 - 2, 4 - 3.6
315 - 630 ii) 5 - 10 -15
400 - 800

400 - 800 i) 1.2 - 2, 4 - 3.6


LH 1000 800 - 1000/5 3-6-9
500 - 1000 ii) 5 - 10 -15
400 - 800
i) 1.2 - 2, 4 - 3.6
LH 1250 800 - 1000 - 1250/5 500 - 1000 3-6-9
ii) 5 - 10 -15
625 - 1250
625 - 1250 i) 3 - 6 - 9
LH 1600 1250 - 1600/5 5 - 10 - 15
800 - 1600 ii) 15 - 20 - 25
625 - 1250
1250 - 1600 - i) 3 - 6 - 9
LH 2000 800 - 1600 5 - 10 - 15
2000/5 ii) 15 - 20 - 25
1000 - 2000
1000 - 2000
LH 2500 2000 - 2500/5 5 - 10 - 15 i) 15 - 20 - 25
1250 - 2500
1000 - 2000
2000 - 2500 -
LH 3200 1250 - 2500 5 - 10 -15 i) 15 - 20 - 25
3000/5
1600 - 3200

1600 - 3200 5 times the


LH 4000 3200 - 4000/5 ----
2000 - 4000 C . T . Tap setting

6 Back - Next Page


Accessories
SHUNT TRIP :
Shunt trip is used for tripping the ACB , remotely or by external relays and in case of thermal
overload relay operation. Normal operating voltage band is 70% tp 110% WIDE VOLTAGE BAND
SHUNT TRIP ( 0 to 110% ) can also be provided as optional. Here shunt trip is fitted with RA unit.

UNDER VOLTAGE TRIP (OPTIONAL) :


Under Voltage trip is used for tripping the ACB during undervoltage, interlocking purposes and
tripping the ACB remotely. Normal operating range is from 85% to 110% of rated voltage with a
dropout voltage range of 35% to 70% TIME DELAYED UNDER VOLTAGE TRIP with a time delayed
tripping upto 0.5 seconds can also be provided as an optional feature. Here UVT is fitted with RC
unit.

AUXILLIARY SWITCHES :
ACBs are fitted with 4 N/O + 4 N/C auxiliary contacts as standard of which 3 N/O + 3 N/C potential
free contacts are available to customer for external wiring.

AUTOMATIC SAFETY SHUTTER (OPTIONAL) :


When ACB is drawn out to maintenance positin, the shutter assembly automatically drops down
and conceals the live main isolating contacts.

DOOR INTERLOCK WITH DEFEAT FACILITY (OPTIONAL) :


Door interlock can be provided to prevent opening of panel door woth ACB in SERVICE & TEST
position for Drawout ACB.
For Fixed type ACB, door interlock can be provided to prevent opening of panel door. When ACB
is switched 'ON', it is possible to defeat the interlock, if necessary.

SLIDING CONTACTS :
In case of drawout ACBs , two sliding contacts for each auxiliary switch are necessary. A
maximum of 30 ( single way ) sliding contacts can be provided per ACB.

CASTEL LOCK ( OPTIONAL) :


For interlocking two or more ACBs, Castel Lock can be fitted on the ACB on request.

7 Back - Next Page


LIST OF ACCESSORIES

STANDARD OPTIONAL
Shunt trip or U/V trip $ Shunt Trip
U/V trip
Potential free3 NO + 3 NC Aux switcheswith Closing release
sliding contact (for D/O ACB )
Closing release * RC Unit for Time delayed U/V trip ( upto 0.50 sec. )
Mech indication for ** RS relay for time delay ( 40 ms fixed ) of S/C trip ##
Service/Test/Isolated Position RS relay for time delay ( 40 - 460 ms ) of S/C trip ##

RA Unit for extending the voltage band ( 0% to 110% ) of shunt


Gasket for moulded escutcheon trip

* Only on Electrically operated ACB Shutter Assembly


** Only ib drawout ACB Micro Switch for s/c trip indication for thermal - magnetic ACB #
$$
ACCESSORIES Micro Switch for AC U/V trip indication
Rating (A) at voltage
240 V 415V AC Castel Lock
Auxiliary 15 A 15A
Door Interlock
Switch
Sliding Contact 10 A 6A Special sliding contacts for service/test position electrical
indication
Micro Switch
EFR for 3ph - 3 wire system
for S/C trip 10 A 5A
EFR for 3ph - 4 wire system
indication
Micro Switch
30 way sliding contats including the one used for internal
for AC UVT 10 A 5A
wireing of Shunt trip, closing release etc.
trip indication
$$ For non inductive loads

STANDARD RATING OF ACCESSORIES


24V 30V 48V 110V 220V 110V 240V 415V
VOLTAGE
DC DC DC DC DC AC AC AC
Shunt Trip A A A A A A A A
Wide Voltage
Band Shunt Trip A
( With RA Unit)
Under Voltage Trip A A A A A A A
Time Delayed UVT (With RC Unit of 220 VAC
A
( o.5 Sec. Time Delay )
Time Delayed S/C Trip for Th. Mag. ACB
(with RS Unit) * * * (40 - 460 ms) A A A A A A A A
Motor A A A A
Closing Release A A A A A A A A
EFR for Th. Mag. ACB A A

A : Available
* * * : Voltage rating of RS relay are available intwo versions. Time delay fixed at 40 ms.
(with 240 V AC Input Supply ) & Time delay variable in steps fron 40 - 460 ms.
# : Not available when fitted with RS relay. ## : Not applicable for ACBs with static release.
$ : Applicable for Thermal - Magnetic ACB. If nothing is specified then 415 VAC Shunt Trip is provided as
standard and if U/V is specified for ACB then shunt trip is optional.

8 Back - Next Page


TRIPPING CHARACTERISTICS

Thermal Magnetic

IDMT Characteristics IDMT Characteristics


for static release for static release
curves I1, I3 & I5 curves I2, I4 & I6

9 Back - Top Page