You are on page 1of 2

Section 2 1MRK 502 047-UUS A

Application

2.2 Available functions

2.2.1 Main protection functions


IEC 61850 or ANSI Function description Generator
Function name

REG650 (B01A)

REG650 (B05A)
Gen+Trafo diff
REG650

Gen diff
Differential protection
T3WPDIF 87T Transformer differential protection, three winding 01 1
REFPDIF 87N Restricted earth fault protection, low impedance 01
HZPDIF 87 1Ph High impedance differential protection 01 1 1
GENPDIF 87G Generator differential protection 01 1
Impedance protection
ZMRPSB 68 Power swing detection 01
ZGCPDIS 21G Underimpedance protection for generators and transformers 01 1 1
LEXPDIS 40 Loss of excitation 01 1 1
OOSPPAM 78 Out-of-step protection 01 1 1
LEPDIS Load encroachment 01 1 1

2.2.2 Back-up protection functions


IEC 61850 or ANSI Function description Generator
Function name
REG650 (B01A)

REG650 (B05A)
Gen+Trafo diff
REG650

Gen diff

Current protection
OC4PTOC 51/67 Four step phase overcurrent protection, 3-phase output 02 2 2
EF4PTOC 51N/67N Four step residual overcurrent protection, zero/negative 02 2 2
sequence direction
SDEPSDE 67N Sensitive directional residual overcurrent and power protection 01 1 1
TRPTTR 49 Thermal overload protection, two time constants 02 2 2
CCRBRF 50BF Breaker failure protection, 3phase activation and output 01 1 1
CCRPLD 52PD Pole discordance protection 01 1 1
Table continues on next page

26
Application manual
1MRK 502 047-UUS A Section 2
Application

IEC 61850 or ANSI Function description Generator


Function name

REG650 (B01A)

REG650 (B05A)
Gen+Trafo diff
REG650

Gen diff
GUPPDUP 37 Directional underpower protection 01 1 1
GOPPDOP 32 Directional overpower protection 02 2 2
AEGGAPC 50AE Accidental energizing protection for synchronous generator 1 1 1
NS2PTOC 46I2 Negative-sequence time overcurrent protection for machines 1 1 1
VRPVOC 51V Voltage-restrained time overcurrent protection 1 1 1
Voltage protection
UV2PTUV 27 Two step undervoltage protection 01 1 1
OV2PTOV 59 Two step overvoltage protection 01 1 1
ROV2PTOV 59N Two step residual overvoltage protection 02 2 2
OEXPVPH 24 Overexcitation protection 01 1 1
STEFPHIZ 59THD 100% Stator earth fault protection, 3rd harmonic based 01 1 1
Frequency protection
SAPTUF 81 Underfrequency function 04 4 4
SAPTOF 81 Overfrequency function 04 4 4
SAPFRC 81 Rate-of-change frequency protection 02 2 2

2.2.3 Control and monitoring functions


IEC 61850 or Function ANSI Function description Generator
name
REG650 (B01A)

REG650 (B05A)
Gen+Trafo diff
REG650

Gen diff

Control
SESRSYN 25 Synchrocheck, energizing check, and synchronizing 01 1 1
SLGGIO Logic Rotating Switch for function selection and LHMI 15 15 15
presentation
VSGGIO Selector mini switch 20 20 20
DPGGIO IEC 61850 generic communication I/O functions double 16 16 16
point
SPC8GGIO Single point generic control 8 signals 5 5 5
AUTOBITS AutomationBits, command function for DNP3.0 3 3 3
Table continues on next page

27
Application manual

You might also like