You are on page 1of 4

STAINLESS STEEL

R GROOVED COUPLINGS 17.25


Style 489
Stainless Steel
Rigid Coupling
PRODUCT DESCRIPTION
Style 489 is designed for achieve this rigidity, it is Style 489 will greatly
1 - 12" (40 - 300 mm) necessary to torque the reduce linear or angular
piping systems and fea- nuts to the values shown in movement and is useful for
tures a heavy stainless steel the table below. Style 489 is valve connections and
housing for pressures up to rated to 600 psi (4136 kPa) other points where rigidity
600 psi (4135 kPa) on stain- on Schedule 40S stainless is required. The coupling is
less steel pipe only. The steel pipe, 300 psi (2065 provided with stainless
housing key is designed to kPa) on Schedule 10S stain- steel bolts and nuts and
clamp the bottom of the less steel pipe and 200 psi standard C-cross section
1 - 4" (40 - 100 mm) Sizes
groove, thus providing an (1375 kPa) on Schedule 5S gasket.
essentially rigid joint. To stainless steel pipe.

6 - 12" (150 - 300 mm);


139,7 - 318,5 mm
Metric and JIS Sizes

Dimensions
DIMENSIONS Pipe Size Allow. Inches/millimeters Approx.
Y Z
Actual Pipe @ Nut Weight
Nominal Outside End Bolts/Nuts Torque Each
Diameter Diameter Sep. # No. - Size ft-lbs Lbs.
Inches/mm Inches/mm In./mm Inches Nm X Y Z kg
X 1 1.900 0.05 18 - 22 2.86 4.42 1.84 1.6
40 48,3 1,3 2 - 2 25 - 30 73 118 47 0,7
2 2.375 0.05 18 - 22 3.34 5.19 1.86 1.6
50 60,3 1,3 2 - 2 25 - 30 85 132 47 0,7
1 - 4" (40 - 100 mm) Sizes 2 2.875 0.05 18 - 22 3.92 5.62 1.86 1.9
65 73,0 1,3 2 - 2 25 - 30 100 143 47 0,9
Y Z 3.000 0.05 18 - 22 4.02 5.72 1.86 2.0
76,1 mm 76,1 1,3 2 - 2 25 - 30 102 145 47 0,9
3 3.500 0.05 45 - 50 4.54 6.78 1.86 2.8
80 88,9 1,3 2 - 2 60 - 68 115 172 47 1,3
X 4 4.500 0.19 45 - 50 5.77 7.90 2.07 4.0
100 114,3 4,8 2 - 2 60 - 68 147 201 53 1,8
5.500 0.25 75 - 100 7.07 11.13 2.38 12.0
139,7 mm 139,7 6,4 2 - 4 100 - 135 180 283 60 5,5
6 - 12" (150 - 300 mm);
139,7 - 318,5 mm 6.500 0.25 125 - 200 8.16 12.68 2.50 15.5
165,1 mm 165,1 6,4 2 - 5 170 - 275 207 321 64 7,0
Metric and JIS Sizes
6 6.625 0.25 125 - 200 8.16 12.68 2.50 15.5
150 168,3 6,4 2 - 5 170 - 275 207 321 64 7,0
8.515 0.25 200 - 300 10.63 15.00 2.75 24.0
216,3 mm 216,3 6,4 2 - 1 5 275 - 400 270 381 70 10,9
8 8.625 0.25 200 - 300 10.63 15.00 2.75 24.0
200 219,1 6,4 2 - 1 5 275 - 400 270 381 70 10,9
10.528 0.25 200 - 300 13.09 17.25 3.00 33.0
267,4 mm 267,4 6,4 2 - 1 6 275 - 400 332 438 76 15,0
10 10.750 0.25 200 - 300 13.09 17.25 3.00 33.0
250 273,0 6,4 2 - 1 6 275 - 400 332 438 76 15,0
12,539 0.25 200 - 300 15.13 19.13 3.13 40.0
318,5 mm 318,5 6,4 2 - 1 6 275 - 400 384 486 80 18,1
12 12.750 0.25 200 - 300 15.13 19.13 3.13 40.0
300 323,9 6,4 2 - 1 6 275 - 400 384 486 80 18,1
# @ Refer to notes on page 2.

VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY


Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 416-675-5575 Phone:32-9-381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 416-675-5565 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.com e-mail: viccanada@victaulic.com e-mail: viceuro@victaulic.be e-mail: vical@victaulic.com e-mail: vicap@victaulic.com

3134 Rev.C 10/02 Registered Trademark of Victaulic Copyright 2002 Victaulic Printed in U.S.A.
PERFORMANCE
Pipe Size Schedule 40S Schedule 10S Schedule 5S
Max. Max. Max. Max. Max. Max.
Actual Joint Perm. Nom. Joint Perm. Nom. Joint Perm. Nom.
Nominal Outside Work. End Wall Work. End Wall Work. End Wall
Dia. Dia. Press.* Load Thick. Press.* Load Thick. Press.* Load Thick.
In./mm In./mm PSI/kPa Lbs./N In./mm PSI/kPa Lbs./N In./mm PSI/kPa Lbs./N In./mm
1 1.900 600 1700 0.145 300 850 0.109 200 570 0.065
40 48,3 4136 7565 3,7 2065 3783 2,8 1379 2537 1,7
2 2.375 600 2660 0.154 300 1330 0.109 200 890 0.065
50 60,3 4136 11837 3,9 2065 5919 2,8 1379 3961 1,7
2 2.875 600 3900 0.203 300 1950 0.120 200 1300 0.083
65 73,0 4136 17355 5,1 2065 8678 3,1 1379 5785 2,1
3.000 600 4240 0.203 300 2120 0.120 200 1415 0.083
76,1 mm 76,1 4136 18868 5,1 2065 9434 3,1 1379 6297 2,1
3 3.500 600 5775 0.216 300 2890 0.120 200 1925 0.083
80 88,9 4136 25699 3,5 2065 12861 3,1 1379 8566 2,1
4 4.500 600 9540 0.237 300 4775 0.120 200 3180 0.083
100 114,3 4136 42453 6,0 2065 21249 3,1 1379 14151 2,1
5.500 600 14250 0.258 300 7130 0.134 200 4750 0.109
139,7 mm 139,7 4136 63413 6,6 2065 31729 3,4 1379 21138 2,8
6.500 600 19910 0.280 300 9955 0.134 200 6640 0.109
165,1 mm 165,1 4136 88600 7,1 2065 44300 3,4 1379 29548 2,8
6 6.625 600 20680 0.280 300 10340 0.134 200 6895 0.109
150 168,3 4136 92026 7,1 2065 46015 3,4 1379 30685 2,8
8.515 600 34175 .0322 300 17090 0.148 200 11390 0.109
216,3 mm 216,3 4136 152079 8,2 2065 76051 3,8 1379 50686 2,8
8 8.625 600 35055 .0322 300 17530 0.148 200 11685 0.109
200 219,1 4136 155995 8,2 2065 78010 3,8 1379 52000 2,8
10.528 600 52230 0.365 300 26115 0.165 200 17410 0.134
267,4 mm 267,4 4136 232424 9,3 2065 116212 4,2 1379 77475 3,4
10 10.750 600 54460 0.365 300 27230 0.165 200 18150 0.134
250 273,0 4136 242345 9,3 2065 121175 4,2 1379 80770 3,4
12,539 600 74100 0.375 300 37050 0.180 200 24700 0.156
318,5 mm 318,5 4136 329745 9,5 2065 164873 4,6 1379 109915 4,0
12 12.750 600 76605 0.375 300 38300 0.180 200 25535 0.156
300 323,9 4136 340890 9,5 2065 170435 4,6 1379 113630 4,0
*Refer to notes below.

NOTES
* Working Pressure and End Load are total, from all internal and external loads, based on stainless steel pipe, roll grooved with Victaulic rolls in accordance with
Victaulic specifications. RX rolls must be used for Schedules 5S, 10S and 10. Standard rolls should be used for Schedule 40S and Standard Weight pipe. Contact
Victaulic for performance on other pipe or cut grooved pipe.
# For field installation only. Style 489 is essentially rigid and does not permit expansion or contraction.
WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 times the figures shown.
@ Metric thread size bolts are available for all coupling sizes upon request. Contact Victaulic for details.
WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.

17.25 - 2
MATERIAL SPECIFICATIONS
Housing: Type 316 stainless plus a variety of dilute acids, +20F to + 300F ( 7C to
steel, conforming to ASTM- oil-free air and many chemi- +149C). Recommended for
A351, A743, and A744 Grade cal services. UL Classified to many oxidizing acids, petro-
CF-8M. ANSI/NSF 61 for cold +86F leum oils, halogenated hydro-
Housing Coating: None (+30C) and hot +180F carbons, lubricants,
Gaskets: (+82C) potable water ser- hydraulic fluids, organic liq-
vice. NOT RECOMMENDED uids and air with hydrocar-
*Services listed are General Ser- FOR PETROLEUM SER- bons.
vice Recommendations only. It VICES.
should be noted that there are Grade A white nitrile
services for which these gas- Grade T nitrile White nitrile (White gasket).
kets are not recommended. Ref- Nitrile (Orange color code). Temperature range +20F to
Exaggerated for Clarity
erence should always be made Temperature range 20F to +180F (7C to +82 C). No
to the latest Victaulic Gasket +180F (29C to +82C). carbon black content. May be
Selection Guide (05.01) for spe- Recommended for petroleum used for food services. Meets
cific gasket service recommen- products, air with oil vapors, FDA requirements and con-
dations and for a listing of vegetable and mineral oils forms to CFR Title 21 Part
services which are not recom- within the specified tempera- 177.2600.
mended. ture range. Not recom- Other gaskets are available.
mended for hot water Please refer to 05.01.
Grade E EPDM services over +150F (+66C)
EPDM (Green color code). Bolts/Nuts: Type 316 stainless
or for hot dry air over +140F steel, oval neck track bolts and
Temperature range 30F to (+60C).
+230F (34C to +110C). heavy hex nuts with chemical
Recommended for cold and Grade O and physical properties of
hot water service within the fluoroelastomer ASTM F-593, Group 2, Condi-
specified temperature range Fluoroelastomer (Blue color tion CW.
code). Temperature range

17.25 - 3
This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.

17.25 - 4