Professional Documents
Culture Documents
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Jaume Salom1, Joakim Widn2, Jos Candanedo3, Igor Sartori4, Karsten Voss5, Anna Marszal6
1
Catalonian Institute for Energy Research, Barcelona, Spain; 2Uppsala University, Uppsala,
Sweden; 3Concordia University, Montral, Canada; 4SINTEF, Oslo, Norway, 5University of
Wuppertal, Wuppertal, Germany; 6Aalborg University, Aalborg, Denmark
(E-mail: jsalom@irec.cat)
- 2514 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
smart grid features, and smart meters in building is usually possible only for periods of about
advanced buildings, implies that new opportunities one day or perhaps a few days.
will be available for information exchange between
Community designers and urban planners
buildings and the grid. It will be possible for the
building to respond dynamically to price signals from LMGI indicators need not be limited to a single
the grid, and to take demand response actions. Load building: they could also be used to describe the
management is of foremost interest for utilities and performance of building clusters or larger
could help in popularizing net-zero energy designs. communities. In this sense, LMGI indicators can
work as descriptors of a generalized energy system.
The indicators presented herein deal with buildings
Building groups or communities may include
using electricity as their sole energy carrier (all-
centralized CHP, storage or district heating systems
electric buildings). Electricity is the main priority in
that could help in managing the load of the
this analysis, since the technical challenges of storing
community over long periods. Designers of such a
electric energy highlight the relevance of the
system could benefit from load matching indicators
building-grid interaction. However, most of these
with low time resolution (for instance, monthly solar
indicators may also be applicable to buildings using
fraction).
other energy carriers (e.g., buildings connected to a
district heating or cooling system). Grid operators at a local distribution level
The indicators presented here are intended only as Operators of distribution grids at medium or low
assessment tools: there is no inherent positive or voltage (a few hundred to a few thousand volts) are
negative value associated with them. For this reason, interested in the load distribution on the grid,
we suggest avoiding the use of the term mismatch especially peak powers, because these are influential
(used in some indicators), which may have a negative on losses and voltage profiles. Therefore, grid
connotation. Matching the buildings load with PV indicators with very high temporal resolution (i.e.,
generation may or may not be appropriate depending time scales of at least hours, or even down to minutes
on the circumstances. or seconds), may help them in assessing and design
The paper is structured as follows: first, target groups the operation limits of the grid. For example, these
for different types of indicators are identified. indicators may help to improve voltage regulation in
Second, a literature review of previously suggested the case of high penetration rates of PV systems
indicators is presented. Third, based on this review, a (Fechner, 2011). Indicators based on probability and
set of LMGI indicators chosen from the literature, as statistical information could be useful for operators
well as some new or modified indicators, are of distribution grids.
evaluated for an example Net ZEB. Finally, the Grid operators at a national or regional level
findings are discussed and conclusions are drawn.
Operators of national energy grids are familiarized
TARGET GROUPS FOR INDICATORS with economic dispatch and planning the operation of
Different target audiences will be interested in generation plants and transmission lines based on
different kinds of quantitative indicators. The level of expected loads. Grid indicators with low temporal
detail, the time resolution and technical complexity resolution (daily or monthly) are useful for this target
of the indicators must be adapted to the needs of group, as they could be used to assess the impact of
different groups. The following potential target net-zero energy buildings in the grid. Aggregated
audiences have been identified: grid indicators at hourly or even less resolution will
help to manage national grids and to increase the
Building designers and owners penetration of renewables in the electric power
When developing a Net ZEB, quantitative load system, especially if high daily peak/baseload ratios
matching indicators may guide the design team in occur.
comparing different design/project scenarios and
REVIEW OF LMGI INDICATORS
selecting equipment. In particular, they could be
useful in sizing energy storage devices and HVAC A literature survey of load matching and grid
components as well as adjusting orientation and slope interaction indicators was carried out. When these
of solar energy systems or optimizing the control two concepts are mentioned in the literature, it is not
strategy for building integrated CHP systems. Load always obvious what the differences between them
match indicators may also serve to assess the are. As it was stated in the introduction, the main
vulnerability of the building to natural catastrophes, distinction made here is that load matching indicators
weather events or a grid breakdown. measure the degree of overlap between generation
and load profiles whereas grid interaction indicators
Building owners or operators could also use grid
take aspects of the unmatched parts of generation or
interaction indicators to better take advantage of
load profiles into account.
time-of-use (TOU) electricity rates or feed-in tariffs
(FIT) (Newsham et al., 2010). Indicators developed Another important distinction to make regards the
based on daily and hourly data may be of interest for information needed for evaluation of the indicators.
this target audience, since energy storage in a Some indicators use only the on-site load and
- 2515 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
generation profiles, while others also use additional purchased or delivered energy for a given time
information such as energy market prices or resolution, normalised by the highest absolute value.
information on a whole set of buildings in an area. The capacity factor, as formulated by Verbruggen et
Given their lower dependency on data, it is evident al. (2011), shows the total energy exchange with the
that indicators of the former type are easier to both grid divided by the exchange that would have
evaluate and generalise, while the latter type occurred at nominal connection capacity, i.e. a
becomes more specific in both time and place. measure of the utilisation of the grid connection.
Table 1 shows a categorisation of the indicators, or Another aspect to be considered is the distribution of
types of indicators, found in the available literature. power peaks for delivered or demanded energy.
A short summary of the findings is given below. These are called peak power indicators here and
could simply be the maximum peak power or the
Table 1. Summary of LMGI indicators.
time duration or mean value of the highest peaks. For
grid connections and distribution grids with a large
Indicator category
number of buildings that are both net users and
Load matching Grid interaction
exporters of energy, the latter indicators could
I II
provide basic information for dimensioning and
Load match index1 Grid interaction
design, using for example dimensioning rate. Colson
On-site load and
4
Cover factor Capacity factor4
namely the microgrid citizenship tool, based on key
Data requirements
Mismatch Profile addition for the degree of generation to load. The storage
data
compensation factor5 indicators3 ratio (SR) gives a measure of how well the installed
3
Market matching Coincidence factor6 generation is supported by its own storage. Finally,
the intermittency ratio (IR) is intended to give a
1
Voss et al. (2010), 2Widn et al. (2009), 3Widn and qualitative indication as to how dependable the
Wckelgrd (2010), 4Verbruggen et al. (2011), 5Lund microgrid (building) is at supplying power.
et al. (2011), 6Willis and Scott (2000), 7Castillo-
Cagigal et al. (2010), 8Colson and Nehrir (2009).
Category III
Category I This category contains indicators that use additional
This category encompasses load matching indicators data to show aspects of load matching that cannot be
that do not need any additional information besides shown with only load and generation data. The
the load and generation profiles. The first four, mismatch compensation factor (MMCF) is the
namely the load match index, the solar fraction, the quotient between the on-site generation capacity that
cover factor and the self-consumption factor, contain meets the annual demand and the capacity that
essentially the same information; the fraction of the compensates for the mismatch (i.e. the capacity that
load covered by on-site generation. makes total generated electricity worth as much as
demanded electricity on an annual basis). A MMCF
The actual concept of a solar fraction is of course
> 1 means that the system that compensates for the
only applicable for on-site solar technologies, while
mismatch is smaller than the system that gives a net
the three others are more general. These four
zero energy balance because generated electricity is,
indicators are, as an example, well suited for
on average, worth more than demanded electricity
describing how much of the demand can be saved by
(Lund et al., 2011). The market matching indicator is
on-site energy supply and how much energy must be
similar to the MMCF and shows the difference
bought from the grid by the building owner. The fifth
between the market value of bought and delivered
indicator, the loss-of-load probability (LOLP) index,
energy (Widn and Wckelgrd, 2010).
instead shows how often the on-site supply is not
enough to cover the demand. The main advantage of these indicators is that they
can value the load matching of the building from the
electricity markets viewpoint. If there is a need for
Category II electricity on the market, the MMCF will be greater
This category collects indicators that can be used to than 1 and the market matching index positive,
show different aspects of the grid interaction of a indicating that the mismatch in the building is
building, without any need for additional data besides generally positive from the systems point of view.
load and generation profiles. The grid interaction Electricity market prices for the studied location are
index shows the variability of the amount of an important additional piece of information needed
to evaluate these indicators.
- 2516 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Category IV PV
Although the energy needs of the whole market may
coincide with an energy surplus from the building,
there may also be unfavourable consequences of
electricity overproduction levels in the local
distribution grid. Category IV lists a few indicators
for identifying such situations. The profile addition
GENERATION
indicators are evaluated for the aggregate load of a SYSTEM (e.g., PV)
local distribution grid to show the effect on the
margin of adding a Net ZEB profile. For example, G(i)
De(i)
the actual indicator evaluated could be one of those l(i) Distribution
METER
+-
listed in category II. This approach needs information Load
Point (L 0.0000
about the aggregate load on the studied grid. The Cs(i) Fe(i)
L(i)
coincidence factor is, in general, the fraction between Ds(i)
- 2517 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
in which the number of samples, N, is given by 7W The connection capacity credit or power reduction
potential can be defined as the percentage of grid
Capacity factor over evaluation period T
connection capacity that could be saved in
iN
comparison with the design connection capacity for a
E (i )
i
building with no local energy supply. It has been
CFb (7) inspired by the kVA credit indicator proposed by
Edes T
Verbruggen et al. (2011).
Loss of load probability
Connection capacity credit
timeL ( i )!>G ( i ) S ( i ) l ( i )@
LOLP (8) Edes
T Ec ,des 1 (16)
Ldes
Peaks above certain barrier (Llim) The two following proposed indices take advantage
time E ( i ) ! Llim of some concepts used in the design of CSP parabolic
E! Llim (9) trough systems and could be useful for determining
T
optimal designs. The generation multiple relates the
Dimensioning rate size of the generation system with the design
capacity load. The equivalent hours of storage
max E (i )
DRb (10) corresponds to the storage capacity expressed in
Edes hours. Both indicators can be used to compare
different Net ZEB designs.
Grid interaction index over period T
Generation Multiple
E (i )
f grid STD (11) Gdes
max E (i ) GM (17)
Ldes
The following three indicators are part of the
microgrid citizenship tool. Equivalent hours of storage
Component Ratio CS
Nh _ S (18)
Ldes
Gdes Ldes
CR (12) The following indices are grid interaction indices or
Gdes Ldes
peak power indicators normalized by the design
Storage ratio capacity load. These indices are better suited for
comparing different Net ZEB design proposals.
Gdes Sdes
SR (13)
Gdes Sdes Relative Feed-in Peak Power
max > E (i )@
Intermittency ratio PPr , f _ e (19)
Ldes
Gdaily avg Sdes
IR (14)
Gdes Sdes Relative Delivered Peak Power
Alternative LMGI indicators min > E (i )@
PPr ,d _ e (20)
Alternative indicators are proposed in this section. Ldes
Some of them consist of minor modifications of the
indicators described in the previous section, in order Relative grid interaction amplitude
to enrich the information they give. Others are Agrid ,r PPr , f _ e PPr ,d _ e (21)
inspired by other kind of systems, such as solar
power plants. Finally, the authors propose indicators Relative grid interaction index
aimed at better describing the flexibility of Net ZEB. E (i )
A modified method to compute the capacity factor is f grid ,r STD (22)
proposed, taking into account the path of the energy Ldes
exchange with the grid. A positive value means that The last proposed index is the no-grid interaction
the building is exporting energy to the grid over the probability, which means the probability that the
evaluation period. building is acting autonomously of the grid. In that
case, the entire load is covered by the direct use of
Capacity factor over evaluation period T
renewable energy system or by the stored energy.
iN
E (i )
i
No grid interaction probability
CFb, E (15) time E i 0.001
Edes T
PE |0 (23)
T
- 2518 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
kWh
-400
Europe competition in 2010 (Team Wuppertal, -600
2010). The building is a Net ZEB, using solar energy -800
as the only energy source and equipped with -1000
technologies that permit maximum energy efficiency. -1200
PV generator systems on the roof and the south -1400
faade contribute, respectively, with about 6.4 and Jan Feb Mar Abr May Jun Jul Aug Sep Oct Nov Dec
3.8 kWp of installed capacity. The system is Figure 3. Load distribution from energy sources and
equipped with a 6 kWh battery, enabling different electricity feed-in to the grid for the case with battery
modes of operation (grid connected, battery-buffered
and occasionally stand-alone). Table 2 summarizes Table 3. Computed LMGI indicators
relevant design parameters used to compute LMGI
indicators. Table 3 shows results of computed LMGI INDICATOR WITHOUT WITH
indicators. BATTERY BATTERY
Load matching indicators
Table 2. Test case design specification parameters f load , h 44.5 % 93.6 %
f load , m 100.0 % 100.0 %
PARAMETER VALUE
Gdes, installed PV Capacity 10.2 kWp f load , y 100.0 % 100.0 %
Ldes, Design load capacity 15 kW J load , h 42.2 % 87.2 %
Edes, Design connection capacity 15 kW J load , m 100.0 % 100.0 %
Sdes, Storage capacity (fully charged to 2.91 kW J load , y 100.0 % 100.0 %
discharged, 1 hour)
LOLPb 57.6 % 17.7 %
Cs, Storage capacity (total) 6 kWh
GM 0.68 0.68
Detailed hourly data from a simulation of the Nh_S 0.0 h 0.5 h
building located in Madrid are available. Simulations Grid interaction indicators
have been performed in cooperation with Fraunhofer CFb 9.8 % 7.5 %
ISE with the DYMOLA simulation environment.
One set of data corresponds to a system without CFb,E 7.2 % 6.9 %
storage. The other data set corresponds to a system OPP 6.82 kW 6.66 kW
with battery, where the battery use is optimized so E! Llim 5 kW 8.93 % 7.63 %
that to preferably match the electricity demand of the DRb 49.1 % 47.8 %
house with its own solar energy generation. Results
Ec,des 0.0 % 0.0%
in Figure 2 and Figure 3 shows that over 9,000
kWh/year are fed-in to the grid for both cases, while CR -0.190 -0.190
grid import is nearly zero in the summer period with SR 1.000 0.556
a storage system. IR 0.262 0.426
Gdaily avg 2.7 kW 2.7 kW
600
400 RES directly Grid import Grid export PPr,f_e 0.49 0.48
200 PPr,d_e -0.10 -0.10
0
-200
Agrid,r 0.59 0.58
-400 fgrid 0.29 0.26
kWh
-600
fgrid,r 0.14 0.13
-800
-1000 PE | 0 0.0 % 56.8 %
-1200
-1400 DISCUSSION
-1600
Jan Feb Mar Abr May Jun Jul Aug Sep Oct Nov Dec
Some points of discussion can be derived from the
test case results. Since the size of the PV system and
the connection capacity are the same for both
Figure 2. Load distribution from energy sources and
scenarios, the values for the indicators GM, CR, Ec,des
electricity feed-in to the grid for the test case without are the same. These indicators might be useful to
battery compare differences in design options, apart from
those due to different energy storage capacities.
- 2519 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
There is a group of indicators peak power (PPr,f_e, Further research is needed to test LMGI indicators
PPr,d_e, Agrid,r, OPP), grid interaction (fgrid, fgrid,r) or using both measured values from actual Net ZEB or
others which computes maximum values of certain results from simulation. This should include not only
variables (DRb, E>lim) which show slight differences all-electrical buildings. Suitable indicators are
between the two test case scenarios. Looking at the important to take advantage of the significant
building energy use results, the peak power is about potential of dynamic building simulation to guide the
1.5 kW. This figure is far from the expected peak design process.
values, which led to a design connection capacity of One of the most important features that LMGI
15 kW. The recorded peak power for energy indicators may grasp is the flexibility of a building. A
consumption during the Solar Decathlon in Madrid buildings flexibility can be described as the ability
(summer 2010) was 5 kW. We conclude that sub- to respond to signals from the grid (smart grids),
hourly resolution, probably less than 10 minutes, is price signals or to some action taken by the residents,
needed to capture more accurately the behaviour of and consequently adjust load, generation and storage
the building when a dynamic simulation is used. control strategies in order to serve the grid, the
For the test case considered above, it is evident that building needs, or adjust to favourable market prices
some indicators show better the impact of using a for energy exports or imports. Such opportunities
battery. For example, both the hourly load match could act on instantaneous values and be
index (fload,h DQG WKH ORDG FRYHU IDFWRU load,h) are implemented automatically by devices such as a
considerably higher when using the battery. The loss smart-meter. What is in the hands of designers at the
of load probability (LOLPb) is significantly reduced design table and what is of interest to the various
when the battery is used, from 57.6% to 17.7%, target groups, e.g. building designers and utility
which reflects an increase in reliability. The no-grid operators is to design the building and its energy
interaction probability ( PE | 0 ) increases from 0% to systems to enhance flexibility.
56.8%, which means that the introduction of the The flexibility could be quantified using suitable
battery increases dramatically the time when no indicator(s), especially those indicators that provide
interaction is registered. This effect can be clearly significantly different values in extreme situations.
appreciated in Figure 4. An extreme situation for an all-electric building is a
Some modifications of existing indicators are feed-in priority strategy (maximum feed-in): the
proposed by the authors. That is the case of the generation system feeds power into the grid
capacity factor (CFb and CFb,E). Different values for regardless of the buildings load or storage
the same scenario (CFb=9.8% and CFb,E=7.2%, for possibilities. The opposite extreme situation is a load
the case without battery) are derived from the matching priority strategy: (maximum load match);
different formulation. The CFb indicator computes storage system and load shifting strategies if any
absolute values of exchanged energy with the grid, provide maximised self-consumption of the
treating exported and imported energy in an generated electricity. The difference between the two
equivalent manner, while CFb,E differentiates values tells how flexible a building is in terms of load
between them. Consequently, CFb,E could take matching and of grid interaction. The higher the
negative values if the delivered energy is higher than flexibility, the better the building will be able to
the feed-in energy. adapt to signals from the grid.
CONCLUSION
8
This work has presented and categorised the LMGI
7
indicators most commonly mentioned in the
6
literature. An example of their application has also
5 been presented. Although the usefulness of each
4 indicator depends on the final objective, LMGI
indicators could add significant value to the output of
kW
3
2 building performance simulation tools, and give a
1 more complete picture of net-zero energy buildings.
0
Although there are no good or bad values,
-1
LMGI indicators enable assessing of the effect of
-2
hours load management strategies (storage, predictive
with_battery without_battery control, orientation, demand response, etc.). In
consequence, they can be used to gauge the
Figure 4. Duration curves for the net energy export
flexibility of a buildings design to respond to
to the grid exchange. Comparison of the test case
variable generation, loads and grid conditions, and to
with and without battery. Positive values means
take advantage of smart grid features.
energy is feed-in to the grid while negative values
means delivered energy from the grid. NOMENCLATURE
CFb Capacity factor for buildings
- 2520 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Cs Charging energy to the storage IEA. 2008. SHC Task 40 ECBCS Annex 52:
CS Total storage capacity Towards Net Zero Energy Solar Buildings.
De Delivered energy from the grid http://www.iea-shc.org/task40/
Ds Discharge energy from the storage Lund, H., Marszal, A., Heiselberg, P. 2011. Zero
DRb Dimensioning rate Energy Buildings and Mismatch Compensation
E Net energy export to the grid Factors. Energy and Buildings. In Press.
Edes Nominal / Design connection
capacity between building and grid Marszal, A., Heiselberg, P., Bourrelle, J.S., Musall,
fgrid Grid interaction index E., Voss, K., Sartori, I., Napolitano, 2011. A.
fload,i Load match index Zero Energy Building A Review of Definition
and Calculation Methodologies. Energy and
J load ,T Load cover factor
Buildings 43 p. 971-979
Fe Feed-in energy to the grid Newsham, G.R and Bowker, B.G. 2010. The effect
G Generation (e.g., on-site PV) of utility time-varying pricing and load control
Gdaily avg Average amount of generated strategies on residential summer peak electricity
energy divided by the average use: a review, NRCC-52707, National Research
number of hours the system is
Council Canada.
generating power per day
i time interval (m=month; y=year) REE 2010, El sistema elctrico espaol 2009, Red
L Building Load Elctrica de Espaa, Madrid.
l Energy looses Sartori, I., Napolitano, A., Marszal, A. J., Pless, S.,
Ldes Nominal / Design capacity load Torcellini, P. and Voss K. (2010) Criteria for
(connection capacity for building Definition of Net Zero Energy Buildings,
with no system generation) EuroSun 2010, 28 Sep. 10 Oct., Graz, Austria
LOLPb Loss of load probability Team Wuppertal 2010 - Bergische Universitt
OPP One percent peak power Wuppertal, Solar Decathlon Europe 2010,
S Net energy exchange with the Project Manual, Update derivable#7, 22.09.2010,
storage system Public available at
T Evaluation period
http://en.sdeurope.org/?p=1079
ACKNOWLEDGEMENT Torcellini, P., Pless, S., Deru, M., Crawley, D. 2006.
The work presented in this paper has largely Zero Energy Buildings: A Critical Look at the
developed in the context of the International Energy Definition. ACEEE Summer Study, Pacific
Agency (IEA) joint programme Solar Heating and Grove, California, USA.
Cooling (SHC) Task40 and Energy Conservation in Verbruggen, B., De Coninck, R., Baetens, R.,
Buildings and Community Systems (ECBCS) Saelens, D., Helsen, L., Driesen, J. 2011. Grid
Annex52: Towards Net Zero Energy Solar Buildings. Impact Indicators for Active Building
Simulation, IEEE PES Conference on Innovative
REFERENCES
Smart Grid Technologies 2011, Anaheim,
Castillo-Cagigal M., Matallanas E., Masa-Bote D., California, US, January 17-19.
Caamao-Martn E., Gutirrez A., Monasterio F. Voss, K., Sartori, I., Napolitano, A., Geier, S.,
& Jimnez-Leube J. 2010. Self-consumption Gonalves, H., Hall, M., Heiselberg, P., Widn,
enhancement with storage system and demand- J., Candanedo, J.A., Musall, E., Karlsson, B.,
side management: GeDELOS-PV system. In 5th Torcellini P. 2010. Load Matching and Grid
International Renewable Energy Storage Interaction of Net Zero Energy Buildings.
Conference (IRES 2010), Berlin, Germany. EuroSun 2010, Graz, Austria. Sep 29th - Oct 1st.
November 22-24.
Widn, J., Wckelgrd, E., Lund, P. 2009. Options
Colson C.M. and Nehrir M.H. 2009. A review of for improving the load matching capability of
challenges to real-time power management of distributed photovoltaics: Methodology and
microgrids. 2009 IEEE Power & Energy Society application to high-latitude data. Solar Energy
General Meeting, Calgary, Alberta. July 26-30. 83: 1953-1966.
EN 50160, 1999. Voltage characteristics of Widn, J., Wckelgrd, E. 2010. Net zero energy
electricity supplied by public distribution solar buildings at high latitudes: The mismatch
systems, CENELEC, 1999 issue. Paper presented at the EASST 2010
Fechner, H. 2011. Energietechniken zur Erreichung Conference: Practicing Science and Technology,
des Plus-Energie-Standards. Presentation at the Performing the Social, Trento, Italy, Sept. 2-4.
workshop Plus-Energie-Technologien und Willis, H.L., Scott, W.G. 2000. Distributed Power
Gebude, January 31st. Generation: Planning and Evaluation, Marcel
Dekker, Inc.: New York.
- 2521 -