An electronic temperature transmitter (4-20mA dc) is calibrated to a range of 0C to 1000C.

The signal output is 8mA dc. What is the measured temperature?

An electronic temperature transmitter (4mA to 20mA DC) is calibrated to a range of -100C


to 300C.
(a) What is the measured temperature when the signal output is 12mA?
(b) What is the equivalent current when the temperature is -50C.
A differential pressure transmitter is calibrated 0 to 50 inches of water and transmits a 4 to
20 mA d.c. signal. This transmitter, is placed across an orifice plate which is sized to create
50 inches of water differential at 5 gallons per minute, What s the flow rate when the signal
is 12mA d.c. ?

A differential pressure is used to measure level of water in a tank. If the transmitter is


calibrated to measure levels from 20 cm to 80 cm, what will the transmitter output when
the level of water is at 45 cm?
In the measurement of level of water (range of 5m to 30m), using a pressure to current
transmitter, a level of 5m corresponds to a current of 4 mA. Determine the current for a
level of 25m.

The flow rate of a liquid flowing in a pipe is measured using a restriction based flow
measurement system.

a) Write the equation relating the pressure drop across the restriction and the flow
rate.
b) If a flow rate of 10 m^3/sec corresponds to a pressure drop of 8 psi, what will be the
flow rate when the pressure drop is 13 psi?
If an input signal of 6 mA d.c. is injected to an electro/pneumatic converter, what is the
output signal in psi?

A tooted-rotor tachometer has a rotor of 12 teeth. If the tachometer output shows a total of
629 pulses, how many revolution has the rotor made?

1 rev = 12 pulses ----- (1)


n rev = 629 pulses ----- (2)

(2)/(1) n rev/1 rev = 629 pulses/12 pulses


n = 52.42 pulses
n = 52 rev
A temperature sensitive device is connected in a circuit shown in figure B2. The resistance of
the temperature sensitive device is 4k at 60C and the temperature coefficient is 8%/C at
60C. Identify the type of temperature sensitive device being used in this application and
calculate the amplitude of the output voltage at 70C.
A J-type thermocouple has an e.m.f. output of 16.88mV at temperature 310C with 0C as
its reference. The e.m.f output of the same thermocouple at 315C is 17.15mV. Calculate
the measured temperature if the e.m.f output of the thermocouple is 16 16.92mV.

A K-type thermocouple was used to measure an unknown temperature. If the output e.m.f
and the cold junction temperature were 5.33mV and 25C respectively, calculate the
unknown temperature.
The circuit shown below is used to measure the temperature of gas in a particular process.
The thermistor has a resistance of 10k at 50C and a negative temperature of 3%/C at
50C. The thermistor forms part of a resistance bridge circuit and its resistance deviation
from the nominal 10k can be picked up by the voltage signal Vdb. If the temperature of
the gas is 55C. What is the voltage output Vdb.
The bridge shown in the diagram has R1 = 100 and R2 100. It was balanced at 100C and
at 200C with the values of the variable resistance R3 of 25 and 30 respectively.
Calculate the temperature coefficient of resistance of the element of 200C.