You are on page 1of 6

THERMAL OVERLOAD

Parameter Values (Range) Unit Step Default

FUNCTION 0-1-2 1 1

DISABLED DURING START UP 0-1 0

THERMAL MODEL 0-1 0

T6 3-40 Sec 1 6

COOL COEFFICIENT 1-10 1 4


TOL ALARM LEVEL 60-100 % 1 90
TOL TRIP LEVEL 60-100 % 1 100
TOL RESET LEVEL 10-60 % 1 50
AMBIENT TEMPERATURE 0-80 C 5 40

STALL PROTECTION
Parameter Values (Range) Unit Step Default

FUNCTION 0-1 1 1

TRIP RESET MODE 2-3-4 1 4


TRIP LEVEL 120-800 % 10 400
TRIP DELAY 0-25 SEC 0.1 0.5

LONG START PROTECTION

Parameter Values (Range) Unit Step Default

FUNCTION 0-1 1 1
LOCKED ROTOR LEVEL 120-800 % 10 120
TRIP DELAY 0-250 SEC 0.1 10
TRIP RESET MODE 2-3-4 1 4

PHASE FAILURE PROTECTION

Parameter Values (Range) Unit Step Default

FUNCTION 0-1,3 1 0

ALARM 10-90 % 1 80
TRIP 10-90 % 1 70
TRIP DELAY 0-60 SEC 1 10
TRIP RESET MODE 2-3-4 1 4

UNBALANCE PROTECTION

Parameter Values (Range) Unit Step Default

FUNCTION 0-1,3 1 0

ALARM 50-90 % 1 90
TRIP 50-90 % 1 85
TRIP DELAY 0-60 SEC 1 10
TRIP RESET MODE 2-3-4 1 4

UNDERLOAD PROTECTION

Parameter Values (Range) Unit Step Default

FUNCTION 0-1,3 1 0

ALARM 20-90 % 1 30
TRIP 5-90 % 1 20
TRIP DELAY 0-1800 SEC 1 10
TRIP RESET MODE 2-3-4 1 4

EARTH FAULT PROTECTION


Parameter Values (Range) Unit Step Default

FUNCTION 0-1,3 1 0

ALARM 100-3000 mA 100 500


TRIP 100-3000 mA 100 800
TRIP DELAY 0.2-60 SEC 0.1 10
TRIP RESET MODE 2-3-4 1 4

START LIMITATION PROTECTION

Parameter Values (Range) Unit Step Default

FUNCTION 0-1 1 0

TIME INTERVAL 1-600 MIN 1 1


NUMBER OF STARTS 2-100 1 2
Description

0=DISABLED; 1= ENABLED; 2=
DISABLED DURING START

0=ENABLED DURING START UP;


1= DISABLED DURING START UP

0=STANDARD MODEL; 1= EEXe


MODEL

Trip time for current IL


max=6xIn from the cold state

TIMES START TIME CONSTANT


THERMAL OL ALARM LEVEL
THERMAL OL TRIP LEVEL
THERMAL OL RESET LEVEL
AMBIENT

Description

0=DISABLED; 1= ENABLED;

2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
STALL PROTECTION TRIP
STALL AFTER START UP

Description

0=DISABLED; 1= ENABLED;
ROTOR LOCKED DURING START UP PROTECTION TRIP
LONG START UP TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE

Description

0=DISABLED; 1= ENABLED; 3=
ALARM ONLY

IL MIN/ILMAX
IL MIN/ILMAX
PHASE FAILURE TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE

Description

0=DISABLED; 1= ENABLED; 3=
ALARM ONLY

IL MIN/ILMAX
IL MIN/ILMAX
UNBALANCE PROTECTION TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE

Description

0=DISABLED; 1= ENABLED; 3=
ALARM ONLY

IL MAX/IRATED
IL MAX/IRATED
UNDERLOAD PROTECTION TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description

0=DISABLED; 1= ENABLED; 3=
ALARM ONLY

I0
I0
EARTH FAULT TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE

Description

0=DISABLED; 1= ENABLED;

TIME INTERVAL FOR NUMBER OF STARTS


NUMBER OF STARTS WITHIN THE DURATION