Project : COURTS AND NOTARY

Date: 20-Feb-17

General Cable Total Approx. % Total


Correction Factors Voltage
Area/ CIRCUIT Demand Demand Size No. of Standard Total Effective Length Voltage Voltage Voltage
Drop
Services Location NO. Load Load ( mm2 ) Cable CCC Standard CCC Air Ground CCC L Drop Drop Drop
Services ( KVA ) ( Amp. ) Table-16 or Sets (Amps.) (Amps.) (Amps.) (Meter)
KT Kgrp Kdpth Krsoil Kgrp mV/A/m mV/A/m Percent % Percent %
( XLPE )

LVS
LVS SCECO ROOM MAIN 399.29 607 1CX630 2 848 1696 1 1 0.95 0.95 0.55 842 20 0.153 0.077 0.24 0.24
EMDB SCECO ROOM 87.32 133 4Cx300 1 580 580 1 1 0.97 0.95 0.63 337 16 0.206 0.206 0.12 0.36
SMDB GROUND FLOOR 71.66 109 4CX150 1 390 390 1 1 0.97 0.96 0.63 229 50 0.316 0.316 0.45 0.70
SMDB-A/C GROUND FLOOR 216.58 329 4Cx185 2 469 938 1 1 0.97 0.95 0.63 545 52 0.273 0.137 0.61 0.86
FIRE PUMP PUMP ROOM 44.74 68 4CX70 1 247 247 1 1 0.97 0.95 0.63 143 52 0.574 0.574 0.53 0.89