You are on page 1of 48

Table of Contents

User Input Data....................................................................................................................................................2


Wind, Material, Thickness & Weights....................................................................................................8
Roof Evaluation/Design & Appendix F..................................................................................................12
Seismic Analysis Results............................................................................................................................16
Anchor Bolt Details........................................................................................................................................31
Anchor Chair Calculations..........................................................................................................................34
Fluid Height Calculations..........................................................................................................................37
Wind Calculations.............................................................................................................................................41
Internal Pressure Calculations..............................................................................................................44
TANK 2016, API-650/653/620 Analysis 2
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

API-650 12th Edition, Addendum 2, January 2016

API-620/650/653 General Tank Data:

------------------------------------------------------------------------------

API Design Code .................................... 650

Design Method (V, O, or A) ......................... One Foot

Run Objective ...................................... Design

Design Temperature ................................. 50.000 C

Design Pressure at Top ............................. 0.00000 KPa

Shell Material ..................................... A-283

Internal Pressure Combination Factor ...........[Fp] 0.40000

Shell Design Stress .....................[Sd or Sts] 0.13789E+06 KPa

Shell Hydro Test Stress ........................[St] 0.15513E+06 KPa

Tank Nominal Diameter ...........................[D] 12.200 m.

Tank Shell Height .............................[HTK] 10.670 m.

Design Liquid Level .............................[H] 9.4500 m.

Liquid Specific Gravity .........................[G] 1.0000

Weight of Attachments/Structures.................... 9535.3 N.

Distance down to Top Wind Girder ................... 0.00000 m.

Joint Efficiency (App A or 653) .................[E] 1.0000

Wind Velocity ...................................... 41.960 M./sec.

Insulation Thickness ............................... 0.00000 mm.

Insulation Density ................................. 0.00000 kg./cu.cm

Include Annular Base Plate Details ................. Yes

Include Wind Moment in Appendix F_4_2 Calculations . Yes


TANK 2016, API-650/653/620 Analysis 3
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Minimum Yield Strength of Bottom Plate: ............ 0.20684E+06 KPa

Number of Shell Courses ............................ 6

Shell Course Height and Thickness:

| Course Height | Thickness | Corrosion Allowance |

# | m. | mm. | mm. |

-----------------------------------------------------------------

1 | 1.83 | 6.0000 | 1.6000 |

2 | 1.83 | 5.0000 | 1.6000 |

3 | 1.83 | 5.0000 | 1.6000 |

4 | 1.83 | 5.0000 | 1.6000 |

5 | 1.83 | 5.0000 | 1.6000 |

6 | 1.52 | 5.0000 | 1.6000 |

Shell Course Material Properties:

| | Sd| St| Fy| UTS| Max Thk |Grade|Group|

# | Material Name | KPa | mm. | | |

-----------------------------------------------------------------------------

1 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

2 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

3 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

4 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

5 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

6 | A-283 | 137892| 155128| 206838| 379203| 25.400 | C | 1 |

Anchor Bolt Input:

------------------------------------------------------------------------------

Anchor Bolt Diameter (optional) .................... 44.450 mm.

Threads per Unit Length ............................ 0.31500 1/mm.


TANK 2016, API-650/653/620 Analysis 4
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Number of Anchor Bolts (optional) .................. 16.000

Bolt Yield Stress .................................. 0.24821E+06 KPa

Bolt Offset from Mean Tank Diameter ................ 0.10000 m.

Anchor Bolt Corrosion Allowance (optional) ......... 1.6000 mm.

Wind Data :

------------------------------------------------------------------------------

Kz parameter ....................................... 1.0400

Kzt parameter ...................................... 1.0000

Kd parameter ....................................... 0.95000

Importance Factor ... ...........................[I] 1.0000

Gust Factor ... .................................[G] 0.85000

Roof Data Input:

------------------------------------------------------------------------------

Roof Type .......................................... Supt Cone

Angle Between Roof and Horizontal .................. 9.4600 deg

Net Area at Roof/Shell Junction ... .............[A] 3236.8 sq.mm.

Thickness of Roof Plate ............................ 5.0000 mm.

Roof Plate Corrosion Allowance ..................... 0.00000 mm.

Ground Snow Load ................................... 0.00000 N/M2

Roof Live Load ..................................... 1000.0 N/M2

Roof Spherical Radius .............................. 0.00000 m.

General Roof Data, No Design

Weight of Roof Plates .............................. 0.00000 N.

Weight of Roof Framing ............................. 0.00000 N.

Percent of Weights Supported by Shell .............. 100.00 %

Roof Joint Efficiency .............................. 0.70000

Supported Cone Roof Data and Roof Material Specification:


TANK 2016, API-650/653/620 Analysis 5
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Structural Database ................................ JIS

Preferred Rafter Type (WH, C ) ..................... C

Preferred Girder Type (WH, C ) .....................

Preferred Column Type (WH, C, P ) ..................

Roof Plate Material ................................ A-283

Roof Plate Allowable Design Stress ................. 0.13789E+06 KPa

Structural Member Material ......................... A-36

Structural Member Allowable Design Str. ............ 0.15995E+06 KPa

Maximum Allowed Rafter Length ...................... 6.1840 m.

Maximum Allowed Girder Length ...................... 1.8850 m.

Center Column Cap Plate Diameter ................... 0.00000 m.

---/ For Analysis of Supported Cone Roofs /---

Number of Girder Rings (Optional) ................. 1

Radius to Girder Ring 1 (Optional) ................. 2.8000 m.

Number of Girders in Ring 1 (Optional) ............. 10

API-650 Seismic Data (App E.):

------------------------------------------------------------------------------

Minimum Yield Strength of Weld Material............. 0.40679E+06 KPa

Nominal Thickness of Bottom Plate ..............[tb] 8.0000 mm.

Seismic Use Group .............................[SUG] 1.0000

Friction Factor .................................... 0.40000

Importance Factor .................................. 1.0000

Initial Anchorage Type ............................. Mechanical

Earthquake Type .................................... Mapped

Site Class ......................................... D

Spectral Acceleration Adjustment Coefficient ....[K] 1.5000

Scaling Factor ..................................[Q] 0.00000


TANK 2016, API-650/653/620 Analysis 6
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Transitional Period ...........................[TL] 0.00000

Mapped maximum earthquake for short periods ...[Ss] 0.00000

Mapped maximum earthquake for 1 sec periods ...[S1] 0.00000

Mapped maximum earthquake for 0 sec period ...[S0] 0.00000

Non-ASCE peak ground acceleration .............[Sp] 0.00000

ASCE short period design accel. parameter .....[SDS] 0.00000

--- Site Specific Data ---

Spectral acceleration parameter at 0 period ..[Sa0*] 0.00000

Spectral acceleration parameter at any period .[Sa*] 0.00000

Computation Control Directives:

------------------------------------------------------------------------------

Roof Projection in Wind Moment = YES

Shell thick converg tolerance = 0.12699999 mm.

Generate Message File = YES

Cosine curve tolerance = 0.30000001

Cosine curve iteration limit = 100.00000

Wind girder shell thickness = MAX

Shell settlement method = FOURIER_SERIES

Corroded Nozzles = NO

653 Corroded hydrotest case = NO

Thickness roundup to nearest = 0.00000000 mm.

Plate material density = 0.78500481E-02 kg./cu.cm.

Modify fluid height by pressure = NO

Round anchor bolts by = 4.0000000

Wind moment in Appendix F = Sect_5.9.7.1

Full shell weight in Appendix F = YES

Use P from F.4.1 only in F.6 = YES

Use non corroded roof weight as dlr = YES


TANK 2016, API-650/653/620 Analysis 7
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 8
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

API-650 12th Edition, Addendum 2, January 2016

Wind Information:

------------------------------------------------------------------------------

Wind Velocity ...................................... 41.960 M./sec.

Velocity Factor .................................... 0.61181

Wind Pressure ...................................... 1.1463 KPa

Area Exposed to Wind ............................... 136.37 m.^2

Sect 5.9.7.1 Wind Moment on Tank ................... 0.87427E+06 N.m.

Wind Shear Force Acting on Tank .................... 0.15632E+06 N.

Wind Girder Height Reduction Factor ................ 1.0000

Material Property Information:

------------------------------------------------------------------------------

The following material properties have been modified in

accordance with API-650 (and API-653 where applicable).

Course | Material Name | Design Stress| Test Stress | App M |

Number | | (Sd or Sts) | (St) | Reduction |

| | (KPa ) | (KPa ) | |

--------------------------------------------------------------------

1 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |

2 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |

3 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |

4 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |

5 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |

6 | A-283 | 0.13789E+06 | 0.15513E+06 | 1.0000 |


TANK 2016, API-650/653/620 Analysis 9
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Shell Course Thickness Data - One Foot Method

------------------------------------------------------------------------------

| Thickness Values for Three Cases |Min. Temp| |

Course | Design | Test | User | (deg C )| Status |

# | (mm. ) | (mm. ) | (mm. ) | |Pass/Fail |

------------------------------------------------------------------------

1 | 6.0000 | 6.0000 | 6.0000 | -11.7 | NA |

2 | 5.0000 | 5.0000 | 5.0000 | -11.7 | NA |

3 | 5.0000 | 5.0000 | 5.0000 | -11.7 | NA |

4 | 5.0000 | 5.0000 | 5.0000 | -11.7 | NA |

5 | 5.0000 | 5.0000 | 5.0000 | -11.7 | NA |

6 | 5.0000 | 5.0000 | 5.0000 | -11.7 | NA |

Shell Course Allowed Fluid Heights:

------------------------------------------------------------------------------

| Fluid Heights for Three Cases |

Course | Design | Test | Required |

| (m. ) | (m. ) | (m. ) |

-------------------------------------------------------

1| 10.452 | 15.872 | 9.4500 |

2| 8.1458 | 13.277 | 7.6200 |

3| 8.1458 | 13.277 | 5.7900 |

4| 8.1458 | 13.277 | 3.9600 |

5| 8.1458 | 13.277 | 2.1300 |

6| 8.1458 | 13.277 | 0.30000 |

Maximum Allowed Fluid Height of Entire Tank For:

Design Thickness Case ............................. 9.9758 m.

Test Thickness Case ............................. 15.107 m.


TANK 2016, API-650/653/620 Analysis 10
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Required fluid height ............................. 9.4500 m.

Base Plate Details - Shell Weight & Center of Gravity:

------------------------------------------------------------------------------

Annular Base Plate Thickness ....................... 7.6000 mm.

(from API-650 Table 5-1 plus corrosion)

Annular Base Plate Width per 5.5.2 ................. 666.40 mm.

( 2 + ThkCrs1 + max[ 24, (2tb * sqrt(Fy/2YHG))] )

Weight of Shell + Nozzles .......................... 0.16280E+06 N.

Total Weight of all Nozzles ........................ 0.00000 N.

Center of Gravity (Shell+Nozzles) .................. 5.1884 m.

Wind Overturning Stability Check:

------------------------------------------------------------------------------

Corroded Shell Weight + %Roof - Uplift ............. 0.14187E+06 N.

Line Load ......................................[wa] 81.495 N./cm.

Moment due to wind (hor+ver) press .............[Mw] 82734. N.m.

Moment due to wind (hor) press ................[Mws] 0.36617E+06 N.m.

Moment due to internal pressure ...............[Mpi] 0.00000 N.m.

Moment due to tank liquid ......................[Mf] 0.19053E+07 N.m.

Moment due to shell & roof ....................[Mdl] 0.75948E+06 N.m.

Anchors not needed for Sect. 5.11

Wind Girder Information:

------------------------------------------------------------------------------

For "open top" tanks ...

Required Section Modulus, Top Girder ............... 56228. mm.^3

Table 5-20 Detail, B value ......................... b 0.00 mm.

Table 5-20 Shape name (if applicable)............... 4x4x.25

Maximum Height of Unstiffened Shell ................ 20.294 m.


TANK 2016, API-650/653/620 Analysis 11
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Wind Girder - Transformed Section Method

Number of Intermediate Girders Reqd ................ 0

Weight Summary:

------------------------------------------------------------------------------

Shell (Corroded) ................................... 112434. N.

Shell (Non-Corroded) ............................... 162803. N.

Annular Base Plate ................................. 14251. N.

Bottom Plate ....................................... 73194. N.

Nozzles ............................................ 0. N.

Roof Plates ........................................ 45614. N.

Roof Framing/Structure ............................. 6658. N.

Shell Attachments .................................. 9535. N.

Shell + Roof Insulation ............................ 0. N.

Operating Fluid .................................... 10818690. N.

Water Weight ....................................... 12215814. N.

Operating Weight (Non-Corroded) .................... 11130744. N.

Test Weight (Non-Corroded, Filled to Top)........... 12527868. N.

Empty Weight (Non-Corroded) ........................ 312054. N.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 12
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

API-650 12th Edition, Addendum 2, January 2016

TANK - Roof Design/Analysis Data

SUPPORTED CONE ROOF Structural Library: JIS

Roof thickness per 5.10.2.2, Cone Roof ............. 5.0000 mm.

Total weight of Roof Plates ........................ 45614. N.

Based on user input thickness

User Specified Design Roof Load .................... 1.3849 KPa

including user plate thickness

Computed Number of Girder Rings: 1

Girder Radii, Number, Length from Tank Center

Ring | Radius Length | Number | Length |

| (m. ) | | (m. ) |

---------------------------------------------

1 | 2.8000 | 10| 1.7305 |

Computed Number of Rafter Rings: 2

Rafter Details from Tank Center

Ring |Number| Outer |NUM/| Inner |NUM/| Max Length |

| | Spacing|GRDR| Spacing|GRDR| (ft. ) |

| | (in. )| | (in. )| | |

-------------------------------------------------------------

1 | 10 | 1730.495 |( 1)| 0.000 |( 0)| 2.839 |

2 | 20 | 1916.372 |( 0)| 865.248 |( 2)| 3.484 |


TANK 2016, API-650/653/620 Analysis 13
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Rafter Size Details from Tank Center

Ring| Rafter Load | Selected | --Section Modulus-- |

| (N./cm. ) | Shape | Required Actual |

| | | (mm.^3 ) (mm. **3) |

--------------------------------------------------------------

1 | 12.661 |C75X40X5X7 | 7972.79| 20221.63|

2 | 19.940 |C75X40X5X7 | 18919.13| 20221.63|

Failed to find Girder structural member for required section modulus.

Roof Evaluations - Appendix F

------------------------------------------------------------------------------

Uplift force due to internal pressure............... 0.00000 N.

Total weight resisting uplift ...................... 0.22461E+06 N.

Max Design Pressure, roof/shell joint.............. 16.856 in of H2O

Max Design Pressure, roof/shell joint.............. 4.1966 KPa

(According to F.4.1)

Compression Ring Failure Pressure .................. 25.892 in of H2O

Compression Ring Failure Pressure .................. 6.4461 KPa

(According to F.6)

Required Compression Areas, Roof/Shell Junction

Area as per Section F.5 ........................... 0.00000 mm.^2

Frangible Roof-to-Shell Junction Area Limit:

Area as per Section 5.10.2.6 ....................... 807.58 mm.^2

API 650 Appendix F Calculations:


TANK 2016, API-650/653/620 Analysis 14
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Nominal Tank Weight

= Shell Weight + Roof Weight + Framing Weight + Attachment Weight

= 36601.3 + 10254.9 + 1496.9 + 2143.7

= 50496.8 lb. [224609.9 N.]

Note: The uplift was less than the total weight.

Appendix M Yield Stress reduction factor, M.3.6 [Mfact]:

= Yield Reduction Factor * Fy / Fyamb

= 1.000 * 30000.0/30000.0

= 1.000 Must be less than or equal to 1.0

Note: Using the new roof weight in Appendix F calcs. There was no corrosion

allowance specified on the roof plates.

Note: The tank is considered anchored since anchor bolts are specified,

therefore Appendix F.4.2 calculations are not required.

Design Pressure per F.4.1 [P]:

= (0.962 * A * Fy * Mfact * tan(theta))/(D^2) + 0.245 * DLR/D^2

= (0.962*5.017*30000.0*1.000*tan(9.46))/(40.0^2)+0.245*11751/40.0^2

= 16.856 in. of water [428.148 mm. of water]

= 0.609 psi [4.197 KPa]

Note: Design Pressure was less than maximum computed per F.4.1

Required Area of the Roof/Shell Junction per F.5.1 [A]:

= D^2(Pi-0.245*DLR/D^2)/(0.962*Fy*Mfact(tan(theta)))

= 40.0^2(0.000 -0.245*11751/40.0^2)/(0.962 *30000.0 *1.000 (tan(9.46 )))

= 0.000 in.^2
TANK 2016, API-650/653/620 Analysis 15
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Maximum Frangible Roof Area 5.10.2.6 [A]:

= DLs/( 2 * pi * Fy * Mfact * tan(theta))

= 39315.1/( 2 * pi * 30000.0 * 1.000 * tan(9.46 ))

= 1.252 in.^2 [807.579 mm.^2]

Calculated failure Pressure from F.6 [Pf]:

= 1.6 * P - (0.147 * Dlr)/D^2

= 1.6 * 16.856 - (0.147 * 11751 )/40.0^2

= 25.892 in. of water [657.649 mm. of water]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 16
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

API-650 12th Edition, Addendum 2, January 2016

Seismic Evaluation Results - Appendix E

Ground Motion Type : Probabilistic

Design Fluid Weight ................................ 0.10819E+08 N.

Design level peak acceleration for non-ASCE ....[Sp] 0.00000

MCE at period of 0.2 seconds ...................[Ss] 0.00000

MCE at period of 0.0 seconds ...................[S0] 0.00000

MCD at period of 1.0 seconds ...................[S1] 0.00000

Design spectral accel parameter ...............[SDS] 0.00000

Acceleration based site coefficient ............[FA] 1.6000

Velocity based site coefficient ................[FV] 2.4000

FvS1 / FaSs ....................................[TS] 0.00000

Convective sloshing period .....................[TC] 3.6690 sec

Convective spectral acceleration parameter .....[Ac] 0.00000

Impulsive spectral acceleration parameter ......[Ai] 0.70000E-02

Effective convective fluid weight ..............[Wc] 0.31907E+07 N.

Effective impulsive fluid weight ...............[Wi] 0.77739E+07 N.

Convective liquid base shear ...................[Vc] 0.00000 N.

Impulsive liquid base shear ....................[Vi] 56602. N.

Total design base shear .........................[V] 56602. N.

Shear resistance ...............................[VS] 0.44523E+07 N.

Ring wall convective moment arm ................[Xc] 6.4918 m.

Ring wall impulsive moment arm .................[Xi] 3.5782 m.

Slab convective moment arm ....................[XCS] 6.8560 m.


TANK 2016, API-650/653/620 Analysis 17
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Slab impulsive moment arm .....................[XIS] 5.4570 m.

Shell+appurtenances weight .....................[WS] 0.17234E+06 N.

Roof+framing+10% snow weight+roof ins..........[Wrs] 19906. N.

Ringwall overturning moment ...................[Mrw] 0.20500E+06 N.m.

Slab overturning moment ........................[Ms] 0.30724E+06 N.m.

Vertical acceleration parameter ................[AV] 0.00000

Effective specific gravity .....................[Ge] 1.0000

Resisting annulus force ........................[wa] 192.61 N./cm.

Tank + roof weight at shell base ...............[wt] 50.159 N./cm.

The anchorage ratio .............................[J] 0.56736E-01

Reqd min annular plate projection ...............[L] 0.00000 m.

Number of anchor bolts required .................[N] 16

Shell compressive stress .......................[Sc] 1538.5 KPa

Shell allowable stress .........................[Sa] 29839. KPa

Height of sloshing wave ............................ 0.00000 m.

Required Freeboard ................................. 0.00000 m.

Hoop Stress versus Allowable Stress

Course | Hoop Stress | Hoop Allowable |

# | (KPa ) | (KPa ) |

----------------------------------------------

1 | 94599.03 | 183396.36 |

2 | 91624.39 | 183396.36 |

3 | 69688.96 | 183396.36 |

4 | 47710.00 | 183396.36 |

5 | 25687.53 | 183396.36 |

6 | 3621.53 | 183396.36 |
TANK 2016, API-650/653/620 Analysis 18
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Seismic Evaluation Summary:

Seismic shell stress check passed.

Base shear within limits.

Hoop stress within allowable.

Appendix E Seismic Analysis Calculations:

Period Parameter per E.2.2 [Ts]:

= 0.000 sec.

Sloshing Period Coefficient per E.4.5.2-c [Ks]:

= 0.578 / sqrt( hyperbolic tangent(3.68 * HL / D ) )

= 0.578/sqrt( hyperbolic tangent(3.68 * 31.004/40.026 ) )

= 0.580

Convective Sloshing Period per E.4.5.2-b [Tc]:

= Ks*sqrt(D)

= 0.580 * sqrt ( 40.026 )

= 3.669 sec.

Intermediate Value per E.4.6.1-1 [SDS]:

= 2.5 * Q * Fa * S0

= 2.5 * 0.000 * 1.600 * 0.000

= 0.000

Impulsive Spectral Accel. Parameter per E.4.6.1-1 [Ai]:

= SDS ( I / Rwi )

= 0.000 ( 1.000/4.000 )

= 0.000
TANK 2016, API-650/653/620 Analysis 19
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Lower bound limit of Ai per E.4.6.1

= 0.007 for sites with S1 < 0.6 per E.4.6.1-2

Final value of Ai:

= max( Ai, lower bound value )

= max( 0.000, 0.007 )

= 0.007 %g

Convective Spectral Acceleration parameter per E.4.6.1-5 [Ac]:

= min((2.5 * K * Q * Fa * S0 * (I / Rwc)) * Ts * TL / Tc^2 , Ai )

= min( (2.5 * 1.500 * 0.000 * 1.600 * 0.000 * (1.000/2.000 ))

* 0.000 * 0.000/3.669^2, 0.007000 )

= min( 0.000000, 0.007000 )

= 0.000 %g

Convective Weight per E.6.1.1-3 [Wc]:

= 0.230 (D/H) * Wp * tanh( 3.67 (H/D) )

= 0.230 (40.03/31.00 ) * 2432259 * tanh( 3.67 (31.00/40.03 ) )

= 717326.750 lb. [3190669.250 N.]

Impulsive Weight per E.6.1.1-2 [Wi]:

= Wp * ( 1.0 - 0.218 (D/H) )

= 2432259 * ( 1.0 - 0.218 (40.026/31.004 ) )

= 1747726.500 lb. [7773887.500 N.]

Convective Liquid Base Shear per E.6.1-3 [Vc]:

= Ac * Wc

= 0.000000 * 717326

= 0.000 lb.
TANK 2016, API-650/653/620 Analysis 20
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Impulsive Liquid Base Shear per E.6.1-2 [Vi]:

= Ai( Ws + Wr + Wf + Wi )

= 0.007 ( 38745.027 + 11751.812 + 19659.277 + 1747726 )

= 12725.179 lb. [56601.594 N.]

Total Design Base Shear per E.6.1-1 [V]:

= sqrt( Vc^2 + Vi^2 )

= sqrt( 0.000^2 + 12725.179^2 )

= 12725.179 lb. [56601.594 N.]

Ringwall Convective Moment Arm per E.6.1.2.1-3 [Xc]:

= (1.0 - (cosh(3.67 (H / D)) - 1.0)

/ (3.67 (H / D) * sinh(3.67 (H / D))))*H

= (1.0 - (cosh(3.67 (31.004/40.026 )) - 1.0)

/(3.67 (31.004 /40.026 ) * sinh(3.67 (31.004 /40.026 ))))*31.004

= 21.299 ft. [6.492 m.]

Ringwall Impulsive Moment Arm per E.6.1.2.1-2 [Xi]:

= H * ( 0.5 - 0.094 (D / H) )

= 31.004 * ( 0.5 - 0.094 (40.026/31.004 ) )

= 11.740 ft. [3.578 m.]

Slab Convective Moment Arm per E.6.1.2.2-3 [Xcs]:

= (1.0 - (cosh(3.67 (H / D)) - 1.937)

/ (3.67 (H / D) * sinh(3.67 (H / D)) ) ) * H

= (1.0 - (cosh(3.67 (31.004/40.026 )) - 1.937)

/(3.67 (31.004 /40.026 ) * sinh(3.67 (31.004 /40.026 ))))*31.004

= 22.493 ft. [6.856 m.]

Slab Impulsive Moment Arm per E.6.1.2.2-2 [Xis]:

= H * ( 0.500 + ( 0.0600 * D / H ) )
TANK 2016, API-650/653/620 Analysis 21
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 31.004 * ( 0.500 + ( 0.0600 * 40.026/31.004 ) )

= 17.904 ft. [5.457 m.]

Ringwall Overturning Moment per E.6.1.5-1 [Mrw]:

= sqrt( ( Ai ( Wi * Xi + Ws * Xs

+ Wr * Xr ) )^2

+ ( Ac * Wc * Xc )^2 )

= sqrt( ( 0.007 ( 1747726 * 11.740 + 38745.027 * 17.022

+ 11751.812 * 36.118 ) )^2

+ ( 0.000 * 717326 * 21.299 )^2 )

= 151209.953 ft.lb. [205004.406 N.m.]

Slab Overturning Moment per E.6.1.5-2 [Ms]:

= sqrt( ( Ai ( Wi * Xis + Ws * Xs

+ Wr * Xr ) ) ^2

+ ( Ac * Wc * Xcs ) ^2 )

= sqrt( ( 0.007 ( 1747726 * 17.904 + 38745.027 * 17.022

+ 11751.812 * 36.118 ) )^2

+ ( 0.000 * 717326 * 21.299 )^2 )

= 226621.4 ft.lb. [307244.2 N.m.]

Vertical Acceleration Parameter per E.6.1.3 [Av]:

= 0.47 * SDS

= 0.47 * 0.000

= 0.000000 %g

Effective Specific Gravity per E.2.2 [Ge]:

= ( 1 - ( 0.4 * Av ) ) * G

= ( 1 - ( 0.4 * 0.000 ) ) * 1.000

= 1.000
TANK 2016, API-650/653/620 Analysis 22
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Resisting Annulus Force per E.6.2.1.1-1b [wa]:

= min( ( 7.9 * ta * sqrt( Fy * H * Ge ) ),

( 1.28 * H * D * Ge ) )

= min( ( 7.9 * 0.173 * sqrt( 30000.000 * 31.004 * 1.000 ) ),

( 1.28 * 31.004 * 40.026 * 1.000 ) )

= min( 1319.821, 1588.443 )

= 1319.821 lb./ft. [19260.383 N./m.]

Tank + Roof Weight at Shell Base per E.6.2.1.1.1-2 [wt]:

= ( Wrs / ( D * pi) ) + ( WS / ( D * pi ) )

= ( 4475.199/( 40.026 * 3.142 ) ) + ( 38745.027/( 40.026 * 3.142 ) )

= 343.710 lb./ft. [5015.821 N./m.]

The Anchorage Ratio per E.6.2.1.1.1-1 [J]:

= Mrw/(D^2( wt(1 - (0.4 * Av)) + wa - 0.4 * wint))

= 151209.953/(40.026^2(343.710 (1-(0.4 * 0.000 ))+1319.821 -0.4*0.0 ))

= 0.056736

Number of Anchor Bolts Required [nA]:

= max( int( (PI * D / 10) + .999 ), 4 )

= max( int( (3.142 * 40.026/10) + .999 ), 4 )

= 13 bolts

Final value after using rounding multiple:

= N + ( Nmul - mod( N , NMUL ) )

= 13 + ( 4 - mod( 16, 4 ) )

= 16 bolts

Shell Compressive Stress per E.6.2.2.1-1b [Sigma_c]:

= (wt (1.0 + 0.4 * Av) + (1.273 * Mrw / (D^2)))

/ ( 12.0 * ts )
TANK 2016, API-650/653/620 Analysis 23
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= (343.710 (1.0 + 0.4 * 0.000 ) + (1.273 * 151209.953/(40.026^2)))

/( 12.0 * 0.173 )

= 223.144 psi [1538.490 KPa]

Shell Allowable Stress [Sa/Fc]:

= min ((1.0E6 * ts / D) , (Fty / 2))

= min ((1.0E6 * 0.173/40.026 ), (30000.000/2))

= 4327.869 psi [29838.926 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 6

Impulsive Hoop Membrane Force per E.6.1.4-2b [Ni]:

= (2.77 * Ai * G * D^2)

* ((Y / D * 0.75) - (0.5 (Y / D * 0.75)^2))

= (2.77 * 0.007 * 1.000 * 40.026^2)

* ((0.984/40.026 * 0.75) - (0.5 (0.984/40.026 * 0.75)^2))

= 1.002 lb./in. [0.175 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 0.984 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2

= 0.000 lb./in.

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0

= 0.0361 * 1.000 * 0.984 * 12.0 * 40.026 * 12.0/2.0

= 102.398 lb./in. [17.932 N./mm.]

Total Combined Hoop Stress per E.6.1.4-5:


TANK 2016, API-650/653/620 Analysis 24
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 1.002^2 + 0.000^2 ) + 102.398 )/0.197

= 525.270 psi [3621.529 KPa]

Seismic Hoop Allowable for Shell Course: 6

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 5

Impulsive Hoop Membrane Force per E.6.1.4-2b [Ni]:

= (2.77 * Ai * G * D^2)

* ((Y / D * 0.75) - (0.5 (Y / D * 0.75)^2))

= (2.77 * 0.007 * 1.000 * 40.026^2)

* ((6.988/40.026 * 0.75) - (0.5 (6.988/40.026 * 0.75)^2))

= 6.390 lb./in. [1.119 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 6.988 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2

= 0.000 lb./in.

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0

= 0.0361 * 1.000 * 6.988 * 12.0 * 40.026 * 12.0/2.0

= 727.025 lb./in. [127.315 N./mm.]


TANK 2016, API-650/653/620 Analysis 25
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Total Combined Hoop Stress per E.6.1.4-5:

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 6.390^2 + 0.000^2 ) + 727.025 )/0.197

= 3725.746 psi [25687.529 KPa]

Seismic Hoop Allowable for Shell Course: 5

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 4

Impulsive Hoop Membrane Force per E.6.1.4-2b [Ni]:

= (2.77 * Ai * G * D^2)

* ((Y / D * 0.75) - (0.5 (Y / D * 0.75)^2))

= (2.77 * 0.007 * 1.000 * 40.026^2)

* ((12.992/40.026 * 0.75) - (0.5 (12.992/40.026 * 0.75)^2))

= 10.535 lb./in. [1.845 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 12.992 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2

= 0.000 lb./in.

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0


TANK 2016, API-650/653/620 Analysis 26
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 0.0361 * 1.000 * 12.992 * 12.0 * 40.026 * 12.0/2.0

= 1351.652 lb./in. [236.699 N./mm.]

Total Combined Hoop Stress per E.6.1.4-5:

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 10.535^2 + 0.000^2 ) + 1351.652 )/0.197

= 6919.909 psi [47710.004 KPa]

Seismic Hoop Allowable for Shell Course: 4

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 3

Impulsive Hoop Membrane Force per E.6.1.4-2b [Ni]:

= (2.77 * Ai * G * D^2)

* ((Y / D * 0.75) - (0.5 (Y / D * 0.75)^2))

= (2.77 * 0.007 * 1.000 * 40.026^2)

* ((18.996/40.026 * 0.75) - (0.5 (18.996/40.026 * 0.75)^2))

= 13.438 lb./in. [2.353 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 18.996 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2

= 0.000 lb./in.
TANK 2016, API-650/653/620 Analysis 27
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0

= 0.0361 * 1.000 * 18.996 * 12.0 * 40.026 * 12.0/2.0

= 1976.279 lb./in. [346.082 N./mm.]

Total Combined Hoop Stress per E.6.1.4-5:

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 13.438^2 + 0.000^2 ) + 1976.279 )/0.197

= 10107.760 psi [69688.961 KPa]

Seismic Hoop Allowable for Shell Course: 3

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 2

Impulsive Hoop Membrane Force per E.6.1.4-2b [Ni]:

= (2.77 * Ai * G * D^2)

* ((Y / D * 0.75) - (0.5 (Y / D * 0.75)^2))

= (2.77 * 0.007 * 1.000 * 40.026^2)

* ((25.000/40.026 * 0.75) - (0.5 (25.000/40.026 * 0.75)^2))

= 15.098 lb./in. [2.644 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 25.000 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2


TANK 2016, API-650/653/620 Analysis 28
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 0.000 lb./in.

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0

= 0.0361 * 1.000 * 25.000 * 12.0 * 40.026 * 12.0/2.0

= 2600.905 lb./in. [455.466 N./mm.]

Total Combined Hoop Stress per E.6.1.4-5:

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 15.098^2 + 0.000^2 ) + 2600.905 )/0.197

= 13289.298 psi [91624.391 KPa]

Seismic Hoop Allowable for Shell Course: 2

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Seismic Hoop combined Force/Stress Calculations for Shell Course: 1

Impulsive Hoop Membrane Force per E.6.1.4-3b [Ni]:

= 1.39 * Ai * G * D^2

= 1.39 * 0.007 * 1.000 * 40.026^2

= 15.588 lb./in. [2.730 N./mm.]

Convective Hoop Membrane Force per E.6.1.4-4b [Nc]:

= cosh ( 3.68 ( H - Y ) / D )/ cosh ( 3.68 * H / D )

* 0.98 * Ac * G * D^2

= cosh ( 3.68 ( 31.004 - 31.004 )/40.026 )

* 0.98 * 0.000 * 1.000 * 40.026^2


TANK 2016, API-650/653/620 Analysis 29
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 0.000 lb./in.

Product Hydrostatic Membrane Force [Nh]:

= 0.0361 * G * Y * 12.0 * D * 12.0 / 2.0

= 0.0361 * 1.000 * 31.004 * 12.0 * 40.026 * 12.0/2.0

= 3225.532 lb./in. [564.849 N./mm.]

Total Combined Hoop Stress per E.6.1.4-5:

= (sqrt( Ni^2 + Nc^2) + Nh) / Thk

= (sqrt( 15.588^2 + 0.000^2 ) + 3225.532 )/0.236

= 13720.743 psi [94599.031 KPa]

Seismic Hoop Allowable for Shell Course: 1

Allowable Hoop Stress per E.6.2.4:

= min( [0.9 * min( Fy, Fyweld ) * je * Mred], ShellAll * 1.33)

= min( [0.9 * min( 30000, 59001 ) * 1.00 * 1.00 ], 20000 * 1.33)

= 26600.0 psi [183396.4 KPa]

Height of Sloshing Wave per E.7.2:

= 0.42 * D * 2.5 * K * Q * Fa * S0

* I * Ts / Tc

= 0.42 * 40.026 * 2.5 * 1.500 * 0.000 * 1.600 * 0.000

* 1.000 * 0.000/3.669

= 0.000 ft.

Required Freeboard per Table E-7:

= 0.7 * wave height

= 0.7 * 0.000

= 0.000 ft.
TANK 2016, API-650/653/620 Analysis 30
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Shear Resistance Force per E.7.6-1 [Vs]:

= MU ( WS + WR + WF + Wfluid ) * ( 1.0 - 0.4 * AV )

= 0.400 (38745.027 +11751.812 +19659.277 +2432259 )*(1.0-0.4*0.000 )

= 1000966.188 lb. [4452297.500 N.]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 31
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

API-650 12th Edition, Addendum 2, January 2016

Anchor Bolt Results - Section 5.12

------------------------------------------------------------------------------

| Uplift | Allowable | Load/Bolt |

| (N. ) | Bolt Stress | (N. ) |

Load Case | | (KPa ) | |

------------------------------------------------------------------------

Wind Loading | 80807.9 | 198569. | 5050 |

Anchor Bolt Results - Section 5.12

------------------------------------------------------------------------------

| Number | Bolt | Bolt Stress |

| of Bolts | Diameter | (KPa ) |

Load Case | | (mm. ) | |

-------------------------------------------------------------------------

Wind Loading | 16 | 44.450 | 4068 |

Final Anchor Bolt Spacing .............. (m. ) 2.43

Specified number of user bolts is sufficient.

Specified user bolt diameter is sufficient.

Bolt Load Calculations per API 650 Table 5.21b:

Compute weight per table 5.21b [W1]:

= Corr. Shell Wght + Attachment Wght + ( Corr. Roof Wght + Ins. ) * %


TANK 2016, API-650/653/620 Analysis 32
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 25277.3 + 2143.7 + ( 10254.9 + 0.0 ) * 0.38

= 31326.2 lb. [139339.0 N.]

Compute weight per table 5.21b [W2]:

= (Corr. Shell Wght + Ins. Wght)+Att. Wght+(Roof Wght + Fram Wght + Ins.)*%

= ( 25277.3 ) + 2143.7 + ( 10254.9 + 1496.9 + 0.0 )*0.38

= 31896.2 lb. [141874.5 N.]

Compute weight per table 5.21b [W3]:

= Nom. Shell Wght + Attachment Wght + (Nom. Roof Wght + Ins. Wght) * %

= 36601.3 + 2143.7 + (11751.8 + 0.0 ) * 0.38

= 42650.2 lb. [189708.0 N.]

Net Uplift due to Wind Pressure:

= PWR * D^2 * 4.08 + [4 * MWS/D] - W2

= 3.530 * 40.0^2 * 4.08 + [4 * 270085/40.0 ] - 31896.2

= 18167.2 lb. [80807.9 N.]

Net Uplift due to Seismic:

= [ 4 * MRW/D ] - W2( 1 - 0.4*Av)

= [ 4 * 151210.0/40.0 ] - 31896.2 ( 1 - 0.4 * 0.00000 )

= -16785.2 lb. [-74660.4 N.]

Note:

The Frangibility case was not analyzed because the design

pressure was zero or the frangibilty requirements in

API 650 paragraph 5.10.2.6 were not met.

Initial Bolt Design for each Load Case (mm., KPa & mm.^2):

Anchor Bolt Database: TEMA-Imperial


TANK 2016, API-650/653/620 Analysis 33
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Case | Number | Diameter | Stress | Bolt Area |

-----------------------------------------------------------------------------

Wind Loading | 16 | 44.450 | 4068.4 | 1241.4144 |

Final Bolt Design for each Load Case (mm., KPa & mm.^2):

Case | Number | Diameter | Stress | Bolt Area |

-----------------------------------------------------------------------------

Wind Loading | 16 | 44.450 | 4068.4 | 1241.4144 |

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 34
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Anchor Chair Cap Input Values:

Thickness of Gusset Plates j 16.000 mm.

Width of Gussets at Top Plate twdt 160.000 mm.

Width of Gussets at Base Plate bwdt 60.000 mm.

Height of Gussets hg 350.000 mm.

Height of Gussets plus top Plate thickness h 375.000 mm.

Distance between Gussets g 120.000 mm.

Dist. from Bolt Center to Gusset (Rg/2) cg 60.000 mm.

External Corrosion Allowance Ca 1.6000 mm.

Top Plate allowable stress S 379203.0 KPa

Number of Gussets per bolt ng 2

Bottom Shell Course Thickness 6.000 mm.

Shell Course Corrosion Allowance 1.6000 mm.

Thickness of Tank Baseplate m 8.000 mm.

Thickness of Top Plate c 25.000 mm.

Radial Width of the Top Plate b 160.000 mm.

Circumferential Width of the Top Plate a 150.000 mm.

Anchor Bolt Diameter d 44.450 mm.

Anchor Chair Cap and Gusset Plate Analysis Results:

Required Thickness of Top Chair Cap Plate per AISI:

P Bolt Load

e Bolt eccentricity (center of bolt to shell OD)

Sb Allowable Bending Stress ( 1.5 * S )

g Distance between Gussets

d Bolt Diameter
TANK 2016, API-650/653/620 Analysis 35
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Top Chair Cap Plate Required Thickness per AISI [Tc]:

= ( P /( Sb * e ) * ( 0.375 * g - 0.22 * d )) + c

= (15151/(568804*97.000)*(0.375*120.00-0.22*44.450))+1.600

= 4.7100 mm.

Stress in the Top Plate at given Thickness [Stpl]:

= P( 0.375 * b - 0.22 * d ) / e / ( c - Ca )

= 15151 (0.375*120.000 - 0.22*44.450 )/97.000/(25.000 -1.600 )

= 10047.7 KPa, must be less than 568804 KPa

Required Gusset Thickness per AISI:

Gusset Plate Thickness is the greater of( 0.5 in (12mm), 0.04( hg ))

= max( 12.700, 0.04( 350.000 ) ) + Ca

= 15.600 mm.

For gusset plates the following must also be true [English Units]:

Gusset Thickness * Average Gusset Width >= (P/1000)/25

= ( 0.630 - 0.063 ) * 4.331 > ( 3406.358/1000)/25 ) Passed

= 2.455 > 0.136 Passed

Local Stress at the Top Plate per AISI, including axial Stress [S]:

= P*e/t[1.32*Z/(1.43*a*h/(R*t)

+ (4(a)(h)).333 + 0.031 /(R*t)

= 15151*97.00/4.40[1.32*0.86/(1.43*150.00*(375.00)/(6101.60*4.40)

+ (4*150.00 (375.00 ))0.333 + 0.031/(6101.60 *4.40 )

= 69250.7 KPa

Intermediate Value [Z]:

= 1/[(0.177*a*m/(R*t))*(m/t) + 1]

= 1/[(0.177*150.000*8.000/(6101.600*4.400))*(8.000/4.400)+1]

= 0.856
TANK 2016, API-650/653/620 Analysis 36
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Radial Distance [e]:

= ( Dc - Ds ) / 2

= ( 12393.999 - 12199.999 )/2

= 97.000 mm.

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 37
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Determine Maximum allowed Fluid Heights:

For Course # 1, Operating Case

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.2362 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 34.291 ft. [10.452 m.]

For Course # 1, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.2362 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 52.072 ft. [15.872 m.]

For Course # 2, Operating Case

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 26.725 ft. [8.146 m.]

For Course # 2, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 43.560 ft. [13.277 m.]


TANK 2016, API-650/653/620 Analysis 38
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

For Course # 3, Operating Case

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 26.725 ft. [8.146 m.]

For Course # 3, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 43.560 ft. [13.277 m.]

For Course # 4, Operating Case

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 26.725 ft. [8.146 m.]

For Course # 4, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 43.560 ft. [13.277 m.]

For Course # 5, Operating Case

Allowed fluid height above this course based on the 1ft method
TANK 2016, API-650/653/620 Analysis 39
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 26.725 ft. [8.146 m.]

For Course # 5, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 43.560 ft. [13.277 m.]

For Course # 6, Operating Case

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0630 )20000.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 26.725 ft. [8.146 m.]

For Course # 6, Hydro Case, not corroded

Allowed fluid height above this course based on the 1ft method

= (Td - ca)Sd/(2.6 * D * G ) + X/12

= (0.1969 - 0.0000 )22500.00/(2.6 * 40.0 * 1.000 ) + 12.000/12

= 43.560 ft. [13.277 m.]

Appendix M Yield Stress reduction factor, M.3.6 [Mfact]:

= Yield Reduction Factor * Fy / Fyamb

= 1.000 * 30000.0/30000.0

= 1.000 Must be less than or equal to 1.0

Roof Analysis:
TANK 2016, API-650/653/620 Analysis 40
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Total Design External Pressure Loading per V.7 [Pr]:

= max[ DL + (Lr or S) + Fpe*Pe, DL + Pe + 0.4(Lr or S)]

= max[8.039 + max[20.886, 0.000 ] + 0.400 * 0.000,

8.039 + 0.000 + 0.4 * max[20.886, 0.000 ]]

= max[ 28.925, 16.393 ]

= 28.925 psf [1384.911 N/M2]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 41
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Wind Load Calculations:

Wind velocity factor 5.2.1 [Vfact]:

= ( Wind Velocity / 120 )^2

= ( 93.9/120 )^2

= 0.612

Vertical projected wind area of tank [VArea]:

= Tank Height * Insulated Tank Diameter

= 35.01 * 40.03

= 1401.181 ft^2 [130.174 m.^2]

Velocity pressure per 5.9.7.1 [p]:

= 0.00256 * Kz * Kzt * kd * V^2 * I * G + 5.0

= 0.00256 * 1.040 * 1.000 * 0.950 * 93.862^2 * 1.000 * 0.850 + 5.0

= 23.941 psf [1146.279 N/M2]

Wind moment on shell [Moment]:

= Wind Pressure * Wind Area * Tank Height/2

= 23.941 * 1401.2 * 35.01/2

= 0.58715E+06 ft.lb. [0.79603E+06 N.m.]

Vertical projected wind area of Cone roof:

= Roof Height * Roof triangular base

= 3.33 * 20.01

= 66.737 ft^2 [6.200 m.^2]

Area Exposed to Wind:

= Wind area of tank + Wind area of roof

= 1401.181 + 66.737
TANK 2016, API-650/653/620 Analysis 42
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 1467.919 ft.^2 [136.374 m.^2]

Wind moment at the base including the cone roof [Total Moment]:

= Moment + ( Wind P * Roof Area( Tank Height + Roof Height/3))

= 587149 + ( 23.941 * 66.7 ( 35.0 + 3.33/3))

= 0.64486E+06 ft.lb. [0.87427E+06 N.m.]

Wind shear force acting on the tank:

= Wind Pressure * (tank area + roof area)

= 23.941 * 1467.9

= 0.35143E+05 lbf. [0.15632E+06 N.]

Moment about shell-to-bottom joint [MDL]:

= ( Shell Weight + Attachement Weight + Framing Weight * % )D/2

= ( 25277.3 + 2143.7 + 1496.9 * 0.38 )40.0/2

= 560189.1 ft.lb [759481.9 N.m.]

Resisting Weight of Fluid [WL]:

= min( 5.6 * tb * sqrt( Fby * H * min( 0.7, G )), 0.45 * H * D )

= min(5.6*0.1732*sqrt(30000.0*31.00*min(0.7,1.000)),0.45*31.0*40.03)

= min( 782.8, 558.4 )

= 558.4 lbf/ft [8.1 N./mm.]

Moment from Fluid Weight [MF]:

= WL * ( PI * D ) * ( D / 2 )

= 558.4 * ( 3.1416 * 40.03 ) * ( 40.03/2 )

= 1405347.8 ft.lb [1905314.1 N.m.]

Moment from Design Internal Pressure [MPI]:

= Design Pressure * pi( Diameter in inches / 2 )^2 * ( D / 2 )

= 0.0000 * 3.1416 ( 480.31/2 )^2 * ( 40.03/2 )


TANK 2016, API-650/653/620 Analysis 43
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 0.0 ft.lb [0.0 N.m.]

Design Pressure per F.4.1 [P]:

= (0.962 * A * Fy * Mfact * tan(theta))/(D^2) + 0.245 * DLR/D^2

= (0.962*5.017*30000.0*1.000*tan(9.46))/(40.0^2)+0.245*11751/40.0^2

= 16.856 in. of water [428.148 mm. of water]

= 0.609 psi [4.197 KPa]

Note: Design Pressure was less than maximum computed per F.4.1

Moment about shell-to-bottom joint [MWS]:

= Pws * D * H^2/2

= 18 * Vfact * (D + Insulation) * H^2/2

= 18 * 0.6118 (40.0 + 0.0 ) * 35.0^2/2

= 270085.9 ft.lb [366171.6 N.m.]

Moment about shell-to-bottom joint [MW]:

= MWS + Wind Uplift * VArea * D / 2

= 270085.9 + 0.1275 * 181193.3 * 40.0/2

= 732287.4 ft.lb [992805.9 N.m.]

Moment about shell-to-bottom joint [MDLR]:

= ( Roof Weight )D/2

= ( 10254.9 )40.0/2

= 205232.5 ft.lb [278246.0 N.m.]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016


TANK 2016, API-650/653/620 Analysis 44
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Determine required thickness per the selected Method:

Shell Course Thickness per the One Foot Method:

Required Thickness for Course # 1

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 2.6D( H - 1 )G/Sd

= 2.6 * 40.026 ( 31.00 - 1 )1.000/20000.0

= 0.156 in. [3.966 mm.]

Minimum thickness per 5.6.1.1 : = 0.236 in. [6.000 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.23622 in. [6.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:

= 2.6D( H - 1 )/St

= 2.6 * 40.026 ( 31.00 - 1 )/22500.0

= 0.13878 in. [3.52491 mm.]

Minimum thickness per 5.6.1.1 : = 0.236 in. [6.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.23622 in. [6.00000 mm.]

Required Thickness for Course # 2

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 2.6D( H - 1 )G/Sd
TANK 2016, API-650/653/620 Analysis 45
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 2.6 * 40.026 ( 25.00 - 1 )1.000/20000.0

= 0.125 in. [3.172 mm.]

Minimum thickness per 5.6.1.1 : = 0.188 in. [4.772 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.18787 in. [4.77200 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:

= 2.6D( H - 1 )/St

= 2.6 * 40.026 ( 25.00 - 1 )/22500.0

= 0.11101 in. [2.81956 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 3

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 2.6D( H - 1 )G/Sd

= 2.6 * 40.026 ( 19.00 - 1 )1.000/20000.0

= 0.094 in. [2.378 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:


TANK 2016, API-650/653/620 Analysis 46
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

= 2.6D( H - 1 )/St

= 2.6 * 40.026 ( 19.00 - 1 )/22500.0

= 0.08324 in. [2.11420 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 4

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 2.6D( H - 1 )G/Sd

= 2.6 * 40.026 ( 12.99 - 1 )1.000/20000.0

= 0.062 in. [1.585 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:

= 2.6D( H - 1 )/St

= 2.6 * 40.026 ( 12.99 - 1 )/22500.0

= 0.05547 in. [1.40885 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.19685 in. [5.00000 mm.]


TANK 2016, API-650/653/620 Analysis 47
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Required Thickness for Course # 5

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 2.6D( H - 1 )G/Sd

= 2.6 * 40.026 ( 6.99 - 1 )1.000/20000.0

= 0.031 in. [0.791 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.19685 in. [5.00000 mm.]

Required thickness per 5.6.3.2, Hydrotest [tt]:

= 2.6D( H - 1 )/St

= 2.6 * 40.026 ( 6.99 - 1 )/22500.0

= 0.02770 in. [0.70350 mm.]

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.19685 in. [5.00000 mm.]

Required Thickness for Course # 6

Required thickness based on the 1ft method per 5.6.3.2, Operating [td]:

= 0.000 in.

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including corrosion and other allowances:

= 0.19685 in. [5.00000 mm.]


TANK 2016, API-650/653/620 Analysis 48
Licensee:
Job: 00SGA01BB101_FIRE FIGHTING WATER TANK : Aug 15,2017 Time: 5:24pm

Required thickness per 5.6.3.2, Hydrotest [tt]:

= 0.00000 in.

Minimum thickness per 5.6.1.1 : = 0.197 in. [5.000 mm.]

Final Selected Thickness including other Code allowances:

= 0.19685 in. [5.00000 mm.]

TANK(TM) Intergraph CADWorx & Analysis Solutions, Inc. 2016

You might also like