You are on page 1of 2

P I 1875C / 6 0 H z

Output Power Ratings Prime* Standby**


rpm Frequency Voltage Kva kW Kva kW
1500 50Hz 400 - - - -
1800 60Hz 380 1619 1295 1875 1500

Engine Technical Data


Engine Make and Model Cummins KTA50-G9
Cylinders 60 Vee, 16-Cylinder
Aspiration Turbochargedand Low Temperature After Cooled
Combustion System Direct Injection
Displacement 50 liters
Governor Electronic
Emissions Regulations N.A.
Electrical Starting System 24Volt ,55Amp Alternator With DC Out Put

Air Systems
Air Filter Type Dry replaceable element
50 Hz 60 Hz
Combustion Air Flow
Prime - 1930 (4100)
Liter/second (cfm)
Standby - 2075 (4400)
Maximum Air Filter Intake Restriction - 6.23KPa

Fuel System
Fuel Filter Type Dual-Spin on (Replaceable)
Recommended Fuel Class A2 Diesel
Engine Speed 1500 rpm 1800 rpm
Fuel Standby - 392 (103.6)
Consumption Prime Power - 330 (87.3)
l/hr (US gal/hr) %75 of Prime Power - 257 (68.0)
%50 of Prime Power - 180 (47.6)
Fuel Tank Capacity: Open / Close N/A

Lubrication System
Lube Oil API-CH4/CI4 SAE 15W-40 (-10 C to 50 C Ambient Temperature)
Lube Oil Capacity 204 L
Oil Pan 178 L
Oil Filter Type Spin on Full Flow (Replaceable)
Oil Cooling Method Water

Cooling System
Coolant Capacity 240L
Cooling System Mounted Radiator
3
Cooling Fan Air Flow m /s - 28.2
50 Hz 60 Hz
Heat Radiation to Room Prime - 170 KWm
Standby - 200 KWm

Exhaust System
Grade Industrial
Silencer Size 6
Qty 2
Exhaust Gas Flow Prime - 4530 (9600)
Littre/s (cfm) Standby - 5025 (10650)
Maximum Allowable Backpressure - 6.8 kPa
50 Hz 60 Hz
Exhaust Gas Maximum
Prime - 470C
Temp
Standby - 515C

Alternator Technical Data STAMFORD


Model Number PI734C
No. of Poles 4
Number of Terminals (Leads) 6
A.V.R. & Excitation MX321, Separately Excited by P.M.G
Regulation %0.5
Ingress Protection IP-23
Insulation Class H
TIF < 50
THD at Full Load % <%5.0
THD at No Load % <%1.5
3
Cooling Air Flow- @ 50 Hz m /s (cfm) 2.69 (5700)
3
Cooling Air Flow- @ 60 Hz m /s (cfm) 3.45 (7300)
Output Voltages 50Hz 60Hz
V 380 400 415 440 415 440 460 480
kVA - - - - 1705 1815 1855 1890
Kw - - - - 1364 1452 1484 1512
P I 1875C / 6 0 H z

Controller Features ComAp AMF9 / DSE6120 (Optional)


Auto Mains Failure (AMF) applications including remote communication ,
Controller Make and Model User configuration and complete gen-set monitoring and protection.
Ready for generators with 3 ph 4 wires / 3 ph 3 wires / Mono ph
Oil pressure Fuel level (Optional)
Engine Protections
Coolant temperature Coolant level (Optional)
Over / Under voltage Over current
Generator Protections Over/Under frequency Charging Alternator Fault
Phases Sequence
3 Nos Configurable analog inputs 6 Nos binary outputs
Inputs and Outputs
4 Nos binary inputs D + Pre-Excitation terminal
Gen-set text alarm log Engine hours history log
Event and Performance Log For More Features We Can Use
Higher Controller

Genset Enclosure Specification (optional)


Enclosure Type Acoustic and Weather Proof
Anticorrosive Protection Polyester Powder Coated Galvanized Sheet
Access Doors 5
Drainage Fuel &Water Drainage Provision
Transportation Tested Four Point Lifting Facility & Forklift Pockets
Noise Level (@Free-Field Conditions) 79 dBA @ 7 meter
Water Fill Radiator Water Filling Provision
Cable Access Cable Inlet and Outlet Provision
Emergency Stop External Emergency Push Button
Canopy RAL Color RAL 2000
Chassis RAL Color RAL 9011

Shipping Data
Type Length (mm) Width (mm) Height (mm) Weight (kg)
Open 5500 2000 3030 10700
Enclosed 8500 2250 3300 18400

Notes:
*Prime power rating of the generating set is where a variable load and unlimited hours usage are applied
on the generating set with an average load factor of 80% of the prime rating over each 24 hour period.
Noting that a 10% overload is available for 1 hour in every 12 hours operation

**Standby power rating of the generating set is where a variable load limited to an annual usage upto
500 hours is applied, with 300 hours
of which may be continuous running. Noting that no overload is permitted

All generators carry a one year or (1000) hours manufacturers warranty

In line with our policy of continuous development, PI reserves the right to change specication without
notice

You might also like