6.1 Building Automation with Desigo 118
6.2 Heating, Ventilation,
Air Conditioning (HVAC) 120
6.3 Planning Notes for
GAMMA instabus (KNX / EIB) 123
6.4 Power Management 125
6.5 SICAM Power I&C System 134
6 Building Management, Comfort and HVAC
To allow for a better structuring of the diversity of techni- . Infrastructural building management comprises,
cal systems, it is worth taking a closer look at the various among other things, systems for the maintenance of the
building management tasks. Usually, the following three building, e.g. the facility management systems (FMS)
task areas are distinguished: which manage the maintenance of the technical
facilities.
. Commercial management is performed by specialized
systems which support the company's business . Technical building management comprises the
processes and comprises various subareas from building automation and security management. While
purchasing to logistics to sales and maintenance. These the building automation deals with, for example,
systems are more or less integrated, depending on the heating, ventilation, air conditioning (HVAC), light and
solution, and can be combined under the name ERP lifts, the security management deals with fire detection,
(Enterprise Resource Planning). Among the most well burglar alarm, access control, video surveillance, and
known companies in this field are SAP and Oracle, for other security topics.
example.
Openness by standards
6.1 Building Automation with Desigo
6 Building automation and security management are part of
To support open communication, standard interfaces and
protocols such as BACnet, KNX / EIB Profinet and others are
the technical building management. provided for a direct integration of subsystems into the
management station.
The main task of the technical building management is the
management of the subsystems. This comprises in particu- Economic efficiency
lar the central monitoring and operation of the subsystems
but also the option of visualization, archiving, logging, and Functionality and user-friendliness are supposed to reduce
evaluation. operating expense and training time and increase the
productivity at a simultaneously high operational safety.
The pyramid shown in Fig. 61/1 reflects the data concen-
tration which arises from one level to the next: The field
level acquires a great deal of information of which, how-
ever, only the relevant part is passed on to the next level. A Planning of
typical example for that are intelligent fire detectors which the company
continuously record the smoke density and temperature, resources
(ERP)
for example, but only periodically signal a degree of dan-
ger to the control center, and only in the case of an alarm
Technical
immediately report the event to the control center.
building
management
Main requirements for a building management system
Automation
Scalable system structure
level
When selecting a building management system (BMS), it
must be made sure that it provides sufficient support for
future alterations and extensions. The stepwise expand- Field
ability of a system and the correspondingly simple and level
efficient system expansion form a central quality charac-
teristic. Total Building Solutions
. Time programs The customer / user must define objectives, this serves as a
Central programming of all time-controlled building basis for the preparation of a requirements specification.
functions. The definition of objectives comprises the following ele-
ments:
. Alarm handling
Detailed overview of the alarms for a fast localization . Scope of the building automation and security
and elimination of faults. Central elements of the alarm management subsystems to be integrated.
handling are therefore the danger identification, danger
alarm and an adequate intervention. This is supported . Definition of the integration:
Combining all subsystems of building installations (fire
by the flexible transmission of alarms to mobile devices,
alarm, gas warning, burglar alarm, access control or
e.g. printers or pagers.
video surveillance, HVAC systems, lighting, and further
. Event control external systems) by integrating them into a building
System-wide monitoring of systems and processes with management system brings the following advantages:
regard to the occurrence of certain criteria for the Improved overview and thus increased safety.
triggering of certain predefined actions. Lower costs in comparison to several independent
. Reporting control centers with regard to acquisition,
6
Modern management stations today work with configuration, and maintenance.
integrated database applications. This allows for the Consistent operational concept and thus less training
storage of an almost unlimited number of past events time and effort, and no danger of confusion in an
and their recorded handling. With these plant-specific emergency.
records and the corresponding query options, the Only one system has to be integrated into the in-
following questions can be answered, for example: house IT infrastructure.
What has happened in the past 24 hours? Interactions between the subsystems are possible in a
How many interferences occurred within a certain much easier way.
period? Alarm escalation and alarm transmission is done in a
Who has done what and when following yesterday's more uniform way.
burglar alarm? Integrated video systems allow for a direct view of the
To provide this main function, a whole range of additional fault cause.
functions is required, which so to speak forms the infra-
structure of the building management system. The most The objective is therefore to integrate all subsystems as
important of these additional functions are, for example: completely as possible into the building management
access rights concept, user administration, password system.
administration, object management in tree and graphic
structures, and graphic level management. . Expected improvements compared to a single-system
solution.
. Conceptual solution (block diagram) with regard to the . Stringent demands on temperature and humidity
networking of the subsystems and management system . Interior rooms, assembly rooms
to be connected
. High thermal loads
. Specification of the graphical user interface with the
objective to obtain a uniform picture for the entire . EDP, machine rooms
building and all installations, with the same detail
sharpness and the same information content as well as Tasks of the HVAC systems
the same viewing angles and brightness.
Depending on the purpose, the tasks of the HVAC systems
Framework conditions can be subdivided in two subareas:
6
In winter, the internal gain of heat can be recovered as
heat contribution and thus the energy consumption be
reduced. Whereas in summer, considerable amounts of
energy have to be employed for cooling.
80 Watt 100 Watt 110 Watt 120 Watt 170 Watt 300 Watt 700 Watt
6
Preparation damp 2226 7585
Production damp 2124 5565
Confectionery
Candy production dry 2427 3545
Chocolate production cool 1825 5060
Museum / paintings constant humidity 1824 4055 20-fold
Indoor swimming pool comfortableness 2630 6070 34-fold
Low buildings
Gymnasium and festival hall comfortableness 2224 45 20-fold
Restaurant comfortableness 2226 4060 540-fold
High-precision assembly small tolerance 21 40
Sewing works comfortableness 2226 50
Department stores 2026 4560 46-fold
Laboratory / chemistry 2224 50 815-fold
Laboratory / physics 2224 (20 const.) 45
Special laboratory 1040 1595
In the planning and implementation of functional and Coordinated room management based on
industrial buildings, future fault-free, cross-function-net- GAMMA instabus
worked and demand-oriented operation as well as the
careful use of energy are considered important criteria for Conventional solutions for the control of lighting, shading
the economic efficiency of the real estate investment. and heating / ventilation / air-conditioning are restricted to
one installation each so that interdependencies between
Conventional electric installations alone can only meet the different installations are not taken into account. Only
such requirements to a limited extent and at the expense the use of the building management technology allows for
of increased labor and material cost. For this reason, a stronger integration of the control of different installa-
planning engineers and investors increasingly opt for tions in the room at justifiable costs.
building management technology in the global KNX / EIB
standard, which complies with EN 50090. With a coordinated room management based on the
building management technology KNX / EIB (Fig. 63/2), the
The use of GAMMA instabus offers the following: use of energy for lighting and room temperature control
over the entire operating time can be reduced by half
. High degree of flexibility for planning and installation
6
compared to conventional systems and that at the same or
thanks to a modular system design. higher comfort!
. Integration of different installations and OEM products
thanks to the global KNX / EIB standard based on Therefore, for the cost-optimized operation of energy-effi-
EN 50090. cient buildings as requested by foresightful investors with
regard to the increase of the property value, a coordinated
. Short installation times due to straightforward wiring room management based on GAMMA instabus is the only
and cable routing.
possible solution.
Design using
KNX/EIB
Sensors
(command
KNX /EIB transmitters)
Fig. 63/1: Cost gradients of conventional and Fig. 63/2: Actuators and sensors in the KNX / EIB system
KNX / EIB installations when comfort and
functionality are increased
.................................................................
Owner / developer:
.................................................................
.................................................................
Planning engineer:
.................................................................
.................................................................
Degree of protection:
.................................................................
Functions: .................................................................
. Provide the required components with interfaces for . Acquisition for status and measurements
measurements and sensors.
. Processing
. Use standardized bus systems and communication- . Operator control and monitoring with visualization,
capable devices.
archiving, reports, import optimization and control of
. Ensure expandability (e.g. expandable cable laying and switchgear
installation of transformers in cabinets) to keep
interruptions during operation at a minimum. The data acquisition level is connected to the processing
6
level by means of field buses and the processing level
communicates with the visualization system and data
Power management system archive via LAN (Local Area Network) (Fig. 64/1).
The focus of a power management system is on the re-
quest for improved transparency of energy consumption The acquired status information is depicted on the status
and energy quality as well as on ensuring the availability of displays in the control center, thus enabling remote con-
power distribution. An all-round transparency is the basis trol. Measured value readings are displayed.
for an optimization of energy costs and consumption. The
obtained information provides a realistic basis for a cost
center allocation as well as for measures to improve the
energy performance. Moreover, savings are documented.
. Operation and configuration For the various levels and components of power distribu-
tion (Fig. 64/2), it has to be taken into account which
Energy import monitoring measurements and messages are required during opera-
tion as well as the various requirements for:
. Load management system
. Critical areas / consuming devices (availability)
Data analyses
. Billing values (plausibility, contract monitoring, cost
. Consumption / cost allocation according center management)
to the user pays principle
. Transparency for operation (measured values, status)
. Logs
. Utilization (expansions, energy import monitoring)
6 . Data export
Energy procurement
nd
na
na
sig
sig
ou
gr
d'
d'
t
pe
pe
r/
ics
lis
re
cto
rip
rip
on
cle
tu
et
et
du
rm
ra
cy
us
us
on
pe
ha
g
/ 'F
/ 'F
FF
d
in
lc
m
F
Vo t
e
nt
ed
ed
at
n
/O
/O
te
ra
lo
r
re
rre
we
lta
er
ut
er
er
pp
pp
ur
N
N
Op
Ov
Ov
Ne
Cu
Po
co
Tri
Tri
O
Transformer
Tapping (primary)
Feeders
Supply
Cables
Supply
Feeders
M Consuming
devices
Fuse-protected switchgear:
Number of switch-disconnectors
Number of status information items per switch-disconnector
Total number of status information items
(for all circuit-breakers) ...................................................................
Measurements:
Number of measuring points
Number of current transformers required ..................................................................
Measuring instruments:
6
Multi-function measuring instruments
(total / measured values per device) ..................... / ...........................................
Electricity meters
(total / measured values per meter) ..................... / ...........................................
Motor management systems
(total / measured values per device) ..................... / ...........................................
Circuit-breakers
(total / measured values per breaker) ..................... / ...........................................
Measurements for other energy types
(number of measured values) ..................... / ...........................................
Measurements Total number of measured values
(of all measuring instruments) ..................... / ...........................................
Plant diagrams:
Number of overview diagrams
Number of diagrams per energy type
Total number of diagrams (of all energy types) ...................................................................
Load management:
Number of electrical consumers
Number of consumers for every other energy type
Total number of import monitoring items
(of all energy types) ...................................................................
The basis of each power management system are the 4 L1 L2 L3 Status display Control
measured values and data from the field level in which the U U<
Monitoring
energy in consumed. A large number of devices can already - ON / OFF
be evaluated via bus systems such as Profibus by a power 3 M 1 - Tripped
management system with regard to some specific data. - Withdr. unit IN
2 ETU Operating
OFF
- OFF
Circuit-breaker-protected switchgear: circuit-breakers - ON / OFF ON
5
(Reset)
Circuit-breaker-protected switchgear can be equipped or
retrofitted with the following signals (Fig. 64/3):
Fig. 64/3: Circuit-breaker-protected switchgear
The auxiliary ON / OFF switch signalizes the status of the
circuit-breaker, ON or OFF.
Control center
The alarm switch signalizes whether the breaker has
tripped. L1 L2 L3 Status display Control
Monitoring
The motorized drive acts on the switching rods and - ON / OFF
permits remote control of the breaker. - Tripped
6 7
6
leases switch when voltage is applied, undervoltage
releases switch when voltage is interrupted. Fig. 64/4: Fuse-protected switchgear
Control center 1
1 UL3-N UL2-3 UL2-N IL3 IL2
The visualization screen shows the circuit-breaker status Phase displacement Power / Work
with the aid of the pictograph ON / OFF / tripped / with- cos L1 P
drawable unit pushed in and additionally by means of the Q
color coding for event / fault / acknowledged / not acknowl- 2
cos
S
Measuring instruments acquire current and voltage values Voltage characteristics acc. to EN 50160
Voltage
in the electric power distribution and, according to their
specified scope of performance, they perform the follow- Voltage dip
ing calculations (Fig. 64/6): wattages, phase displacement, Voltage change
Short-time/long-time interruption
work, and voltage characteristics in line with DIN EN 50160 Flicker
Overvoltages
(Voltage characteristics of electricity supplied by public Harmonic content
distribution networks).
Fig. 64/6: Typical measured values in electric power distributions
Multi-function measuring instruments
Built-in device for electric power supply systems with direct . E-meter for 3- / 4-wire connection; multi-rate meter
measurement display large back-lit high-resolution graphic Drum-type registers for electricity consumed (kWh) for
display, suitable for connection in three-phase networks, in high-rate and low-rate price
3-wire and 4-wire design, for identical loads or different S0 interface (pulses) per rate type
loads, also suitable for single-phase networks, for indus-
trial networks up to 3~690 / 400 V (e.g. SENTRON . Multi-meter
PAC4200).
Built-in modular device for electric power distribution
6
Parameterization can easily be performed by either using systems with direct measurement display large back-lit
the front keys on the instrument panel or the PC-based graphic display, suitable for connection in three-phase
parameterization software. The number of measuring networks, in 3-wire and 4-wire design, for identical loads
screens and their contents, i.e. measured quantities, can or different loads, also suitable for single-phase networks.
be configured by the user as desired.
Measured quantities:
The instrument has parameterizable digital inputs / outputs
for counter / energy pulses, status monitoring, limit-value . R.m.s. values of phase currents and voltages
violations, measuring period synchronization, high
rate / low rate changeover, switching to remote control via
. Network frequency
system software. . Active power per phase and for the entire system
Measured quantities: . Apparent power per phase
. R.m.s. values of phase currents and voltages, PEN . Reactive power for the entire system
conductor current
. Power factor for the entire system
. Network frequency . Active energy import, export for the entire system at
. Active, reactive, and apparent power per phase and for high-rate and low-rate price
the entire system
. Reactive energy, inductive and capacitive, for the entire
. Electricity meter for high-rate and low-rate price system at high-rate and low-rate price
. Power factor per phase and for the entire system . Apparent energy for the entire system at high-rate and
low-rate price
. Symmetry factor of currents and voltages
If the meters are to be used for accounting energy quanti-
. Harmonic contents of voltages and currents ties, meters which are suitable for an accurate recording of
. Total harmonic distortion (THD) consumptions are required (meters have to be re-
placed / calibrated at regular intervals). These meters must
Electricity meters be identified separately.
6000
. Presentation of different, general switch types via
kW
pictographs (e.g. in the single-line diagram) 5000
6
of views.
2000
96
192
288
384
480
576
672
hours
In addition to the display of the system status in the con-
trol system, e.g. in a single-line diagram, and the reports,
Fig. 64/8: Load curves for electric power distribution
the time-based evaluation of measured values and status
changes provides a basis for the assessment of the con-
suming device with regard to efficiency. Load curve dia-
grams are timely accurate representations with the corre-
sponding selected periods for measured values, and CMD switch ON
operating cycle lists likewise represent status changes. The CMD switch OFF
presentation of these archived values is done with stan- CMD shunt trip
Switch is N
dard means of the control system.
Switch is OFF
Tripped
Load curves Withdrawable unit
is pulled out
00:00
00:15
00:30
00:45
01:00
01:15
01:30
01:45
02:00
02:15
02:30
Switching
Actual-value display P [kW]
T7.3 110 A
Limit value display
As an active component to the functions for status moni- Monitoring status Operating cycles list
Q12.4
toring, general switches are provided with operating ON / OFF
Fuse tripped local
ON / OFF
functions for switching in addition to the switching status tripped
t
6
Date ident. Time ident. Site ident. Plant ident. Device ident. Function ident. Event text
2000.01.14 22:59:03 Hall B Infeed Q1.0 local OFF Infeed switch switched off locally
2000.01.14 23:16:24 Hall B Infeed Q1.0 local ON Infeed switch switched off locally
1 Consumer a ON OFF
2 Consumer b
3 Consumer c
Energy import monitoring
release
P
Release
Blocking
. Switching and / or signaling according to priority list for In addition to this, reports on energy data can be gener-
consuming devices ated with standard means on the control system via open
. Rolling switching of consuming devices interfaces.
. Configuration to adapt to the given process conditions These can then also be combined to comprehensive re-
ports with the other acquired data of the system (status,
. Characteristic data for system or consumption behavior measurements) (Fig. 64/13).
(e.g. hysteresis, delay, off-time, ON / OFF switching
times)
11:14:00 04:11:2006
powerrate Reporting
Time setting
End Time: 13:16:00 04:11:2006
Time Aggregation: None Start Time: 11:16:00 08:11:2006
140
120
100
80 0 600,00
60
40 0 500,00
20
Consumption [kWh]
0 0 400,00
0 20 40 60 80 100 120 140 160 180
Analyses 0 300,00
0 200,00
0 100,00
SIEMENS 11,18 15,32 14,11 8,95 18,93
0 000,00
Cost center 1 Cost center 11 Cost center 21 Cost center 30 Cost center 32
Cost center
powerrate Reporting
A power management module provides various preconfig- Time setting
Consumption [kWh] Costs []
Consumption data
6
Exports
Cost center 1
Cost center 1
Consumption [kWh]
0.319,32
Costs []
11,18
Reports
Cost center 11 0.437,66 15,32
Cost center 21 0,403,10 14,11
Cost center 30 0.255,72 8,95
Cost center 32 0.540,99 18,93
For the creation of predefined standard reports and the Total 1.160,07 40,60
6
supply as a whole. Our starting point is the supply by your
power utility company or the generation in your own It goes without saying that your energy automation system
power plant. With suitable and correctly dimensioned is optimally integrated in your system environment. For
medium-voltage switchgear and a reliable low-voltage interfacing to and exchange of information with other
power distribution, we are able to adapt your power supply systems important for the operation of the installation,
exactly to your requirements for a safe and profitable e.g. building automation, we use OPC (OLE for Process
operation. Control). Interfacing to higher-level control systems can
also be implemented via an IEC 60870-5-101 or
More power in the system IEC 60870-5-104 protocol. To ensure defined values for
failure safety and availability, parts of our systems can be
An integrated energy automation system comprises all designed redundantly, depending on your requirements. It
systems from the supply input of the local power utility to goes without saying that we also provide concepts and
the integration of the emergency power supply and the solutions for a high degree of availability with regard to
low-voltage level. Additionally, important signals of the the other components used (PCs, switches, control sys-
building automation system can also be displayed in the tem).
same system.
Remote access
Building
automation GPS Printer Router Firewall
system Corporate
network
6
Low-voltage main distribution Low-voltage main distribution Low-voltage main distribution
Fig. 65/1: Our solutions integrate all voltage levels and all the information required from the environment of the power supply in a
system
System integration
6
We are represented in almost all countries in the world and
High reliability of supply on all continents. With this global network, we are able to
support you in the implementation of a customized energy
Reduce the risk of supply interruption by specifically dis- automation virtually all over the world.
connecting less important installation components. Built-in
load shedding functions support you in the case of insta-
bilities of the power supply (e.g. unbalanced loads or
overloads).
c Alarm management
Project data:
c Archiving
c Name
c Monitoring and control (SCADA)
c End customer
c Power management
c Planning engineer / EPC / consultant
c Cost center allocation
c Installation type
c Load shedding
c City / Country
c Load management
c New project
c Switching sequences
c Expansion
c Fault record processing
Existing documentation: c Synchronization
c Single-line c ........................................
c Topology plan
Preferred system: 6
Systems to be connected or possibly already existing c Software solution (PC-based)
(manufacturer):
c Hardware solution (subrack-based)
c Protection
c ........................................
c Substation automation
Required communication protocols:
c Power quality
Topology: c Modbus
c Number of signals / IOs (digital / analog) c Distance bay devices control system . . . . . . . . . . . m
c Radio
.................................................................
c Serial
.................................................................
c ........................................
.................................................................
Visualization system Human Machine Interface (HMI):
.................................................................
c Number of control centers
.................................................................
c Number of local workplaces
.................................................................
c Option for laptop connection
c ........................................ .................................................................
c Redundancy .................................................................
c Firewall
6
.................................................................
c Security
.................................................................
c Explosion-proof area
.................................................................
c Special environmental conditions
(e.g. temperature / humidity)
.................................................................
c ........................................
.................................................................
Schedule / dates:
.................................................................
c Invitation to tender / concept
.................................................................
c Submission of quotation
.................................................................
c Commissioning
c ........................................ .................................................................
c Name .................................................................
c E-mail
.................................................................