Professional Documents
Culture Documents
TABLE OF CONTENTS
1 INTRODUCTION.............................................................................................1-3
2 SPECIFICATIONS..........................................................................................2-1
3 DIMENSIONS:................................................................................................3-1
4 GENERAL INFORMATION............................................................................4-1
5 OPTIONS........................................................................................................5-1
6 INSTALLATION..............................................................................................6-1
1
VR6-B Service Manual
6.1 CONNECTIONS..................................................................................................6-1
6.1.1 TERMINAL DESCRIPTIONS................................................................................6-1
6.2 INTERNAL ADJUSTMENTS......................................................................................6-2
6.3 CONNECTION DIAGRAMS.......................................................................................6-3
8 MAINTENANCE..............................................................................................8-1
9 TROUBLESHOOTING PROCEDURES.........................................................9-1
2
VR6-B Service Manual
1 Introduction
The VR6-B is designed as an improvement to and replacement for the VR3 and
VR3F. It has the same footprint, same functionality and similar wiring to the
VR3(F) with the added benefit of adjustable knee frequency and stability. More
importantly, it is UL508 Recognized, CSA Certified and is in conformity with CE
for electro-magnetic emissions. The droop adjustment is on the VR6-B
eliminating the need for an external circuit. One regulator model works with SE or
PM generators. The following gives those who are familiar with the VR3(F)
operation a brief overview of the similarities and differences between the VR3(F)
and the VR6-B.
1.1 Mounting
The VR6-B mounts in the same space with the same hardware as the VR3(F).
1.2 Wiring
Note: Detailed wiring diagrams are provided later in this manual.
The terminals on the bottom of the VR6-B are the same as those on the VR3(F).
Sensing leads are connected to 20, 22 and 24, PMG leads to 26, 28 and 30, and
F1 and F2 to the exciter field, exactly as they are to the VR3(F). The only
difference is that when using the VR6-B with an SE generator terminal 20 must
be jumpered to terminal 28, terminal 22 to terminal 30, and terminal 24 to
terminal 26. The jumpers come installed for service. These jumpers must be
removed for use with a PM generator.
When using the VR3(F)SE for single phase sensing a jumper is installed from
terminal 20 to terminal 28. This is not necessary on the VR6-B. Single phase
sensing is not available on the VR3(F)PM. The VR6-B provides single-phase
sensing for SE and PM generators. This is done through connections on the top
terminals discussed below.
There are a number of differences in wiring to the terminals on the top of the
VR6-B. The VR6-B is compatible with the Basler Var/PF Controller Model
Number SCP250G-50 for 50 Hz operation or SCP250G-60 for 60 Hz operation.
This is connected on terminals 2 and 3.
When using a remote voltage adjust rheostat with the VR3(F) you remove the
jumper between 4 and 7 and connect the rheostat between terminals 6 and 7.
For internal voltage adjust on the VR3(F) the jumper is in place from terminal 4 to
terminal 7. On the VR6-B the wiring is similar. The difference is that the remote
voltage adjust rheostat is connected between terminals 6A and 7. The jumper
between terminal 4 and terminal 7 is on for internal voltage adjust and removed
for remote, exactly like the VR3(F).
On the VR3(F) the droop current transformer (CT) circuit is connected between
terminal 5 and terminal 6. On the VR6-B the a 1Amp CT is connected between
3
VR6-B Service Manual
1.3 Adjustments:
Like the VR3(F) the VR6-B has an internal voltage adjust pot. Unlike the VR3(F)
this pot must be turned fully clockwise to use the remote voltage adjust rheostat.
The VR6-B has a knee frequency adjustment pot and a stability pot that must be
adjusted for correct operation. The VR3(F) does not have these features. See the
Adjustment section of this manual for full instructions on how to use these. The
knee frequency pot allows the knee frequency to be adjusted to match the
frequency of the engine. The stability pot allows adjustment to obtain the quickest
possible response to block loading while maintaining voltage stability at steady
state operation.
4
VR6-B Service Manual
2 Specifications
Refer to Table 1-1 for the electrical specifications and to Table 1-2 for the physical
specifications of the VR6-B.
Table 2-1. Electrical Specifications
Output Power (with a 240 Vac 12 Adc @ 65 Vdc maximum continuous.
Input): 25 Adc @ 125 Vdc forcing for 10 seconds.
AC Input Power: 180 to 264 Vac, single-phase or three-phase, 50/60 Hz;
or 63 to 105 Vac, three-phase, 100 to 240 Hz, PMG,
3125 VA maximum; or 240 Vac, single-phase, 100 to 240
Hz, PMG, 3125 VA.
AC Sensing Voltage: 180 to 264 Vac, 50/60 Hz; single- or three-phase.
External Voltage Adjust Rheostat: 10 kohm, 2 W, potentiometer
Regulation Accuracy: 1% of voltage setpoint
Voltage Drift: 1% voltage variation for a 40C (104F) change.
Response Time: < 4 milliseconds
Frequency Compensation: 1 or 2 V/Hz jumper selectable with knee adjustable from
45 Hz to 65 Hz.
EMI Suppression: Internal filter
Voltage Build-Up: Internal provisions for automatic voltage build-up from
generator residual voltages as low as six Vac.
Overexcitation Shutdown: Overexcitation protection starts timing at 90 Vdc 5%
and takes the output to zero in greater than 30 seconds.
The output can be 125 Vdc for greater than 10 seconds.
Droop 1 A or 5 A, <10 VA, Adjustable from 0 to 10% at rated
input current, 0.8 power factor
Power Dissipation: 50 W maximum.
UL Recognized/CSA Certified UL Recognized per Standard 508, UL File NO. E97035.
CSA Certified per Standard CAN/CSA-C22.2 No. 14-95,
CSA File No. LR 23131
Specifications 1
VR6-B Service Manual
Specifications 2
VR6-B Service Manual
3 Dimensions:
(In Inches)
.281 DIA. HOLE
(4 PL)
.51 DIA.
(4 PL) .750
2 3 4 5 5a 6 6a 7 8 9
DRP
FAC CAL
VLT ADJ
UF
STB
8.01
7.500
0.438 20 22 24 26 28 30 F1 F2
2.96
5.500 0.438
D2590-23.vsd
0.593 06-08-00
6.01
Dimensions 1
VR6-B Service Manual
4 General Information
This manual covers the VR6-B voltage regulator, which is used on 4/6 and 10/12
lead, self-excited and permanent magnet generators. The VR6-B is typically
located in the generator terminal box or the generator set marshalling box.
4 T1
7 1
11 T2
T3
5
8
10 6 2
9 Stability
F2 F1 Adjust 22 24 20 5 6 3
Overexcitation Level
Comparator Reference Adjust
Protection
UF Knee Adjust
VR6-B
D2590-29.vsd
01-22-00
6A 8
Jumper
1. Generator Lines (3 phase voltage) 4. Main stator 8. Rectifiers
2. Generator lines (sensing voltage 5. Main rotor 9. Generator line (DC excitation voltage)
AC power) 6. Exciter stator 10. Permanent magnet
3. VR6-B regulator 7. Exciter rotor 11. Permanent magnet stator
General Information 1
VR6-B Service Manual
(7). This increased three-phase AC voltage from the exciter rotor (7) causes
more AC current to flow. The three-phase ACV is then rectified to DCV by the
three-phase full wave rectifier (8). The increased DC output from the bridge
rectifier is carried to the main rotor (5) by conductors, which are routed through a
passage in the generator shaft. Increased current through the main rotor (5)
increases the magnetic field of the generator. The increased magnetic field
induces a larger AC voltage into the main stator (4). Therefore, the three-phase
AC voltage (1) increases until the voltage regulator no longer senses a
decreased output voltage.
When the voltage regulator senses an increase in output voltage due to a
decrease in load, the regulator will decrease the DC voltage to the exciter. A
decrease in generator voltage will occur due to similar responses to the regulator
sensing a decrease in output voltage, as described above.
General Information 2
VR6-B Service Manual
4.2.6 Droop
When operating a generator set in parallel with another generator set, it is
necessary that the output voltages match, to prevent circulating currents. Based
on power factor, droop raises or lowers the reference voltage, to evenly match
the generator sets. This results in a slight lowering of the output voltage. The
droop adjustment regulates how much droop is used.
4.2.7 Stability
Because of a time delay from when the regulator senses a change in voltage to
when the generator voltage is increased or decreased, the generator voltage can
become unstable (or hunt). The time delay varies dependent on exciter and
generator time constants. The stability circuit slows the regulator response
enough to stabilize the voltage. The stability adjust is used to ensure the
regulator responds as quickly as possible while still keeping the voltage stable.
4.2.8 Power Supply
The power for the DC voltage supplied to the exciter comes through terminals 26,
28 and 30 as AC voltage. When using a PM generator, the power comes from the
PMG. When using an SE generator the power comes from the generator sensing
lines. The power circuit rectifies this power to the DC voltage and current
needed.
4.2.9 Excitation
The excitation control adjusts the DC output voltage to the exciter based on the
error signal it receives from the comparator.
4.2.10 Overexcitation Protection
If the reference and comparator circuit ask the excitation control for more DC
excitation voltage than it is rated for a defined period of time, the overexcitation
control will shut the regulator off and it will provide no DC excitation voltage. The
generator set must be turned off for the regulator to reset.
General Information 3
VR6-B Service Manual
VR6 Regulator
(12) Terminal Strip for Attachments
(13) Droop Adjustment
(14) Factory Voltage Adjust Range Calculation
(15) Voltage Adjust
(16) Knee Frequency Adjust
(17) Stability Adjust
(18) Terminal Strip for Sensing and Power
Note: Rated sensing voltage for the VR6-B is 240VAC for 60Hz systems and
200VAC for 50 Hz systems. The sensing voltage can be adjusted +10% or 25%.
Generator taps, sensing lead connection to midpoint generator connections or
PTs must be used to step generator voltage down to regulator range when
generator has a different operating voltage.
On PM generators, leads from PMG (11) are connected to terminals 26, 28 and
30 (18) and provide power to the regulator. On SE generators, terminal 20 is
jumpered to 28, terminal 22 to 30, and terminal 24 to 26. The sensing leads
provide the power.
General Information 4
VR6-B Service Manual
The excitation system can be disabled by removal of power from the VR6-B. A
switch removing voltage from terminals 26, 28 and/or 30 will remove power.
General Information 5
VR6-B Service Manual
5 Options
Options 1
VR6-B Service Manual
The Manual Voltage Control can be used to control generator voltage when there
is a failure in the generator regulator assembly. The manual voltage control will
manually control the current flow to the exciter stator.
The manual voltage control panel has switch (1) and voltage control (2) for the
manual-operating mode. Switch (1) is used to make the selection between
AUTO, MAN and OFF. In the AUTO position, the VR6-B regulator controls the
generator voltage. In the OFF position, the voltage will go to zero. In the MAN
position, generator voltage is controlled by voltage control rheostat (2).
Note: The manual voltage control panel must not be installed in a location that is
subject to engine vibrations or to outside weather.
Note: When the manual voltage control is operating in the manual mode, it is not
necessary for the VR6-B regulator to be connected to the generator. However,
the manual control must remain connected to the generator sensing lines.
Options 2
VR6-B Service Manual
When generators operate in parallel there are two primary objectives. First, the
generators share the real power requirements of the electrical load. The
generators also share the reactive power requirements of the electrical load. The
engine governors will control sharing of the real power requirements (kW) and
the voltage regulator will control sharing of the reactive power requirements
(kVAR) of the total system load. Occasionally, one generator output voltage is
slightly higher than the other generators. This will supply lagging reactive current
to the other generators that are connected in the group. The lagging reactive
current will circulate between generators. This could possibly cause ampere
overloading. In order to minimize ampere overloading, an individual generators
output voltage droops in proportion to the lagging reactive current flow. The
reactive current flow is measured with a current transformer.
As reactive lagging generator output current increases, the regulator will cause
the output voltage to lower proportionally. If the measured reactive current is
leading, the output voltage will rise. In either case, this action will tend to reduce
the reactive current for better kVAR sharing with other units.
The following items are required in order to provide the voltage droop function:
1Amp or 5 Amp droop transformer (CT1) (1) and wiring harness. The transformer
senses load current in lead T2 (2) of 4/6 lead generators or in lead T8 of 10/12
lead generators. The droop adjustment on the VR6-B provides adjustment of the
droop voltage.
Transformer CT1 and wiring harness are standard on some generators and an
attachment on other generators.
Note: At full rated CT current (1 Amp or 5Amp) the droop adjustment is up to
10%. As the CT current decreases the amount of droop adjustment decreases
proportionally. It is important to size the CT correctly for the load the generator
will be carrying.
Options 3
VR6-B Service Manual
6 Installation
The VR6 is typically mounted in the generator terminal box or the generator set
marshalling box. See specific generator set drawings for exact location.
6.1 CONNECTIONS
Before connecting the VR6-B into your system, review the terminal descriptions
provided in Table 6-1, the internal adjustments provided in Table 6-2, and the
typical interconnection diagrams shown in Figures 6-1 through 6-18. When
automatic voltage regulation is used with a permanent magnetic excited
generator, ensure that the jumpers are removed between terminals 20 - 28,
22 - 30, and 24 26.
6.1.1 Terminal Descriptions
Table 6-1. Terminal Descriptions
Terminal Number Terminal Description
Upper Terminal Strip
2 Auxiliary Input from var Power Factor Controller
3 Auxiliary Input from var Power Factor
Controller
4 Connect to 7 to use internal voltage adjust, no
connection for external voltage adjust
5 1 Amp Current Transformer
5a 5 Amp Current Transformer
6 Current Transformer Common
6a Common connection for selectable features
7 Connect Remote Adjust from 7 to 6a,
connect to 4 for internal voltage adjust
8 Connect to 6a to select 1v/Hz
underfrequency slope
9 Connect to 6a to select 3 phase sensing
Lower Terminal Strip
20 Phase C sensing input
22 Phase A sensing input
24 Phase B sensing input
26 3-phase power input
28 1-phase or 3-phase power input
30 1-phase or 3-phase power input
F1 Field +
F2 Field -
Installation 1
VR6-B Service Manual
Installation 2
VR6-B Service Manual
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
D2590-11.vsd
06-08-00
Installation 3
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
1
CR1-6 ROTATING RECTIFIERS CONNECT TO TERMINAL 5 FOR 1 AMP CT,
CR7,8 SURGE SUPPRESSION CONNECT TO TERMINAL 5a FOR 5 AMP CT.
DIODES
E1 POSITIVE HEAT SINK
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a
L1 EXCITER FIELD (STATOR) 7 AND REMOVE LINK 4-7 IF FITTED
TO
L2 EXCITER ARMATURE (ROTOR) WITH
REMOTEA ADJUST.
L3 ROTATING FIELD (MAIN
ROTOR)
L4 STATOR (MAIN STATOR) CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
L5 PM EXCITER STATOR 2V/Hz UNDERFREQUENCY SLOPE.
M ROTATING PERMANENT MAGNET CONNECT 6a TO 9 FOR 3-PHASE SENSING;
R2 REMOTE LEVEL RHEOSTAT OPEN FOR 1-PHASE SENSING.
R5 SUPPRESSION RESISTOR
RFA REVOLVING FIELD ASSY
T1 VOLTAGE DROOP 3
CONNECT 2 AND 3 TO SCP250 VAR/PF
TRANSFORMER
(MAY NOT BE SUPPLIED) CONTROLLER. SHORT WHEN NOT USED.
D2590-12.vsd
06-08-00
Installation 4
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
KTK-12
D2590-13.vsd
06-08-00
Installation 5
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
KTK-12
KTK-12
1
CR1-6 ROTATING RECTIFIERS CONNECT TO TERMINAL 5 FOR 1 AMP CT,
CR7,8 SURGE SUPPRESSION CONNECT TO TERMINAL 5a FOR 5 AMP CT.
DIODES
E1 POSITIVE HEAT SINK
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a
L1 EXCITER FIELD (STATOR) TO
7 AND REMOVE LINK 4-7 IF FITTED WITH
L2 EXCITER ARMATURE (ROTOR) A
REMOTE ADJUST.
L3 ROTATING FIELD (MAIN
ROTOR)
L4 STATOR (MAIN STATOR) CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
L5 PM EXCITER STATOR 2V/Hz UNDERFREQUENCY SLOPE.
M ROTATING PERMANENT MAGNET CONNECT 6a TO 9 FOR 3-PHASE SENSING;
R2 REMOTE LEVEL RHEOSTAT OPEN FOR 1-PHASE SENSING.
R5 SUPPRESSION RESISTOR
RFA REVOLVING FIELD ASSY
T1 VOLTAGE DROOP 3
CONNECT 2 AND 3 TO SCP250 VAR/PF
TRANSFORMER
(MAY NOT BE SUPPLIED) CONTROLLER. SHORT WHEN NOT USED.
D2590-14.vsd
06-08-00
Installation 6
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
D2590-15.vsd
06-08-00
Installation 7
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
1
CR1-6 ROTATING RECTIFIERS CONNECT TO TERMINAL 5 FOR 1 AMP CT,
CR7,8 SURGE SUPPRESSION CONNECT TO TERMINAL 5a FOR 5 AMP CT.
DIODES
E1 POSITIVE HEAT SINK
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a
L1 EXCITER FIELD (STATOR) TO
7 AND REMOVE LINK 4-7 IF FITTED WITH
L2 EXCITER ARMATURE (ROTOR) A
REMOTE ADJUST.
L3 ROTATING FIELD (MAIN
ROTOR)
L4 STATOR (MAIN STATOR) CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
L5 PM EXCITER STATOR 2V/Hz UNDERFREQUENCY SLOPE.
M ROTATING PERMANENT MAGNET CONNECT 6a TO 9 FOR 3-PHASE SENSING;
R2 REMOTE LEVEL RHEOSTAT OPEN FOR 1-PHASE SENSING.
R5 SUPPRESSION RESISTOR
RFA REVOLVING FIELD ASSY
T1 VOLTAGE DROOP 3
CONNECT 2 AND 3 TO SCP250 VAR/PF
TRANSFORMER
(MAY NOT BE SUPPLIED) CONTROLLER. SHORT WHEN NOT USED.
D2590-16.vsd
06-08-00
Installation 8
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
KTK-12
D2590-17.vsd
06-08-00
Installation 9
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
KTK-12
KTK-12
1
CR1-6 ROTATING RECTIFIERS CONNECT TO TERMINAL 5 FOR 1 AMP CT,
CR7,8 SURGE SUPPRESSION CONNECT TO TERMINAL 5a FOR 5 AMP CT.
DIODES
E1 POSITIVE HEAT SINK
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a
L1 EXCITER FIELD (STATOR) TO
7 AND REMOVE LINK 4-7 IF FITTED WITH
L2 EXCITER ARMATURE (ROTOR) A
REMOTE ADJUST.
L3 ROTATING FIELD (MAIN
ROTOR)
L4 STATOR (MAIN STATOR) CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
L5 PM EXCITER STATOR 2V/Hz UNDERFREQUENCY SLOPE.
M ROTATING PERMANENT MAGNET CONNECT 6a TO 9 FOR 3-PHASE SENSING;
R2 REMOTE LEVEL RHEOSTAT OPEN FOR 1-PHASE SENSING.
R5 SUPPRESSION RESISTOR
RFA REVOLVING FIELD ASSY
T1 VOLTAGE DROOP 3
CONNECT 2 AND 3 TO SCP250 VAR/PF
TRANSFORMER
(MAY NOT BE SUPPLIED) CONTROLLER. SHORT WHEN NOT USED.
D2590-18.vsd
06-08-00
Installation 10
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
4
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6 20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
CR1-6 ROTATING RECTIFIERS
CR7,8 SURGE SUPPRESSION DIODES 1 CONNECT TO TERMINAL 5 FOR 1 AMP CT,
E1 POSITIVE HEAT SINK CONNECT TO TERMINAL 5a FOR 5 AMP CT.
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a TO
L1 EXCITER FIELD (STATOR)
7 AND REMOVE LINK 4-7 IF FITTED WITH A REMOTE ADJUST.
L2 EXCITER ARMATURE (ROTOR)
CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
L3 ROTATING FIELD (MAIN ROTOR)
2V/Hz UNDERFREQUENCY SLOPE.
L4 STATOR (MAIN STATOR)
L5 PM EXCITER STATOR CONNECT 6a TO 9 FOR 3-PHASE SENSING;
M ROTATING PERMANENT MAGNET OPEN FOR 1-PHASE SENSING.
R2 REMOTE LEVEL RHEOSTAT 3 CONNECT 2 AND 3 TO SCP250 VAR/PF
R5 SUPPRESSION RESISTOR
CONTROLLER. SHORT WHEN NOT USED.
RFA REVOLVING FIELD ASSY
3-PHASE VOLTAGE SENSING LEADS - CONNECT TO
4
(MAY NOT BE SUPPLIED) T1 VOLTAGE DROOP TRANSFORMER 240 VOLT SECONDARY OF METERING TRANSFORMERS.
PHASE RELATION WITH TRANSFORMER T1 IS IMPORTANT
CONNECT TERMINAL 22 TO P.T. ON GENERATOR T1
D2590-19.vsd CONNECT TERMINAL 24 TO P.T. ON GENERATOR T2
06-08-00 CONNECT TERMINAL 20 TO P.T. ON GENERATOR T3
Installation 11
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
ABC 10 AMP
L5
S N
M ABC 10 AMP
CR1-6 ROTATING RECTIFIERS
CR7,8 SURGE SUPPRESSION 1
CONNECT TO TERMINAL 5 FOR 1 AMP CT,
DIODES
E1 POSITIVE HEAT SINK CONNECT TO TERMINAL 5a FOR 5 AMP CT.
E2 NEGATIVE HEAT SINK 2 CONNECT REMOTE VOLTAGE ADJUST FROM 6a
L1 EXCITER FIELD (STATOR) TO
7 AND REMOVE LINK 4-7 IF FITTED WITH A REMOTE
L2 EXCITER ARMATURE (ROTOR) ADJUST.
L3 ROTATING FIELD (MAIN CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
ROTOR) 2V/Hz UNDERFREQUENCY SLOPE.
L4 STATOR (MAIN STATOR)
L5 PM EXCITER STATOR CONNECT 6a TO 9 FOR 3-PHASE SENSING;
M ROTATING PERMANENT MAGNET OPEN FOR 1-PHASE SENSING.
R2 REMOTE LEVEL RHEOSTAT 3
CONNECT 2 AND 3 TO SCP250 VAR/PF
R5 SUPPRESSION RESISTOR CONTROLLER. SHORT WHEN NOT USED.
RFA REVOLVING FIELD ASSY
4 3-PHASE VOLTAGE SENSING LEADS - CONNECT TO
(MAY NOT BE SUPPLIED)T1 VOLTAGE DROOP 240 VOLT SECONDARY OF METERING TRANSFORMERS.
TRANSFORMER PHASE RELATION WITH TRANSFORMER T1 IS IMPORTANT
CONNECT TERMINAL 22 TO P.T. ON GENERATOR T1
D2590-20.vsd CONNECT TERMINAL 24 TO P.T. ON GENERATOR T2
06-08-00 CONNECT TERMINAL 20 TO P.T. ON GENERATOR T3
Installation 12
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
4
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
Installation 13
VR6-B Service Manual
10K
T1 T2 T3
R2
T5 T6 2
T4
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
POWER
TRANSFORMER
KTK-12
KTK-12
Installation 14
VR6-B Service Manual
1 1
CONNECT TO TERMINAL 5 FOR 1 AMP CT,
1 CONNECT TO TERMINAL 5a FOR 5 AMP CT. PF VAR 5 kOHMS
CONNECT REMOTE VOLTAGE ADJUST FROM 6a
2 TO
7 AND REMOVE LINK 4-7 IF FITTED WITH
A
REMOTE ADJUST.
CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
2V/Hz UNDERFREQUENCY SLOPE.
CONNECT 6a TO 9 FOR 3-PHASE SENSING; X Y J K S1 S2 S3 P1 P2 P3
OPEN FOR 1-PHASE SENSING.
T1
1
3
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6
20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
L1
KTK-12
KTK-12
D2590-24.vsd
12-12-00 KTK-12
Installation 15
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T2 T1
T3 3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
R5
L2
KTK-12
L1
KTK-12
KTK-12
4 SPIKE
21 TB1 PN 4 3 SUPPRESSION
3 MODULE
CBS212/CBS212A 1 CONNECT TO TERMINAL 5 FOR 1 AMP CT,
TB2 2 1
CONNECT TO TERMINAL 5a FOR 5 AMP CT.
CR1-6 ROTATING RECTIFIERS L5 PM EXCITER STATOR CONNECT 6a TO 8 FOR 1V/Hz; REMOVE FOR
CR7,8 SURGE SUPPRESSION DIODES M ROTATING PERMANENT MAGNET 2V/Hz UNDERFREQUENCY SLOPE.
E1 POSITIVE HEAT SINK R2 REMOTE LEVEL RHEOSTAT CONNECT 6a TO 9 FOR 3-PHASE SENSING;
E2 NEGATIVE HEAT SINK R5 SUPPRESSION RESISTOR OPEN FOR 1-PHASE SENSING.
L1 EXCITER FIELD (STATOR) RFA REVOLVING FIELD ASSY
T1 VOLTAGE DROOP TRANSFORMER
L2 EXCITER ARMATURE (ROTOR) 3
L3 ROTATING FIELD (MAIN ROTOR) (MAY NOT BE SUPPLIED) CONNECT 2 AND 3 TO SCP250 VAR/PF D2590-27.vsd
CONTROLLER. SHORT WHEN NOT USED. 06-08-00
L4 STATOR (MAIN STATOR)
Installation 16
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6 20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
3 SPIKE
SUPPRESSION
4 MODULE KTK-12
L1
KTK-12
KTK-12
D2590-25.vsd
06-08-00
Installation 17
VR6-B Service Manual
10K
T1 T2 T3
R2
T0 T8 2
T1
3 1
2 3 4 5 5a 6 6a 7 8 9
VR6-B
L3
CR8
CR7
CR1 CR4
RFA
CR2 CR5
CR3 CR6 20 22 24 26 28 30 F1 F2
E1 E2
R5
L2
KTK-12
L1
100 MV
SHUNT
TO ALARM OR
SHUTDOWN
4
CIRCUITS
KTK-12
KTK-12
D2590-26.vsd
06-08-00
Installation 18
VR6-B Service Manual
5
4
3
2
Greater than 1 VA SENSING 1
TRANSFORMERS
4 5
1:1
E1 9 3
MAGNETEK
SERIES
BOOST
E2 8
MODULE 2
FIELD
E3
22 F1
24
VR6-B
20 F2
P0004-30.vsd
12-11-00
Installation 19
VR6-B Service Manual
CT
GEN 1
5 or 5A
0.1
52b
6
VR6-B
CCC
ENABLE
VR6-B
0.1 CONTACT
5 or 5A
52b
6 LOAD
GEN 2
CT
VR6-B
5 or 5A
0.1
52b
6
GEN 2 P0001-18.vsd
CT 07-13-00
Installation 20
VR6-B Service Manual
7.3 ADJUSTMENTS
For location of the adjustments referenced in the following paragraphs, refer to
Installation Section.
7.3.1 Field Flashing
When the regulator is operated with the generator for the first time, the polarity of
the residual magnetism may not be correct or of sufficient magnitude. If
generator residual voltage is less than 6 Vac at terminals 26,28 and 30 shut
down the prime mover and follow the procedures in the generator manual for
flashing the field.
7.3.2 Knee Frequency Adjustment
The underfrequency knee can be set for 50 (60) Hz operation as described in the
following paragraphs.
1. Adjust the generator frequency for 50 (60) Hz.
2. Adjust the underfrequency potentiometer (UF) fully CCW or until voltage does
not increase with further turning.
3. Adjust the Voltage Adjust for 200 (240) Vac.
4. Adjust the underfrequency potentiometer (UF) CW until the voltage begins to
decrease.
5. Adjust the underfrequency potentiometer (UF) CCW until the voltage just
returns to the value set in Step 3.
6. The underfrequency knee is now set just below the nominal operating
frequency. Further rotation in the CCW direction will lower the frequency at
which underfrequency compensation begins.
7. Connecting a jumper from terminal 8 to terminal 6a will provide an
underfrequency slope of 1 pu V/Hz. No connection to terminal 8 will result in
an underfrequency slope of 2 pu V/Hz.
7.3.3 Stability (STB) Adjustment
An oscilloscope or other voltage-recording device should be used if an optimal
stability setting is desired. Adjust the stability setting with the generator at no
load. Good response can be obtained with the following procedure.
1. Rotation of the front panel STB control in the clockwise (CW) direction will
slow response time.
2. Rotation of the front panel STB control in the counter-clockwise (CCW)
direction will speed response time. If rotated too far CCW, the generator
voltage may oscillate (hunt).
3. If voltage is unstable, rotate the STB control CW until it is stable. Rotate the
front panel STB control CCW until the system just begins to oscillate and then
rotate CW just past the point where oscillation occurred.
7.3.4 Voltage (VLT ADJ) Adjustment
1. Installation of a jumper across terminals 4 and 7 allows the internal (front
panel) VLT ADJ adjustment to vary the generator nominal voltage over the
operating range.
2. Remove the jumper between terminals 4 and 7 and connect a 10k ohm
external voltage adjust potentiometer across terminals 6A and 7 to allow
operation of the external voltage adjust potentiometer. On generator sets with
a Control Panel voltage adjustment, the voltage adjust potentiometer is
located in the Control Panel. The internal voltage adjustment should be set
fully CW for proper operation of the external adjustment.
CAUTION
The factory calibration (FAC CAL) adjustment is intended for use by factory
technicians only. The following procedure can be used if the factory calibration
has been disturbed.
and 180 Vac. The unit is calibrated and the calibration potentiometer can be
sealed.
8 Maintenance
Maintenance 1
VR6-B Service Manual
9 Troubleshooting Procedures
100 W
Lamp
240
Vac
10
ohm
F1 F2 28 26 30 20 22 24
VR6-B
D2590-28.vsd 2 3 4 5 5a 6 6a 7 8 9
06-08-00
1. Check that you are using a meter that is reading correctly. If you are reading
the voltage from the Control Panel check that this is correct with a meter. DO
NOT TAKE THE READING DIRECTLY OFF THE POWER LEADS. Take the
Troubleshooting Procedures 1
VR6-B Service Manual
Troubleshooting Procedures 2
VR6-B Service Manual
Troubleshooting Procedures 3
VR6-B Service Manual
- NO Go to step 15.
- Symptom If the frequency is high and the knee frequency is not set
correctly, the voltage will increase proportionally to the frequency. If the
frequency is over rated frequency, the voltage will be over rated
voltage.
15. Check Voltage Regulator
Troubleshooting Procedures 4
VR6-B Service Manual
1. Check that you are using a meter that is reading correctly. If you are reading
the voltage from the Control Panel check that this is correct with a meter. DO
NOT TAKE THE READING DIRECTLY OFF THE POWER LEADS. Take the
reading at a low current customer connection point or at the voltage sensing
leads, correcting this for any power transformers or midpoint connections.
- METER OK Go to step 2
- METER NOT OK Get correct meter, if voltage still low proceed to step
2.
2. Turn genset off. Check that terminal 4 is not jumpered to terminal 7 if you are
using a remote voltage adjust pot.
- NOT USING REMOTE VOLTAGE ADJUST POT AND TERMINALS 4
AND 7 ARE JUMPERED OR USING REMOTE VOLTAGE ADJUST
POT AND TERMINAL 4 NOT JUMPERED TO TERMINAL 7 Go to
step 3
- USING REMOTE ADJUST POT AND TERMINAL 4 IS JUMPERED TO
TERMINAL 7. Remove jumper from terminal 4 to terminal 7, go to
step 3.
- Symptom: Voltage set point is 30% lower if using remote voltage
adjust pot and terminal 4 is jumpered to terminal 7.
3. If you are using a remote voltage adjust pot, turn it fully clock-wise.
Disconnect from regulator. Measure resistance at 80 and 82. Resistance
should be between 9.5K and 10.5K.
- RESISTANCE BETWEEN 9.5K AND 10.5K - Go to step 4
- RESISTANCE LOWER THAN 9.5K OR GREATER THAN 10.5K -
Go to Voltage Regulator Attachment Troubleshooting Section,
troubleshoot voltage adjust pot. If voltage still low, go to step 4.
- Symptom: If the resistance of the voltage adjust pot is to low, this can
prevent the pot from increasing the voltage to the proper setting.
4. If you are using a three-phase sensing connection, check that there is a
jumper between terminal 6A and terminal 9.
- USING THREE PHASE SENSING AND THERE IS A JUMPER
BETWEEN TERMINAL 6A AND TERMINAL 9, OR USING SINGLE-
PHASE SENSING CONNECTION AND JUMPER BETWEEN
TERMINAL 6A AND 9 HAS BEEN REMOVED Go to step 5
- USING THREE PHASE SENSING AND THERE IS NO JUMPER
BETWEEN TERMINAL 6A AND TERMINAL 9 Install jumper between
terminal 6A and 9, go to step 5.
- Symptom: If you are using three-phase sensing and there is no
jumper from 6A to 9, the terminal voltage will be 33% below the
desired setting.
5. If you are not using a VAR/PF Controller, ensure that terminal 2 and terminal
3 are jumpered.
Troubleshooting Procedures 5
VR6-B Service Manual
Troubleshooting Procedures 6
VR6-B Service Manual
Troubleshooting Procedures 7
VR6-B Service Manual
22. Is the sensing voltage correct and the generator voltage incorrect?
- YES The regulator is not the problem. There is something wrong with
the generator taps, PT ratios, generator connections or sensing wire
connections.
- NO Go to step 23.
23. Check the voltage between F1 and F2. Is it unusually high for no load?
- YES Check the rotating diodes per generator manual.
- NO Go to step 24.
24. Check Regulator.
Troubleshooting Procedures 8
VR6-B Service Manual
1. Check that you are using a meter that is reading correctly. If you are reading
the voltage from the Control Panel check that this is correct with a meter. DO
NOT TAKE THE READING DIRECTLY OFF THE POWER LEADS. Take the
reading at a low current customer connection point or at the voltage sensing
leads, correcting this for any power transformers or midpoint connections.
- METER OK Go to step 2
- METER NOT OK Get correct meter, if voltage still unstable proceed to
step 2.
2. Turn genset off. Check all generator and regulator wiring. Pay special
attention to a) sensing circuit from generator connection through any PTs, to
regulator connection at terminals 20, 22 and 24; b) power connections at
terminals 26, 28 and 30 from PMG or jumpered from terminals 20, 22 and 24;
and c) Exciter connections at terminals F1 and F2.
- GENERATOR AND REGULATOR CONNECTIONS OK Go to step 3
- CONNECTION PROBLEM FOUND Fix problem, go to step 3.
- Symptom: A loose wire or solder joint in the sensing circuit, power
supply, or excitation circuit can cause unstable voltage.
3. Turn genset on and run at no load. Is voltage stable?
- YES Go to step 6
- NO Go to step 4
4. Is engine rpm stable?
- YES Go to step 5
- NO The regulator is not the problem, go to engine manual to
troubleshoot for unstable rpm.
- Symptom: If the engine rpm is unstable, the frequency is unstable and
the voltage will follow the frequency.
5. Readjust the stability pot per instructions in this manual.
- VOLTAGE STABLE Go to step 6
- CANNOT STABILIZE VOLTAGE WITH STABILITY POT
ADJUSTMENT Go to step 11.
6. Add load to generator. Is voltage stable?
- YES FINISHED
- NO Go to step 7
7. Check load. Is voltage as stable as could be expected with varying nature of
load?
- YES FINISHED Regulator is not the problem. You will need to
consult with someone about generator sizing and system setup.
- NO Go to step 8.
8. Check engine. Is the rpm stable?
- YES Go to step 9,
- NO Regulator is not the problem, go to engine manual.
9. Is there harmonic distortion in load above 20% or severe notching.
Troubleshooting Procedures 9
VR6-B Service Manual
- YES regulator is not the problem. You will need to consult someone
about reducing the harmonics and/or notching of the load.
- NO Go to step 10.
10. Is there noise in the circuit from attachments that would account for the
instability?
- YES - Regulator is not the problem, you will need to consult with
someone to reduce the noise.
- NO Go to step 11,
11. Check Regulator.
Troubleshooting Procedures 10
VR6-B Service Manual
Troubleshooting Procedures 11
VR6-B Service Manual
Troubleshooting Procedures 12
VR6-B Service Manual
Droop Circuit
1. Connect droop circuit ensuring connections are correct.
2. Run genset, add load. Does voltage increase quickly to very high and then go
very low?
- YES Go to step 3,
- NO Go to step 4.
3. Switch wires to terminals 5 and 6 for a 1Amp CT or 5A and 6 for a 5Amp CT.
Run generator at no load. Is problem corrected?
- YES Go to RFI Filter troubleshooting section,
- NO Go to step 4,
4. Check voltage between terminals 5 and 6 for a 1Amp CT or terminals 5A and
6 for a 5Amp CT. Is there a voltage?
- YES Go to RFI Filter troubleshooting section,
- NO CT is bad, replace it.
RFI Filter
1. Reconnect RFI Filter.
2. Start genset. Is there a problem?
- YES replace RFI filter,
- NO Go to KVAR/PF Controller troubleshooting section.
KVAR/PF Controller
1. Reconnect KVAR/PF controller. Remove jumper between terminals 2 and 3.
2. Start genset. Is there a problem?
YES Refer to manufacturers troubleshooting procedures.
Troubleshooting Procedures 13
VR6-B Service Manual
NO FINISHED.
Troubleshooting Procedures 14