FEATURES
Aluminium (LM6) Die-cast body and components.
Housing treated against Porosity through a special process.
Complete meshing of teeth to avoid play in the gears.
No overshooting of the pointer on the dial at the two extremes possible.
The cam assembly can be pre-adjusted as per customer’s requirement to set off the alarm at any point before the
empty position.
Precision positioning of magnets to ensure complete union in their movement.
The presence of only one box at the bottom of the dial offers simplicity in design & avoids excess internal wiring in the
indicator
1/4 3/4 3 D 12 12
EMPTY FULL
E 65 65
4
MADE IN INDIA F 50 50
5 GØ 11 13
H (Nos) 6 8
P.C.D. 165 209.7
3/4” B.S.Conduit or Weight
9 8 6 7 10 Metric on demand in Kgs. 2.5 3.0
ALL DIMENSIONS IN mm
PARTS LIST
SR. No. DESCRIPTION MATERIAL
1. MAIN BODY AL (LM6)
2. LIMIT STOPPERS BRASS
3. LEVER WITH GEAR BRASS
4. FLOAT-ARM BRASS
5. FLOAT BRASS
6. HOLE FOR CABLE GLAND
7. CONNECTOR
8. MERCURY SWITCH GLASS GLASS
9. NUT (FOR ADJ. MER. SWITCH) BRASS
10. DIAL WITH POINTER AL
FIG. 2 5 2
1. MERCURY SWITCH
2. INTERNAL WIRING
WIRING DIAGRAM
3. CONNECTOR
4. EXTERNAL WIRING
5. ALARM
The float is hinged and swings up or down when Oil Level ALARM SWITCH
rises or falls. This rise or fall rotates the bevel gear and thus
One, normally open, mercury switch is provided to actuate
the pinion of the gear assembly. The pinion in turn rotates the
low level alarm. The switch is adjustable to compensate error
driving magnet inside the conservator. The follower magnet
in orientation of pad. Leads of this switch are connected to
positioned outside carries a pointer and a cam. The pointer
the terminals.
reads Oil level and the cam is set to operate the mercury
switch at a predetermined low level. APPLICATION
MOUNTING The ‘ATVUS’ Magnetic Oil Level Gauges can be used for
various purposes. In a transformer they are mounted on the
A suitable pad has to be provided to mount the indicator. The conservator to read oil level and to set off an alarm when the
mounting can be done vertically or at an inclination to facilitate oil Level falls below a predetermined level.
SPECIFICATIONS
1. Operating liquids : Transformer oil to IS 335 and other oils.
2. Working temperature
o
: 0 to 100 C of oil.
3. Working Pressure : 0 to 4 Kg/cm 2
4. Environment : Suitable for indoor and outdoor use.
5. Electric Switch : One SPST Mercury Switch.
6. Contact Rating : 5 Amps 240V AC. 0.5 Amp 240V DC.
7. Switch Operation : Normally open, closes when oil level drops to near empty condition.
Switch recovers automatically on rising of oil level.
8. Weight & Dimensions : See table 1 in fig. 1.
FIG. 3
Metallic Wall
Cam
Float
Pointer
SCHEMATIC
FIG. 4 DETAILS OF MOUNTING PADS
Note:
1. The mounting pad is not in
our scope of supply. Hence only
important dimensions are shown.
Model SO-4 Model SO-6
2. Pad should be welded to conservator
6 STUDS 8 STUDS wall with correct orientation.
M 10 ON 165 PCD M 10 ON 209.7 PCD
A=31 B=120 A=31 B=165 3. Use gasket of 4 to 6 mm thickness.
C=130 D=190 C=175 D=236
FIG. 5 APPLICATIONS
Conservator
Air-cell
Float
MOG