Product Description

Issue 05

Date 2013-08-15

HUAWEI TECHNOLOGIES CO., LTD.


Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com
Email: support@huawei.com

Huawei Proprietary and Confidential


Issue 05 (2013-08-15) i
Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description About This Document

About This Document

Overview
This document presents the exteriors and describes the functions, technical specifications,
application scenarios, structure, components, and cable connections of the APM30H (Ver.D).
It also describes the configurations, functions, and specifications of the modules and boards,
and details such as cable types, cable connections, and connector specifications.
APM30H is short for advanced power module with heat exchanger.

Product Version
Product Name Product Version
APM30H Ver.D (APM30H for short) V300R003C00

Intended Audience
Base station installation personnel
System engineers
Site maintenance personnel

Issue 05 (2013-08-15) Huawei Proprietary and Confidential ii


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description Contents

Contents

About This Document .................................................................................................................... ii


1 Cabinet Exterior .................................................................................................................................................. 4
2 Cabinet Engineering Specifications .................................................................................................................... 4
3 Engineering Specifications of Customer Equipment in the APM30H ................................................................ 8
4 Cabinet Application Scenarios .......................................................................................................................... 11
5 Cabinet Interior ................................................................................................................................................. 13
6 Components in an APM30H ............................................................................................................................. 16
6.1 EPU05A ................................................................................................................................................... 16
6.2 AC Junction Box ...................................................................................................................................... 33
6.3 FAN 02D .................................................................................................................................................. 35
6.4 ELU .......................................................................................................................................................... 36
6.5 Door Status Sensor ................................................................................................................................... 37
6.6 (Optional) Filler Module .......................................................................................................................... 38
6.7 (Optional) AC Heater ............................................................................................................................... 39
6.8 (Optional) SOU ........................................................................................................................................ 40
6.9 APM30H Cables ...................................................................................................................................... 41

Cable List ................................................................................................................................................. 41

Cable Connections ................................................................................................................................... 43


PGND Cable ............................................................................................................................................ 46

Equipotential Cable ................................................................................................................................. 48

Power Cables ........................................................................................................................................... 50

Signal Cables ........................................................................................................................................... 60

(2013-08-15) Huawei Proprietary and Confidential iii


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

1 Cabinet Exterior
The advanced power module with heat exchanger (APM30H) is used for Huawei wireless
products outdoors. It is small and easy to transport.
The following figure shows the exterior of the APM30H.

Figure 1 Exterior of the APM30H

2 Cabinet Engineering Specifications


This section describes the engineering specifications of the APM30H, including the power
specifications, equipment specifications, surge protection specifications, and environment
specifications.

Power Specifications
The APM30H supports the input power of 220 V AC single-phase, 220/380 V AC three-phase,
110 V AC dual-live-wire, 120 V AC dual-live-wire, and the output power of -48 V DC. When
AC power is used, the base station converts AC power into -48 V DC power.
The following table lists the AC input voltage range supported by the APM30H.

Table 1 AC input specifications

Power Rated Operating Rated Input Input


Supply Voltage Voltage Input Voltage Protection
Current Frequency
220 V AC 200 V AC to 176 V AC to 80 A 45 Hz to 65 Overvolt
single-phase 240 V AC 290 V AC Hz age
protectio
220/380 V 200/346 V 176/304 V 32 A n: The

(2013-08-15) Huawei Proprietary and Confidential 4


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Power Rated Operating Rated Input Input


Supply Voltage Voltage Input Voltage Protection
Current Frequency
AC AC to AC to system
three-phase 240/415 V 290/500 V generates
AC AC an alarm
when the
110 V AC 100/200 V 90/180 V 80 A input
dual-live-wir AC to AC to voltage
e 120/240 V 135/270 V exceeds
AC AC the AC
overvolta
120 V AC 120/208 V 105/176 V 80 A
ge alarm
dual-live-wir AC to AC to
threshold
e 127/220 V 150/260 V
(301 V
AC AC
by
default).
Undervol
tage
protectio
n: The
system
generates
an alarm
when the
input
voltage is
lower
than the
AC
undervolt
age alarm
threshold
(74 V by
default).

Heat consumption in the APM30H: 1500 W (heat dissipation capability at the ambient
temperature of 50oC or 122oF) (including the BBU, power system, and transmission
equipment)

Equipment Specifications
The following table lists the equipment specifications of the APM30H.

Table 2 Equipment specifications

Item Specifications Remarks


Dimensions (H x Cabinet (without the -
W x D) base): 700 mm x 600
mm x 480 mm (27.56
in. x 23.62 in. x 18.90

(2013-08-15) Huawei Proprietary and Confidential 5


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Item Specifications Remarks


in.)
Base: 200 mm x 600
mm x 434 mm (7.87
in. x 23.62 in. x 17.09
in.)
Space for the Configured with one The depth includes 280 mm (11.02 in.) away
customer BBU: 5 U x 19 in. x from the rear of the subrack mounting ears
equipment (H x 380 mm and 100 mm (3.94 in.) away from the front.
W x D) Configured with two
BBUs: 3U x 19 in. x
380 mm
Cabinet weight 68 kg (149.94 lb) Total weight of the equipment
Including the cabinet frame, inner air
circulation fan, outer air circulation fan,
core of the heat exchanger, EPU subrack,
and cables
Excluding the BBU, customer
transmission equipment, PMU, and PSUs
87 kg (191.84 lb) Weight with full configuration
Including the total weight of the
equipment, one PMU, five PSUs, and one
BBU
Excluding the customer transmission
equipment
Cabling and 70 mm (2.76 in.) -
maintenance
space at the front

Surge Protection Specifications


The following table lists the surge protection specifications of the APM30H.

Table 3 Surge protection specifications

Item Specifications
Surge protection for AC In differential mode:
input ports Rated through-current capacity (8/20 us): 30 kA
Maximum through-current capacity (8/20 us): 60 kA
In common mode:
Rated through-current capacity (8/20 us): 30 kA
Maximum through-current capacity (8/20 us): 60 kA
Surge protection for DC In differential mode (8/20 us): 10 kA

(2013-08-15) Huawei Proprietary and Confidential 6


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Item Specifications
output ports In common mode (8/20 us): 20 kA
The DC output corresponds to the secondary load.
NOTE
The surge protection capacity of the shield layer in an RRU power
cable is 40 kA.

Surge protection for signal E1/T1 port:


ports In differential mode (8/20 us): 3 kA
In common mode (8/20 us): 5 kA
FE port:
In differential mode (8/20 us): 3 kA
In common mode (8/20 us): 5 kA

Environment Specifications
The APM30H can be used outdoors. The following table lists the environment specifications
of the APM30H.

Table 4 Environment specifications

Item Specifications Remarks


Operating -40oC to +50oC (-40oF to A heater is required when the
temperatur +122oF)with solar radiation of temperature is lower than -20oC
e 112010% W/m2 (-4oF).
NOTE
The temperature at which the heater is
required is specified as the local average
lowest temperature of each day in the
coldest month of the year.

Relative 5% RH to 100% RH -
humidity
Altitude -60 m to +4000 m (-196.85 ft to From the altitude of 1800 m (5905.44
+13123.2 ft) ft), the maximum operating
temperature drops by 1oC (33.8oF)
each time the altitude increases by
220 m (721.78 ft).
Wind 67 m/s -
speed
Storage -40oC to +70oC (-40oF to +158oF) To avoid product degradation,
temperatur storage time should not exceed one
e year.
Dustproof IP55 -
and
waterproof

(2013-08-15) Huawei Proprietary and Confidential 7


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Item Specifications Remarks


Noise When the heat consumption of the -
cabinet is equal to or less than 700
W, noise specification meets the ETS
300 753 4.1E standard (rural area)
When the heat consumption of the -
cabinet is equal to 1500 W or
between 700 W and 1500 W, noise
specification meets the ETS 300 753
4.1E standard (urban area)

3 Engineering Specifications of Customer Equipment in


the APM30H
The customer equipment to be installed in Huawei cabinets must meet the requirements for
engineering specifications.
The following conditions must be met when the customer equipment is installed in the
following cabinets: APM30H (Ver.B)/APM30H (Ver.C)/APM30H (Ver.D)/APM30H
(Ver.D_B)/APM30H (Ver.D_A2)/APM30 (Ver.D_A1):
Dimension requirements
The dimension requirements are shown in Figure 2-3.
The width is 19 inch.
The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right is less than or equal to 280 mm (11.02 in.). The depth of
the customer equipment which supports heat dissipation from front to rear is less than
250 mm (9.84 in.).
The cabling space in front of the front panel is less than or equal to 100 mm (3.94
in.).
Heat dissipation requirements
If the customer equipment has built-in fans, the fans must dissipate heat out from left
to right or from front to rear.
If the customer equipment does not have built-in fans but uses natural ventilation, a
minimum of 1 U space must be reserved above and below the customer equipment to
ensure heat dissipation.
Temperature requirements
Temperature requirements for customer equipment are different in ordinary areas and
high-temperature areas. The following figure lists the detailed requirements.

Figure 2 Temperature requirements for the customer equipment

(2013-08-15) Huawei Proprietary and Confidential 8


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Ordinary areas and high-temperature areas are differentiated as follows:


Ordinary areas: The highest ambient temperature is equal to or less than 40oC.
High-temperature areas: The highest ambient temperature exceeds 40oC.
The following description illustrates the preceding figure using ordinary areas as an example.
Assuming that the operating temperature of the customer equipment is t, if -15oC t 60oC, the
customer equipment meets requirements; if the operating temperature is in a different range, for
example, -5oC t 60oC, the customer equipment does not meet requirements.

Figure 3 Dimension requirements and heat dissipation requirements

(1) Equipment using (2) Equipment dissipating heat (3) Equipment dissipating heat
natural ventilation out from left to right out from front to rear

(2013-08-15) Huawei Proprietary and Confidential 9


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

The customer equipment to be installed in the APM30, APM30H (Ver.A), TMC, or TMC11H
(Ver.A) must meet the following requirements:
Dimension requirements
The dimension requirements are shown in Figure 2-5.
The width is 19 inch.
The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right is less than or equal to 310 mm (12.20 in.). The depth of
the customer equipment which supports heat dissipation from front to rear is less than
280 mm (11.02 in.).
The cabling space in front of the front panel is less than or equal to 70 mm (2.76 in.).
Heat dissipation requirements
If the customer equipment has built-in fans, the fans must dissipate heat out from left
to right or from front to rear.
If the customer equipment does not have built-in fans but uses natural ventilation, a
minimum of 1 U space must be reserved above and below the customer equipment to
ensure heat dissipation.
Temperature requirements
Temperature requirements for customer equipment are different in ordinary areas and
high-temperature areas. The following figure lists the detailed requirements.

Figure 4 Temperature requirements for the customer equipment

Ordinary areas and high-temperature areas are differentiated as follows:


Ordinary areas: The highest ambient temperature is equal to or less than 40oC.
High-temperature areas: The highest ambient temperature exceeds 40oC.
The following description illustrates the preceding figure using ordinary areas as an example.
Assuming that the operating temperature of the customer equipment is t, if -15oC t 60oC, the
customer equipment meets requirements; if the operating temperature is in a different range, for
example, -5oC t 60oC, the customer equipment does not meet requirements.

(2013-08-15) Huawei Proprietary and Confidential 10


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Figure 5 Dimension requirements and heat dissipation requirements

(1) Equipment using (2) Equipment dissipating heat (3) Equipment dissipating heat
natural ventilation out from left to right out from front to rear

4 Cabinet Application Scenarios


The APM30H can apply to a distributed base station or a separated macro base station.

Distributed Base Stations Configured with an APM30H

Distributed or separated base stations configured with an IBBS200D and with an IBBS200T are the same
in scenarios configured with an APM30H. This section uses the IBBS200D as an example.

The following figure shows the distributed base station where an APM30H is stacked on a
battery cabinet.

Figure 6 Distributed base station where an APM30H is stacked on a battery cabinet

(2013-08-15) Huawei Proprietary and Confidential 11


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

In a distributed base station, an APM30H is configured as follows:


The APM30H provides 5 U space for transmission equipment and uses an embedded
power system to feed -48 V DC power into the distributed base station, transmission
equipment, and storage battery groups in the battery cabinet.
When the mains power supply is unavailable, storage battery groups feed -48 V DC
power into the distributed base station and transmission equipment.

Separated Macro Base Stations Configured with an APM30H


The following figure shows the separated macro base station configured with an APM30H.

Figure 7 Separated macro base station configured with an APM30H

(2013-08-15) Huawei Proprietary and Confidential 12


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

In a separated macro base station, an APM30H is configured as follows:


The APM30H provides 5 U space for transmission equipment and uses an embedded
power system to feed -48 V DC power into the BBU, RFUs, transmission equipment,
and storage battery groups in the battery cabinet.
When the mains power supply is unavailable, storage battery groups feed -48 V DC
power into the BBU, RFUs, and transmission equipment.
The APM30H reports alarms from the fans of the RFC, door status sensor, DCDU, and
battery cabinet.

5 Cabinet Interior
The APM30H supplies DC power to the distributed or separated macro base station in outdoor
scenarios. It provides space for both the BBU and transmission equipment. If an AC heater or
an SOU is not configured in the APM30H and one BBU is installed, 5 U space is provided for
the customer equipment.
The following figure shows the interior of the APM30H. The following figure uses an
APM30H in the separated macro base station as an example. For more details about the
interior of the APM30H in a distributed base station, see DBS3900 Hardware Description.

Figure 8 Interior of the APM30H

(2013-08-15) Huawei Proprietary and Confidential 13


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

The following table describes the components in the APM30H.

Table 5 Components in the APM30H

N Compone Op Ma Remarks
o. nt tio xim
nal um
or Qu
Ma anti
nd ty
ato in a
ry Sin
gle
Cab
inet
1 Outer air Ma 1 The assembly is installed on the front door, providing
circulation nda inner and outer air circulation and dissipating heat from
assembly tor the cabinet.
y
2 Junction Ma 1 The junction box converts one AC input to four AC
box nda outputs and is used in the scenario where a service outlet
tor unit (SOU) and multiple heating films or heaters are
y configured.
3 FAN 02D Ma 1 The fan assembly is configured with fans and central
nda monitoring unit type EA (CMUEA), dissipating heat
tor from the cabinet.
y

(2013-08-15) Huawei Proprietary and Confidential 14


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

N Compone Op Ma Remarks
o. nt tio xim
nal um
or Qu
Ma anti
nd ty
ato in a
ry Sin
gle
Cab
inet
4 SLPU Ma 1 To provide protection for trunk signals, a signal
nda lightning protection unit (SLPU) is mandatory and
tor installed in the top 1 U space of the cabinet. It is
y configured with the universal E1/T1 lightning
protection unit (UELP) or universal FE lightning
protection unit (UFLP).
To provide protection for monitoring signals, an
SLPU is optional and installed in the 1 U space below
the BBU. It is configured with two universal signal
lightning protection unit 2 (USLP2) boards.
5 Door status Ma 1 The door status sensor monitors the status (open or
sensor nda closed) of the cabinet door.
tor
y
6 ELU Ma 1 The electronic label unit (ELU) reports the cabinet type
nda automatically to facilitate troubleshooting.
tor
y
7 EPU05A Ma 1 The EPU converts AC input power to DC output power
nda and distributes the DC power to all the components in the
tor cabinet. The EPU consists of the EPU subrack, PMU,
y and PSUs.
8 BBU3900 Opt 2 A maximum of two BBU3900s can be configured in an
ion APM30H.
al The BBU3900 provides physical ports for
communication between the BBU3900 and the BSC
or RNC, and enables interaction between the base
station and the BSC or RNC.
The BBU3900 provides CPRI ports for
communication between the BBU and RF modules.
The BBU3900 processes uplink and downlink data.
9 EMUA Opt 1 The environment monitoring unit type A (EMUA)
ion monitors environment of the equipment.
al
10 Filler Ma 3 A filler module is a 1 U high plastic component, which
module nda prevents the heat reflux in the empty space below the
tor

(2013-08-15) Huawei Proprietary and Confidential 15


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

N Compone Op Ma Remarks
o. nt tio xim
nal um
or Qu
Ma anti
nd ty
ato in a
ry Sin
gle
Cab
inet
y BBU.
11 AC heater Opt 1 The AC heater ensures that components in the cabinet
ion work within the acceptable temperature range when the
al surrounding temperature is low. It can be installed in the
1 U space at the bottom of the cabinet. If both an AC
heater and an SOU are configured, the heater is installed
in the 1 U space above the SOU.
12 SOU Opt 1 The service outlet unit (SOU) transfers AC power supply
ion to the customer equipment. It can be installed in the 1 U
al space at the bottom of the cabinet.

6 Components in an APM30H
This section describes the mandatory and optional components in an APM30H.

6.1 EPU05A
An EPU05A converts AC power into DC power and distributes the power, it can be used in
APM30H(Ver.D), APM30H(Ver.D_A1), APM30H(Ver.D_A2), APM30H(Ver.D_B),
BTS3012(Ver.D_Z), BTS3012AE(Ver.D_Z), and IMS06. The EPU05A is classified into four
types: EPU05A-02, EPU05A-03, EPU05A-04, and EPU05A-05. An EPU05A-02 or
EPU05A-04 applies to a separated macro base station, and an EPU05A-03 or EPU05A-05
applies to a distributed base station.

Components of an EPU05A-02 or EPU05A-04


An EPU05A-02 or EPU05A-04 consists of an EPU05A-02 or EPU05A-04 subrack, a PMU
11A, and PSUs (R4850G2).
The following figure shows the components of an EPU05A-02 or EPU05A-04.

Figure 9 Components of an EPU05A-02 or EPU05A-04

(2013-08-15) Huawei Proprietary and Confidential 16


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) PMU (2) PSU (3) Filler (4) EPU05A-02 or EPU05A-04


11A (R4850G2) panel Subrack

The following table describes the components of an EPU05A-02 or EPU05A-04.

Table 6 Components of an EPU05A-02 or EPU05A-04

Module Description

PMU 11A It is installed in slot 0.


PSU (R4850G2) A minimum of two PSUs must be
configured. The PSUs must be installed in
adjacent slots in the sequence of slot 1 to
slot 5.
Filler panel A filler panel must be installed in a slot not
configured with a PSU (R4850G2).
EPU05A-02 or EPU05A-04 subrack Figure 2-9 shows how slots are numbered in
an EPU05A-02 or EPU05A-04 subrack.

Components of an EPU05A-03 or EPU05A-05


An EPU05A-03 or EPU05A-05 consists of an EPU05A-03 or EPU05A-05 subrack, a PMU
11A, and PSUs (R4850G2).
The following figure shows the components of the EPU05A-03 or EPU05A-05.

Figure 10 Components of the EPU05A-03 or EPU05A-05

(2013-08-15) Huawei Proprietary and Confidential 17


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) PMU (2) PSU (3) Filler (4) EPU05A-03 or EPU05A-05


11A (R4850G2) panel Subrack

The following table describes the components of the EPU05A-03 or EPU05A-05.

Table 7 Components of the EPU05A-03 or EPU05A-05

Module Description

PMU 11A It is installed in slot 0.


PSU (R4850G2) A minimum of two PSUs must be
configured. The PSUs must be installed in
adjacent slots sequentially from slot 1 to slot
5.
Filler panel A maximum of five PSUs can be configured
in the APM30H (Ver.D). Filler panels must
be installed in vacant slots.
EPU05A-03 or EPU05A-05 subrack Figure 2-10 shows how slots are numbered
in the EPU05A-03 or EPU05A-05 subrack.

EPU05A-02 or EPU05A-04 Subrack


An EPU05A-02 or EPU05A-04 subrack houses the PMU 11A and PSUs (R4850G2). It also
distributes AC input power and DC output power. An EPU05A-02 or EPU05A-04 applies to a
separated macro base station in different AC input scenarios.

Application of an EPU05A-02 or EPU05A-04 Subrack


The following table describes the application of an EPU05A-02 or EPU05A-04 subrack.

(2013-08-15) Huawei Proprietary and Confidential 18


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 8 Application of an EPU05A-02 or EPU05A-04 subrack

Type Application Description


Separated macro base station with It is a 5 U subrack and houses a
EPU05A-02
external 220 V AC input maximum of five PSUs (R4850G2)
Separated macro base station with and one PMU. It distributes large-
EPU05A-04 and small-capacity DC power.
external 110 V AC input

Exterior
Figure 2-11 and Figure 2-12 show the exteriors of EPU05A-02 and EPU05A-04 subracks,
respectively.

Figure 11 Exterior of an EPU05A-02 subrack

(1) AC surge (2) PSU1/4 circuit breaker, (3) AC OUTPUT (4) BAT circuit
protector PSU2/5 circuit breaker, and circuit breaker breaker
PSU3 circuit breaker
(5) Circuit (6) Circuit breaker for RFC2 (7) Output port for (8) RFC1 output
breaker for the storage battery port
RFC1
(9) RFC2 (10) LOAD0 to LOAD8 output (11) Spare fuse (12)
output port ports box Short-circuiting
bara
(13) AC (14) AC OUTPUT - -
INPUT

(2013-08-15) Huawei Proprietary and Confidential 19


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

a: When a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3
terminals, the EPU subrack supplies 220 V AC single-phase power. When the EPU subrack supplies 220
V AC three-phase power, the short-circuiting bar needs to be removed.

Figure 12 Exterior of an EPU05A-04 subrack

(1) AC surge (2) PSU circuit (3) AC OUTPUT1/AC (4) BAT


protector breaker OUTPUT2 circuit breaker circuit breaker
(5) Circuit (6) Circuit breaker (7) Output port for the storage (8) RFC1
breaker for RFC1 for RFC2 battery output port
(9) RFC2 output (10) LOAD0 to (11) Spare fuse box (12) AC
port LOAD8 output ports INPUT
(13) AC - - -
OUTPUT

Function
An EPU05A-02 or EPU05A-04 subrack distributes AC and DC power.
An EPU05A-02 or EPU05A-04 subrack performs the following AC power distribution
functions:
Provides two AC outputs. One is used for the service outlet unit (SOU). The other
one is connected to the AC junction box on the left of the cabinet, and divided into
four AC power outputs, which are then provided for the heater or heating film.
Reports AC input surge protection alarms.
An EPU05A-02 or EPU05A-04 subrack provides 12 DC outputs for a separated macro
base station.

(2013-08-15) Huawei Proprietary and Confidential 20


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Port
The following figure shows the power input and output ports on an EPU05A-02 or
EPU05A-04 subrack. Table 2-9 and Table 2-10 list the ports in detail.

Figure 13 Power input and output ports on an EPU05A-02 or EPU05A-04 subrack

Table 9 AC input and output ports on an EPU05A-02 or EPU05A-04 subrack


AC Input/Output Wiring Terminal Connector
Terminal

AC INPUT (EPU05A-02) L1, L2, L3, N OT terminal (M6)


AC INPUT (EPU05A-04) L1, L2, N, PE
AC OUTPUT L1, N1, L2, N2

Table 10 DC input and output ports and terminals on an EPU05A-02 or EPU05A-04 subrack

DC output DC Power Protector Protector Connector


ports Supply Unit Specification
LOAD0 and BBU Fusec 9x30 A EPC4 or EPC6
LOAD1
LOAD2 FAN
LOAD3 TM_0a
LOAD4 TM_1
LOAD5 TM_2 or
EMUA
LOAD6 TM_3 or BBU
LOAD7 TMC

(2013-08-15) Huawei Proprietary and Confidential 21


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

DC output DC Power Protector Protector Connector


ports Supply Unit Specification

LOAD8 IBBSb
RFC1 RFC1 Breaker 2x125 A OT terminal
(M6)
RFC2 RFC2
BAT BAT 1x250 A OT terminal
(M8)

a: TM is the customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are DC output
terminals for the transmission equipment, supporting four DC outputs.
b: When the IBBS200D is configured, LOAD8 is the DC output port for the IBBS200D fan power cable.
When IBBS200T is configured, LOAD8 is the DC output port for the IBBS200T TEC power cable.
c: The spare fuse box contains five 5 A fuses and three 30 A fuses for onsite replacement.

Circuit Breaker
There are several circuit breakers on the EPU05A-02 or EPU05A-04 subrack panel to control
the DC outputs. The following figure shows the positions of circuit breakers and the following
table describes the specifications of circuit breakers.

Figure 14 Circuit breakers on an EPU05A-02 or EPU05A-04 subrack

(2013-08-15) Huawei Proprietary and Confidential 22


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 11 Circuit breakers on an EPU05A-02 or EPU05A-04 subrack

Circuit Breaker Silkscreen on the Panel Requirement for the


Circuit Breaker
PSU circuit breakers PSU1/4 1x40 A/1 P
(EPU05A-02)
PSU2/5 1x40 A/1 P
PSU3 1x25 A/1 P
PSU circuit breakers PSU 1x100 A/2 P
(EPU05A-04)
AC output circuit breaker AC OUTPUT 1x16 A/2 P
(EPU05A-02)
AC output circuit breaker AC OUTPUT1 and AC 2x16 A/1 P
(EPU05A-04) OUTPUT2
Storage battery circuit BAT 1x125 A/2 P
breaker
RFC circuit breaker RFC 1 and RFC 2 2x125 A/1 P

Technical Specifications
The following table describes the technical specifications of an EPU05A-02 or EPU05A-04
subrack.

Table 12 Technical specifications of an EPU05A-02 or EPU05A-04 subrack

Component Specifications
Output voltage -44 V DC to -58 V DC
Rated voltage -53.5 V DC
Output current 0 A to 250 A

EPU05A-03 or EPU05A-05 Subrack


An EPU05A-03 or EPU05A-05 subrack houses the PMU 11A and PSUs (R4850G2). It also
distributes AC and DC power. The EPU05A-03 and EPU05A-05 subrack applies to a
distributed base station in different AC input scenarios.

Applications of an EPU05A-03 or EPU05A-05 Subrack


The following table describes the applications of an EPU05A-03 or EPU05A-05 subrack.

(2013-08-15) Huawei Proprietary and Confidential 23


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 13 Applications of the EPU05A-03 or EPU05A-05 subrack

Type Application Description


Distributed base station supplied It is a 5 U subrack and houses a
EPU05A-03
with 220 V AC power maximum of five PSUs (R4850G2)
and one PMU 11A. It distributes
Distributed base station supplied large- and small-capacity DC
EPU05A-05
with 110 V AC power power.

Exteriors
Figure 2-15 and Figure 2-16 show the exteriors of the EPU05A-03 and EPU05A-05 subracks,
respectively.

Figure 15 Exterior of the EPU05A-03 subrack

(1) AC surge (2) PSU1/4 circuit (3) AC OUTPUT (4) BAT circuit
protector breaker, PSU2/5 circuit circuit breaker breaker
breaker, and PSU3 circuit
breaker
(5) Circuit (6) Output terminal for (7) Output terminal (8) Output
breaker for RFC 1 storage batteries for RFC 1 terminals for
LOAD 0 to
LOAD 8
(9) Output (10) Spare fuse box (11) (12) AC INPUT
terminals for Short-circuiting
RRU 0 to RRU 5 bara
(13) AC - - -

(2013-08-15) Huawei Proprietary and Confidential 24


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

OUTPUT

a: When a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3
terminals, the EPU subrack supports 220 V AC single-phase power. When the EPU subrack supports 220
V AC three-phase power, the short-circuiting bar needs to be removed.

Figure 16 Exterior of the EPU05A-05 subrack

(1) AC surge (2) PSU circuit (3) AC OUTPUT 1 or (4) BAT circuit
protector breaker AC OUTPUT 2 circuit breaker
breaker
(5) Circuit breaker (6) Output (7) Output terminal for (8) LOAD 0 to
for RFC 1 terminal for RFC 1 LOAD 8 output
storage batteries terminals
(9) Output (10) Spare fuse (11) AC INPUT (12) AC OUTPUT
terminals for RRU box
0 to RRU 5

Function
An EPU05A-03 or EPU05A-05 distributes AC and DC power.
An EPU05A-03 or EPU05A-05 subrack performs the following AC power distribution
functions:
Provides two AC outputs. One is used for the service outlet unit (SOU). The other
one is connected to the junction box on the left side of the cabinet interior, and
divided into four AC power outputs, which are then provided to the heater or heating
film.

(2013-08-15) Huawei Proprietary and Confidential 25


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Reports AC input surge protection alarms.


An EPU05A-03 or EPU05A-05 subrack provides 17 DC outputs for a distributed base
station.

Terminals
The following figure shows the power input and output terminals on the EPU05A-03 or
EPU05A-05 subrack, as shown in Table 2-14, Table 2-15.

Figure 17 Power input and output terminals on the EPU05A-03 or EPU05A-05 subrack

Table 14 AC input and output terminals on the EPU05A-03 or EPU05A-05 subrack

AC Input/Output Wiring Terminal Connector


Terminal

AC INPUT (EPU05A-03) L1, L2, L3, N OT terminal (M6)


AC INPUT (EPU05A-05) L1, L2, N, PE
AC OUTPUT L1, N1, L2, N2

Table 15 DC input and output terminals on the EPU05A-03 or EPU05A-05 subrack


DC Output DC Power Protector Protector Connector
Terminal Supply Unit Specification
LOAD 0 and BBU Fusec 15x30 A EPC 4 or EPC 6
LOAD 1

(2013-08-15) Huawei Proprietary and Confidential 26


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

DC Output DC Power Protector Protector Connector


Terminal Supply Unit Specification

LOAD 2 FAN
LOAD 3 TM_0a
LOAD 4 TM_1
LOAD 5 TM_2 or EMUA
LOAD 6 TM_3 or BBU
LOAD 7 TMC
LOAD 8 IBBSb
RRU 0 to RRU EPC 5
RRU 5
RFC 1 RFC Breaker 1x125 A OT terminal (M6)
BAT BAT 1x250 A OT terminal (M8)

a: TM is the customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are DC output
terminals for the transmission equipment, supporting four DC outputs.
b: When the IBBS200D is configured, LOAD8 is the DC output terminal connecting to the IBBS200D fan
power cable. When IBBS200T is configured, LOAD8 is the DC output terminal connecting to the
IBBS200T TEC power cable.
c: The spare fuse box can provide five 5 A fuses and three 30 A fuses, which can be used to replace broken
ones onsite.

Circuit Breakers
There are several circuit breakers on the EPU05A-03 or EPU05A-05 subrack panel to control
the DC outputs. The following figure shows the positions of the circuit breakers and the
following table describes the specifications of the circuit breakers.

Figure 18 Circuit breakers on the EPU05A-03 or EPU05A-05 subrack

(2013-08-15) Huawei Proprietary and Confidential 27


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 16 Specifications of the circuit breakers on the EPU05A-03 or EPU05A-05 subrack

Circuit Breaker Silkscreen Requirement for the


Circuit Breaker
PSU circuit breakers PSU1/4 1x40 A/1 P
(EPU05A-03)
PSU2/5 1x40 A/1 P
PSU3 1x25 A/1 P
PSU circuit breaker PSU 1x100 A/2 P
(EPU05A-05)
AC output circuit breaker AC OUTPUT 1x16 A/2 P
(EPU05A-03)
AC output circuit breakers AC OUTPUT1 and AC 2x16 A/1 P
(EPU05A-05) OUTPUT2
Circuit breaker for storage BAT 1x125 A/2 P
batteries
RFC circuit breaker RFC1 1x125 A/1 P

(2013-08-15) Huawei Proprietary and Confidential 28


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Technical Specifications
The following table describes the technical specifications of the EPU05A-03 or EPU05A-05
subrack.

Table 17 Technical specifications of the EPU05A-03 or EPU05A-05 subrack

Component Specifications
Output voltage -44 V DC to -58 V DC
Rated voltage -53.5 V DC
Output current 0 A to 250 A

PMU 11A
A power monitoring unit 11A (PMU 11A) manages the power system and battery, monitors
power distribution, and reports alarms. It can be used in BTS3900(Ver.D), BTS3900L(Ver.D),
BTS3900AL(Ver.A), OMB(Ver.C), BTS3900(Ver.D_A), BTS3900(Ver.D_B),
APM30H(Ver.D), APM30H(Ver.D_A1), APM30H(Ver.D_A2), APM30H(Ver.D_B),
BTS3012(Ver.D_Z), BTS3012AE(Ver.D_Z) cabinets and IMS06 subrack.

Exterior
The following figure shows the exterior of a PMU 11A.

Figure 19 Exterior of a PMU 11A

Function
A PMU 11A performs the following functions:
Communicates with the upper-level device through an RS485 port.
Manages the power system and the charge and discharge of storage batteries.
Monitors the door status and the temperature of storage batteries.
Monitors power distribution and reports alarms.

(2013-08-15) Huawei Proprietary and Confidential 29


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Communicates with the battery cabinet through an RS485 port.

Port
The following figure shows the ports on a PMU 11A.

Figure 20 Ports on a PMU 11A

The following table describes the ports on a PMU 11A.

Table 18 Ports on a PMU 11A

No. Silkscreen Connector Description


1 GATE 2-pin connector Connects to a door status sensor.
2 TEM_BAT 2-pin connector Connects to a battery temperature sensor.
3 COM_IN RJ45 connector Connects to the BBU or communicates
with the upper-level monitoring board.
4 COM_OUT RJ45 connector Communicates with the lower-level
monitoring board.
5 COM_485 RJ45 connector Connects to the monitoring board in the
battery cabinet, and receives monitoring
signals from the battery cabinet.

Indicator
The following table describes the indicators on a PMU 11A.

Table 19 Indicators on a PMU 11A

Silksc Meanin Color State Description


reen g
RUN Running Green Steady on The module is performing startup,
indicator self-check, loading, and activation.
Blinking (on for The PMU 11A is functional and
1s and off for communicating with the main control
1s) board in the BBU properly. (This status

(2013-08-15) Huawei Proprietary and Confidential 30


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Silksc Meanin Color State Description


reen g
does not necessarily mean that the PMU
11A has been configured.)
Blinking (on for The PMU 11A is functional but unable
0.125s and off to communicate properly.
for 0.125s)
Steady off The module is faulty or there is no DC
power supply.
ALM Alarm Red Steady on Alarms are generated, and the module
indicator must be replaced.
Steady off No alarm is generated.
Blinking (on for An alarm is generated and you need to
1s and off for locate the fault before determining
1s) whether to replace the module.

DIP Switch
There is a DIP switch on the left panel of the PMU 11A. The DIP switch has eight bits, where
the four least significant bits 1, 2, 3, and 4 define the monitoring address of the PMU 11A,
and the four most significant bits 5, 6, 7, and 8 are not defined but reserved for future use.
ON is indicated by 1, and OFF is indicated by 0. The monitoring address of the PMU 11A is
set to 3 by default before delivery, as shown in the following figure.

Figure 21 DIP switch on the left panel of the PMU 11A

At a site configured with two or more APM30Hs, if two PMU units are connected to one RS485 bus for
the BBU, the monitoring address of the other PMU is set to 4. That is, the lower four bits of the DIP switch
are set to 0010.

PSU (R4850G2)
A power supply unit (PSU) (R4850G2) converts 110 V AC or 220 V AC power into -48 V DC.
It can be used in BTS3900(Ver.D), BTS3900L(Ver.D), BTS3900AL(Ver.A), OMB(Ver.C),

(2013-08-15) Huawei Proprietary and Confidential 31


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

BTS3900(Ver.D_A), BTS3900(Ver.D_B), APM30H(Ver.D), APM30H(Ver.D_A1),


APM30H(Ver.D_A2), APM30H(Ver.D_B), BTS3012(Ver.D_Z), BTS3012AE(Ver.D_Z)
cabinets and IMS06 subrack.

Exterior
The following figure shows the exterior of a PSU (R4850G2).

Figure 22 Exterior of a PSU (R4850G2)

Function
A PSU (R4850G2) performs the following functions:
Converts 110 V AC or 220 V AC power into -48 V DC and adjusts the output voltage.
Provides protection against overcurrent, overvoltage, and overtemperature for its DC
outputs.
Dissipates heat using its built-in fans.

Indicator
The following figure shows the indicators on a PSU (R4850G2).

Figure 23 Indicators on a PSU (R4850G2)

The following table describes the indicators on a PSU (R4850G2).

(2013-08-15) Huawei Proprietary and Confidential 32


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 20 Indicators on a PSU (R4850G2)

Silkscree Color State Description


n
(1) Power Green Steady on The board is functional.
indicator
Blinking (on for The PSU is loading software online.
0.125s and off for
0.125s)
Steady off The mains supply or the module is faulty.
(2) Yello Steady off Normal
Protection w
indicator Steady on An alarm triggered by an external factor
is generated.
Blinking (on for 1s The communication between the module
and off for 1s) and the PMU is interrupted.
(3) Fault Red Steady off Normal
indicator
Steady on The module is faulty or is shut down in an
emergency. Locate the fault and replace
the module.

6.2 AC Junction Box


When a heater or a heating film is configured, the AC Junction Box feeds power to the heater
or the heating film. It is used in the BTS3900AL, APM30H, TMC11H, IBBS700D, and
IBBS700T cabinets.

Exterior
An AC Junction Box is installed on the left inner side of the APM30H, TMC11H, IBBS700D,
or IBBS700T. In the BTS3900AL, the AC Junction Box is installed on the right inner side of
the cabinet. The following figure shows the position and exterior of the AC Junction Box in
the APM30H.

Figure 24 Exterior of the AC Junction Box

(2013-08-15) Huawei Proprietary and Confidential 33


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Functions
The AC Junction Box used in the BTS3900AL, APM30H, TMC11H, IBBS700D and
IBBS700T performs the following functions:
The PDU05A-01 feeds power to the AC Junction Box in the BTS3900AL. The power is
divided into four AC power outputs, which are then provided for the heater in the
cabinet.
The EPU subrack feeds power into the AC Junction Box in the APM30H. The power is
divided into four AC power outputs, which are then provided for the heater in the cabinet
or heating film in the IBBS200D.
The AC Junction Box in the APM30H feeds power into the AC Junction Box in the
TMC11H. The power is divided into four AC power outputs, which are then provided for
the heater or service outlet unit (SOU) in the cabinet.
The AC Junction Box in the primary cabinet (APM30H, BTS3900AL, or
TP48600A-H17B1) feeds power into the AC Junction Box in the IBBS700D or
IBBS700T. The power is divided into four AC power outputs, which are then provided
for the heater in the cabinet.

Interior
The following figure shows the interior of an AC Junction Box.

Figure 25 Interior of an AC junction box

(2013-08-15) Huawei Proprietary and Confidential 34


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) Four AC output L (2) Four AC output N (3) Four AC output PE


wiring terminals wiring terminals wiring terminals
(4) Cable holes (5) AC input N wiring (6) AC input L wiring
terminal terminal

6.3 FAN 02D


A FAN 02C dissipates heat and detects temperature. It can be used in an APM30H(Ver.D),
APM30H(Ver.D_B), APM30H(Ver.D_A2), APM30H(Ver.D_A1), TMC11H(Ver.D),
TMC11H(Ver.D_B), TMC11H(Ver.D_A2), TMC11H(Ver.D_A1).

Exterior
A FAN 02D consists of the fan subrack, fans, and CMUEA. The following figure shows the
exterior of a FAN 02D.

Figure 26 Exterior of a FAN 02D

(1) Fan subrack (2) Fans (3) CMUEA

For details about the ports and indicators on the CMUEA, see CMUEA.

(2013-08-15) Huawei Proprietary and Confidential 35


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

6.4 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting. ELU can be used in BTS3900, BTS3900L, APM30H series, and
IBBS700D/IBBS700T cabinets.

Exterior
The following figure shows the exterior of an ELU.

Figure 27 Exterior of an ELU

(1) Shell (2) RJ45 port

The ELU in a BTS3900 or BTS3900L cabinet has no shell.

Installation Position

Figure 28 Position of the ELU in an APM30H cabinet

(2013-08-15) Huawei Proprietary and Confidential 36


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

An ELU is located on the right inner wall of the APM30H, TMC11H, or RFC, or on the left inner wall of
the IBBS200D or IBBS200T. The preceding figure shows an APM30H and an IBBS200D as an example.

6.5 Door Status Sensor


A door status sensor reports the status (open or closed) of a door. It can be used in any of the
following cabinets: BTS3900AL(Ver.A), OMB, OMB (Ver.C), APM30H, RFC, TMC11H,
IBBS200D, IBBS200T, IBBS700D, and IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the
exteriors of them.

Figure 29 Exterior of the magnet of a door status sensor

(1) Magnetic shell (2) Magnet

(2013-08-15) Huawei Proprietary and Confidential 37


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

The following figure shows the exterior of the switch of a door status sensor.

Figure 30 Exterior of the switch of a door status sensor

Installation Position
A door status sensor is installed at the same position in the BTS3900AL (Ver.A), IBBS700D,
and IBBS700T. The following figure uses the BTS3900AL (Ver.A) as an example.

Figure 31 Position of a door status sensor in the APM30H (Ver.D)

6.6 (Optional) Filler Module


A filler module is a standard plastic component, which prevents heat reflux in the empty space
below the BBU and improves the heat dissipation in the cabinet. Filler modules can be
installed in the customer space of an APM30H(Ver.B), APM30H(Ver.C), TMC11H(Ver.B),
TMC11H(Ver.C), BTS3012AE(Ver.D_Z).

Exterior
A filler module is 1 U high. The following figure shows the exterior of a filler module.

(2013-08-15) Huawei Proprietary and Confidential 38


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Figure 32 Exterior of a filler module

Function
A filler module is installed in the customer space below the BBU to prevent heat reflux in the
empty space below the BBU.

In an APM30H, TMC11H, BTS3012AE(Ver.D_Z)the filler module is configured in the customer space by


default. Before installing other modules, first remove the filler module. For details about removing a filler
module, see chapter "Installing Optional Modules and Cables" in the "Installation Guide".

6.7 (Optional) AC Heater


An AC heater ensures that the customer equipment in a cabinet works within the acceptable
temperature range. It is optionally installed in the customer space in an APM30H or
TMC11H.

Exterior
An AC heater is 1 U high. The following figure shows the exterior of an AC heater.

Figure 33 Exterior of an AC heater

Technical Specifications
The following table lists the technical specifications of an AC heater.

Table 21 Technical specifications of an AC heater

Counter Specification
The temperature of the AC heater starts < 1oC (6oC)
working
The temperature of the AC heater stops > 15oC (3oC)
working

(2013-08-15) Huawei Proprietary and Confidential 39


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Counter Specification
Rated heating power 330 W

6.8 (Optional) SOU


A service outlet unit (SOU) transfers AC power to the customer equipment. An SOU is
optionally installed in the customer space in an APM30H.

Exterior
An SOU is 1 U high. The following figure shows the exterior of an SOU.

Figure 34 Exterior of an SOU

(1) Input power port (2) Breaker (3) Socket (European standard)

An SOU applies to the four types of sockets meeting the following standards: North American
standard, European standard, Universal standard, and British standard. The following figure
shows the exteriors of the four types of sockets.

Figure 35 Exteriors of different types of sockets

(1) North American (2) European (3) Universal (4) British


standard standard standard standard

Technical Specifications
The following table lists the technical specifications of an SOU.

(2013-08-15) Huawei Proprietary and Confidential 40


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 22 Technical specifications of an SOU

Counter Specification
Dimensions (H x W x D) 482.6 mm x 91 mm x 55 mm (7.87 in. x
23.62 in. x 17.09 in.)
Weight 1.5 kg (3.31 lb)
Input voltage range 200 V AC to 240 V AC
Maximum input current 10 A
Output voltage range 200 V AC to 240 V AC
Maximum output current 10 A
Frequency band 50 Hz or 60 Hz
Operating temperature -40oC to +55oC
Altitude 4,000m
NOTE
Above the altitude of 3000 m (9842.52 ft), the
maximum operating temperature drops by 1oC
(33.8oF) as the altitude increases by 100 m
(328.08 ft).

Protection class IP20

6.9 APM30H Cables


The APM30H cables consist of the power cables, equipotential cables, PGND cables, and
signal cables.

Cable List
APM30H cables mainly consist of the PGND cables, equipotential cables, power cables, and
signal cables.

Power Cables, PGND Cables, and Equipotential Cables


The following table lists the power cables, PGND cables, and equipotential cables.

Table 23 Power cables, PGND cables, and equipotential cables

Classif Cable One End The Other End


ication
Connector Installation Connector Installation
Position Position
Cables BTS3900A OT terminal L and N Depending External
to be DBS3900 terminals on on external power
installe the AC power equipment
d onsite INPUT equipment
terminal

(2013-08-15) Huawei Proprietary and Confidential 41


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Classif Cable One End The Other End


ication
Connector Installation Connector Installation
Position Position
block on the
EPU
2.7.3 PGND OT terminal Ground bar in OT terminal Ground
Cable the APM30H busbar outside
the cabinet
2.7.4 OT terminal Ground bar in OT terminal Ground bar in
Equipotential the APM30H the lower
Cable cabinet
DCDU-12B OT terminal RFC1 output OT terminal RTN(+) and
Power Cable port on the NEG(-)
EPU in the terminals on
APM30H the INPUT
terminal block
on the
DCDU-12B
Cables FAN 02D EPC4 or LOAD5 port 3V3 PWR port on
installe Power Cables EPC6 on the EPU in connector the fan
d connector the APM30H assembly in
before the APM30H
deliver
y AC Heater OT terminal L0 and N0 C13 Input power
Power Cables terminals on connector port on the
(in the the AC AC heater
APM30H) junction box
in the
APM30H and
the cabinet
ground bar
SOU Power OT terminal M4 ground C13 INPUT port
Cables screw, L2 connector on the SOU
terminal, and
N2 terminal
on the AC
OUTPUT
terminal
block on the
EPU
Power Cables OT terminal M4 ground OT terminal L and N
for an AC screw, L1 terminals on
Junction Box terminal, and the AC
(in the N1 terminal junction box
APM30H) on the AC in the
OUTPUT APM30H and
terminal the cabinet
block on the ground bar
EPU

(2013-08-15) Huawei Proprietary and Confidential 42


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

The connection of power cables for optional components depends on the delivery mode. Table 2-23
describes the power cables in a macro base station.

Signal Cables
The following table describes the signal cables.

Table 24 Signal cables


Classi Cable One End The Other End
ficati
on Connecto Installation Connect Installation
r Position or Position
Cables - - - - -
to be
install
ed
onsite
Cables PMU RJ45 COM_IN port on RJ45 COM_OUT port
install 11A-CMUE connector the PMU connector on the CMUEA on
ed A the fan assembly in
before Monitoring the APM30H
deliver Signal
y Cable
ELU Signal RJ45 ELU RJ45 ELU port on the
Cable connector connector CMUEA
Monitoring 2-pin GATE port on the Bare wire Door status sensor
Signal connector PMU
Cable for
the Door
Status
Sensor
Monitoring Interconne Transfer terminal 4-pin FAN_EXT port on
Signal ction on the front door connector the CMUEA
Transfer terminal of the APM30H
Cable for
the Fan in
the Front
Door

Cable Connections
This section describes the principles for connecting power cables and signal cables in the
APM30H.

(2013-08-15) Huawei Proprietary and Confidential 43


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Power Cable Connections


This section describes the power cable connections in the APM30H.

Cable Connections in a Distributed Base Station


The following figure shows the APM30H power cable connections in a distributed base
station.

Figure 36 Power cable connections in a distributed base station

(1) Power Cables for an AC (2) FAN 02D Power (3) Storage Battery Power
Junction Box Cables Cables
(4) DCDU-12B Power Cable (5) SOU Power Cables (6) AC Heater Power
Cables

Cable Connections in a Separated Macro Base Station


The following figure shows the APM30H power cable connections in a separated macro base
station.

Figure 37 Power cable connections in a separated macro base station

(2013-08-15) Huawei Proprietary and Confidential 44


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) Power Cables for an AC (2) FAN 02D Power Cables (3) Storage Battery
Junction Box Power Cables
(4) Power Cables for the DC (5) Power Cables for the DC (6) SOU Power
Junction Box in an RFC Junction Box in an RFC Cables
(7) AC Heater Power Cables - -

Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables.
The following figure shows the monitoring signal cable connections in the APM30H.

Figure 38 Monitoring signal cable connections in the APM30H

(1) Monitoring signal cable for the fans (2) Monitoring signal transfer cable for the fans
on the front door on the front door

(2013-08-15) Huawei Proprietary and Confidential 45


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(3) PMU-CMUEA monitoring signal (4) Monitoring signal cable for the door status
cable sensor in the APM30H
(5) ELU signal cable -

PGND Cable
PGND cables ensure that cabinets and internal components are properly grounded and that
base stations run properly. PGND cables include classified into PGND cables for cabinets and
PGND cables for components.

Exterior
The following figure shows the exterior of a PGND cable.

Figure 39 Exterior of a PGND cable

(1) One-hole OT terminal (2) Two-hole OT terminal

In most cases, the PGND cable is a yellow and green colored cable. When 110 V dual-live-wire power is
supplied for BTS3900A (Ver.C) and BTS3900A (Ver.D) cabinets, the PGND cables are green.

Description
The cross-sectional areas and maximum lengths of PGND cables vary according to the types
of cabinets. Table 2-25 and Table 2-26 describe PGND cables.

(2013-08-15) Huawei Proprietary and Confidential 46


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 25 PGND cables for cabinets

Base Station Cabinet Maximum Cross- Connect Exterior


Type Length Section or
al Area
BTS3900A RFC (Ver.B) 8 m (26.25 16 mm2 One-hole The exterior
(Ver.B) ft) (0.025 OT is shown by
in.2) terminal illustration
(M6) 1 in the
preceding
figure.
BTS3900A RFC (Ver.C) 8 m (26.25 25 mm2 One-hole The exterior
(Ver.C) ft) (0.039 OT is shown by
in.2) terminal illustration
(M6) 1 in the
preceding
figure.
BTS3900A RFC (Ver.D) 8 m (26.25 16 mm2 One-hole The exterior
(Ver.D) ft) (0.025 OT is shown by
in.2) terminal illustration
(M6) 1 in the
preceding
figure.
IBBS700D and 5 m (16.4 35 mm2 The The exterior
IBBS700T ft) (0.054 cable has is shown by
in.2) a illustration
one-hole 1 in the
OT preceding
terminal figure.
(M6) on
the
cabinet
side and
a
one-hole
OT
terminal
(M8) on
the
ground
bar side.
DBS3900 APM30H 8 m (26.25 16 mm2 One-hole The exterior
(Ver.B) series ft) (0.025 OT is shown by
cabinets in.2) terminal illustration
(M6) 1 in the
preceding
figure.
APM30H 8 m (26.25 25 mm2 One-hole The exterior
(Ver.C) series ft) (0.039 OT is shown by
cabinets in.2) terminal illustration
(M6) 1 in the

(2013-08-15) Huawei Proprietary and Confidential 47


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Base Station Cabinet Maximum Cross- Connect Exterior


Type Length Section or
al Area
preceding
figure.
APM30H 8 m (26.25 16 mm2 One-hole The exterior
(Ver.D) series ft) (0.025 OT is shown by
cabinets in.2) terminal illustration
(M6) 1 in the
preceding
figure.

Table 26 PGND cables for components

Base Station Cabinet Maximum Cross-S Connect Exterior


Type Length ectional or
Area
BTS3900 (Ver.B) BTS3900 (Ver.B) 15 m (49.21 6 mm2 One-hole The
and BTS3900L and BTS3900L ft) (0.009 OT exterior
(Ver.B) (Ver.B) in.2) terminal is shown
BTS3900 (Ver.C) BTS3900 (Ver.C) (M4) by
and BTS3900L and BTS3900L illustratio
(Ver.C) (Ver.C) n 1 in the
preceding
BTS3900 (Ver.D) BTS3900 (Ver.D) figure.
and BTS3900L and BTS3900L
(Ver.D) (Ver.D)
BTS3900A APM30H (Ver.B) 15 m (49.21 6 mm2 One-hole The
(Ver.B) IBBS200D ft) (0.009 OT exterior
(Ver.B) in.2) terminal is shown
(M4) by
IBBS200T illustratio
(Ver.B) n 1 in the
preceding
figure.

Equipotential Cable
An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential
bonding between cabinets and safe operation of base stations.

Exterior
The following figure shows the exterior of an equipotential cable.

Figure 40 Exterior of an equipotential cable

(2013-08-15) Huawei Proprietary and Confidential 48


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) One-hole OT terminal (2) Two-hole OT terminal

In most cases, the equipotential cable is a green and yellow cable. When 110 V dual-live-wire power is
supplied for the cabinets used by the BTS3900A (Ver.C) or BTS3900A (Ver.D), the equipotential cable is
green.

Description
The following table describes equipotential cables.

Table 27 Equipotential cables


Base Cross-Sectional Area Connect Exterior
Station or
Type
BTS3900 16 mm2 (0.025 in.2) One-hole The exterior is shown by
(Ver.B) OT illustration 1 in the preceding
BTS3900 terminal figure.
(Ver.C) (M6) at
each end
BTS3900
(Ver.D)
BTS3900(V
er.D)-IMS06
BTS3900L(
Ver.D)-IMS
06
BTS3900A 16 mm2 (0.025 in.2) One-hole The exterior is shown by
(Ver.B) OT illustration 2 in the preceding
terminal figure.
(M6) at
each end

(2013-08-15) Huawei Proprietary and Confidential 49


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Base Cross-Sectional Area Connect Exterior


Station or
Type
BTS3900A The cross-sectional areas of One-hole The exterior is shown by
(Ver.C) cables vary according to the OT illustration 1 in the preceding
way that cabinets are terminal figure.
combined. (M6) at
16 mm2 (0.025 in.2) for each end
stacked cabinets
25 mm2 (0.039 in.2) for
side-by-side cabinets
BTS3900A 16 mm2 (0.025 in.2) One-hole The exterior is shown by
(Ver.D) OT illustration 1 in the preceding
terminal figure.
(M6) at
each end

Power Cables
This section describes the exteriors, functions, and pin assignments of the power cables in the
APM30H.

EPU05A-02 or EPU05A-04 Power Cables


An EPU05A-02 or EPU05A-04 power cable feeds external AC power into the EPU05A-02 or
EPU05A-04 in the APM30H (Ver.D) in a BTS3900A base station, or in the IMS06 in a
BTS3900 or BTS3900L base station. The maximum length of an EPU05A-02 or EPU05A-04
power cable is 15 m (49.21 ft).

Exterior
The number of core wires contained in an EPU05A-02 or EPU05A-04 power cable depends
on the power system where the EPU05A-02 or EPU05A-04 is used. The following figure
shows the exteriors of EPU05A-02 or EPU05A-04 power cables in the 220 V AC single-phase
scenario.
The color and number of core wires of power cables for the EPU05A-02 and EPU05A-04
differ. The following figure shows the exteriors of the power cables for the EPU05A-02 or
EPU05A-04.

Figure 41 Exteriors of the power cables for the EPU05A-02 or EPU05A-04

(2013-08-15) Huawei Proprietary and Confidential 50


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) OT terminal (M6)

Description
The following table lists power cables for the EPU05A-02 or EPU05A-04.

Table 28 Description of power cables for the EPU05A-02 or EPU05A-04

Cable Wire Color Cross-sectional Exterior


Area

EPU05A-02 L1 Brown 6 mm2 (0.009 in.2) See illustration 1


power cable in a in the preceding
220 V AC L2 Black figure for the
three-phase exterior.
L3 Gray
scenario
N Blue
PE Green
and

(2013-08-15) Huawei Proprietary and Confidential 51


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Cable Wire Color Cross-sectional Exterior


Area
yellow
EPU05A-02 L Brown 25 mm2 (0.039 See illustration 2
power cable in a in.2) in the preceding
220 V AC N Blue figure for the
single-phase exterior.
PE Green
scenario
and
yellow
EPU05A-04 L1 Black 25 mm2 (0.039 See illustration 3
power cable in.2) in the preceding
L2 Red figure for the
exterior.
N White
PE Green

The colors and structures of cables vary according to countries and regions. If cables are purchased locally,
the cables must comply with local rules and regulations.

EPU05A-03 or EPU05A-05 Power Cables


An EPU05A-03 or EPU05A-05 power cable feeds external AC power into the EPU05A-03 or
EPU05A-05 in the APM30H (Ver.D) in a DBS3900 base station. The maximum length of an
EPU05A-03 or EPU05A-05 power cable is 15 m (49.21 ft).

Exterior
The color and number of core wires of power cables for the EPU05A-03 and EPU05A-05
differ. The following figure shows the exteriors of the power cables for the EPU05A-03 or
EPU05A-05.

Figure 42 Exterior of the power cable for the EPU05A-03 or EPU05A-05

(2013-08-15) Huawei Proprietary and Confidential 52


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) OT terminal (M6)

Description
The following table lists the power cables for the EPU05A-03 or EPU05A-05.

Table 29 Description of the power cables for the EPU05A-03 or EPU05A-05

Cable Wire Color Cross-Sectional Exterior


Area

EPU05A-03 L1 Brown 6 mm2 (0.009 in.2) See illustration 1


power cable in the preceding
in a 220 V AC L2 Black figure for the
three-phase exterior.
L3 Gray
scenario
N Blue
PE Green and
yellow

(2013-08-15) Huawei Proprietary and Confidential 53


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Cable Wire Color Cross-Sectional Exterior


Area
EPU05A-03 L Brown 25 mm2 (0.039 See illustration 2
power cable in.2) in the preceding
in a 220 V AC N Blue figure for the
single-phase exterior.
PE Green and
scenario
yellow
EPU05A-05 L1 Black 25 mm2 (0.039 See illustration 3
power cable in.2) in the preceding
L2 Red figure for the
exterior.
N White
PE Green

The colors and structures of cables vary according to countries and regions. If cables are purchased locally,
the cables must comply with local rules and regulations.

DCDU-12B Power Cable


A DCDU-12B power cable feeds DC power into a DCDU-12B from power equipment. This
section describes the specifications of various DCDU-12B power cables when the
DCDU-11B is configured in different cabinets. If external power equipment is used, the
maximum length of the DCDU-12B power cable is 10 m (32.80 ft).

Exterior
The DCDU-12B power cables vary depending on the power equipment. The following figure
shows the exteriors of various DCDU-12B power cables.

Figure 43 Cable exterior

(1) OT terminal (M6)

(2013-08-15) Huawei Proprietary and Confidential 54


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Description
The following table lists the specifications of DCDU-12B power cables when a DCDU-12B is
configured in different cabinets.

Table 30 Description

Cable Cabinet Type Power Cable Specifications


Exterior Equipment

APM30H (Ver.D) EPU05A-03 or 25 mm2 (0.039 in.2), one group


EPU05A-05 in
an APM30H

SOU Power Cables


The power cable for a service outlet unit (SOU) feeds AC power into the SOU from the AC
OUTPUT port on the EPU or EPS.

Exterior
The following figure shows the exterior of an SOU power cable.

Figure 44 Exterior of an SOU power cable

(1) C13 connector (2) OT terminal (M4)

Description
The following table describes an SOU power cable.

(2013-08-15) Huawei Proprietary and Confidential 55


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 31 SOU power cable

Wire Color Silkscreen Cross-Sectional Area


W1 Brown L 2.5 mm2 (0.004 in.2)
W2 Green and yellow PE
W3 Blue N

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables
are purchased locally, the cables must comply with local rules and regulations.

AC Heater Power Cables


A power cable for an AC heater feeds power into an AC junction box from the AC OUTPUT
port on an EPU or EPS. Then the AC junction box distributes power to the AC heater.

Power Cable for an AC Heater


Exterior
If a heater is configured in the -48 V DC input scenario, one more AC power input must be
added for the heater. In this case, the maximum length of the power cable for the heater is 15
m (49.21 ft).
The following figure shows the exterior of the power cable for an AC heater.

Figure 45 Exterior of the power cable for an AC heater

(1) C13 connector (2) OT terminal (M4)

Description
The following table lists the power cable for an AC heater.

(2013-08-15) Huawei Proprietary and Confidential 56


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Table 32 Description of the power cable for an AC heater

Wire Color Identifier Cross-Sectional


Area

W1 Brown L 1.5 mm2 (0.002


in.2)
W2 Green and yellow PE
W3 Blue N

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

Power Transfer Cable for an AC Heater


A power transfer cable for the AC heater connects the AC output terminal on the EPU in the
APM30 (Ver.D_A1) to the transfer terminal on the heater.
The following figure shows an input power cable for the heater in the APM30 (Ver.D_A1).

Figure 46 Power transfer cable for an AC heater

(1) OT terminal (M4, 1 mm2 or 0.002 in.2) (2) Cord end terminal

FAN 02D Power Cables


A FAN 02D power cable feeds -48 V DC power into the FAN 02D in an APM30H (Ver.D).

Exterior
Figure 2-54 and Figure 2-55 show the exterior of a FAN 02D power cable.

Figure 47 Exterior of a FAN 02D power cable in most regions

(2013-08-15) Huawei Proprietary and Confidential 57


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) 3V3 connector (2) EPC4 or EPC6 connector

Description
The following table describes a FAN 02D power cable.

Table 33 FAN 02D power cable

Cable Wire Wire Color in Most


Regions

FAN 02D power RTN(+) Black


cable
NEG(-) Black

Power Cables for an AC Junction Box


A power cable for the AC junction box feeds AC power from the power devise into the AC
junction box. The power is divided into four AC outputs, which are then provided to other
components, such as the heater or heating film.

Exterior
The following figure shows the exterior of a power cable for an AC junction box.

Figure 48 Power cable for an AC junction box

(2013-08-15) Huawei Proprietary and Confidential 58


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

(1) OT terminal (2) Cord end terminal

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables
are purchased locally, the cables must comply with local rules and regulations.

Description
The following table describes a power cable for an AC junction box.

Table 34 Power cable for an AC junction box


Base Cabinet Power Wire Color Cross-Section Exterior
Stati Equipme al Area
on nt
Type
B APM30H EPU or L Brown 1.5 mm2 (0.002 The exterior is
TS EPS in.2) shown by
39 subrack N Blue illustration 1 in
00 the preceding
A figure.
D
BS
39
00

(2013-08-15) Huawei Proprietary and Confidential 59


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Signal Cables
This section describes the exteriors, functions, and pin assignments of the signal cables in the
APM30H.

ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in
the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable.

Figure 49 Exterior of an ELU signal cable

(1) RJ45 connector

Description
The following table describes an ELU signal cable.

Table 35 ELU signal cable

X1 End X2 End Color Wire Type


X1.1 X2.1 White Twisted pair
X1.2 X2.2 Orange
X1.3 X2.3 White Twisted pair
X1.6 X2.6 Green
X1.5 X2.5 White Twisted pair
X1.4 X2.4 Blue
X1.7 X2.7 White Twisted pair
X1.8 X2.8 Brown

(2013-08-15) Huawei Proprietary and Confidential 60


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

In different cabinets, the ELU signal cable is connected to different monitoring boards. The
following table lists monitoring boards that collect ELU in different cabinets.

Table 36 Monitoring boards to which an ELU reports information

Cabinet Monitoring Board


APM30H (Ver.B) CMUA
APM30H (Ver.C) CMUE
APM30H (Ver.D) CMUEA

Monitoring Signal Cable for the Door Status Sensor


A monitoring signal cable for the door status sensor is used to inform the monitoring board of
the door status that is obtained from the door status sensor. Cabinets configured with door
status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, BTS3900AL,
OMB, OMB (Ver.C), IBBS700D and IBBS700T.

Exterior
Monitoring signal cables for door status sensors are classified into three types according to the
cabinets being monitored. Figure 2-58, Figure 2-59, and Figure 2-60 show their exteriors.

Figure 50 Exterior of a monitoring signal cable for the door status sensor (1)

Figure 51 Exterior of a monitoring signal cable for the door status sensor (2)

(2013-08-15) Huawei Proprietary and Confidential 61


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Cable 1 has a 2-pin straight socket at one end, which is connected to the HPMI. Cable 1 has a bare wire
and a cord end terminal at the other end, which are connected to a door status sensor and a cable
terminal block, respectively.
Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end
terminal at the other end, which is connected to a cable terminal block.
Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports
on one side of the cable terminal block.

Figure 52 Exterior of a monitoring signal cable for the door status sensor (3)

(2013-08-15) Huawei Proprietary and Confidential 62


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the PMU. Cable
1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor
and a cable terminal block, respectively.
Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end
terminal at the other end, which is connected to a cable terminal block.
Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports
on one side of the cable terminal block.

Description
In different cabinets, the monitoring signal cable for the door status sensor is connected to
different monitoring boards. The following table lists monitoring boards that collect door
status information in different cabinets.

Table 37 Types of monitoring signal cables for door status sensors

Cabinet Monitoring Exterior


Board

APM30H (Ver.B) and APM30H (Ver.C) HPMI Figure 2-59 shows


the exterior.
APM30H (Ver.D) PMU 11A Figure 2-60 shows
the exterior.

(2013-08-15) Huawei Proprietary and Confidential 63


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Monitoring Signal Transfer Cable for the Fan in the Front Door
A monitoring signal transfer cable for the fan in the front door feeds power into the fan in the
front door of the APM30H. It also transmits fan monitoring signals to a monitoring board in
the cabinet.

Exterior
The following figure shows the exteriors of monitoring signal transfer cables for fans in the
front doors.

Figure 53 Exteriors of monitoring signal transfer cables for fans in the front doors

(1) 4-pin connector (2) Interconnection terminal

Cable Type
The following table lists the types of monitoring boards to which the monitoring signals are
reported. Monitoring signal cables vary according to the boards.

Table 38 Cable type

Cable Cabinet Monitoring Board to Exterior


Which the
Monitoring Signals
Are Reported
Monitoring APM30H (Ver.B) CMUA The exterior is shown
signal by illustration 1 in the
transfer APM30H (Ver.C) CMUE following figure.
cable for
the fan in APM30H (Ver.D) CMUEA The exterior is shown
the front by illustration 2 in the
door following figure.

(2013-08-15) Huawei Proprietary and Confidential 64


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

Description
The following table describes a monitoring signal transfer cable for the fan in the front door.

Table 39 Monitoring signal transfer cable for the fan in the front door

Wire X1 End X2 End Color


W1 X1.1 X2.1 Black
W2 X1.2 X2.2 Black
W3 X1.3 X2.3 Black
W4 X1.4 X2.4 Black

PMU 11A-CMUEA Monitoring Signal Cable


The PMU 11A-CMUEA monitoring signal cable connects the PMU and the CMUEA in the
FAN 02D. It transmits the RS485 signals collected by the PMU to the BBU through the
CMUEA. This monitoring signal cable is 1.1 m (3.61 ft) long.

Exterior
The following figure shows the exterior of a PMU 11A-CMUEA monitoring signal cable.

Figure 54 Exterior of a PMU 11A-CMUEA monitoring signal cable

(1) RJ45 connector

Description
The following table describes a PMU 11A-CMUEA monitoring signal cable.

Table 40 PMU 11A-CMUEA monitoring signal cable

X1 End X2 End Wire Type

X1.1 X2.1 Twisted pair


X1.2 X2.2

(2013-08-15) Huawei Proprietary and Confidential 65


Copyright Huawei Technologies Co., Ltd.
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D)
Product Description

X1 End X2 End Wire Type


X1.3 X2.3 Twisted pair
X1.6 X2.6
X1.4 X2.4 Twisted pair
X1.5 X2.5
X1.7 X2.7 Twisted pair
X1.8 X2.8

(2013-08-15) Huawei Proprietary and Confidential 66


Copyright Huawei Technologies Co., Ltd.