Professional Documents
Culture Documents
II. PARALLEL RLC LOAD FREQUENCY CHARACTERISTICS that a load with f0 < fg is net capacitive at the grid frequency
because the current leads the voltage (load > 0 ). Conversely,
The values of the frequency and magnitude of the voltage at a load with f0 > fg is net inductive at the grid frequency.
the PCC after grid disconnection (islanding condition) depend
heavily on the local load characteristics. This section presents III. NDZ FOR FREQUENCY DRIFTING ACTIVE IDMS
some equations related to the load that are required to analyze
the operating principles and assess the performance of common The operating principles of active IDMs are frequently pre-
frequency drifting active IDMs. sented for the worst-case condition of the passive UFP-OFP and
According to the IEEE Std 9292000 [1], the quality factor UVP-OVP IDM, that is, under zero power imbalance or mis-
Qf is defined as 2 times the ratio of the maximum stored match for rated grid voltage and frequency. In such a case the
energy to the energy dissipated per cycle at a given frequency. magnitude and frequency of the voltage would remain constant
For a parallel RLC load after grid disconnection.
One economically attractive strategy to implement active
2 12 CR2 I 2 R C IDMs is to attempt to drift the frequency or the magnitude of
Qf = = 0 RC = =R (1)
RI 2 /0 0 L L the voltage at the PCC outside the allowed normal range of the
parameters that are set in the UFP-OFP and UVP-OVP. Recall
where 0 = 2f0 = (1/ LC) is the angular resonant fre- that these devices are mandatory for grid connected inverters
quency of the load. and they would provide the capability to shut down the inverter
The magnitude and phase of the impedance of a parallel RLC with no additional cost for added components [1].
load at an arbitrary frequency f , as a function of the quality The steady state value of the magnitude Vis and frequency fis
factor Qf and resonant frequency f0 of the load, are given by of the voltage in an islanded system with a local load represented
1 R by an RLC circuit can be calculated from the power balance
|Zload | = 2 = 2 (2) equations:
1
R2 + 1
L C 1 + Q2f ff0 f
f0
Vis2
PLoad,is =
R
= PINV (4)
1 2 LC f0 f
load = tan1 R = tan1 Qf . 2
L f f0 Vis2 f0
QLoad,is = 1 = QINV (5)
(3) XC ,g fis
It can be shown that the magnitude of the load impedance where the subscript is refers to the islanding condition and the
changes very little with frequency for loads with Qf < 2.5. subscript g to the grid connected condition.
Because the normal frequency limit according to IEEE Standard One sees in (4) that Vis depends only on PINV and R. Voltage
9292000 is relatively small (59.4 Hz to 60.5 Hz), it is assumed drifting under islanding conditions can be achieved by varying
that the voltage magnitude does not vary with system frequency. PINV , but is not very practical because Vis varies with the square
The load phase angle load (load = load ) versus fre- root of PINV . Thus, a significant variation of PINV is required
quency characteristic curves of loads with different quality fac- to trip the UVP-OVP [4]. However, assuming that Vis depends
tors and different resonant frequencies, f0 , are shown in Fig. 2. only on PINV and R, one can control and drift fis by varying
The curves show that for a larger Qf , there is a larger variation QINV as shown in (5). A positive feedback for frequency drifting
of load for a variation of the system frequency around f0 . In under islanding conditions can be implemented by varying the
addition, the intersection of the load versus f curves and the angle of the current, as in the SMS IDM, as a function of the
zero phase angles always takes place at f0 . Further, one can see frequency deviation from the rated value.
LOPES AND SUN: PERFORMANCE ASSESSMENT OF ACTIVE FREQUENCY DRIFTING ISLANDING DETECTION METHODS 173
f0 fis f
The passive IDM method is mentioned as a reference to be tan1 Qf = . (9)
used for comparison with the active IDMs. As discussed earlier fis f0 fis + f
and according to (5) whenever the load is supplied by a stand- Thus,
alone inverter operating with current control and unity power
fis tan[AFD (fis )]
factor, the frequency of the system will be the resonant frequency f02 f0 fis2 = 0. (10)
of the load f0 . If fmin f0 fmax , UFP-OFP will not trip and Qf
islanding will occur regardless of the Qf of the load. The NDZ
of this method is included in the plots that present the NDZs of To calculate the NDZ of the AFD IDM, the islanding fre-
the active IDMs. quency is first adjusted to a threshold frequency (fmin or fmax ).
Then the value of Qf is varied and finally a calculation is made
of the resonant frequency of the load at the threshold of the
B. Active Frequency Drift IDM
NDZ. One can also use this equation in the design process, by
When the active frequency drift (AFD) method is used, specifying Qf , fmax , and f0 and then calculating f .
the waveform of the inverter current is slightly distorted, pre- Fig. 3 shows the NDZ of an AFD IDM for different values
senting a zero current segment for a drift-up operation. AFD of f for a normal frequency range of 59.3 Hz f 60.5 Hz.
can be implemented by forcing the current frequency to be Loads with values of Qf and f0 lying between the curves calcu-
f (<1.5 Hz) above the voltage frequency in the previous cycle lated with fis = fmin and fis = fmax are in the NDZ of a given
174 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 1, MARCH 2006
IDM. There one sees that the main effect of the AFD is to shift
the NDZ to lower values of f0 as f increases. For Qf = 2.5 and
f = 0.5 Hz the method will fail to detect islanding for loads
with 58.99 Hz f0 60.19 Hz. It can be shown that the size of
the range of the resonant frequencies f0 = f0 max f0 min for
which islanding occurs is the same as of the passive UFP-OFP,
1.2 Hz. Therefore, the use of the AFD IDM does not really seem
to result in an improved performance because the net capacitive
(f0 < 60 Hz) loads that would not yield islanding with passive
IDM (f = 0 Hz) actually cause islanding for speed-up AFD
IDM. However, this IDM can be quite effective for net inductive
loads. According to Fig. 3, no islanding would occur for induc-
tive loads with Qf < 2 if speed-up AFD IDM with f = 1 Hz
is used. For loads with high Qf this active IDM does not present
any improvement with respect to the passive UFP-OFP because
Fig. 4. NDZs of SMS IDM for different m and with fm fg = 3 Hz.
the frequency drifting capacity is significantly reduced.
Thus
C. Slip Mode Frequency Shift IDM fis tan[SMS (fis )]
f02 f0 fis2 = 0. (16)
SMS method applies positive feedback to the phase of the Qf
voltage at the PCC as a means of shifting the phase and hence The resulting NDZ for SMS IDM in the Qf versus f0 space
the short-term frequency [3]. The phase angle of the current is obtained from the solution of (16) is shown in Fig. 4 for different
controlled as a function of the deviation of the frequency of the values of m . There one sees that the NDZ is null for Qf <
last cycle fv k 1 from the nominal operating frequency of the 2.5 when m = 10 and fm fg = 3 Hz, as per the design
utility grid fg . That is, specifications. Besides, as m decreases, the load quality factor
for which islanding occurs also decreases. As for the previous
ik = 2I sin(2fv k 1 t + SMS ) (11) active IDM, the performance of this method is similar to that of
passive UFP-OFP (m = 0 ) for loads with high Qf .
f fg
SMS = m sin (12)
2 fm fg
D. Sandia Frequency Shift IDM
where fm is the frequency at which the maximum phase shift The Sandia frequency shift (SFS) IDM is based on the use of
m occurs. one zero-current segment (tz ) per line semicycle [3]. A positive
After grid disconnection, the frequency of the islanded system feedback is used to increase the chopping factor (cf), which is
will drift from the rated value fg if defined as the ratio of the zero time tz to half of the period of
the voltage waveform Tv /2. Thus
dload
dSMS
< . (13)
df
f =f g df
f =f g
2tz
cf = (17)
Tv
Thus, the following design equation can be derived for the with increasing deviation of the frequency away from nomi-
SMS AFD nal. The increasing deviation is usually selected to be a linear
function of the frequency of the PCC voltage
m 12Qf
(14)
fm fg 2 cf = cf 0 + k(f fg ) (18)
where Qf is the maximum value for which islanding has to where cf 0 is the chopping fraction when there is no frequency
be detected and fm fg is usually taken as 3 Hz so that sta- error and k is an accelerating gain. For a cf 0 = 0.05, the Total
ble operation points lie outside the normal frequency range. Harmonic Distortion (THD) of the inverter current is equal to
For achieving islanding protection for loads with Qf < 2.5 and 5% at the rated line frequency [8]. The main effect of the zero
SMS IDM with fm fg = 3 Hz, one calculates m = 10 . No- current segment is to advance the fundamental component of
tice that if Qf increases, m has to increase. This also increases the inverter current with respect to the voltage at the PCC. The
the reactive power that the inverter will have to supply or absorb inverter angle for the SFS IDM (SFS ) can be calculated as
at the limit values of grid frequency for the normal conditions tz cf(f )
(PF = cos SMS ). SFS (f ) = = . (19)
2 2
The NDZ of the SMS IDM in the Qf versus f0 space is The NDZ of the SFS IDM in the Qf versus f0 space is derived
derived using the phase criteria using the phase criteria:
reference current with the selected IDM and matches the local
loads active power. The UFP-OFP and UVP-OVP block mea-
sures the frequency and the rms value of the PCC voltage and
shuts down the inverter if the frequency or voltage at the PCC
exceeds IEEE Standard 9292000s limits for six line cycles.
Fig. 7. Islanding detection test for an inverter with f = 1 Hz AFD IDM and Fig. 8. Islanding detection test for an inverter with f = 1 Hz AFD IDM and
a local load with f0 = 60 Hz and Q f = 2.5. (a) PCC voltage, inverter current, a local load with f0 = 59 Hz and Q f = 2. (a) PCC voltage, inverter current,
and fault signal waveforms and (b) voltage frequency values. and fault signal waveforms and (b) voltage frequency values.
fPCC decreases. It becomes lower than the setting of the UFP comparison of the theoretical and simulated SMS NDZs. Here
at t = 0.4027 s that changes the fault signal to 1 shutting down one sees that the agreement between the simulated and the cal-
the inverter six cycles later. Thus, a load with f0 = 60 Hz and culated results is very good for all values of Qf . Further, the
Qf = 2.5 lies outside the SMS NDZ for SMS with m = 10 simulation results confirmed that there is no NDZ in the area
and fm fg = 3 Hz. This agrees with the theoretical results where Qf < 2.5.
shown in Fig. 4. By comparing Figs. 7 and 10, one sees that for
this load and parameters used for the AFD and SMS IDMs, the
first yields faster islanding detection. This can not be inferred C. Verification of the NDZs for the SFS IDM
from the load parameter space that represents only the steady- Fig. 12 shows the time domain response of the system with
state operation. Even so, in both cases islanding was detected base load and SFS IDM with cf 0 = 0.05 and k = 0.05. In this
within the 2 s required by the IEEE Std 9292000. case, the frequency at the PCC increases when the grid breaker
The theoretical boundaries of the SMS NDZ in the Qf versus opens, exceeding the set point of the OFP at t = 0.1626 s. Six
f0 space were verified by simulation following the same pro- line cycles later, the fault signal changes to 1, shutting down
cedure described in the previous subsection. Fig. 11 shows a the inverter. Thus, a load with f0 = 60 Hz and Qf = 2.5 lies
LOPES AND SUN: PERFORMANCE ASSESSMENT OF ACTIVE FREQUENCY DRIFTING ISLANDING DETECTION METHODS 177
Fig. 9. NDZs mapped by Laplace transform compared with simulation and calculation results.
Fig. 10. Time domain response of the system with SMS IDM supplying a Fig. 12. Time domain response of the system with SFS IDM supplying a local
local load with f0 = 60 Hz and Q f = 2.5. load with f0 = 60 Hz and Q f = 2.5.
outside the SFS NDZ for SFS with cf 0 = 0.05 and k = 0.05.
This verifies the calculation results shown in Fig. 5.
The theoretical boundaries of the SFS NDZ were also
verified by simulation. Fig. 13 shows a comparison of the
theoretical and simulated SFS NDZs. The agreement between
the simulation and calculation results is good for all values
of Qf . The error produced by the equation that defines
the inverter current angle for this zero current segment
IDM does not greatly affect the NDZ boundaries, because
there is no NDZ for loads with Qf < 2.5. However, the
resonant frequency of the load where the system frequency
under islanding conditions can drift up or down, i.e., where
the upper and lower boundaries overlap, is slightly different
Fig. 11. Comparison of SMS NDZ of the simulation and calculation. from the theoretical one and has no meaningful practical effects.
178 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 1, MARCH 2006
02 i2
= tan 1
4Qf 1 2
2
sin(2fi t) 0 t Ti , 0 + i2
i(t) = , i(t + T ) = i(t) (23)
0 Ti t T R
k1 = 2
where
1 + Q2f 0
i i
0
1 1
fi = fv + f, Ti = , T = . 2 Q 2f
2
fi fv
Q2f 0
i i
0 + 4Q 2f 1
0
i + i
0
. k2 = R 2 . (29)
The current waveform also can be expressed as 1 + Q2f 0
i
i 0
i(t) = i1 (t) + i1 (t T )u(t T ) The approach for obtaining the upper boundary of the NDZ
+ i1 (t 2T )u(t 2T ) + (24) for AFD in the Qf versus f0 space is as follows. First one
chooses a value for Qf and 0 = 2 f0 . Then for i =
where 2 (fmax + f ), one calculates the value of v from (27) for
t = T = 1/fmax . The values of Qf and f0 are at the boundary
i1 (t) = sin 2fi t sin 2fi (t Ti )u(t Ti ). of the NDZ when v(T ) 0.
sin[b(t nT ) + ]u(t nT )
v(t) = k1
sin[b(t nT Ti ) + ]u(t nT Ti )
n =0
e(tn T )c sin[a(t nT ) + ]u(t nT )
k2 (tn T T i )c (28)
e sin[a(t nT Ti ) + ]u(t nT Ti )
n =0
180 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 1, MARCH 2006