You are on page 1of 17

ACI STRUCTURAL JOURNAL TECHNICAL PAPER

Title no. 105-S43

Design and Analysis of Heavily Loaded Reinforced


Concrete Link Beams for Burj Dubai
by Ho Jung Lee, Daniel A. Kuchma, William Baker, and Lawrence C. Novak

This paper presents a study on the shear capacity and behavior of The center hex reinforced concrete core walls provide the
reinforced concrete link beams designed for the Burj Dubai Tower, torsional resistance of the structure similar to a closed pipe
which is the tallest building in the world and will be ready for or axle, as shown in Fig. 3. The center hex walls are
occupancy in 2009. Several thousand reinforced concrete link
beams were used in this structure to interconnect structural walls;
in some cases, the factored shear forces in these link beams were
up to three times the traditional nominal ACI shear force strength
limit. This study presents an examination of the factors that control
the design and behavior of heavily loaded reinforced concrete link
beams. Nonlinear finite element analysis methods were used to
validate and inform the design of the reinforced concrete link
beams for Burj Dubai and to examine if the ACI nominal sectional
shear force limit is appropriate for this type of member. The results
illustrate the undue conservatism of the ACI design provisions and
the role of nonlinear analyses in design.

Keywords: beam; design; nonlinear finite element analysis; reinforced


concrete; shear; strut-and-tie model.

INTRODUCTION
The Burj Dubai Tower, when completed, will be the
worlds tallest structure. Whereas the final height of this
multi-use skyscraper is a well-guarded secret, it will
comfortably exceed the current record holder of 509 meter Fig. 1Tower rendering.
(1671 ft) tall Taipei 101. The 280,000 m2 (3,000,000 ft2)
reinforced concrete tower will be used for retail, an Armani
hotel, residences, and offices. The goal of the Burj Dubai
Tower is not simply to be the worlds highest buildingit is
to embody the worlds highest aspirations.
Designers purposefully shaped the structural concrete for
the Burj Dubai to be Y-shaped in plan to reduce the wind
forces as well as to keep the structure simple and foster
constructibility. The structural system can be described as a
buttressed core, as shown in Fig. 1 and 2. Each wing, with its
own high-performance concrete core and perimeter
columns, buttresses the others via a six-sided central core, or
hexagonal hub. The result is a tower that is extremely stiff
torsionally. The design team purposely aligned all the
common central core and column elements to form a
building with no structural transfers.
Each tier of the building steps back in a spiral pattern that
causes the towers width to change at each setback. The
advantage of this stepping and shaping is to confuse the
wind. The wind vortexes never become organized because
at each new tier the wind encounters a different building
shape that reduces the overall wind loads on the structure.
Due to the tapering of the tower, the primary demand on the Fig. 2Construction photo of tower.
link beams is from gravity load redistribution, flow from the
taller core to the perimeter of the structure. The 280,000 m2 ACI Structural Journal, V. 105, No. 4, July-August 2008.
(3,000,000 ft2) tower and 185,000 m2 (2,000,000 ft2) MS No. S-2007-030 received January 19, 2007, and reviewed under Institute
publication policies. Copyright 2008, American Concrete Institute. All rights reserved,
podium structures are currently under construction, as shown including the making of copies unless permission is obtained from the copyright proprietors.
Pertinent discussion including authors closure, if any, will be published in the May-
in Fig. 2. The project is scheduled for completion in 2009. June 2009 ACI Structural Journal if the discussion is received by January 1, 2009.

ACI Structural Journal/July-August 2008 451


concrete strengths ranging from C80 to C60 cube strength
Ho Jung Lee is an Engineer with SC Solutions, Inc., Sunnyvale, CA. He received his
BS and MS from the Seoul National University, Seoul, South Korea, and his PhD from and contained portland cement and fly ash. Local aggregates
the University of Illinois at Urbana-Champaign, Urbana, IL. were used for the concrete mixture design. The wall and
column sizes were optimized using virtual work/LaGrange
Daniel A. Kuchma, FACI, is an Assistant Professor in the Department of Civil and
Environmental Engineering at the University of Illinois at Urbana-Champaign. He multiplier methods.1 This results in a very efficient structure.
received his PhD from the University of Toronto, Toronto, ON, Canada. He is a The structure was analyzed for gravity (including P-
member of ACI Subcommittee 318-E, Shear and Torsion.
analysis and creep and shrinkage), wind, and seismic loads
William Baker is a Partner of Skidmore, Owings & Merrill LLP, Chicago, IL. by a three-dimensional analysis model that consisted of
the reinforced concrete walls, link beams, slabs, mats, piles,
Lawrence C. Novak is an Associate Partner of Skidmore, Owings & Merrill LLP. and the spire structural steel system. The model consisted of
over 73,500 shells and 75,000 nodes.
buttressed by the wing walls and hammer head walls, which
behave as the webs and flanges of a beam to resist the wind RESEARCH SIGNIFICANCE
shears and moments. Outriggers at the mechanical floors This paper examines methods for the design and analysis
allow the columns to participate in the lateral load resistance for reinforced concrete link beams that are cast integral with
of the structure; hence, all of the vertical concrete is used to wall piers. In particular, the appropriateness of the
support both gravity and lateral loads. The walls had strut-and-tie method and shear design stress limits for this
class of member are reviewed. The results of this investigation
indicate that much higher shear stress levels should be
permitted in ACI 318, as this would greatly extend the utility
of this class of member.

OVERVIEW OF LINK BEAM DESIGN


The demands on the link beams vary greatly and are
dependent on the location of the link beam relative to a
setback with the largest shear forces being generated in the
beams closest to a setback. The typical link beams used in
the Burj Dubai are quite stocky with a shear-span ratio (l/2h)
of 0.85, a width of 650 mm (2.13 ft), and a height of 825 mm
(2.7 ft). For the design of reinforced concrete link beams, the
conventional deep beam design method in the ACI 318-992
and the strut-and-tie method in ACI 318-023 were used, with
Fig. 3Three-dimensional view of single floor. Appendix A enabling the design of link beams somewhat
beyond the conventionally designed maximum deep beam
stress limit of 10 f c in psi (0.83 f c in MPa), which is
based on ACI 318-99,2 Section 11.8.4, as will be discussed
in the following. In the case of members subjected to very
large shear forces, embedded built-up structural steel
sections were provided within the core of the concrete link
beams to carry the entire shear and flexure demand.
This study was principally conducted during the structural
design of the Burj Dubai and used to check and inform the
design by the different methods and to examine the condition
and stiffness of the reinforced concrete link beams under
service and factored loads. In addition, a study was made of
the appropriateness of nominal shear stress limits for link
beams. A series of nonlinear analyses were conducted
that can account for the influence of many factors on
response including the amount of flexural reinforcement,
the distribution of vertical and horizontal web reinforcement,
the span-depth ratio, and the confinement provided by walls
at the ends of the link beams. The nonlinear finite element
analysis tools used in this investigation were ABAQUS,4
ADINA,5 and VecTor2.6

DESIGN DETAILS OF LINK BEAMS


The geometry, factored loads, and design methods of four
Burj Dubai link beams, LB1 to LB4, are shown in Table 1.
These link beams, which have the same external dimensions,
capture the range of typical shear design force levels for
which different design solutions were used. Table 2 and Fig. 4
present details on Link Beams LB1 and LB2, as well as Link
Fig. 4Design details for analyzed link beams. (Note: 1 mm = Beams LB2A and LBRCMAX that are more heavily reinforced
0.0394 in.) and hypothetical link beams whose behavior is evaluated in the

452 ACI Structural Journal/July-August 2008


nonlinear analyses. Link Beam LB1 was designed by the The strut-and-tie model used for the design of Link Beam LB2
deep design method specified in ACI 318-99.2 Link Beam is shown in Fig. 5. The design yields the required amount of
LB2 was designed by the strut-and-tie model in Appendix A horizontal and vertical tie reinforcement and the required
of ACI 318-02.3 Vertical shear or tie reinforcement in Link strength of diagonal concrete struts and nodal zones. Minimum
Beams LB1 and LB2 was determined using the selected horizontal web reinforcement was provided in the link beams
design approaches to support their factored design loads. even though it was not specifically required when the strut-and
Horizontal web reinforcement close to the minimum amount tie design procedure is used. In this link beam design, the amount
suggested for deep beams in ACI 318-023 was used in Link of horizontal and vertical ties can simply be increased to support
Beams LB1 and LB2. The design of Link Beam LB2 using the larger shear loads until the strength is limited by the strength of
strut-and-tie method in the ACI 318-023 provisions, unchanged the diagonal struts and nodal zones.
in ACI 318-05,7 is described in the next section. As previously The use of Appendix A in ACI 318-023 and ACI 318-057
mentioned, a pure reinforced design concrete solution was not provides for a direct design of the diagonal strength of struts so
possible for all members by ACI 318-02,3 or would be by ACI as to avoid a diagonal compressive failure. This permits a
318-05,7 such that composite members with steel-embedded member to be designed for a higher shear stress than the limit for
sections were used to support the shear design in members deep beams in ACI 318-99.2 This deep beam stress limit was also
subjected to very large shear and flexural forces, including Link set to guard against diagonal compression failures but is not
Beams LB3 and LB4. An objective of this study was to investigate considered to be necessary for deep beams as will be discussed in
whether or not it was possible to develop a pure reinforced the following. In the design of Link Beam LB2 by
concrete solution to support the very large shear forces in Link Appendix A of ACI 318-02, the conservative assumption of
Beams LB3 and LB4. To this end, the behavior of more heavily
narrow bottle-shaped diagonal struts were made even though
reinforced members, Link Beams LB2A and LBRCMAX, as
the results of the analyses indicate that there is a uniform
described in Table 2 and Fig. 4, will also be examined.
field of diagonal compression throughout these members.
The concrete cylinder compressive strength used in the
Thus, it was considered that the nominal capacity calculated
design of these link beams was fc = 64 MPa (9280 psi); a
for this strut-and-tie model by ACI 318-02 would lead to a
concrete cube strength of 80 MPa (11600 psi) was specified
conservative design.
and actual cube and cylinder breaks indicate considerably
stronger concrete. The design yield strength of flexural rein-
forcement used in the link beams was 460 MPa (67 ksi) and MAXIMUM SHEAR STRENGTH SPECIFIED
of the vertical stirrups and horizontal web reinforcement was IN CODE PROVISIONS
420 MPa (61 ksi). Reinforcement with a yield strength of There is a large variation in the nominal shear design stress
460 MPa (67 ksi) was actually provided, but in accordance limit that is specified in codes of practice even though the
with Section 11.5.2 of ACI 318-02,3 the effective strength reason for this limit is the same as guarding against a diagonal
was taken as 420 MPa (61 ksi). Nonlinear finite element
analyses of these reinforced concrete link beams (LB1, LB2, Table 1Geometry, loading, and design methods
LB2A, and LBRCMAX) were performed as will be presented. for link beams
Geometry Factored loads
STRUT-AND-TIE MODEL USED IN LINK BEAM Beam Width, Depth, Span, Shear, Moment
The strut-and-tie method has recently developed as a rational ID mm mm mm kN kN-m Design method used
method in the design of discontinuity (D)-regions in structural Conventional (ACI 318-99,
LB1 650 825 1400 1705 1194
concrete such as deep beam, squat walls, pile caps, and other Section 11.8)
elements in which plane sections do not remain plane. The Strut-and-tie
strut-and-tie method provides a conceptually simple design LB2 650 825 1400 2805 1164 (ACI 318-02,
Appendixes A and C)
methodology based on the lower-bound theorem of limit
LB3 650 825 1400 3750 2625 Steel plate
analysis.8 Provisions for using the strut-and-tie method were
LB4 650 825 1400 5250 3675 Built-up steel I-beam
included as Appendix A in ACI 318-02.3
Notes: Factored loads are equal for both ends of link beams. Ratio of ultimate load to
sustained day-to-day (gravity only) service loads is approximately 2.5. Walls adjacent
to link beams are 650 mm thick and are typically reinforced with a minimum of
T20mm at 350 mm on each vertical and horizontal face. 1 in. = 25.4 mm; 1 kip =
4.448 kN; and 1 ft-kip = 0.356 kN-m.

Table 2Reinforcing details of link beams


analyzed in study
Reinforcement Stirrups
Top Bottom Side bars Spacing,
Beam ID bars bars each face Size mm Type
LB1 5-T32 5-T32 5-T12 T16 150 Two hoops
LB2 12-T32 12-T32 4-T12 T16 125 Two hoops
LB2A 18-T32 18-T32 4-T12 T16 80 Three hoops
LBRCMAX 27-T32 27-T32 4-T12 T16 75 Five hoops
Notes: T32, T20, T16, and T12 are deformed reinforcing bars with respective diameters of
32, 20, 16, and 12 mm. In LB2, top and bottom bars were used in two layers each. LB2A
and LRCMAX were not used in Burj Dubai project. They are included for purpose of
examining appropriateness of current ACI 318-05 limit on maximum shear stress. LB2A
Fig. 5Strut-and-tie model used in design of Link Beam LB2. has significantly more longitudinal tension reinforcement and transverse reinforcement
than LB2. LBRCMAX is analyzed to figure out maximum shear capacity of reinforced
(Note: 1 in. = 25.4 mm; 1 kip = 4.448 kN; 1 psi = 6.89 concrete link beam. In LB2A and LBRCMAX, top and bottom bars were placed in two
103 MPa; and 1 ft-kip = 1.356 kN-m.) layers and three layers each, respectively. 1 in. = 25.4 mm.

ACI Structural Journal/July-August 2008 453


compression failure. For the limits shown in Table 3, the beams is investigated in the nonlinear finite element analyses
range in maximum permitted shear stress is more than a that are presented in the next section.
factor of two for the 64 MPa (9280 psi) concrete used in the
design of the Burj Dubai. The ACI conventionally designed NONLINEAR FINITE ELEMENT ANALYSIS
beam shear limit of 10 f c (psi) (0.83 f c [MPa]) was The structural behavior of reinforced concrete link beams
derived from simply supported beam tests in which there is is influenced by many factors including the amount of flexural
a funneling and thus magnification of diagonal compressive reinforcement, vertical and horizontal shear reinforcement, the
stresses as they flow from the top of the beam to its support span-depth ratio, and the confinement effect of the adjacent
and in which anchorage failures are common. The AASHTO pier walls. Nonlinear finite element analyses can be used to
LRFD9 and CSA (Canadian) code 10 shear stress limit of evaluate the effect of these parameters. In this section, the
0.25fc for reinforced concrete members was derived from nonlinear finite analyses of the Burj Dubai link beams (LB1
the modified compression field theory.11) In this approach, and LB2) and the more heavily reinforced link beams (LB2B
the influence of diagonal tensile strains on the capacity of a and LBRCMAX), as described in Table 2, are presented.
uniform diagonal compression field is directly considered. Three different programs, ABAQUS, ADINA, and
The flow of diagonal forces in link beams, which are VecTor2, were used for the finite element analysis of these
supported over their ends, are expected to be uniform as reinforced concrete link beams. In ABAQUS, the concrete
illustrated later and thus the limit in the LRFD and CSA damaged plasticity model was selected. This model is based
provisions is more appropriate. For the reinforced concrete on the work of Lubliner et al.12 and Lee and Fenves.13 The
link beams used in the Burj Dubai, there is the further structural concrete damaged plasticity model is intended to provide a
advantage of the confinement effect from the pier walls. The general capability for the analysis of concrete structures
walls on both sides help to prevent vertical expansion of the link subjected to static and dynamic loading under low confining
beams at their ends, which limits diagonal cracking. The pressures. It is based on the combination of nonassociated
use of a higher shear design stress limit in these link multi-hardening plasticity and scalar damaged elasticity
models. The program ADINA provided the option to adjust
various concrete strength and ductility parameters as well as
failure envelopes to better represent the concrete behavior
for a specific application. The program VecTor2 implements
the rotating-angle smeared-crack model of the modified
compression field theory and quadrilateral elements are
used in the analyses.
Before conducting the finite element analyses of these link
beams, the finite element models were calibrated and validated
using experimental results that accounted for the effects of
complex geometries, loadings, and edge effects. Because
this study focuses on the strength of the link beams, it was
investigated to see if the selected parameters for the concrete
material model in ABAQUS, ADINA, and VecTor2 predict
well the strength of link beams tested to failure in laboratories.
One of the comparisons used the link beam tested under
monotonic loading by Galano et al.14 that had a shear span
Fig. 6Geometry and detailing of link beam tested by Galano ratio of 0.75. This ratio was the closest to that of the Burj
et al.14 (Note: 1 in. = 25.4 mm; and 1 psi = 6.89 103 MPa.) Dubai link beams (shear ratio = 0.85) for the identified test
data. The geometry and reinforcement details of the tested

Table 3Maximum nominal shear design stress


permitted by code provisions
Maximum shear strength,
Design code Vn, max

ACI 318-02 and ACI 318-05 V c + 8 f c b w d

AASHTO STD1 V c + 8 f c b w d

AASHTO LRFD 3 0.25f c b v d v + V p

AASHTO segmental bridges 2 12 f c b w d

CSA (1994)10 0.25f c b v d v + V p

CSA (2004)11 0.25f c b v d v + V p

JSCE14 15 f c b w d
Notes: Vc equals nominal shear resistance provided by concrete, fc equals concrete
compressive strength, bw equals width, d equals distance from compression face to
Fig. 7Predicted load-deformation response of link beam centroid of longitudinal tension reinforcement, bv equals web width including adjustment
tested by Galano et al.14 (Note: 1 in. = 25.4 mm; and 1 kip = for presence of ducts, dv equals effective shear depth, and Vp equals component in
direction of applied shear of effective prestressing force.
4.448 kN.)

454 ACI Structural Journal/July-August 2008


link beam are shown in Fig. 6. Four-node plane stress isopara- concrete). These input parameters define the stress-strain
metric elements were used in the analyses. Reinforcing steel curve of concrete.
was modeled as two-node truss elements. The top section of In ABAQUS, the compressive and tensile response was
the left wall is restrained and the shear force is applied to the defined similarly as in ADINA, but the prediction by
bottom section of the right wall by displacement control; the ABAQUS was based on the concrete damaged plasticity
same prescribed vertical displacement is used along the model. In this model, the value of the flow potential eccentricity
section. The analysis results are presented in Fig. 7 and the parameter has a significant effect on the concrete response. This
strengths predicted by ABAQUS, ADINA, and VecTor2 are value was set to be 20 based on the calibration with experimental
shown to predict the experimentally measured capacity data, whereas the dilation angle was similarly selected to be 36.
reasonably well. The results of other validation studies were Default values were used for the other input parameters in
similar. Therefore, the selected parameters for the concrete the concrete damaged plasticity model.
model in ABAQUS, ADINA, and VecTor2 were taken to be
sufficiently accurate for capacity evaluation of the four link DISCUSSION OF PREDICTED LINK
beams in this study. BEAM BEHAVIOR
The load and boundary conditions of the finite element The finite element analysis results of Link Beam 1 (LB1)
model for the Burj Dubai link beams are shown in Fig. 8. The are shown in Fig. 9 through 11. ABAQUS, ADINA, and
wall boundary is extended vertically up to the depth of the VecTor2 all predicted similar responses for Link Beam LB1.
link beam and horizontally up to the length of the link beam. According to Fig. 9, the predicted capacity is much larger
This extension with the constraints put in the finite element than the factored design load. Therefore, the use of the deep
model provides a realistic boundary for the investigation of beam design method as specified in the ACI 318-992 Code is
link beam capacity that was expected to lead to conservative considered to lead to a very conservative design for this link
(lower bound) estimations of capacity. The load and beam. Crack patterns at the loading steps similar to the
boundary conditions are the same as that of the link beam factored design load and at the ultimate load are shown in
tested by Galano et al.14 except the stiff perimeter steel was Fig. 10. At the factored design load, flexural cracks occur at
used to account for the constraining effect of the wall as the the boundary regions of the link beam under tension,
boundary of the model. The additional benefit of axial
compression in the walls, as investigated by other analyses
not presented in this paper, was found to only have a very
minimal beneficial effect on the capacity of the link beams;
it is the link beam end restraint rather than axial compression
in the wall piers that influences the behavior of the link
beams. Thus, the axial load acting on the walls was not
considered in the reported analyses. The strain variation of
reinforcing steel identified in Fig. 8 was investigated as well
as the crack patterns and capacity of the link beams.
Additional information on the finite element models is
now presented and this is followed in the next section by the
predicted capacity and behavior of the link beams. In
creating the finite element models, it was necessary to select
and specify material models and select convergence limits.
In all analyses, the response of the reinforcement was linear
elastic and perfectly plastic. The default value of the
convergence limit in VecTor2 was used, a convergence
value of up to 0.01 was used in ADINA, whereas the stability Fig. 8Load and boundary conditions used in modeling of
command was used in ABAQUS, but its use was found to Burj Dubai link beams.
have little effect on the predicted behavior. The philosophy
of VecTor2 is that the user is not required to select nonbasic
material parameter values and thus only the compressive
cylinder strength was specified and all other default values
were accepted. ADINA and ABAQUS require the user to
select many other parameter values. The selections made in
these programs are given in the following.
In ADINA, the required concrete material input parameters
were tangent modulus at zero strain (44,000 MPa [6380 ksi]),
Poissons ratio (0.15), uniaxial cut-off tensile stress (4.83 MPa
[700 psi]), post-cracking uniaxial cut-off tensile stress (4.83 MPa
[700 psi]), uniaxial maximum compressive stress (64 MPa
[9280 psi] for unconfined concrete; 102.4 MPa [14848 psi] for
confined concrete) and corresponding compressive
strains (0.002 for unconfined concrete; 0.0032 for confined
concrete), ultimate uniaxial compressive stress (54.4 MPa
[7888 psi] for unconfined concrete; 87 MPa [12615 psi]
for confined concrete), and ultimate uniaxial compressive Fig. 9Predicted load-deformation response of Link
strain (0.003 for unconfined concrete; 0.0048 for confined Beam LB1. (Note: 1 in. = 25.4 mm; and 1 kip = 4.448 kN.)

ACI Structural Journal/July-August 2008 455


whereas no shear cracking was observed in the central analysis of Link Beam LB2, the capacity of Link Beam LB2
portion of the link beam. The development of straining in the is slightly decreased due to concrete crushing at the ends of
longitudinal and shear reinforcement is presented in Fig. 11. the link beam. This is not expected in practice because the
The longitudinal tensile strain increased gradually with pier walls provide significant restraint to the vertical expansion
increasing shear force until the capacity of the member was of the link beam and this increases the concrete compressive
reached at the point of longitudinal yielding. As shown in strength at the ends of these link beams. VecTor2 directly
Fig. 11(b), the transverse reinforcement strain rapidly considers concrete confinement and softening without
increased with the formation of diagonal cracks, but the additional input from users. When the confined concrete
transverse strain at the capacity of the member was less than
the yield strain of 0.0021. At the ultimate load, severe flex-
ural cracks occurred and extensive shear cracking was
predicted. In summary, the finite element analysis results
predict that the failure mode of Link Beam LB1 was yielding
of longitudinal tension reinforcement and that shear failures
did not occur. It is also observed that Link Beam LB1, as
designed by the deep beam design method in ACI 318-99,2
was more conservatively designed for shear than for flexure.
The predicted load-deformation response of Link Beam 2
(LB2) by the nonlinear finite element analyses is shown in
Fig. 12 in which the predicted capacity is considerably larger
than the factored design load. The strut-and-tie method specified
in ACI 318-057 was therefore observed to lead to a conservative
design for this link beam. ABAQUS, ADINA, and VecTor2
provide similar predictions of behavior of this link beam.
Two different concrete models were used in the ADINA
analyses. One is an unconfined concrete stress-strain model
and the other is a confined concrete model. ADINA and
ABAQUS do not directly consider the confinement effect by
the pier walls at the end of the link beams. Thus, if the
unconfined model is used in ABAQUS and ADINA for the

Fig. 11Predicted development of reinforcement strains in


Link Beam LB1. (Note: 1 kip = 4.448 kN.)

Fig. 12Predicted load-deformation response of Link


Fig. 10Predicted crack patterns by ADINA for Link Beam LB2. (Note: 1 psi = 6.89 103 MPa, 1 in. = 25.4 mm;
Beam LB1. (Note: 1 kip = 4.448 kN.) and 1 kip = 4.448 kN.)

456 ACI Structural Journal/July-August 2008


model is used in ABAQUS and ADINA for the analysis of strains were considerably smaller than yield strain at the
the link beams, it gives similar results to those of the VecTor2 point of yielding of the longitudinal reinforcement.
default model. The predicted development of reinforcement Therefore, it is predicted that the capacity of these link
strains for Link Beam LB2 is shown in Fig. 13. For Link beams is limited by their flexural capacities.
Beam LB2, the strain in the transverse reinforcement Sectional analyses of Link Beams LB2A and LBRCMAX
reaches yield before yielding of the longitudinal reinforcement. were also performed using the sectional analysis program
The capacity and mode of failure of Link Beam 2 is predicted Response 2000.15 Response 2000 15 is also based on the
to occur at the point of yielding of both the longitudinal and modified compression field theory and employs the engineering
transverse reinforcement. beam theory assumption that plane sections remain plane.
The finite element analysis results of hypothetical Link Unlike with the nonlinear finite element analyses,
Beams LB2A and LBRCMAX, which contained higher Response 200015 cannot account for the beneficial effects of
levels of longitudinal and shear reinforcement, are shown in confinement and strut action. Under combined shear and
Fig. 14 through 17. ABAQUS, ADINA, and VecTor2 bending loads, the sectional capacities predicted by
provide similar predictions of the behavior of these link beams. Response 200015 for Link Beams LB2A and LBRCMAX
Without consideration of the confinement effect by the walls, were 6026 and 7600 kN (1355 and 1709 kips), respectively.
the analysis results predict a maximum shear stress capacity The state of cracking in Link Beam LBRCMAX was also
limit that is 70% larger than the conventionally designed predicted by program Response 200015 as shown in Fig. 18
beam shear stress limit of 10 f c (psi) (0.83 f c [MPa]) that is at its ultimate capacity. The member analysis by Response
specified in ACI 318-05.7 If the confinement effect by the 200015 for Link Beam LBRCMAX supports the conclusion
pier walls is considered in the analysis through the use of from the nonlinear finite element analyses that a shear
the confined concrete stress-strain model, the shear stress force close to the LRFD and CSA limit can be supported
capacity of the reinforced concrete link beam can be 2.5 times by a reinforced concrete link beam of the dimensions used
the ACI shear stress limit. This is illustrated in the in the Burj Dubai.
predicted behavior of Link Beam LBRCMAX in which The strength results of this investigation are summarized
very significant amounts of longitudinal and transverse in Fig. 19, which presents a comparison of the factored shear
reinforcement were provided. For both Link Beams LB2A
and LBRCMAX, the predicted transverse reinforcement

Fig. 14Predicted load-deformation response of hypothetical


Link Beam LB2A. (Note: 1 in. = 25.4 mm; and 1 kip =
4.448 kN.)

Fig. 15Predicted load-deformation response of hypothetical


Fig. 13Predicted development of reinforcement strains in Link Beam LBRCMAX. (Note: 1 in. = 25.4 mm; and 1 kip =
Link Beam LB2. (Note: 1 kip = 4.448 kN.) 4.448 kN.)

ACI Structural Journal/July-August 2008 457


design loads for link beams (LB1 to LB4) in the Burj Dubai for Link Beam LB1 that was designed by the ACI 318-992
and the predicted shear capacities by the nonlinear finite deep beam provisions and for Link Beam LB2 that was
element analyses for Link Beams LB1, LB2, LB2A, and designed by the strut-and-tie model of Appendix A in ACI
LBRCMAX. The shear force corresponding to the ACI 318-02.3 In the Burj Dubai, composite link beams with large
318-057 conventionally designed beam shear stress limit of embedded sections were used to support the shear and
10 f c (psi) (0.38 f c [MPa]) is also shown. The results of flexure demand when this demand was in excess of what
the analyses predict that the designs are very conservative could be designed for by ACI 318 sectional or strut-and-tie
design procedures. The results of the analyses for hypothetical
Link Beams LB2A and LBRCMAX suggest that it would have
been possible to support the large shear force demands in Link
Beams LB3 and LB4 with reinforced concrete link beams;
however, reinforcing bar congestion and constructibility
concerns would need to be evaluated for Link Beams LB2A and
LBRCMAX.

CONCLUSIONS
In this paper, the design and capacity of heavily loaded
reinforced concrete link beams were investigated by
nonlinear finite element analyses using the programs
ABAQUS,4 ADINA,5 and VecTor2.6 The following is a
summary of results from this study:
1. The effect of the pier walls at the ends of the link beams
was predicted by the analyses to reduce the vertical transverse
expansion at the ends of the members and thereby reduce the
demands on transverse reinforcement. The pier walls also
provided confinement that enabled the link beams to support
larger compressive stresses at their ends. Furthermore, they
enabled a more uniform field of diagonal compression and
vertical distribution of shear over the depth of the member
throughout the entire length of the link beam;

Fig. 16Predicted development of reinforcement strains in


hypothetical Link Beam LB2A. (Note: 1 kip = 4.448 kN.)
Fig. 18Predicted cracking in hypothetical Link Beam
LBRCMAX by Response 2000 at ultimate load (V = 1709 kips
[7600 kN]). (Note: 1 in. = 25.4 mm; and 1 kip = 4.448 kN.)

Fig. 17Predicted development of reinforcement strains in


hypothetical Link Beam LBRCMAX (Location A in Fig. 8). Fig. 19Comparison of shear demands and capacities in
(Note: 1 kip = 4.448 kN.) link beams.

458 ACI Structural Journal/July-August 2008


2. The use of the deep beam design method in the ACI REFERENCES
318-992 provisions leads to very conservative shear designs 1. Baker, W.; Novak, L.; Sinn, R.; and Viise, J., Structural Optimization
for link beams as suggested by the results of multiple of 2000 Tall 7 South Dearborn Building, Proceedings of the 2000 ASCE
nonlinear finite element analyses. The ACI 318-992 shear Structures Congress, Track: 14th Analysis and Computational Conference,
stress limitation for deep beams, which is a function of the 2000.
span-depth ratio and imposed to guard against a diagonal 2. ACI Committee 318, Building Code Requirements for Structural
compression failure, unnecessarily limits the load-carrying Concrete (ACI 318-99) and Commentary (318R-99), American Concrete
capacity of stocky link beams supported over their heights Institute, Farmington Hills, MI, 1999, 369 pp.
such as those used in the Burj Dubai project; 3. ACI Committee 318, Building Code Requirements for Structural
Concrete (ACI 318-02) and Commentary (318R-02), American Concrete
3. The strut-and-tie model in Appendix A of ACI 318-023
Institute, Farmington Hills, MI, 2002, 443 pp.
and ACI 318-057 permits reinforced concrete link beams to be
4. ABAQUS, Version 6.4.3, Hibbitt, Karlsson & Sorensen, Inc.,
designed for substantially higher loads than would be possible
Pawtucket, RI, 2004.
by the use of ACI sectional design methods. In the use of the
5. ADINA, A Finite Element Program for Automatic Dynamic Incre-
strut-and-tie model, a direct check is made to ensure that the mental Nonlinear Analysis, Version 8.3, ADINA R & D, Inc., 2006.
diagonal compressive struts have adequate capacity. There- 6. Vecchio, F. J., VecTor2, Nonlinear Finite Element Analysis Program
fore, a design completed by the strut-and-tie model negates the of Reinforced Concrete, University of Toronto, Toronto, ON, Canada, 2002.
need to satisfy any sectional shear stress limitation; 7. ACI Committee 318, Building Code Requirements for Structural
4. The results of nonlinear finite element analyses indicate Concrete (ACI 318-05) and Commentary (318R-05), American Concrete
that reinforced concrete link beams have significantly larger Institute, Farmington Hills, MI, 2005, 430 pp.
shear capacities than the nominal strengths calculated by the 8. Schlaich, J.; Schafer, K.; and Jennewein, M., Toward a Consistent
strut-and-tie model of ACI 318-05.7 The capacity of the Design of Structural Concrete, PCI Journal, V. 32, No. 3, 1987, pp. 75-149.
members was predicted to be controlled by yielding of the 9. AASHTO, AASHTO LRFD Bridge Design Specifications, third
longitudinal reinforcement; the compressive and nodal stress edition, Washington, DC, 2004, 1450 pp.
limits in ACI 318-057 were found to be conservative; and 10. CSA Committee A23.3, Design of Concrete Structures (CSA
5. There is a wide variation in the maximum shear stress A23.3-04), Rexdale, ON, Canada, 2004.
limits in codes of practice. The difference is more than a 11. Vecchio, F. J., and Collins, M. P., The Modified Compression Field
factor of two between the sectional design models in ACI Theory for Reinforced Concrete Elements Subjected to Shear, ACI
318-057 (10 f c [psi] [0.83 f c (MPa)]) and the Canadian JOURNAL, Proceedings V. 83, No. 2, Feb. 1986, pp. 219-231.
and AASHTO LRFD Design Codes (0.25f c ) for link beams 12. Lubliner, J.; Oliver, J.; Oller, S.; and Oate, E., A Plastic-Damage
cast with 64 MPa (9280 psi) concrete, as used in the Burj Model for Concrete, International Journal of Solids and Structures, V. 25,
Dubai. The higher shear stress limit in the Canadian and 1989, pp. 299-329.
AASHTO LRFD code was found to be appropriate for short 13. Lee, J., and Fenves, G. L., Plastic-Damage Model for Cyclic
link beams that are supported over their height at their Loading of Concrete Structures, Journal of Engineering Mechanics,
ends by continuous wall piers. ASCE, V. 124, No. 8, 1998, pp. 892-900.
14. Luciano, G., and Vignoli, A., Seismic Behavior of Short Coupling
Beams with Different Reinforcement Layouts, ACI Structural
ACKNOWLEDGMENTS
The analyses presented in this paper were performed for Skidmore, Journal, V. 97, No. 6, Nov.-Dec. 2000, pp. 876-885.
Owings & Merrill LLP (SOM) LLP, Chicago, IL, under the direction of 15. Bentz, E. C., and Collins, M. P., Response 2000, http://
W. Baker, L. Novak, A. Ozkan, and S. Korista. www.ecf.utoronto.ca/~bentz/r2k.htm, 2000.

ACI Structural Journal/July-August 2008 459


DISCUSSION
Disc. 105-S37/From the July-August 2008 ACI Structural Journal, p. 395 and p. 405

Design of Deep Beams Using Strut-and-Tie ModelsPart I: Evaluating U.S. Provisions and Part II: Design
Recommendations. Papers by Michael D. Brown and Oguzhan Bayrak

Discussion by Dipak Kumar Sahoo, Bhupinder Singh, and Pradeep Bhargava


Research Scholar, Department of Civil Engineering, Indian Institute of Technology Roorkee, Roorkee, India; Assistant Professor, Department of Civil Engineering, Indian Institute of
Technology Roorkee; Professor, Department of Civil Engineering, Indian Institute of Technology Roorkee

The authors are complimented for the exhaustive compilation 1


and meticulous evaluation of a large database of 596 reinforced -------------
-
k2
(C)
concrete beams with a/d ratios less than 2 to identify the ( fc )
unconservatism in the strut-and-tie model (STM) provisions
of ACI 318-05 and the AASHTO LRFD. Recently, Yang where k1 and k2 are two independent exponents that can be
and Ashour (2008) analyzed a large shear database, part of evaluated by suitably grouping the database considering one
which is also used by the authors, and observed similar parameter at a time while keeping the other parameter
unconservatism in the STM provisions of the ACI 318-05 constant. Finally, combining Eq. (B) and (C), the composite
and the Eurocode 2 (2004) as well, with these provisions model relating the strut efficiency factor to the a/d and fc
being even more unsafe, particularly for continuous deep will become
beams. The discussers would like to draw the authors attention
to two points: k1 k2
1. With reference to the findings of Part I, it may be noted = k0 ( a d ) ( fc ) (D)
that the cylinder compressive strengths of concrete used in
the 596 beams of the database fall in a wide range28 to where k0 is a constant coefficient that can also be evaluated
83 MPa (4000 to 12,000 psi)whereas the applicability of from the database.
the STM provisions of ACI 318-05, Appendix A, is limited The discussers feel that unless the values of both k1 and k2
to concrete with compressive strengths up to 41 MPa (6000 psi). (evaluated using the database as discussed) are close enough
The literature suggests that the strut efficiency factor to unity, two independent exponents may be preferred.
decreases with an increase in the concrete compressive
strength and, therefore, it should be expected that the higher-
REFERENCES
strength concrete beams will be unsafe when evaluated using EN 1992-1-1:2004, 2004, Eurocode 2: Design of Concrete Structures
the ACI 318-05 provisions; and Part 1-1: General Rules and Rules for Buildings, British Standards Institution,
2. With reference to Fig. 1 of Part II, the authors have London, UK., 225 pp.
Yang, K.-H., and Ashour, A. F., 2008, Code Modeling of Reinforced-
suggested a correlation of the following form between the Concrete Deep Beams, Magazine of Concrete Research, V. 60, No. 6,
strut efficiency factor and the two important influencing pp. 441-454.
parameters: the shear span-to-effective depth ratio (a/d) and
the concrete compressive strength fc. AUTHORS CLOSURE
The authors would like to thank the discussers for their
1 1 interest, and hope these comments resolve the outstanding
= k0 ( a d ) ( fc ) (A) issues related to the papers.
The discussers present two comments related to the two-
The strut efficiency factor is known to decrease with an part paper. The first comment relates to the limitation of
increase in the concrete compressive strength fc. Because 6000 psi (41 MPa) in Appendix A of ACI 318. This limitation
the strut efficiency is related to the splitting tensile strength applies only to Section A.3.3.1 and no other provisions
of concrete, a parameter linearly linked to fc, the authors within Appendix A. Additionally, when examining the
are fully justified in correlating with fc. However, the effects of concrete compressive strength within the database
discussers are not clear why the authors have chosen a of experimental results, the authors did not find a significant
power function to correlate with the a/d, which is simply difference between test results of various strengths of
cot, with being the angle of inclination of the strut with concrete. This result may be due to the relatively limited data
the horizontal. stemming from tests with high-strength concrete.
The second point raised by the discussers relates to the
The composite correlation pattern followed by the authors choice of the exponent in the proposed equations. The two
in Eq. (A) can be expressed as two independent power functions parameters (a/d and fc) were evaluated independently
indicated in the following though the course of developing the proposed equations. In
both cases, the values of the exponents were very close to
1 1.0. Figure 1 was intended to illustrate that result with the
-----------------k- (B) value of the exponent on the product of the two parameters
1
(a d) equal to 0.97.

378 ACI Structural Journal/May-June 2009


Disc. 105-S37/From the July-August 2008 ACI Structural Journal, p. 395

Design of Deep Beams Using Strut-and-Tie ModelsPart I: Evaluating U.S. Provisions. Paper by Michael D.
Brown and Oguzhan Bayrak

Discussion by Andor Windisch


ACI Member, PhD, Karlsfeld, Germany

The historical remembrance is sometimes incorrect: the shown (Windisch 2000) that the failure of most reinforced
truss mechanism where the stirrups act in pure tension was concrete panels (all of which were loaded by deformation
proposed by Hennebique in his patent. Reporting on this control) was caused by the yielding of the weaker char of
patent, Ritter1 was in doubt about this. He proposed to place reinforcement in the panel. Therefore, Eq. (3) and (4) can not
the stirrups along the tensile trajectories 45 degrees inclined be related to allowable concrete stresses. The authors reser-
to the supports. vation concerning the calculation of the average concrete
strain during the design process is more than justified.
CURRENT U.S. CODE PROVISIONS
The authors are to be complimented for their concise DATABASE OF EXPERIMENTAL RESULTS
summary of the current code provisions for the use of strut- Irrespective of the sense of database evaluations, the data
and-tie modeling. In Fig. 1 and Table 1, the strut efficiency should be split with reference to the type of reinforcement:
factors are given: earlier tests beams (for example, contained mild steel
In the case of a strut with a uniform cross section over round bars) having an average yield stress of 46,000 psi
its length, = 1.0. (317 N/mm2).35 These results shall be treated separately. In
This is the case when (using the legend of Fig. 1) b = L many of the specimens, the shear failure occurred after the
but also when L = b, that is, when the strut with b = h is flexural reinforcement yielded, that is, the flexural capacity
loaded on its full width. was exhausted; hence, these specimens should also be excluded.
The following comments arise:
According to the theory of plasticity, the failure load STRAIN ENERGY IN STRUT-AND-TIE MODELS
does not decrease if the cross section is increased with The discusser wondered about the possibility of the highly
load-bearing material. subjective choice of models. The recommendation11 that the
Being so, why is the effective compression strength fce model with the least strain energy is likely to be the most
less if L < b, that is, the total loading is much less? appropriate is not verified. The authors are to be complimented
In the Eurocode 2 (2004), the minimum reinforcement that they pointed it out as well. If this recommendation is
according to Eq. (2) (with = 90 degrees) is obligatory true, then the application of refined strut-and-tie modelsas
in all reinforced concrete structures, even in the case suggested in SP-20817could not be possible.
of struts with an assumed uniform cross section over The two-panel model in Fig. 5(b) was chosen for panels
their length. with vertical shear reinforcement. The corresponding vertical
The sudden failure of the specimen during the split tie turned the strut. Nevertheless, neither the trajectories nor the
cylinder test is mentioned as the formidable example of the crack pattern of the panel are influenced by the vertical shear
jeopardizing effect of induced tension. Nevertheless, one reinforcement. It would have been more realistic to make use
should calculate the compressive stress along the line load of the one-panel model, increasing the efficiency factor of
on the cylinder and compare it to the effective compressive the strut in relationship to the rate of reinforcement.
strength according to Table 1. Huge differences exist! Concerning the combined model, the following questions
The crack shown in Fig. 3 of the paper has nothing to do arise: How does the efficiency of the inclined strut of the
with the dispersion of the compressive force in the bottle- one-panel truss interfere with the tension in the vertical tie of
shaped strut, that is, tensile stresses induced by the associated the two-panel truss? Does it increase it or reduce it?
equilibrium, and does not reduce the load-bearing capacity
of this strut. SUMMARY AND CONCLUSIONS
Looking at the struts in Fig. 5, why is the strut in the As mentioned previously, the control of the load-bearing
compression zone not forming a bulge, at least downwards? capacity of the single direct strut between the load point and
Conclusion: the bottle-shaped strut is a useless component of the reaction may result in specimens that fail in flexure. It
a questionable model in fashion. would be interesting to find out which type of failures
Why is the strut-and-tie model, which is so easy to be occurred at those beams that showed efficiency factors less
applied, questionable? It is dangerous, as it may give the than the nominal values. Do the strut efficiency factors
impression that having a closed system of dashed and remain valid in the case of deep beams with uniformly
continuous lines (struts and ties) and maybe some concrete distributed loading on their top or when the concentrated
efficiency factors, will make the structural member safe. For load acts on the bottom edge of the beam?
example, deep beams with shear span-depth ratios of
approximately 1 or less, with flexural reinforcement REFERENCES
determined according to the strut-and-tie models shown in EN 1992-1-1, 2004, Eurocode 2: Design of Concrete StructuresPart 1-1:
Fig. 4 and the truss models shown in Fig. 5 would fail in flexure. General Rules and Rules for Buildings, Brussels, Belgium, 225 pp.
Windisch, A., 2000, On the Design of Two-Way Reinforcements in
With reference to the modified compression field theory R/C, Studi e ricerche, Scuola di specializzazione in Costruzioni in C. A.
(MCFT)-based usable compressive stress in the strut, it was Fratelli Pesenti, Politecnico di Milano, V. 21, pp. 283-302.

ACI Structural Journal/May-June 2009 379


Disc. 105-S38/From the July-August 2008 ACI Structural Journal, p. 405

Design of Deep Beams Using Strut-and-Tie ModelsPart II: Design Recommendations. Paper by Michael D.
Brown and Oguzhan Bayrak

Discussion by Andor Windisch


ACI Member, PhD, Karlsfeld, Germany

DEVELOPMENT OF EFFICIENCY most cases rather than a strength concern. After the splitting
FACTOR EQUATIONS crack forms, the tensile stresses in concrete along the crack
Analysis of database vanish and the state of stress more closely resembles uniaxial
It can be treated as a deficiency of the new expression for compression. As Cross (1952) noted, however, strength is
the efficiency factor that the square root of the compressive not the only concern. The presence of transverse reinforcement
strength was taken as a parameter. This could give the in a bottle-shaped strut will help to reduce crack widths at
impression that the concrete tensile strength has some service loads, which improves durability provided that
fundamental influence on the shear strength of strut efficiency, service level loads do not result in yielding of these bars.
which physically can not be the case. It might be that an Given that these horizontal bars are likely present in most
improved definition of the effective shear span (taking into cases, it is prudent to consider them in the truss model. The
account the effective lengths of the plates at support and authors agree with the discussers comments regarding strut
loading) could have been found to decrease the scatter. without transverse reinforcement: they should be avoided as
stated in Part I.
Reinforcement in bottle-shaped strut The authors disagree with the discussers suggestion that
According to the authors, the reason for the reinforcement specimens in which the longitudinal reinforcement reached
in bottle-shaped struts is to carry the transverse splitting yield before shear failure occurred should be excluded from
force after the formation of the splitting crack along the axis the database. Rather, these are the primary specimens that
of the strut. As already discussed with regard to Part I, the should be examined. Current ACI 318 Code provisions are
bottle-shaped strut is a questionable formation. Moreover, until based on some level of ductility within a properly designed
now, any reinforcement beyond the minimum reinforcement structure. The use of different strength reduction factors for
according to ACI 318-05 should be included into the truss as the various failure modes is evidence of this fact. Furthermore,
a tie, which rearranges the truss configuration. Suddenly, a the assumption of a fully plastic structure undergoing plastic
calculated amount of reinforcement is hidden behind a deformations, consistent with strut-and-tie modeling, suggests
dashed line (strut). How can a dashed line be perceived as an that the reinforcement has yielded before failure occurs. A
ductile failure mode, such as yielding of the reinforcement,
ordinary strut or one with reinforcement, which must be
is preferable to a brittle one, such as crushing of a strut.
dimensioned? Why does a strut that models the compression
zone not split? In general, a strut does not fail through splitting The authors examination of strain energy in the strut-and-
but rather along a sliding surface. This develops mostly at the tie models was not refined to the degree necessary to answer
end of a flexural-shear or shear crack. The flexural-shear or the discussers questions. This evaluation of strain energy, as
shear crack borders the strut, but does not split it. stated in the paper, was a simplistic attempt to examine the
concept of minimum strain energy in various models. To that
end, limited though it may have been, the authors believe the
Node geometry attempt was successful for the stated objective.
The authors are completely correct: whether the node is
hydrostatic or not is a rather irrelevant question. When the The authors classified specimens based on the various
web has the same width as the bottom flange at the support, failure types by using definitions developed by Kani et al.28
then only two tasks must be solved by the engineer: proper (in Part I). No strong correlation between Kani et al.s failure
types and efficiency factor was found. The specimens
size of the bearing plate (with some local zone reinforcement)
studied in this database, however, were confined to two of
and the proper anchorage of the longitudinal reinforcement.
Kani et al.s four failure types. Perhaps this classification
Hence any further theorization of the node problem might be may have been too crude to yield meaningful results.
impressive, but remains useless.
In regard to the discussers question about deep beams
with uniform loads applied on the top of a beam or a
COMPARISON OF STRUT-AND-TIE MODEL concentrated load applied near the bottom of a beam, the
PROVISIONS AND SUMMARY authors can provide some insight. Based on previously
The histograms (Fig. 10 through 12) of the ultimate published research by the authors (Brown and Bayrak 2006;
strength to nominal strength ratio with the high rate of over- Brown et al. 2006), it would be expected that the failure
dimensioned specimens permits a single conclusion only: loads of specimens subjected to distributed loads on their top
even if the strut-and-tie model would be a proper model, the surface would be higher than the failure loads predicted
strength of the inclined struts is certainly not the governing using the equations presented in these papers. As for specimens
factor for safe structures. The authors are strongly encouraged subjected to concentrated loads near their bottom surface,
to continue their activity to detect all inconsistencies of the the authors would expect the failure loads predicted with the
strut-and-tie models. proposed equations could overestimate the shear strength.
This overestimation would be due to the tensile stresses
AUTHORS CLOSURE induced in the web of such a member. This particular question,
The discusser presents many questions related to the use of however, has not been studied by the authors, and our
bottle-shaped struts. In general, the authors are in agreement supposition that specimens loaded near their bottom surface
with the discussers comments. The splitting crack that should be taken for what it is: speculation based on review of
forms in a bottle-shaped strut is a serviceability concern in limited experimental research related to such structures.

380 ACI Structural Journal/May-June 2009


REFERENCES Brown, M. D.; Bayrak, O.; and Jirsa, J. O., 2006, Design for Shear
Based on Loading Conditions, ACI Structural Journal, V. 103, No. 4,
Brown, M. D., and Bayrak, O., 2007, Investigation of Deep Beams with July-Aug., pp. 541-550.
Various Load Configurations, ACI Structural Journal, V. 104, No. 5, Cross, H., 1952, Engineers and Ivory Towers, McGraw-Hill, New York,
Sept.-Oct., pp. 611-620. 142 pp.

Disc. 105-S42/From the July-August 2008 ACI Structural Journal, p. 440

Punching Shear Strength of Reinforced Concrete Slabs without Transverse Reinforcement. Paper by
Aurelio Muttoni

Discussion by Andor Windisch


ACI member, PhD, Karlsfeld, Germany

The author is to be complimented for his new failure criterion The contributions of shear friction and dowel action can be
for punching shear based on the critical shear crack theory. neglected, too. (The size effect originates from the limited
The failure procedure is explained12 as follows: the shear extent of the process zone in fracture mechanics and must be
strength is reduced by the presence of a critical shear crack taken into account.)
that propagates through the slab into the inclined compression The shear strength formulas in the different codes, that is,
strut carrying the shear force to the column. Eq. (1), (2), and (4), referring to the slab depth d and the
Regarding Fig. 2, this explanation shall be complemented arbitrary control perimeter, smear the different contributions.
as follows: at the critical shear crack shown in Fig. 2(a), the The smeared, mechanically inconsistent material characteristic
continuous thick line consists of (at least) two different is than approximated with fc1/2 or fc1/3, which have no real
sectionsthe upper part is a typical flexural-shear crack and physical meaning; they are relatively close to the calculated
the lower part is a sliding surface across the compression figures only.
zone of the slab around the column, that is, this part cannot The authors interesting new failure criterion based on the
be considered an ordinary crack. The theoretical strut rotation of the slab must be opposed due to the two load-rotation
depicted in Fig. 2(b) cannot exist as described. It does not curves shown in Fig. 3(a). The detrimental effect of the
develop around the critical shear crack, nor develops the critical supplementary reinforcing ring db12 (one No. 4) cannot be
crack across the strut. The source of the inclined compressive predicted by the rotation. Mentrey29 found similar
force in this strut, as shown in Fig. 2(b), is not clear either. jeopardizing influence of reinforcing rings in his tests.
How does it develop on the top of the slab? The discusser
The author is correct: the punching strength is a function
would like to assume that the author had similar doubts. The of the opening of a critical shear crack in the slab. Nevertheless,
elbowed-shaped strut in Fig. 2(c) confirms this feeling. The
the position of this crack can not be predicted through the
sliding surface part of the critical shear crack crosses the
slab rotation, hence can not be considered as an independent
node where both struts join. The truss model with the elbow-
variable of the phenomenon.
shaped strut shown in Fig. 2(c) is completely irrelevant (as is
the entire strut-and-tie model). How would a shifting of the The paper gives very valuable impacts for looking for a
loading, for example toward the column, influence the truss? mechanically sound model on punching shear strength.
And concerning the load-bearing capacity of the triple lines,
the ties that should had been of concrete: who cares? The REFERENCES
strut-and-tie model shows its limits very clearly. 28. Windisch, A., Towards a Consistent Design Model for Punching
Shear Capacity, International Workshop on Punching Shear Capacity of
The discusser means that the source of the punching shear RC Slabs, Royal Institute of Technology, Stockholm, Sweden, 2000,
strength of slabs without transverse reinforcement is the pp. 293-301.
shear load-bearing capacity of the compression zone.28 The 29. Mentrey, P., Relationship between Flexural and Punching Failure,
inclined or curved compression strut has no function at all. ACI Structural Journal, V. 95, No. 4, July-Aug. 1998, pp. 412-419.

Disc. 105-S42/From the July-August 2008 ACI Structural Journal, p. 440

Punching Shear Strength of Reinforced Concrete Slabs without Transverse Reinforcement. Paper by
Aurelio Muttoni

Discussion by N. Subramanian
ACI member, PhD, Consulting Structural Engineer, Gaithersburg, MD

The author has to be appreciated for developing a a given critical rotation of the slab, and that a similar
comprehensive analytical model for predicting the proposal has been included in the Swedish standards.
punching shear strength of reinforced concrete slabs However, the equation for calculating mRd (the flexural
without transverse reinforcement. It is also interesting to capacity of the slab in the column region reduced by the
note that the author has developed failure criteria based on strength reduction factor) used in Eq. (9) is not given. Only

ACI Structural Journal/May-June 2009 381


when mRd is evaluated can the load-rotation relationship and 31. Theodorakopoulos, D. D., and Swamy, R. N., Analytical Model to
the punching shear strength be calculated. Hence, the author Predict Punching Shear Strength of FRP-Reinforced Concrete Flat Slabs,
ACI Structural Journal, V. 104, No. 3, May-June 2007, pp. 257-266.
is requested to give the equation for the same.
In this connection, the discusser wishes to note another
comprehensive analytical model developed by Theodora- AUTHORS CLOSURE
The author would like to thank the discussers for their
kopoulos and Swamy30 to predict the ultimate punching
interest in the paper and for their encouraging words about
shear strength of slab-column connections. This model is
the ideas of the critical shear crack theory.
also based on the physical behavior of the connections and is
applicable to both lightweight and normalweight concrete. It
Closure to discussion by Windisch
also incorporates several variables that affect the punching
The sketch of Fig. 2 is a physical explanation of how the
shear strength of flat slabs including the concrete strength, development of the critical shear crack influences the
tension steel ratio, compression reinforcement, and loaded
behavior of the slab, allowing to understand, for instance, the
area. It was compared with 60 reported tests in literature and
decompression of the soffit of a slab measured during
found to agree with them with reasonable accuracy. The testing. As the discusser may note, no quantitative, only
discusser requests that the author compare the results of his
phenomenological, explanations are obtained from this figure.
analytical model with their results, and show the significant
The same happens with respect to Fig. 3. It explains the
advantage of using his model. The discusser is unable to do influence of tangential cracking and of its location on
so due to the unavailability of the equation for mRd in Eq. (9).
punching shear strength. The model itself, however, deals
Theodorakopoulos and Swamy31 recently extended the
with ordinary (orthogonal) reinforcement layout for which
aforementioned theory for predicting the punching shear the failure criterion of Fig. 5 is proposed.
strength of FRP-reinforced concrete flat slabs. They found
that the model gives excellent correlation with test results of
Closure to discussion by Subramanian
slabs reinforced with FRP reinforcing bars. The value of mRd (design moment capacity per unit width)
can, for instance, be calculated according to ACI 318-08,
REFERENCES Sections 10.2 and 10.3. The assumptions on the shape discussed
30. Theodorakopoulos, D. D., and Swamy, R. N., Ultimate Punching
Strength Analysis of Slab-Column Connections, Cement and Concrete in Section 10.2.6 have limited influence on the value of the
Composites, V. 24, No. 6, 2002, pp. 509-521. design moment capacity for typical reinforcement ratios.

Disc. 105-S43/From the July-August 2008 ACI Structural Journal, p. 451

Design and Analysis of Heavily Loaded Reinforced Concrete Link Beams for Burj Dubai. Paper by Ho Jung Lee,
Daniel A. Kuchma, William Baker, and Lawrence C. Novak

Discussion by Andor Windisch


ACI Member, PhD, Karlsfeld, Germany

STRUT-AND-TIE MODEL USED IN LINK BEAM affecting the wall sections, much more pronounced cracked
The authors are to be complimented for their interesting regions would have been found.
paper. What is the speciality of the strut-and-tie model For the validation of the concrete material models of the
shown in Fig. 5, where the reader might perceive that this is three programs, a test14 under monotonic loading was used.
a D-region? According to MacGregor16 In D-regions...a Following are some questions and comments:
major portion of the load is transferred directly to the The link beams in the tower are subjected to wind loads
supports by in-plane compressive forces in the concrete and from different directions. This alternating load results
tensile forces in reinforcement and a different design in pronounced cracking in the relevant tension region
approach is needed. How was the horizontal position of the that becomes the compression zone in the next loading
C-C-C nodes found that resulted in the = 39.1-degree strut phase. Did the concrete material model consider this
inclination? Nor is it not clear when a bottle-shaped or a effect? That is a further reason why more realistic
narrow bottle-shaped strut or a uniform field of diagonal boundary conditions should have been chosen.
compression throughout a deep beam shall be assumed. A The situation under seismic loads is much more dramatic.
direct design looks different. Did the authors consider this issue in the design?
The three predicted load-deformation responses (Fig. 7)
are close to each other; nevertheless, they overestimate
NONLINEAR FINITE ELEMENT ANALYSIS
the failure load quite substantially. (As the load-defor-
The load and boundary conditions shown in Fig. 8 do not mation response of the test specimen is not shown, it is
properly model the real conditions: along the (horizontal) not clear whether the predicted response was close enough
boundary cross sections of the walls, significant bending to the measured one.) Did the nonlinear finite element
moments (besides normal and shear forces) act that can models at least predict the type of failure properly?
considerably influence the load-bearing capacity of the link For a designer, the most important aspect is the load-
beam. Reference should be given to the predicted crack bearing capacity. What criterion can be formulated for
patterns shown in Fig. 10under the opening moments the finite element analysis to indicate failure?

382 ACI Structural Journal/May-June 2009


DISCUSSION OF PREDICTED 3. Brown and Bayrak17 emphasized that the use of the
LINK BEAM BEHAVIOR current provisions for STM in both ACI 318-05 and
The predicted crack patterns displayed in Fig. 10 show a AASHTO LRFD does not produce adequate levels of
pronounced opening corner effect with inclined cracks
around the corners. This opening-corner effect should have safety. Who is right?
been considered in the strut-and-tie model. (Until now, after 4. The authors are right. It is well known (nevertheless,
more than 30 years of development, no valid strut-and-tie systematically neglected by the users of strut-and-tie
model has been developed for opening corners at all. Even modeling) that in D-regions, more longitudinal flexural
MacGregor16 does not give any assistance.) reinforcement is needed as advised by strut-and-tie
The predicted cracking shown in Fig. 18 reveals that modeling where the internal lever arm is regularly taken as
horizontal web reinforcement would be as efficient as the 0.9d, even if the region is prestressed, which increases the
vertical stirrups, especially in the neighborhood of the pier
walls. The strut-and-tie model focuses only on vertical ties as depth of the compression zone; and
shear reinforcement, whereas horizontal web reinforcement 5. The discusser strongly doubts whether the code provisions
is never referred to. cited would be valid for link beams under alternating loading
such as in the Burj Dubai.
CONCLUSIONS
1. The reported effect of the pier walls could be less REFERENCES
advantageous if the real loading effects would have been 16. MacGregor, J. G., Derivation of Strut-and-Tie Models for the 2002
considered in the model. The reversed loading could have ACI Code, Examples for the Design of Structural Concrete with Strut-
even more detrimental influences; and-Tie Models, SP-208, K. Reineck, ed., American Concrete Institute,
2. A more detailed analysis (if the model is correct) Farmington Hills, MI, 2002, pp. 7-40.
deserves a more economical solution compared to a much 17. Brown, M. D., and Bayrak, O., Design of Deep Beams Using Strut-
quicker (and cheaper) calculation model, that is, the model in and-Tie ModelsPart II: Design Recommendations, ACI Structural
ACI 318-99; Journal, V. 105, No. 4. July-Aug. 2008, pp. 405-413.

Disc. 105-S43/From the July-August 2008 ACI Structural Journal, p. 451

Design and Analysis of Heavily Loaded Reinforced Concrete Link Beams for Burj Dubai. Paper by Ho Jung Lee,
Daniel A. Kuchma, William Baker, and Lawrence C. Novak

Discussion by Kent A. Harries


FACI, William Kepler Whiteford Faculty Fellow and Assistant Professor, Department of Civil and Environmental Engineering, University of Pittsburgh, Pittsburgh, PA

The discussed paper presents varied analyses of very large Under reversing loads, intersecting cracks propagate
link or coupling beams coupling the walls of the Burj Dubai across the entire depth of the beams at their ends. As subsequent
tower. The link beams are clearly shear critical, having their inelastic load reversals are applied, concrete at the ends [is]
design moment capacity determined as M = VL/2, where V is destroyed by cracking, abrasion and spalling. With the
the design shear and L is the span of beam. Based on the concrete destroyed, shear transfer by truss action is not
nature of coupled wall structures, the large shear forces possible and the transverse hoops become ineffective. Interface
induced in the beams result from lateral loads applied to the shear transfer is lost. Eventually, dowel action of longitudinal
structure. The beams permit the individual wall piers to act reinforcement [provides] the primary shear resistance
as a unit; thus, lateral forces are resisted by a combination of Deterioration of the concrete at the ends of the beams [is]
cantilever wall pier action and an axial couple generated intensified by elongation of the beams, caused by residual
between walls resulting from the frame action imparted by tensile strains in the longitudinal reinforcement. These
the beams. strains developed with successive load reversals into the
The analyses and discussion presented by the authors inelastic range.
appear to suggest the use of the strut-and-tie method to overcome Sliding shear at the face of the wall begins to affect the
what is suggested to be the restrictive shear stress limits on these response of conventional beams having shear stresses in the
members imposed by ACI 318. The reviewer is concerned range of 4fc to 6fc psi (0.3fc to 0.5fc MPa). The failure
that this conclusion, while correctly deduced from the of the Mount McKinley Building during the 1964 Anchorage
authors work, is nonetheless erroneous and potentially Earthquake21 is an often-cited example illustrating the
dangerous with respect to the behavior of coupled high-rise shortcomings of conventionally reinforced coupling beams.
structures. The primary reason for these misleading By providing intermediate midheight longitudinal bars,
conclusions is that the authors have considered only the the hysteretic response is improved (through additional
case of a monotonically loaded beam. The following brief dowel action) and strength deterioration due to shear is
discussion refutes the findings of the discussed paper as they delayed, although not mitigated.22-24 Beams with intermediate
relate to high-rise coupled wall structures. bars do not perform well when the shear stress is greater than
Conventionally reinforced concrete coupling beams are 6fc psi (0.5fc MPa). Providing cranked diagonal reinforce-
recognized to be susceptible to sliding shear failure at the ment near the beam ends has been shown to improve the
beam-wall interface.18,19 Sliding shear is described as follows.20 hysteretic behavior by preventing sliding shear and by

ACI Structural Journal/May-June 2009 383


spreading the hinging regions away from the wall face.25,26 and Ductility of Reinforced Concrete Coupling Beams of Shear Walls,
This detail, however, poses construction difficulties and ACI Structural Journal, V. 93, No. 6, Nov.-Dec. 1996, pp. 711-720.
25. Paparoni, M., Model Studies of Coupling Beams, Proceedings of
results in extra cost. Additionally, designers may avoid this the International Conference on Tall Concrete and Masonry Buildings, V. 3,
detail because it is not explicitly covered in ACI 318. Similarly, 1972, pp. 671-681.
the use of high-strength concrete27,28 or fiber-reinforced 26. Aristizabal-Ochoa, J. D., Seismic Behavior of Slender Coupled
concrete29 has shown some improvement in delaying the Wall Systems, Journal of the Structural Division, ASCE, V. 113, No. ST10,
1987, pp. 2221-2234.
occurrence of sliding shear.
27. Bristowe, S., Seismic Response of Normal and High-Strength
Diagonally reinforced coupling beams exhibit better Concrete Members, PhD dissertation, McGill University, Montreal, QC,
performance19,30 and theoretically overcome limits imposed Canada, 2000, 244 pp.
by concrete shear capacity. As demonstrated by Harries et al.,31 28. Xiao, Y.; Esmaeily-Ghasemabadi, A.; and Wu, H., High-Strength
however, the design of diagonally reinforced beams becomes Concrete Short Beams Subjected to Cyclic Shear, ACI Structural Journal,
V. 96, No. 3, May-June 1999, pp. 392-399.
largely impractical for all but the shortest beams at gross 29. Canbolat, B. A.; Parra-Montesinos, G. J.; and Wight, J. K.,
section shear stresses exceeding approximately 6fc psi Experimental Study on Seismic Behavior of High-Performance Fiber-
(0.5fc MPa). Reinforced Cement Composite Coupling Beams, ACI Structural Journal,
There are three methods by which sliding shear may be V. 102, No. 1, Jan.-Feb. 2005, pp. 159-166.
30. Shiu, N. K.; Barney, G. B.; Fiorato, A. E.; and Corley, W. G.,
avoided: Earthquake Resistant WallsCoupled Wall Test, Report to NSF, Portland
1. Reduce the shear stress in the beam. This may result Cement Association, Research and Development, Skokie, IL, 1981.
in impractically large coupling beam cross sections31; 31. Harries, K. A.; Fortney, P.; Shahrooz, B. M.; and Brienen, P.,
2. Provide diagonal reinforcement. Diagonal reinforcement Design of Practical Diagonally Reinforced Concrete Coupling BeamsA
Critical Review of ACI 318 Requirements, ACI Structural Journal, V. 102,
is perhaps the only successful solution for reducing the No. 6, Nov.-Dec. 2005, pp. 876-882.
potential for sliding shear and enhancing the hysteretic 32. Aktan, A. E., and Bertero, V. V., The Seismic Resistant Design of
characteristics of coupling beams having span-depth ratios R/C Coupled Structural Walls, Report No. UCB/EERC81/07, Earthquake
as large as 3.33.32 Steel placement in diagonally reinforced Engineering Research Center, University of California-Berkeley, Berkeley,
beams having span-depth ratios greater than 1.5, however, is CA, 1981.
33. Harries, K. A.; Gong, B.; and Shahrooz, B., Behavior and Design of
generally impractical31; and Reinforced Concrete, Steel and Steel-Concrete Coupling Beams,
3. Provide a steel or hybrid coupling beam33,34 as reportedly Earthquake Spectra, V. 16, No. 4, Nov. 2000, pp. 775-800.
was done for the more heavily loaded Beams LB3 and LB4 34. Harries, K. A., and Shahrooz, B., Hybrid Coupled Wall Systems,
in the Burj Dubai. Concrete International, V. 27, No. 5, May 2005, pp. 45-51.
35. Galano, L., and Vignoli, A., Seismic Behavior of Short Coupling
Conventionally reinforced concrete coupling beams Beams with Different Reinforcement Layouts, ACI Structural Journal,
having relatively high magnitudes of shear stress should be V. 97, No. 6, Nov.-Dec. 2000, pp. 876-885.
expected in practice. A review of the experimentally
observed behavior of such beams reveals that strains in the AUTHORS CLOSURE
longitudinal reinforcement barely achieve yield prior to the The authors appreciate the discussions provided by
onset of sliding shear.18,20,24,35 In cases where conventional Windisch and Harries. The authors will first address the
reinforcement was used in beams having span-depth ratios concern raised by Harries, and shared by Windisch, that the
less than 1.5, the beams were unable to achieve the loads for design approach used in the Burj Dubai and the analytical
which they were designed prior to the onset of sliding shear.18,24 validation was not suitable for beams subjected to significant
While the strut-and-tie approach would appear to permit load reversals. The authors will then address the additional
greater capacities to be achieved, the behavior of the comments of Windisch.
structural system must be accounted for and results from In the paper, the authors stated that Due to the tapering of
previous work, particularly experimental results, cannot be the tower, the primary demand on the link beams is from
overlooked. In this case, the discusser maintains that the gravity load redistribution, flow from the taller core to the
conclusions of the discussed paper are incorrect in context. perimeter of the structure. The largest shear demands are in
Furthermore, the discusser has some concern for the LB2 the beams at the location of these setbacks where there is not
beams that have been reportedly used in the Burj Dubai. the concern for the type of load reversal or opposite direction
Finally, there is a minor typographical error in Table 1: the shear cracking raised in the discussions. Harries comments
design moment for LB2 = 1964 kN. are premised by his assumption that Based on the nature of
coupled wall structures, the large shear forces induced in the
REFERENCES beams result from lateral loads applied to the structure.
18. Paulay, T., Coupling Beams of Reinforced Concrete Shear Walls, Thus, the concerns raised by Harries are not applicable to the
Journal of the Structural Division, ASCE, V. 97, No. ST3, 1971, pp. 843-862. link beams that were the subject of this paper. The authors
19. Paulay, T., and Binney, J. R., Diagonally Reinforced Concrete
Beams for Shear Walls, Shear in Reinforced Concrete, SP-42, American
agree with the technical arguments presented and summarized
Concrete Institute, Farmington Hills, MI, 1974, pp. 579-598. by Harries that would apply to link beams whose demands
20. Barney, G. B., et al., Earthquake Resistant Structural Walls Test of are governed by lateral loadings. One of the authors is presently
Coupling Beams, Report to NSF, submitted by Portland Cement Association, engaged in testing a large multi-story reinforced concrete
Research and Development, Skokie, IL, 1978. coupled wall structure that was designed to resist cyclic
21. Berg, V. B., and Stratta, J. L., Anchorage and the Alaska Earthquake
of March 27, 1964, AISC, New York, 1964, 63 pp.
lateral loading from seismic actions. In this test structure,
22. Aktan, A. E., and Bertero, V. V., Seismic Response of R/C Frame- diagonal reinforcement has been used for the reasons given
wall Structures, Journal of the Structural Division, ASCE, V. 110, No. ST8, in Harries discussion.
1984, pp. 1803-1821. This response is also considered to address the concerns of
23. Scriber, C. F., and Wight, J. K., Delaying Shear Strength Decay in Windisch regarding the influence of significant reverse
Reinforced Concrete Flexural Members under Large Load Reversals,
Report UMEE 78 R2, Department of Civil Engineering, University of
loading on the design and performance of link beams.
Michigan, Ann Arbor, MI, 1978. Because two ACI members both raised this concern, the
24. Tassios, T. P.; Moretti, M.; and Bezas, A., On the Coupling Behavior authors should have better anticipated that many readers

384 ACI Structural Journal/May-June 2009


would naturally assume that the dominant shear demands computational tool requires the conduct of sensitivity analyses
were from lateral loads. Thus, the authors should have been to investigate the influence of modeling decisions on the
more emphatic about the source of the demands for the link predicted capacity and behavior so that conservative yet
beams in Burj Dubai. realistic assumptions can be employed in the final, selected
The other comments of Windisch were on the following model to be used in the study. It also involves using failure
topics: the shape of the strut-and-tie model, the appropriateness criteria that are specific to the models being used. For
of the selected finite element model, comparisons with test example, in the predictions by VecTor2 that account for the
data, the criteria used to assess the predicted capacity, influence of compression softening, for each element the
cracking patterns, and the role of horizontal reinforcement. ratio of principal compressive stress to a compressive
As presented in Fig. 5, the shape of the strut-and-tie model strength (dependent on the principal transverse tensile
was selected so that the full shear force would need to be straining) was examined so that the determined reliable
lifted up over the length of the link beam, as opposed to capacity was well below the point in which crushing would
having a portion of the shear flow along a diagonal strut that be expected.
runs from one wall pier to the other pier. The strut-and-tie As pointed out by Windisch, the extensiveness of corner
design philosophy permits the designer to use any admissible cracking is a significant factor to consider in the selection of
shape for the truss model; the designer selected what was the shape of the strut-and-tie model to use in design. The
considered to be a conservative design that also provided model presented in this paper was chosen to take this pattern
substantial vertical reinforcement to resist bursting forces in of cracking into consideration. It is certainly possible to
the middle region of the link beam. In response to the imagine a different model in which the designer relied on the
specific question of the horizontal position of the CCC node, transfer of shear over the full depth of the interface between
it was selected to provide sufficient width to support the the link beam and wall pier. Given the range of application
vertical force Vu given in Fig. 5. of the strut-and-tie design methodology, designers should
In the nonlinear finite element model presented in Fig. 8, be encouraged to consider the location and extent of
only a segment of the surrounding pier walls was modeled. cracking as is being suggested by Windisch. Nonlinear
In the Burj Dubai, the wall piers were sufficiently large so finite element analysis tools can be effective means of
that the bending of these walls was insignificant and thereby predicting this cracking.
not a factor that was considered to affect the behavior of the Windisch also comments on the role of horizontal
link beams. The test result presented in Fig. 7 was from a reinforcement. The authors agree that the effect of this
beam subjected to cyclic loading and not the type of monotonic horizontal reinforcement is not captured by the selected
situation in the Burj Dubai. Thus, the use of this test data to strut-and-tie model, but its role is illustrated in the predictions of
validate the computational model was a conservative approach. nonlinear finite element tools. The role of horizontal
The matter of what criteria to use for determining the reinforcement has been captured in studies and strut-and-tie
capacity predicted by a nonlinear finite element analysis is a models for the flow of forces in deep beams.
critically important issue for the use of computational tools The authors have not commented on the work by Brown
for design validation. Unfortunately, there is not a clear set and Bayrak as providing a public critique of their work in
of criteria that can be applied to these analytical predictions response to this discussion; it was considered outside the
for assessing capacity due to the dependency of these limits of this response. It is useful to note that while the
predictions on differences in the capabilities and limitations general applicability of the strut-and-tie method is a great
of existing material and behavioral models, and how they strength, any assessment of the conservatism of this
have been employed in computational tools and in the approach greatly depends on the specific geometry and
development of finite element models in any specific inves- loading of the structure and the selected shape of the strut-
tigation. Consequently, assessing a reliable capacity from a and-tie model.

ACI Structural Journal/May-June 2009 385

You might also like