Be2K Users Manual V-8.XX.XX February 2006 1

Be 2K Users Manual
for NFPA-110 and CAN/CSA-C282-M89 applications

The information in this document is subject to change without notice.


No part of this document may be copied or reproduced in any form or any means without the prior written
consent of Bernini Design company. Bernini Design assumes no responsibility for any errors which may appear
in this instruction manual or in the wiring diagrams.
Although Bernini Design has taken all possible steps to ensure that the User Manual is complete, bug free and
up-to-date, we accept that errors may occur. If you encounter problems with this instruction manual, please
complete this form and send it back to us.

FAX Message (0755-27153030), From:________________________________________

Name:_____________Company:_____________________Tel/Fax:___________________

I would like to report the following error(s):


__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

Bernini Design srl - Italy


0755-27153030

Customer Support e-mail: sales@wellfut.com mobile: 13537855559

Warranty
Bernini Design SRL (hereinafter "BD") warrants that BE2K shall be free from defect in material or workmanship
for a period of 3 years from the BD delivery date. BD shall, at its option, repair or replace the product without
charge. BD shall return the BE2K to the buyer with the Default parameters at no extra charge. The buyer shall
furnish sufficient information on any alleged defects in the product so as to enable BD to determine their cause
and existence. If the BE2K is not defective, or the product is defective for reason other than covered by this
warranty, the buyer will be charged accordingly. This warranty shall not apply if the BE2K has not been used in
accordance with the User Manual and other operating instruction, particularly if any defects are caused by
misuse, improper repair attempts, negligence in use or handling.
This purchase is non-refundable.

This equipment complies with the EMC protection requirements

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 2

Index (Note: the display messages are indicated by letters or numbers enclosed in square brackets)

-A- -E-
Alarms ...............................6.0 EMERGENCY LED ...........7.0
[ALARM 1] [ALARM 2]......5.1.6 Enable pushbutton ..........1.1
Alphanumeric Display .....5.0 Engine menu .....................5.5
Auto/Man LED ..................3.02, 7.0 Engine speed ....................5.5
AUTO Operating Mode .....3.02, 3.06 [Er LIMIT]................................6.0
Auto-Man pushbutton ......1.1 EVENTS Memory (LOG) ...5.4.5
AUTOMATIC Test ...............3.03 External Stop.....................6.0
-B- [EXT.ON] - [EXT.OFF].......3.0.4
Battery, Alarms.................5.1.5
Belt Break..........................5.4.5 -F-
[BREAKER] .......................5.2 Fail to Start .......................6.0
[FAILURE] .........................5.2
-C- [FAULT01] - [FAULT07]....5.1
[COOLING] ........................5.2 Front Panel .......................1.1, 7.0
Clock settings ..................5.4.4 Frequency..........................5.3
[CLK ERR] ........................5.1.6
[CYC ERR] ........................5.1.6
Contactors ........................3.07 -G-
Current Transformer ........5.2 GEN-SET test ...................3.03
Current, settings...............5.2 [GEN FAIL] ........................5.1.2
Generator Under Voltage.5.1.2
-D- Generator Over Hz ...........5.1.2
Data/h menu .....................5.4 Generator Under Hz .........5.1.2
Display Menu ....................5.0 Generator Frequency .......4.0
Display...............................5.0 Generator Failure ............5.1.2
Display Alphanumeric......5.0 Glow Plugs (PREGLOW)..5.2
Display Messages ............5.1
DOWN pushbutton ..........1.1 -H-
Hour Counter ....................5.4.2
-K- [HI FUEL] ...........................5.1.5
kW, kVA, indication ..........5.3 [HI BATT]...........................5.1.5
[HI TEMP] ..........................5.1.4
-L-
LED, LEDs .........................1.1 -O-
Lamp Test .........................4.0 Over Frequency ..................5.1.2
LEFT pushbutton .............1.1 Over Speed..........................5.1.1
Load Control ....................2.03 Over Voltage........................5.1.2
[LO BATT] .........................5.1.5 [OVER Aac]..........................5.1.2
[LO FUEL]..........................5.1.5 [OVER kW]...........................5.1.2
[LO TEMP] .........................5.1.4 [OVER KVA].........................5.1.2
Low Battery voltage..........5.1.5 [OVERLOAD] .......................5.1.2

-M- -P-
Mains Voltage/Hz .............5.3 Parameters reading ............5.2
Mains Failure ....................3.02 Periodic Test ......................5.2
Mains Over Voltage ..........5.2 Power measurements.........5.3
Mains Under Voltage........5.2 [PREGLOW].........................5.2
Mains Over Frequency.....5.2 Push buttons.......................1.1, 7.0
Mains Under Frequency...5.2
Mains Restore...................5.2 -R-
Mains Simulation..............3.04 Read (parameters) ..............5.2

t
Manual Operating mode ..2.0 RIGHT pushbutton [>] ........1.1, 7.0,

u
MENU ................................5.0 REMOTE controls ..............3.03

lf
Messages (Display) ..........5.4.1 [RESTORE] ..........................5.2

el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 3

-O-
Oil pressure alarms ..........5.1.3 -S-
OFF pushbutton.................1.1 Set-Up ..................................1.1
OFF Operating Mode .......2.04 [SERVICE]............................5.4.3
Operating modes ..............2.0, 3.0 Speed alarms ......................5.1.1
Operating message ..........5.4.1 Start, manual .......................2.01
OPEN pushbutton [O].......1.1 START pushbutton ............1.1, 7.0

-U-
-S- Under Voltage ....................5.1.2
[SCH. DATE]..TIME].............5.2 Under Frequency ...............5.1.2
Service (Scheduled) ...........5.4.3 [UNDER Hz] .........................5.2
Settings (Parameters).........5.2 [UNDER V] ...........................5.2
Starting Failure ...................6.0 [U/SPEED]............................5.1.1
Start Attempts .....................5.2 [UNDSPEED] .......................5.2
[STATUS] .............................5.2 UP pushbutton ...................1.1, 7.0
STOP pushbutton ..............1.1
[STOPPING] .........................5.2 -V-
Voltage.................................5.3
-T- Voltage reading ratio ..........5.2
[TEET N.]..............................5.2 [VIEW] display mode .........5.2
Temperature alarms ...........6.0
Temperature indication ......5.5 -W-
Test, Remote Test ...............3.03 Warm-Up time .....................5.2
[TEST >] , Automatic test ...3.03 Warn.(Warning) Menu ........5.1
Test LED, Lamp Test ..........4.0 [WARN Aac].........................5.2
Transformer, Current..........5.2 [WARN OIL] .........................5.2
[T OV/SPD]...........................5.2 [WARM UP]..........................5.2
[T UN/SP] .............................5.2 [WARN Aac].........................5.2
[T OVERV]............................5.2
[T UNDERV] .........................5.2
[T OVERHZ] .........................5.2
[T UNDHZ]............................5.2
[T OVER A] ..........................5.2

WARNING High voltage is present inside the instrument. To avoid electric-shock hazard,
operating personnel must not remove the protective cover. Do not defeat the grounding
connection. Any interruption of the grounding connection can create an electric-shock hazard.
Before making external connections always ground the BE2K first by connecting the male-

t
blade terminal to a proper ground.

lfu
el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 4

Table of Contents

1.0 First Time Operation and Safety Recommendation......4


1.1 Front panel description ...........................................4

2.0 'Manual' Operating Instruction ..................................5


2.01 Manual Start ....................................................................5
2.02 Manual Stop.....................................................................5
2.03 Manual Load Control .......................................................6
2.04 Off Operating Mode .........................................................6

3.0 'Auto' Operating Instruction.......................................6


3.01 'Manual' operating mode set up......................................6
3.02 'Auto' operating mode set up ..........................................6
3.03 Remote Controls and Automatic Periodic TEST .............6
3.04 Mains Simulation ............................................................6
3.05 'Auto' Operating mode: Stop............................................7
3.06 'Auto' Operating mode description...................................7
3.07 'Auto' and 'Manual' selection ..........................................7

4.0 Display features and Lamp Test................................7

5.0 Alphanumeric Display and menu facilities ..............7


5.1 'Warning.' menu ............................................................8
5.1.1 Speed Alarm Messages........................................8
5.1.2 Generator Alarm Messages ..................................8
5.1.3 Oil Pressure Alarm Messages ..............................8
5.1.4 Temperature Alarm Messages..............................8
5.1.5 Battery and Fuel Alarm Messages........................8
5.1.6 Miscellaneous Alarm Messages ...........................8
5.2 Program menu: [VIEW>] Display Mode.......................9
5.3 'Mains' menu .................................................................11
5.4 'Events/h' menu.............................................................11
5.4.1 Operating Messages.............................................12
5.4.2 Rent register and Hour Counter............................12
5.4.3 Service Schedule Prompt .....................................12
5.4.4 Clock .....................................................................13
5.4.5 LOG Events ..........................................................13
5.5 'ENGINE' menu............................................................14
6.0 Alarms and shut downs................................................15
7.0 Front Panel .................................................................16
8.0 Installation and Plant information.................................17
9.0 Note .............................................................................17

1.0 First Time Operation and Safety recommendation

DANGER : THE BE2K DOES NOT GENERATE A WARNING OR AUDIBLE SIGNAL PRIOR TO
INITIATING THE STARTING PROCEEDINGS. DO NOT WORK ON EQUIPMENT, WHICH IS
CONTROLLED BY THE BE2K UNIT. WE RECOMMEND THAT YOU PLACE WARNING SIGNS ON
THE MAIN PARTS OF THE GENERATING-SET.

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 5

1.1 Front Panel Description


The front panel (section 7.0) features:
- One Alphanumeric green Display made of 8 digits.
- Three Displays made of 4 digits.
- Six red LEDs for alarm indication.
- One yellow LED for Fuel Level warning and One green LED for Engine Running indication.
- Four yellow LEDs to indicate the menu.
- One red LED to indicate the Warning menu of the display.
- Two yellow LEDs for 'Mode Display' selection.
- Two green LEDs to indicate AUTO and MAN operating mode.
- Four green LEDs to indicate the status of the contactors and voltage presence.
The pushbuttons have the functions described below.
[^][v] (Up/Down pushbuttons): select the Menu.
[<][>] (Left/Right pushbuttons): select Parameters.
[START]: starts the engine (it must be used simultaneously with the [ENABLE] pushbutton).
[STOP]: stops the engine (section 2.02).
[ I ]: closes the contactor of the Generator (section 2.03).
[ O ]: opens the contactor of the Generator (section 2.03).
[AUTO/MAN]: Auto or Manual control (to use simultaneously with [ENABLE] pushbutton).
[ENABLE]: enables the use of [START], [ I ] and [AUTO/MAN] pushbuttons.
[OFF]: allows Alarm Clear and shuts down the Panel.
[ACK]: controls Alarms acknowledge, Horn silence and Parameter reading.
[MODE-SAVE]: controls Mode Display.

2.0 'Manual' Operating Instructions


Push [ENABLE] and [AUTO/MAN] simultaneously until the green LED MAN illuminates.
(NOTE: if an external Key Switch is used, the BE2K will enter directly into 'MANUAL' operating mode).
The KM green LED will be turned on to indicate Load transferred to the Mains. Now, you can either:

- Turn the BE2K to 'OFF operating mode by pushing the [OFF] pushbutton as described in
Section 2.04 or,
- Turn the BE2K to 'AUTO' operating mode using the [ENABLE] and [AUTO/MAN] pushbuttons
as described in Section 3.02 or,
- START and STOP the set by using [START][STOP] pushbuttons as described in sections 2.01
and 2.02 or,
- Select a menu for the Alphanumeric Display by using the [^] and [v] pushbuttons as described
in Section 5.0.

2.01 Manual Start


A) - Cancel all alarms by using [ACK] and [OFF] pushbuttons.
B) - If a STOP cycle is energised (it is indicated by the message [STOPPING]), wait for the end of
the cycle, or, if the engine has already stopped, push the [STOP] pushbutton to cancel the timing.
C) - Press the [ENABLE] and [START] pushbuttons simultaneously until engine starts. The green
'ENGINE RUNNING' LED will illuminate. If the PREGLOW is used in the BE2K settings, the
message [PREGLOW] will appear before the starting attempts.
During the cranking of the engine, the LEDs and Displays are turned off.

2.02 Manual Stop


Press the [STOP] pushbutton until the message [STOPPING] appears. At the end of the 'STOP'

t
cycle, push the [OFF] pushbutton if you want to enter the 'OFF' operating mode.

lfu
el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 6

2.03 Manual Load Control


In Manual operating mode, the load is automatically transferred to the Mains, independently of the
status of the Mains (the green KM LED energises). In order to transfer the load to the Generating-
Set, press the [ I ] pushbutton simultaneously with the [ENABLE] pushbutton. The KM contactor
opens, and then, after a 2 second delay, if all parameters of the Generator are met, the KG will
energise. The contactor can be opened at anytme by the [O] pushbutton and the load will be
transferred back to the Mains.

2.04 OFF Operating mode


To enter the OFF operating mode, push the [OFF] pushbutton for a few seconds. The BE2K will
enter low power consumption mode. The Load will be transferred to the Mains and the engine will be
stopped. Only the green KM LED will be illuminated.

3.0 'Auto' Operating Instruction


If the BE2K is already in MANUAL operating mode, follow the instructions of section 3.02. Otherwise,
proceed to section 3.01.

3.01 Manual operating mode Set Up


a)- push the [ENABLE] and [AUTO/MAN] pushbuttons simultaneously until the green LED MAN
illuminates. The green LED KM will be turned on to indicate that the Load has been transferred to the
Mains.

3.02 Auto operating mode Set Up


b)- push the [ENABLE] and [AUTO/MAN] pushbuttons simultaneously until the green LED AUTO
illuminates. (NOTE: if an external Key Switch is used, the BE2K enters directly into 'AUTO' operating mode)
If the Mains fails, the BE2K starts the engine after a programmable delay, and transfers the load to
the Generating-Set after the warm-up time. To open the contactor of the generator, select the 'MAN'
operating mode and push the [0] pushbutton. If the button is pushed in 'AUTO' operating mode, the
engine stops and the alarm 'EMERGENCY' energises. If the Mains restores, the load connects back
to the Mains. After a programmable delay, the engine will stop.

3.03 Remote Controls and Automatic Periodic Test (A.P.T.)


The GEN-SET TEST and ENGINE TEST functions are enabled in AUTO operating mode. The
ENGINE TEST starts the engine and does not transfer the load to the Generator.
The GEN-SET TEST starts the engine and transfers the load to the Generator. The display
indicates the corresponding message on the Data/h menu (see section 5.4.1). To activate the test,
use the test switch (if provided by your Panel manufacturer).
A Cooling down time is executed before stopping the engine. The Be2K allows automatic periodic test
(A.P.T) with real time clock control. The A.P.T. works only in AUTO operating mode. After an A.P.T.,
the Be2K updates the display in order to inform the user about the next A.P.T. cycle (see section 5.2
parameters [STATUS], [SCH.DATE] and [SCH.TIME])

3.04 Mains Simulation


If provided by your panel manufacturer, the Mains Simulation Switch operates as indicated in the
table. The status of the Mains simulation switch is displayed in the Mains menu with the messages
[EXT.ON] and [EXT.OFF].

Display Message MAINS STATUS MAINS SIMULATION SWITCH BE2K-MODE


[EXT. ON] Normal Closed to ground Stand by mode
[EXT. OFF] Normal Open Stand by mode
[EXT. ON] Failure Closed to ground Stand by mode
[EXT. OFF] Failure Open Starting mode

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 7

3.05 Auto operating mode: Stop

The Generating-Set stops automatically if the Mains restores or if the remote control (if provided by
your panel manufacturer) returns to stand by. The user can stop the Generating-Set in 'MANUAL'
operating mode, by pushing the [STOP] pushbutton. The user may press the [STOP] or [0]
pushbutton in automatic operating mode but, in this case, the red 'EMERGENCY' LED alarm will
energise and the Load will be transferred to the Mains. The [OFF] pushbutton stops the engine and
turns the BE2K to OFF operating mode.

3.06 Auto operating mode description

The Automatic Sequences include the [FAILURE] (*), [BREAKER], [RESTORE], [WARM UP] and
[COOLING] timings. In case of Mains failure, the Mains Contactor opens after the [BREAKER] time-
out. The [FAILURE] timing takes place if the Mains Failure persists. After this time-out, the BE2K
starts the engine. The [WARM UP] timing allows the engine to warm up.
After the [WARM UP], if all electrical parameters are met, the Contactor of the generator will close. If
the Mains restores, the [RESTORE] timer starts to count, and the load will be transferred to the
Mains. The engine will stop after the [COOLING] time.
The Engine Starting Parameters are controlled by the [CR.DELAY], [IDLE], [PREGLOW], [CRANK],
[REST], [ATTEMPTS] and [CRANKOFF] parameters. The [PREGLOW] energises before the starting
attempts. Between the starting attempts ([REST]) the PreGlow Output will remain energised.
(*) The setting of the timings indicated above are listed in the section 5.2.

3.07 Auto and Manual selection

Press the AUTO-MAN and ENABLE CONTROL pushbuttons simultaneously: the AUTO and
MANUAL green LEDs will illuminate in accordance with the selected operating mode.

NOTE : the BE2K stores the AUTO operating mode in the memory. If the supply fails and then
restores, the BE2K enters the AUTO operating mode automatically.

4.0 Display Features and Lamp test


The BE2K has 4 displays: one Alphanumeric green Display and three 7-segment red LED Displays.
During the starting attempts, all displays are turned off. After 2 minutes without operating the
[<][>][v][^] pushbuttons, the Alphanumeric Display will reduce the luminosity. The light intensity
returns to normal when you press one of the [<][>][v][^] pushbuttons.
The Alphanumeric Display can show five menus: Warning-Mains-Power-Data/h and Engine
(see section 5.0). The red Displays indicate electrical measurements of the Generator according to
the selection done with the [MODE-SAVE] pushbutton. The yellow Mode LEDs indicate 4 menus:
Voltage-Current-Pf and Frequency.
The 'LAMP-TEST' is obtained by pushing [^] and [v] simultaneously.

5.0 Alphanumeric Display and menu facilities


The display has five menus: Warning-Mains-Power-Data/h and Engine. The selection is done
using the [^], [v], [<], [>] and [ACK] pushbuttons:
[^][v] (Up/Down Cursors) select the menu
[<][>] (Left/Right Cursor) browse the menu
[ACK] (Acknowledge) updates information of the display

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 8

5.1 Warning menu


If the display contains an alarm message, the red LED Warning will blink. To read the message,
select the Warning menu by using the [^] pushbutton. To remove the message, use the following
instructions:

a) - push [ACK] to silence the Horn


b) - eliminate the source of the alarm
c) - push [ACK] to cancel the message

If an alarm occurs, consult the Gen-set user manual. The list of the possible alarms follows:

Message Description Display [MESSAGE]

5.1.1 SPEED Alarm Messages


- Under Speed shut down: ..................... [U/SPEED]
- Pick Up Failure shut down: ................. [FAULT 05]
- Pick Up Failure calibration error: ......... [FAULT 07]

5.1.2 GENERATOR Alarm Messages


- Under Frequency shut down: ............... [UNDER Hz]
- Over Frequency shut down: ................ [OVER Hz]
- Over Current shut down: ..................... [OVER Aac]
- Over Current warning:.......................... [WARN Aac]
- Overload shut down: ........................... [OVERLOAD]
- Generator Phase Sequence error: ...... [G-PHASES]
- Over Voltage shut down: ..................... [OVER V]
- Under Voltage shut down:.................... [UNDER V]
- Alternator Failure shut down: ............... [GEN.FAIL]
- Over Active Power shut down: ............ [OVER KW]
- Over Apparent Power shut down: ........ [OVER KVA]

5.1.3 OIL PRESSURE Alarm Messages


- Low Oil Pressure' warning:......................................[WARN OIL]
- Oil Sensor Failure warning: ....................................[FAULT 02]

5.1.4 TEMPERATURE Alarm Messages


- High Temperature' warning: ..................................................... [HI TEMP]
- Low Temperature' warning: ...................................................... [LO TEMP]
- Temperature' Sender failure warning: ...................................... [FAULT 03]
- Temperature 2 shut down: ....................................................... [TEMPER 2]

5.1.5 BATTERY and FUEL Alarm Messages


- Battery Voltage warning: .........................................[LO BATT] [HI BATT]
- No FUEL Shutdown: ...............................................[NO FUEL]
- FUEL Level' sensor failure warning:.......................[FAULT 04]
- 'Level Fuel' warning:................................................[HI FUEL] [LO FUEL]
- PUMP ERROR: ......................................................[PRG PUMP]
5.1.6 MISCELLANEOUS Alarm Messages
- BE2K internal failure alarm: ...................................[FAULT 01]
- Service Schedule Time out prompt: .......................[SERVICE]
- Alarm 1 shut down: ...............................................[ALARM 1 ]
- Alarm 2 shut down: ...............................................[ALARM 2 ]
- Auxiliary alarm 1: ....................................................[AUX 1 ]
- Auxiliary alarm 2: ....................................................[AUX 2 ]
- Auxiliary alarm 3: ....................................................[AUX 3 ]

u t
lf
- Clock failure alarm: ...............................................[CLK ERR ]

l
- Periodic Test alarm: ..............................................[CYC ERR ]

e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 9

- Belt break shut down: .............................................[BELT BRK ]


- Less than 48 hours rental period remaining: ..........[RENT <48h ]
- The rental period has expired: ...............................[RENT = 0h ]

5.2 Program menu: [VIEW>] Display Mode


To select the menu, push the [^] (or [v]) pushbutton until the yellow LED Program illuminates. The
[VIEW>] menu only displays the setting of the parameters. To program a parameter, consult your
panel supplier. Push the [<] (or [>]) pushbutton to select a parameter; push the [ACK] pushbutton to
display the setting. We recommend that you read the parameters and record all modifications on this
paper (setting column).The list of the parameters follows.

Parameter Setting Description


[STATUS] Automatic Periodic: TEST ON or OFF
[INTERVAL] Interval day(s) between Automatic Periodic TESTS
[DURATION] Duration of the Automatic Periodic TEST
[SCH.DATE] Automatic Periodic TEST date
[SCH. TIME] Automatic Periodic TEST starting time
[DATE FRM] Display mode of the date DD/MM/YY or MM/DD/YY
[FAILURE] Engine start delay: 0-59 seconds or 1-30 minutes
[RESTORE ] Mains Restore Time: 0-59 seconds or 1-30 minutes.
[BREAKER] Mains Contactor Delay: 0-59 seconds or 1-30 minutes
[M OVERV] Mains Over Voltage limit : 60-998 Vac or [INHIBIT].
[M UNDERV] Mains Under Voltage limit: [INHIBIT] or 60-998 Vac.
[M OVERHz] Mains Over Frequency limit: 20-70 Hz / [INHIBIT].
[M UND/Hz] Mains Under Frequency limit: [INHIBIT] or 20-70Hz.
[G OVERV] Generator Over Voltage Shut Down: 60-998 V / [INHIBIT].
[T OVERV] Over Voltage bypass timing: 1-15 seconds
[G UNDERV] Generator Under Voltage : [INHIBIT] or 60-998 Vac.
[T UNDERV] Under Voltage bypass timing: 1-15 seconds
[G OVERHz] Generator Over Frequency: 20-70 Hz or [INHIBIT].
[T OVERHz] Over Frequency bypass timing: 1-15 seconds
[G UNDRHz] Generator Under Frequency Setting: [INHIBIT] or 20-70Hz.
[T UND/Hz] Under Frequency bypass timing: 1-15 seconds
[OVER KW] Over Power kW limit: 10-5000 kW or [INHIBIT]
[OVER KVA] Over Power kVA limit: 10-5000 kVA or [INHIBIT]
[Max. KW] Maximum limit of KW
[T Max. KW] Timing delay for the maximum KW limit
[Min. KW] Minimum limit of KW
[T Min. KW] Timing delay for the minimum KW limit
[TIMEOUT] Maximum time allowed for a remote test (from PC or SMS)
[OVER Aac] Over Current Shut Down Setting: 10-9900Aac or [INHIBIT]
[T OVER A] Over Current Shut Down bypass Timing: secs or mins.
[WARN Aac] Over Current Warning Setting:10-9900Aac or [INHIBIT]
[T WARN A] Over Current Warning timing: 1-59 secs or 1-15 minutes
[ATTEMPTS] Number of Crank attempts: 3-15
[CR. DELAY] Crank delay Time: 0-15 secs.
[CRANK] Crank timing: 3-15 seconds.
[REST] Rest timing: 3-15 seconds.
[ IDLE ] IDLE speed control: 0-59secs, 1-15 mins

u t
lf
[PREGLOW] Engine Glow PREGLOW Time: 0-59secs

el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 10

[WARM UP] Off Load Generating-Set Running: 0-59 secs or 1-15 mins.
[COOLING] Cooling Down Time: 0-59 seconds or 1-15 minutes.
[STOPPING] Stop Cycle: 1-99 secs
[EJP TIME] Time delay before the contactor is energized in EJP mode
[OV/SPEED] Over Speed Setting:100-4000 rpm or [INHIBIT].
[T OV/SPD] Over Speed bypass delay: 1-10 secs.
[UNDSPEED] Under Speed Setting: [INHIBIT] or 100-4000 rpm.
[T UN/SPD] Under Speed bypass delay: 1-10 secs.
[CRANKOFF] Crank Termination setting: 100-800 r.p.m.
[TEETH N.] Number of Teeth of the Flywheel: [INHIBIT] or 1-500 teeth
[WARN OIL] Low Oil Pressure Warning: [INHIBIT] or 0.1-20.0BAR
[HI TEMP] High Temperature Warning: 40-250C or [INHIBIT]
[LO TEMP] Low Temperature Warning setting: [INHIBIT] or 1-80C
[HORN] Alarm Horn Time-out: 5-59 secs,1-15 mins or [NO STOP]
[LO FUEL] Minimum Fuel Level Warning Setting: [INHIBIT] or1-99%
[HI FUEL] Maximum Fuel Level Warning Setting: [INHIBIT] or 1-99%
[PUMP ON] Start of the pump setting: [INHIBIT] or 1-99%.
[PUMP OFF] Stop of the pump setting: [INHIBIT] or 1-99%.
[OUTPUT 1] Programmable Output 1 option
[POL. OUT1] Programmable Output 1 polarity
[OUTPUT 2] Programmable Output 2 option
[POL. OUT2] Programmable Output 2 polarity
[OUTPUT 3] Programmable Output 3 option
[POL. OUT3] Programmable Output 3 polarity
[INP. JH1] AUX INPUT1: normally open or closed
[INP. JH2] AUX INPUT2: normally open or closed
[INP. JH3] AUX INPUT3: normally open or closed
[JH1 MODE] Programmable options for INPUT1
[JH2 MODE] Programmable options for INPUT2
[JH3 MODE] Programmable options for INPUT3
[ALARM 2] Alarm 2 Switch: normally Open or Closed
[TEMPER.2] Temper. 2 Switch:normally Open or Closed
[SIMULAT. ] Mains simulation Switch:normally Open or Closed
[PHASES] 3-Phase or single Phase selection.
[C.T.SIZE] Current Transformer size: 50A/5-9900Aac/5Aac
[Vac RATIO] Reading ratio X1 or X2
[ D+/WL] Engine running trigger: 3-20Vdc, [INHIBIT]
[BYPASS] Engine alarms monitoring bypass: 2-90 secs.
[UNIT No.] Node Address: 1-9
[BE15 o01] BE15 programmable output 1
[BE15 o02] BE15 programmable output 2
[BE15 o03] BE15 programmable output 3
[BE15 o04] BE15 programmable output 4
[BE15 o05] BE15 programmable output 5
[BE15 o06] BE15 programmable output 6
[BE15 o07] BE15 programmable output 7

t
[BE15 o08] BE15 programmable output 8
[BE15 o09] BE15 programmable output 9

lfu
el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 11

[BE15 o10] BE15 programmable output 10


[BE15 o11] BE15 programmable output 11
[BE15 o12] BE15 programmable output 12
[BE15 o13] BE15 programmable output 13
[BE15 o14] BE15 programmable output 14
[BE15 o15] BE15 programmable output 15
[VERSION] Version of the software (to read the version, push [ACK])

5.3 Mains menu

This menu indicates electrical measurements, Mains Simulation Status and Phase Sequence Status.
Push [v] or [^] to select the menu and [<] or [>] to select a measurement. To display the parameters
indicated with (), push the [ACK] pushbutton.

Mains Voltage Vr to Vs ................................................................................. [Vrs XXXV]


Mains Voltage Vs to Vt .................................................................................. [Vst XXXV]
Mains Voltage Vr to Vt .................................................................................. [Vrt XXXV]
Mains Frequency ........................................................................................... [M XX.XHz]
Mains Phase Sequence counter clockwise ................................................... [M.PH OK]
Mains Phase Sequence clockwise ................................................................ [M.PH ERR]
Mains Phase Sequence not available (e.g. Single Phase Mode) ................. [M.PH --]
Mains Simulation Disabled ........................................................................... [EXT.OFF]
Mains Simulation Enabled ............................................................................ [EXT. ON]

Generator Voltage VL1 to Neutral () ............................................................ [L1N XXXV]


Generator Voltage VL2 to Neutral ()............................................................. [L2N XXXV]
Generator Voltage VL3 to Neutral ()............................................................. [L3N XXXV]

Generator, Phase L1 Reactive Power kVAr: () .......................................... [kVAR 1] [ XXXX ]


Generator, Phase L2 Reactive Power kVAr: () .......................................... [kVAR 2] [ XXXX ]
Generator, Phase L3 Reactive Power kVAr: () .......................................... [kVAR 3] [ XXXX ]
Generator,Total Reactive Power kVAr........................................................... [XXXX kVAR]
Generator,Total Apparent Power kVA .......................................................... [XXXX kVA]
Generator,Total Active Power kW ................................................................. [XXXXkW]
Generator Power Factor () .......................................................................... [PF X.XX]
Generator Frequency..................................................................................... [G XX.XHz]
Generator Sequence Phase clockwise ......................................................... [G.PH OK]
Generator Sequence Phase counter clockwise ............................................ [G.PH ERR]
Generator Sequence Phase not available (e.g. Single Phase Mode) ........... [G.PH --]

() The Phase to Phase voltage is indicated by the 4-Digit display

5.4 Events/h menu

This menu contains five sub-menus:


- Operating Messages (section 5.4.1)
- RENT register and Hour Counter (section 5.4.2)
- Service Scheduled Alarm (section 5.4.3)
- Clock (section 5.4.4)
- Events Memory (section 5.4.5)

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 12

5.4.1 Operating Messages


An operating message is automatically displayed in this menu, according to the internal status of the
BE2K. The list of the messages follows:

[SHUTDOWN]..............The BE2K shuts down the engine


[COOLING]................. Cooling Down timing cycle
[ENG.TEST]................ Indication of a Engine Test cycle
[ LOAD ] ................... The Generating-Set is running on load.
[MANUAL] .................. The BE2K is in Manual operating mode
[M FAULT].................. Indicates Mains Failure or Breaker timing cycle.
[PREGLOW] ............... Preglow cycle.
[RESTORE] ................ Indication of a Mains Restore cycle.
[REST] ........................ Rest timing.
[PC-GEN.]................... The BE2K runs the engine because of a Start Command from a remote
computer. The BE2K will transfer the load to the generator.
[PC-ENG.]................... The BE2K runs the engine because of a Start Command from a remote
computer. The BE2K will not transfer the load to the generator.
[STARTING] ............... The message is displayed one second before the crank attempt.
[STOPPING] ............... Stop Solenoid timing cycle
[SET-TEST] ................ Indication of Generating-Set Test cycle.
[SMS-GEN.]................ The BE2K runs the engine because of a Start Command from a Mobile
Phone. The BE2K will transfer the load to the generator.
[SMS-ENG.]................ The BE2K runs the engine because of a Start Command from a Mobile
Phone. The BE2K will not transfer the load to the generator.
[STANDBY]................ The BE2K is in Auto operating mode waiting for a command.
[WAIT GEN]..The BE2K is waiting for the stabilization of the electrical parameter of the
Generator.
[WARM UP] ............... The unit is waiting for the Warm-Up time-out before closing the Contactor of
the Generator
[CYC-TEST]................ Automatic periodic test cycle (Real time clock tagged). This message
energises according to the settings of the parameters [STATUS],
[DURATION], [SCH.DATE] and [SCH.TIME]
[ -- ]...................No function
[EJP STA.].................. The engine is running because of a request from the EJP input .
[ DELAY] .................. It indicates that BE2K is counting the delay time before starting the engine.

5.4.2 Rent register and Hour Counter


5.4.2A The sub-menu [RENT h] indicates the remaining hours before termination of the rent contract.
Push [ACK] to display the count of the hours.

5.4.2B The sub-menu [PRG.RENT] indicates the hours of the rent contract. Push [ACK] to display the
hours.

5.4.2C The Hour Counter can record up to 9999 hours. The display indicates the hours by means of
the message [XXXXh] (*).
(*) note: XXXX indicates a 4 digit number

5.4.3 Service Schedule Prompt


The display indicates, in the form [SERV XXX] (XXX means a 3-Digit hour indication), the remaining
number of hours before the Service Prompt Alarm sounds. By pushing the [ACK] pushbutton, the
[SET XXX] message will indicate the original setting. The timer [SERV XXX] counts down when the
engine runs. When the counter reaches zero, the Alarm energises and the message [SERVICE] will

t
be displayed in the Warning menu. In this case, consult the Gen-set user manual or your Electric

u
Panel supplier.

l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 13

5.4.4 Clock

This menu displays the real time clock on two screens: [Day/Month/Year] and
[hours:minutes:seconds]. Using the [<] and [>] pushbuttons the display toggles the information. To
obtain the reading in the form [Month/Day/Year] consult your Electric Panel supplier.

How to set the clock:


A) Select the 'Data/h' menu by using the [v] and [^] pushbuttons
B) - If an alarm moves the menu into 'Warning' mode, push the [v] pushbutton to return to the 'Data/h'
menu.
C) - Push the [>] pushbutton 5 times to display [Day/Month/Year]
D) Push & hold the [ACK] pushbutton: the Year flashes. Push [^] or [v] to set the year.
E) Push & hold the [ACK] pushbutton and push the [<] to select 'Month'. Use the [^] or [v]
pushbutton to set the month.
F) - Push+hold the [ACK] pushbutton and push the [<] to select 'Day'. Use the [^] or [v] pushbutton to
set the date.
G) - Release the [ACK] pushbutton.
H) - Push the [>] pushbutton: the display will show [hh:mm:ss]
I) - Repeat the steps D)- E)- F) to set the time [hours:minutes:seconds]
L) - Release the [ACK] pushbutton according to your reference clock.

NOTE: The BE2K can run the clock for 2 days without power supply. When the clock does not work,
the BE2K displays the message [CLK ERR]. In this case, push the [ACK] pushbutton and follow the
instructions to set the clock.

5.4.5 LOG Events


The Be2K can display 20 events in the form [EVENTXX ] [ Message ] [DD/MM/YY] [hh:mm:ss].
To read an event:
A - Push the [^] or [V] pushbutton to select the menu 'DATA/h'.
B - Push the [>] pushbutton as many times as necessary to obtain the desired events.
C - Push [ACK] and hold to display the name of the event.
D - Push [>] once to show [DD/MM/YY] and once again to show [hh:mm:ss]

NOTE: consult your Electric Panel supplier in case of alarm(s).

The events are listed in the following table:

[ Message ] - - - - - - - - - - - Description - - - - - - - - - - -
[ALARM 1 ] Alarm 1 shut down
[ALARM 2 ] Alarm 2 shut down
[ AUTO ] The BE2K is turned to AUTO
[ AUX 1 ] Auxiliary alarm 1
[ AUX 2 ] Auxiliary alarm 2
[ AUX 3 ] Auxiliary alarm 3
[ BELT BRK ] Engine Belt break/Charger Failure
[ CYC- TEST] Automatic Periodic Test
[ CYC- ERR] Automatic Periodic Test Fault
[ CLK- ERR] Real time clock failure
[EXT. STOP] Emergency Stop Shut Down
[Er. LIMIT] Parameter error indication
[FAULT 01] BE2K internal failure alarm

t
[FAULT 02] Oil Sender Failure warning
[FAULT 03] Temperature Sender failure warning
[FAULT 04] Fuel Level Sender failure warning

lfu
el
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 14

[FAULT 05] Pick Up Failure shut down


[FAULT 07] Pick Up Failure calibration error
[NO FUEL] Fuel, Level Switch shut down
[G-PHASES] Generator Phase Sequence error
[GEN.FAIL] Alternator Failure shut down
[HI BATT] High Battery Voltage warning
[HI FUEL] Maximum Level Fuel warning
[HI TEMP] High Temperature warning
[ KM ON ] The contactor of the Mains closes
[ KM OFF] The contactor of the Mains opens
[ KG ON ] The contactor of the Generator closes
[ KG OFF ] The contactor of the Generator opens
[LO TEMP] Low Temperature warning
[LO BATT] Low Battery Voltage warning
[LO FUEL] Low Level Fuel warning
[MANUAL] The BE2K is turned to MANUAL
[MODE OFF] The BE2K is turned to OFF
[M FAULT ] The Mains failed
[NO START] Starting Failure
[ OIL ] Low Oil Pressure shut down
[OVER Hz] Over Frequency shut down
[OVER Aac] Over Current shut down
[OVERLOAD] Overload shut down
[OVER V] Over Voltage shut down
[OVER SP] Engine Overspeed shut down
[OVER KW] Over Active Power shut down
[OVER KVA] Over Apparent Power shut down
[POWER ON] The supply is applied to the BE2K
[PRG PUMP] Error in the setting of the parameters
[ RESTORE] The Mains restores
[RESERVE] Low Level Fuel switch
[RUNNING] The engine is running
[STOPPED] The engine has been stopped
[SERVICE] Service Schedule Time out prompt
[TEMPER 1] Temperature 1 shut down
[TEMPER 2] Temperature 2 shut down
[UNDER Hz] Under Frequency shut down
[U/SPEED] Under Speed shut down
[UNDER V] Under Voltage shut down
[WARN OIL] Low Oil Pressure Warning
[WARN Aac] Over Current warning
[RENT <48h] Less than 48 hours to the termination of the rental contract
[RENT =0h ] The rent period has expired

5.5 ENGINE menu


The display shows the following measurements:
- Engine Speed up to 4000 R.P.M.: [XXXX RPM]
- Oil Pressure up to 20.0 Bar: [XX.X BAR]
- Engine Temperature up to 250 C: [XXX C]
- Battery Voltage measurement up to 36.0Vdc: [XX.X Vdc]
- Tank Fuel remaining up to 99%: [FUEL XX%]
- Charging Alternator Voltage up to 36.0Vdc: [D+XX.XV]
Note 1: the symbol X means one Digit of numerical value.
u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 15

Note 2: according to the programming done by your Electric Panel supplier, some readings may not
be available and the display will indicate [--------].

6.0 Alarms and shut downs


The BE2K features Shutdowns (the engine stops) or Warnings (only optical and acoustic information).
The BE2K provides:
1 - red or yellow LEDs on the front panel (see section 7.0 and below)
2 - a red LED 'Warning' to indicate the presence of a message on the display (see section 5.1)
3 a message on the Event Memory (see section 5.4.5)
4 an acoustic alarm by means of an external horn (if provided by your Panel supplier)

If an alarm occurs, push the ACK pushbutton to silence the horn. An optical indication will inform you
about the nature of the alarm. To cancel the alarm totally, remove the alarm source, and then press
the [OFF] pushbutton. Always consult the Genset user manual or your Electric panel supplier.

The alarms directly indicated on the front panel, by means of LEDs, are described below.

LOW OIL PRESSURE (red LED)


- There is a failure in the oil circuit. Consult your generating set manufacturer or the engine user
manual.

HIGH ENGINE TEMPERATURE (red LED)


- There is a failure in the cooling system. Verify the level of the coolant and consult the engine user
manual.

FAIL TO START (red LED)


- The engine failed to start automatically. Verify the status of the battery and the level of the fuel in the
tank. Consult your generating set manufacturer.

CHARGER FAILURE (red LED)


- There is a failure of the charger alternator, or the alternator belt is broken. Consult your generating
set manufacturer.

EMERGENCY STOP (red LED)


- An external emergency pushbutton has been energized, or the [STOP-OFF] pushbutton was
pressed while the engine was running. Consult the electric panel section of the user manual.

OVERSPEED (red LED)


- There is a failure of the speed regulator. Consult your generating set manufacturer.

FUEL (yellow LED)


- This warning informs you about the low level of the tank. It is only an optical warning. You are
prompted to stop the engine and to fill the tank according to the genset manufacturer instructions.

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 16

u t
l lf
e
w
www.wellfut.com 13537855559 13612921202
Bernini Design BE2K Users Manual February 2006 17

8.0 Installation and Plant Information


Fill in the following form:

PANEL Serial N PANEL Model/Rating

GEN-SET Serial N GEN-SET Model/KVA

BE2K Serial N SOFTWARE Version:

MANUFACTURER NAME TELEPHONE / FAX

DATE SIGNATURE

9.0 NOTE

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________