Check List for UPS

Location: UPS Rating : UPS No.


Sl. No Description YES NO REMARKS
1 Isolate the incoming source and apply LOTO.
2 Make sure that supply is not available at the i/p terminal of the equipment

3 Provide cap for all the Fire detectors inside the UPS room before cleaning work is carried out.

4 Check genral cleanliness and wipe clean the panel surface if necessary.
5 Check and ensure all the cooling fans for UPS are working
6 Check all the batteries connection tightness.
7 Visually inspect batteries for cracks, leaks or corrosion.
8 Check and ensure the double earthing of UPS, Battery rack and Distribution panel
9 Clean the switchboard surface to remove debris and dust.

10 Check lighting, sockets, emergency lighting of the UPS room

11 Check and re-tighten any lose bolts and nuts in proper sequence.

Check and Record the batteries individual Voltage and total voltage (Note: Switch off the incomer supply to UPS before taking readings)

1 5 9 13 17 21 25 29 Remarks
12
2 6 10 14 18 22 26 30
3 7 11 15 19 23 27 31
4 8 12 16 20 24 28 32 Total Voltage :

Check and ensure the Voltage, load current of the Distribution board switches

DB - DB - DB - DB - DB - DB- DB-

13 Ph-N(V) Ph-N(V) Ph-N(V) Ph-N(V) Ph-N(V) Ph-N(V) Ph-N(V)


Ph-Ph(V) Ph-Ph(V) Ph-Ph(V) Ph-Ph(V) Ph-Ph(V) Ph-Ph(V) Ph-Ph(V)
N-E(V) N-E(V) N-E(V) N-E(V) N-E(V) N-E(V) N-E(V)
L (A) L (A) L (A) L (A) L (A) L (A) L (A)

PM Done by : Spares Used


Signature :
Inspected By :
PM done On :
Start Time :
End time :
Next PM due on :