InspectionandTestPlanforFanandBlower
ActivityBy Remark
No. InspectionandTestPlan ReferenceDocument AcceptanceCriteria VerifyingDocument
Manuf. TPI Client

1 PreInspectionMeeting Spec. Spec. MOM H H H

BeforeManufacturing
DWG,Design, DWG,
2 API673 API673 H R A
CalculationDocument Calculationbook
3 WPS&PQR ASME ASMEIX WeldingBook H R A
WelderQualification
4 ASME ASMEIX Certificates H R
Certificates
5 NDTprocedures ASME ASMEV,VIII,IX Procedures H R A
NDEPersonnel
6 ASME ASMEV Certificates H R
Certificates
PWHTProcedure
7 API673/ASME API673/ASME Procedure H R A
(ifneeded)

Fan/BlowerImpeller
8 DynamicandOverspeed API673 API673 Procedure H R A
BalanceTestProcedures

FanandBlower
9 MechanicalRunningTest API673 API673 Procedure H R A
Procedure
FanandBlower
10 PerformanceTest AMCAStandard AMCAStandard Procedure H R A
Procedure

PressureTest
11 API673/ASMEVIII ASMEVIII/API673 Procedure H R A
Procedure

1
www.inspectionforindustry.com
12 PaintingProcedure Spec. Spec. Procedure H R A

Materials
OriginalMaterial
13 MaterialCertificates ASMEII/ASTM ASMEII/ASTM H R
Certificates
14 MaterialIdentification ASMEII/ASTM ASMEII/ASTM Report H W

Visual,Dimensionand
MarkingControl(Fan
Housing,Ducting,
15 ASMEII/ASTM ASMEII/ASTM Report H W
Gaskets,NutandBolts,
Bearings,BearingHouses,
Shaft,Wheelsandetc.)

DuringFabrication
ComponentsVisual
16 API673 API673 Report H W
Inspectionfordamage
ComponentsDimensional
17 ChecktoDrawing DWG/API673 DWG/API673 Report H W
Requirements

VisualExaminationof
18 ASME/API673 ASME/API673 Report H W
Weldedparts

ComponentsConfirmation
19 of ASME/API673 ASME/API673 Report H W
SatisfactoryNDE

Ductinginspection
21 Procedure/API673 Procedure/API673 Report H H
(Welded,Riveted,Rolled)

2
www.inspectionforindustry.com
22 DuctingPressureTest WPS/API673 WPS/API673 Report H W

AuxiliaryEquipment
InspectionandTesti.e.
27 API673 API673 Report H W
Silencer,Piping,Lubeoil
Systemandetc.

Impellervisualand
28 DWG/API673 DWG/API673 Report H W
DimensionalInspection

ImpellerConfirmationof
30 ASME/API673 ASME/API673 Report H W
SatisfactoryNDE

ImpellerDynamic
31 Procedure/API673 Procedure/API673 Report H H
BalanceTest
32 ImpelleroverspeedTest Procedure/API673 Procedure/API673 Report H H

Fan/Blower
35 Procedure/API673 Procedure/API673 Report H H
MechanicalRunningTest

Fan/BlowerPerformance
38 Procedure/API673 Procedure/API673 Report H H
Test

FinalInspection
FinalVisual&
39 DWG/Spec. DWG Report H H
DimensionalCheck
SurfacePreparationand
40 Procedure SSSP/Spec. Report H W
Painting
41 CheckofNamePlate DWG DWG Report H H
Submitted
42 CheckofFinalBook Spec. Spec. DWG/P.O H R
by

3
www.inspectionforindustry.com
Documentation

43 InspectionReports Spec./DWG Spec./DWG Report H R

44 NCR Spec./DWG Spec./DWG Report H R

45 ReviewFinalDataReport Spec./DWG Spec./DWG Report H R

PreShipmentInspection

46 PreservationandPacking Spec. Spec. Report H H

47 Marking Spec. Spec. Report H H

48 LoadingInspection Spec. Spec. Report H H


ShippingDocument
49 Procedure Spec. PackingList H H
Control
auxiliaryequipmentsuchaslubeoilsystem,filter,strainer,piping,steelstructureandetc.arenotincludedtothisITP

Abbreviations:

H:HoldPoint=HoldontheproductiontillTPIInspectorperformsinspectionandsupervisetherequiredtest
W:WitnessPoint=ManufactureshallnotifyclientandTPIInspectorbutthereisnoholdontheproduction;
ClientcanwaivethisinspectionbasedonhisdiscretionandinformsTPIInspectoraccordingly.

R:DocumentReview=ReviewmeansReviewdocument,whichincludesofmaterialtestcertificates,WPS,PQR,NDTProceduresandetc.
A:Approval
SW:SpotWitness=foritemswithspotwitnessmanufactureshallnotifyTPIinspectorasfulfillingthemonitoring;
ForexampleonerandomvisitforwholeUTtestsoroneortwovisitsforwholesurfacepreparationworksforpainting.