Packaged Control Products

Milwaukee, WI 53204 U.S.A.


Publication 2100-WD1 - July, 1994
Supersedes None
Copyright 1994 Allen-Bradley Company, Inc.
Printed in USA

WIRING DIAGRAMS
A Reference Resource for
CENTERLINE Motor Control Centers
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
1

CONTENT GUIDE
Wiring Class
Class I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Class II, Class I-S and II-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Wiring Type
Type A Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Type B Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Type C Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Photos - Type A, Type B-T, Type B-D, and Type C Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 and 7
Customer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Control Circuit Wiring and Devices
Control Circuit Wiring, Terminal Blocks, Pilot Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Schematic Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 through 17
Wiring Diagrams
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Allen-Bradley Wiring Diagram Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 and 21
Bulletin 2102L-Full Voltage Lighting Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Bulletin 2103L-Full Voltage Lighting Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Bulletin 2106-Full Voltage Reversing Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Bulletin 2107-Full Voltage Reversing Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Bulletin 2112-Full Voltage Non-Reversing Starter With Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Bulletin 2112-Full Voltage Non-Reversing Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Bulletin 2113-Full Voltage Non-Reversing Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Bulletin 2113-Full Voltage Non-Reversing Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Bulletin 2122E-Two Speed 2-Winding Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Bulletin 2122F-Two Speed 1-Winding Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Bulletin 2123E-Two Speed 2-Winding Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Bulletin 2123F-Two Speed 1-Winding Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Bulletin 2126E-Two Speed Reversing 2-Winding Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . 34
Bulletin 2126F-Two Speed Reversing 1-Winding Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . 35
Bulletin 2127J-Two Speed Reversing in Low Speed Only 2-Winding with Circuit Breaker . . . . . . . . . . . . . . . . . . 36
Bulletin 2127-Two Speed Reversing in Low Speed Only 1-Winding with Circuit Breaker . . . . . . . . . . . . . . . . . 37 .
Bulletin 2154E-Comb. Solid State Motor Controller with Fusible Disconnect (SMC-2) . . . . . . . . . . . . . . . . . . . . . 38
Bulletin 2154F-Comb. Solid State Motor Controller with Fusible Disconnect (SMC PLUS) . . . . . . . . . . . . . . . . . . 39
Bulletin 2155F-Comb. Solid State Motor Controller with Circuit Breaker (SMC PLUS) . . . . . . . . . . . . . . . . . . . . . 40
Bulletin 2162J-Bulletin 1333 Variable Freuency AC Drive with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . 41 .
Bulletin 2163-Bulletin 1336 Variable Freuency AC Drive with Circuit Breaker-75p . . . . . . . . . . . . . . . . . . 42
...
Bulletin 2172-Closed Transition Reduced Voltage Autotransformer Type Starter with Fusible Disconnect . . . . . . . 43
Bulletin 2173-Closed Transition Reduced Voltage Autotransformer Starter with Circuit Breaker . . . . . . . . . . . . . . 44
Bulletin 2182E-Bulletin 1771 PLC I/O Rack with Fusible Disconnect and Transformer . . . . . . . . . . . . . . . . . . . . . 45
Bulletin 2182J-Bulletin 1746 SLC 500 PLC with Fusible Disconnect and Transformer . . . . . . . . . . . . . . . . . . . . 46
Bulletin 2183E-Bulletin 1771 PLC I/O Rack with Circuit Breaker and Transformer . . . . . . . . . . . . . . . . . . . . . . . . 47
Bulletin 2190-Metering Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Bulletin 2191F-Outgoing Feeder Lug Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Bulletin 2191M-Incoming Line Lug Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Bulletin 2192F-Fusible Disconnect-Feeder - Dual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Bulletin 2192M-Fusible Disconnect-Main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Bulletin 2193F-3-Pole Circuit Breaker - Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Bulletin 2193M-3-Pole Circuit Breaker - Main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Bulletin 2193LE-Bolt-On Lighting Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Bulletin 2196-Control and Lighting Transformer with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Bulletin 2197-Control and Lighting Transformer with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Bulletin 2402-Full Voltage Contactor with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Bulletin 2403-Full Voltage Contactor with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Bulletin 2406-Combination Full Voltage Reversing Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . . . . . 60
Bulletin 2407-Combination Full Voltage Reversing Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Bulletin 2412-Combination Full Voltage Non-Reversing Starter with Fusible Disconnect . . . . . . . . . . . . . . . . . . . 62
Bulletin 2413-Combination Full Voltage Non-Reversing Starter with Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 63
Bulletin 2492F-Fusible Disconnect Switch - Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
2 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers

Wiring Class

Class I
Independent Units
Class I motor control centers (MCC) consist
of mechanical groupings of combination
starter units, feeder and other units, and
electrical devices arranged in a convenient
package.

AllenBradley furnishes drawings that


include:
Overall dimensions of the MCC, identifi-
cation of units and their locations in the
MCC, locations of incoming line termi-
nals, mounting dimensions, and available
conduit entrances.
Standard diagrams for individual units
consisting of drawings that identify elec-
trical devices, indicate electrical connec-
tions, and indicate terminal numbering
designations.
When a combination schematic and / or
wiring diagram for a unit is supplied
showing optional devices, AllenBradley
provides information to indicate which
devices are actually furnished.
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
3

Class II
Interconnected Units
Class II motor control centers
are the same as Class I but with
the addition of fact furnished
electrical interlocking and
wiring between units, a
specifically described in
overall control
system diagrams supplied by
the purchaser. In addition to
the drawings furnished for
Class I MCCs, AllenBradley
furnishes drawings that show
factory interconnections within
the MCC.

Class I-S & Class II-S


Motor Control Centers
Requiring Custom Drawings
Class IS and Class IIS motor
control centers are the same as
Class I and Class II MCCs
except that custom drawings
are provided as specified by the
customer rather than standard
drawings. Examples are:

special identifications for


electrical devices
91C-111 special terminal numbering
designations
special drawing sizes.

These drawings give the same


information as those for Class I
and Class II motor control
centers, plus show customer
modifications.
4 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers

WiringType

Type A Wiring - No Terminal Blocks

Type A wiring is available for Class I motor


control centers. When Type A wiring is specified,
components within the unit are wired directly to
each other, and no terminal blocks are supplied for
customer wiring. The customer must connect
external control and load wiring directly to the
electrical devices within the unit. See Photo 1 on
page 6.

Type B Wiring - Terminal Blocks

Type B wiring is available for Class I and Class II


motor control centers. NEMA/EEMAC defines
Type B wiring as follows:

ICS 2-322.10 TYPES OF WIRING


.02 Type B
a. Type B user field load wiring for combination motor control
units size 3 or smaller shall be designated as B-D or B-T,
according to the following
B-D connects directly to the device terminals, which are
located immediately adacent, and readily accessible, to the
vertical wireway
B-T connects directly to a load terminal block in, or adacent
to, the unit.
NEMA Standard 3-6-1985

b. Type B user field load wiring for combination motor control


units larger than size 3, and for feeder tap units, shall connect
directly to unit device terminals.
NEMA Standard 3-6-1985

c. Type B user field control wiring shall connect directly to


unit terminal block(s) located in or adacent to each combination
motor control unit.
NEMA Standard 3-6-1985
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
5

CENTERLINE Motor Control Centers provide the


following:

Type B-T Type B-D Type B

Power wired to Power wired to


terminal blocks device terminals
(See Photo 2 on page 6) (see Photo 3 on page 7)
Size 1, 2 Pull apart control
Pull apart control
(except 0.5 space fac No power terminal N/A
Pull apart power
tor) blocks
Pull apart control
Pull apart control
Size 3 No power terminal N/A
Non-pull apart power
blocks
Pull apart control
Size 4 and larger N/A N/A No power terminal
blocks
0.5 space factor units Pull apart control terminal blocks
and Bul. 2400 units. No power terminal blocks
N/A = Not applicable, undefined by NEMA/EEMAC

Type C Wiring - Master Terminal Compartment

Type C wiring is available for Class II motor


control centers. See Photo 4 on page 7.

Control wiring from each unit within an MCC


section is wired from the units terminal blocks to
master terminal blocks contained in a separate unit
mounted at the top or bottom of that section.

The customer connects the external control wires


to the master terminal blocks. The customer
connects the load wiring for size 3 or smaller to
the master terminal blocks. The customer connect
the load wiring for size 4 or larger to unit device
terminals.
6 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers

Photo 1. Type A Wiring

93C-491-3

Photo 2. Type B-T Wiring

93C-491-2
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
7

Photo 3. Type B-D Wiring

93C-491-1

Photo 4. Type C Wiring

87C-143-13
8 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers

Customer Wiring
The method that a customer uses to connect their
external wiring differs depending upon whether or
not terminal blocks are supplied:

When control When no


and/or power terminal blocks
terminal blocks are supplied:
are supplied:

The customers external The customer must


control and/or load wires connect the external
are connected to those control and load wires
blocks that are located directly to the applicable
adjacent to the vertical electrical devices
wireway and are readily internal to the unit.
accessible.
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
9

Control Circuit Wiring and Devices


Control Circuit Wiring
For Bulletin 2100 units, the standard control circuit wiring is 16 AWG copper wire
with Type MTW (TEW) insulation. 14 AWG (tinned) copper wire with Type
MTW (TEW) insulation and 14 AWG (tinned) copper wire with Type SIS
insulation are other available options (when specifications do not allow PVC
insulation).
For Bulletin 2400 units, the standard control circuit wiring is 18 AWG copper
wire with Type MTW (TEW) insulation. 16 AWG copper wire with Type MTW
(TEW) insulation is also available as an option.

Terminal Blocks
Different terminal blocks will accept different wire quantities and sizes. The
maximum wire sizes accepted are as follows:

Pull-apart Terminal Blocks Maximum Wires Per Pole


Two (2) 14 AWG wires
5pole control or
One (1) 12 AWG wire

3pole power One (1) 4 AWG wire

Two (2) 18 AWG wires


10pole control or
(used on all 0.5 space factor units) One (1) 16 AWG wire

Pilot Devices
There are several types of pilot devices supplied on our Bulletin 2100 and 2400
units. The maximum wire sizes accepted are as follows:

Pilot Device Maximum Wires Per Pole


Bulletin 800T Two (2) 14 AWG wires
Bulletin 800M
One (1) 14 AWG wire
(w/small terminals)
Bulletin 800M
Two (2) 12 AWG wires
(w/large terminals)
Two (2) 14 AWG wires
Bulletin 800E or
One (1) 12 AWG wire

For further information on types of pilot devices supplied with each unit, see
Publication 21003.0.
Wiring Diagram Reference Resource
10 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

Schematic Symbols

US/Canadian International / British German

CB

An automatic device that under abnormal conditions will open a


Three-Pole currentcarrying circuit without damaging itself (unlike a fuse that must be
Circuit Breaker replaced when it blows).

DS
Three-Pole Generally, an airbreak switch, however, containing no fuses. A power
Disconnect Switch circuit employing this type of switch must have some kind of circuit
protection elsewhere.

Three-Pole
Fusible Disconnect FDS
Switch Generally, an airbreak switch with a fusing unit in the blade. Used for
opening and closing power circuits.

FDS
IEC Fusible An applicationrated version of an airbreak switch with a fusing unit in the
Disconnect Switch blade.

Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 11

US/Canadian International / British German

Dark black nodes on a circuit schematic indicate that an electrical connection


Node is made. It is a point of connection for two or more conductors in an
electrical circuit.

A device attached to the end of a wire or cable for convenience in making


Terminal Block (TB) electrical connections.

A coupling device that provides an electrical and/or mechanical junction


Connector between two cables.

Part of a contactor, motor starter, or relay consisting of a number of turns of


wire wound around an iron core. When voltage is applied, an
Coil electromagnetic field is set up in the coil causing the contacts of the
contactor, starter, or relay to change state.

SUP

This device is mounted directly across the coil terminals of contactors and
starters with 120V or 240V AC coils. The purpose of the supressor is to
limit voltage transients for applications requiring interface with solid state
Surge Suppressor components.


Wiring Diagram Reference Resource
12 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

US/Canadian International / British German

Symbolized by N.O. designation applied to the contacts of a relay or starter


Contact - when they are connected so that the circuitry will be broken when the relay
Normally Open (N.O.) or starter coil is not energized.

Contact -
Normally Closed Symbolized by N.C. designation applied to the contacts of a starter or relay
(N.C.) when they are connected so that the circuit will be completed when the relay
or starter coil is not energized.

I I

A device that automatically disconnects the circuit whenever the current or


Overload Relay temperature becomes excessive.

OL

Overload Relay Contact Relay contacts designed to open when its coil current rises above a
(OL) predetermined value.

Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 13

US/Canadian International / British German

Power Factor
Correction A device that stores electrical energy, blocks the flow of DC, and permits the
Capacitor flow of AC to a degree dependent upon the capacitance and the frequency.
Used in an inductive (motor) circuit in order to increase the power factor by
making the total current more nearly in phase with the applied voltage.

L1/1 T1/2

SMC Reduced Voltage L2/3 T2/4


Motor Starter
L3/5 T3/6

10 20 30 40 50 60 70 80 90
SMC PLUS AUXILIARY
Interface Module CONTACTS
SMC PLUS TM CONTROL TERMINALS

FU
Fuse

A protective device that melts and breaks the circuit when the current
exceeds the rated value.

H2 H3
H1 H4
TRANS.
X1 X2

An electrical device that by electromagnetic induction transforms electric


Control Circuit energy from the power circuit to the control circuit at the same frequency but
Transformer at a lower voltage.

Wiring Diagram Reference Resource
14 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

US/Canadian International / British German

GRD
Ground
A conductor that carries no current but serves to connect exposed metal
surfaces to an earth ground to prevent hazards in case of breakdown between
currentcarrying parts and the exposed surfaces.

Push Button - Switch where button must be depressed each time contacts are to be opened.
Normally Closed

Push Button - Switch where button must be depressed each time contacts are to be closed.
Normally Open

1 2
OFF ON 1 2

Selector Switch - A two position switch that permits one conductor to be connected to another
2-Position conductor.

OFF
HAND AUTO 1 0 2
1 2 3
BA
BB

Selector Switch - A multiposition switch that permits one or more conductors to be connected
3-Position to any of several other conductors.

Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 15

US/Canadian International / British German

Toggle Switch -
Normally Open A twoposition snap switch operated by a projecting lever to open or close
circuits, contact is normally in the open position.

Toggle Switch -
Normally Closed A twoposition snap switch operated by a projecting lever to open or close
circuits, contact is normally in the closed position.

Timed Contact -
Normally Open, T.O.

Timed Open
The contact of a timer relay with an appreciable time interval between the
deenergizing of the coil and the opening of its contact.

Timed Contact - T.C.

Normally Closed,
Timed Closed The contact of a timer relay with an appreciable time interval between the
deenergizing of the coil and the closing of its contact.

Timed Contact -
Normally Open, T.C.

Timed Closed
The contact of a timer relay with an appreciable time interval between the
energizing of the coil and the closing of its contact.

Timed Contact -
Normally Closed,
Timed Open T.O.

The contact of a timer relay with an appreciable time interval between the
energizing of the coil and the opening of its contact.

Wiring Diagram Reference Resource
16 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

US/Canadian International / British German

An electromechanical device having a terminal on each end of the resistive


element, and a third terminal connected to the wiper contact. The electrical
Potentiometer input is divided as the contact moves over the element, thus making it
possible to mechanically change the resistance.

Insert color code Insert color code next to symbol


inside symbol

Pilot Light A light that indicates the state of a circuit.


Insert color code next to symbol

Similar to a regular pilot light but can be depressed to test if the bulb is
Pilot Light - functional.
Push-To-Test
1PT
H1 X1
H2 X2 GRD

2PT
H1 X1

Two H2 X2

Potential Transformers Threephase configuration of instrument transformers, the primary windings


-Schematic Diagram of which are connected in parallel with the circuit whose voltage is to be
measured or controlled.

A transformer intended for measuring or control purposes and designed to


have its primary winding connected in series with a circuit carrying the
Current Transformer current to be measured or controlled.

Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 17

US/Canadian International / British German


(H1)
(X1)
1CT

3-Phase (H1)
(X1)
Current Transformer 2CT
-Schematic Diagram (H1)
(X1)
3CT

GRD
Threephase current transformer configuration used for inputs to digital
metering system.

Meter
Insert function code Insert function code Insert function code
inside symbol. inside symbol. inside symbol.

An electrical instrument used to measure electrical parameters, such as


voltage, current, and power.

Motor MTR 3
M
3
M

A machine that converts electric energy into mechanical energy to do work.



Wiring Diagram Reference Resource
18 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

Notes
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 19

Wiring Diagrams

Connection diagrams
AllenBradley connection diagrams are that portion of the wiring diagram
that shows an approximate physical layout of the components that make up
the unit. This diagram gives the relative locations of the electrical devices
and includes wire numbers for easy identification of how the components are
wired together.

Schematic diagrams
AllenBradley schematic diagrams are the portion of the wiring diagram that
shows an electrical representation of how the circuits operate. Both the
power and control circuits are represented. The schematic diagram is often
used by assemblers to wire the units and by maintenance electricians for
installation and troubleshooting purposes.

Wiring diagrams
A schematic diagram together with a connection diagram make up an
AllenBradley customer specific wiring diagram. See the following two
pages for an example of a full wiring diagram (CS70024150 Bul. 2113).

Catalog number specific diagrams


Beginning on page 22, you will find diagrams that are specific to
AllenBradley catalog numbers. These diagrams are the schematic portions
taken from the full wiring diagrams.
Wiring Diagram Reference Resource
20 Wiring Diagram Reference Resource for CENTERLINE Motorfor
Control Centers Motor Control Centers
CENTERLINE

1 2 3 4 5
NOTES CONNECT BETWEEN SIMILARLY MARED TERMINALS

TO BUS
L1 L2 L3

1L1 1L2
1 2
B ST
ST
CB
TRANS.
GRD. 2 1
2
1 FU 2

C 1L1 1L2 1L3

OFF ON
4 A 2 3 A 2

START
D
3 2

STOP
1L1 1L2 1L3 A1 A2 A3
1 21
24 1A 1L1 1L2
E
24 22
A1 A2 A3 T1 T2 T3
DOOR 3 5 1 OL
(REAR VIEW)
2 6 4
M
2
F

1 22
21A2345612 TB

G
BLOWN FUSE
LIGTS FOR
P.F. CAP. BAN P.F. CAPACITOR
1A1
1A1 1A2 1A3
1A2 FU FU FU
A3 1A3 A2 1A2 A1 1A1 1A3 A1 A2 A3
A1 A2 A3
H
VAR
FLANGE
(REAR VIEW)
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 21

5 6 7 8

1L1 M A1 OLS
L1 T1
TO
BUS 1L2 A2 T2 1
L2 MTR
480V B
3P 1L3 A3 T3
60 L3
CB

FUA1 1A1

C
FUA2 P.F.
1A2 CAPACITOR

FUA3 1A3

2 1 2
FU TRANS. GRD D

1 2
START
OL STOP 1A 3 2
1 24 2 M
J
M ON
A
E

M OFF
4
A

5 M 6 21 OL 22 F

References BUL. 2113 SIE 4 (2.5SF) ACAD


Revision Dimensions Apply Before
Surface Treatment TYPE B
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
.02
Dr.PPEN577B Date 10/02/93 Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date N/A Dwg
Size
CS70024150
Angles 1
Refer.
Book Appd.N/A Date N/A D
91793 Packaged Control Cadds
5 6 7 8

1L1 C T1
TO L1
A
BUS 1
1L2 T2
480V L2 LOAD
3 PH 1L3 T3
60 HZ L3
FDS

2 H2 H3
H1 H4
CB TRANS. GRD C
X1
OFF ON X1 X2

3 X2
1 BA C

C ON
2
R
D

C OFF
4
G

1A 5 C 6 7 C 8
E
(SPARE)
9 C 10

NOTES:
1

REMOTE DEVICE
2 F
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY X 1 1 2 34 5 6 7 8 9 1 T T T
PROTECTED TRANSFORMER. (TYPE "B" WIRING ONLY) 2 A 0 1 2 3 TB
PRIMARY FUSING NOT
REQUIRED.

References BUL. 2102L 30-60AMP ACAD


Revision Dimensions Apply Before
TYPE A
Surface Treatment
Release Dimensions in Inches
A 04/15/93 Tolerances Unless
Otherwise Specified
2 Place Decimal
+.02 Dr. PPEN577B Date 10/02/93 H
Sheet 1 Of 1
3 Place Decimal
+.005 Chkd. N/A Date N/A Dwg

Refer.
Size
CS70006974
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

22
5 6 7 8
1C
1L1 1T1
TO L1
BUS 1
480V L2 1L2 1T2 A
3 PH LOAD
60 HZ L3 1L3 1T3
1CB
2C
2L1 2T1
1
2L2 2T2
LOAD
2L3 2T3 B
2CB

3FU 5FU
1H1 H2 H3 1H4
H1 H4 1
1FU 1X1 TRANS. GRD
X1 X2 C

1 2 3 1X2
1C

1C

2L2
2L1
E

4FU 6FU
2H1 2H4
H2 H3
H1 H4 2
2FU 2X1 TRANS. GRD
X1 X2

32 33 2X2 F
31 2C

NOTES: 2C
1 REMOTE DEVICE

2 INTERNAL CB AUXILIARIES
SUPPLIED WITH UNMOUNTED
CONNECTION BLOCKS. G

References Dual Bul. 2103L 30-60 Amp ACAD


Revision Dimensions Apply Before
Surface Treatment
Type A
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size CS70024114
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

23
5 6 7 8
1L1 MFU F OL'S T1
2L1
L1
TO 1L2
BUS 2L2 T2 1 A
L2 MTR
480V
3 PH 1L3 2L3 T3
60 HZ L3
DS
R

H2 H3
2 H1 H4
FU TRANS. GRD
X1 X2
FORWARD
STOP R OL C
1 1A 2 3 6 8 X2
F
"J1"
F FORWARD
"J2" R

REVERSE
4 5 F 7
R
D

R REVERSE
R

OL OVERLOAD
A E

NOTES:
9 F 10 13 F 14
1
11 R 12 15 R 16
REMOTE DEVICE

2 (TYPE "B" WIRING ONLY)


THIS UNIT IS SUPPLIED
WITH AN INTERNALLY X 1 1 1 1 1 1 1 1 T T T
1 2 3 4 5 9 TB
PROTECTED TRANSFORMER. 2 A 0 1 2 3 4 5 6 1 2 3
PRIMARY FUSING NOT
REQUIRED.
"J1"
ON TYPE "A" WIRING, JUMPER "J1" WILL G

BE ON DOOR MOUNTED PUSH BUTTONS.

References BUL. 2106 SIZE 1-2 (2SF) ACAD


Revision Dimensions Apply Before
Type A
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024115
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

24
5 6 7 8

F
1L1 1A1 OL'S T1
TO L1 A
BUS
1L2 1A2 T2 1
480V L2 MTR
3 PH (H1) CT 3
1L3 (H2) 2L3 1A3 T3
60 HZ L3
CB WHT (X1) (X2) BLK
R

C1 C2
AMMETER
B
AM GRD

1FU 2FU
H1 H4
H2 H3
H1 H4
CB GRD
TRANS.
X1 X2 C

1 1A 2 3 R 6 8 OL X2
F
"J1"
SUP
F
"J2"

D
4 5 F 7
R

SUP
R

NOTES:
1
REMOTE DEVICE E

3 X 1 T T T
AMPS NAMEPLATE RATIO 1 2 3 4 5 TB
AMPS EFFECTIVE RATIO WITH 2 A 1 2 3
PRIMARY TURNS
SECONDARY TURNS
BE SURE TO CONNECT PER "J1"
POLARITY MARKINGS.

SECONDARY CONNECTIONS OF F
CURRENT TRANSFORMER MUST
BE CONNECTED TO A LOAD OR
SHORTED TOGETHER TO AVOID
A HIGH VOLTAGE ACROSS
SECONDARY LEADS.

References Bul. 2107 Size 1-2 (1.5SF) ACAD


Revision Dimensions Apply Before
Release Surface Treatment Type B
Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024116
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

25
1 2 3 4 5 6 7 8

1L1 M 1A1 OL T1
L1 (1/L1) (2/T1)
TO
BUS 1L2 1A2 T2 1
L2 (3/L2) (4/T2) MTR
480V
3 PH 1L3 1A3 T3
B 60 HZ L3
(5/L3) (6/T3)
FDS

1FU 2FU

H1 H2

H1 H2
C FU X1 TRANS. GRD
X1 X2
START
STOP
1A 2 3 3A OL
1 X2
M (95) (96)
"J"
M
D

E
NOTES
1

REMOTE DEVICE

UNIT INSTALLATION
THE HANDLE EXTENDER KIT, 2100-
NE1, MAY BE NECESSARY FOR ANY
F
TOP UNIT OPERATING HANDLES THAT
ARE HIGHER THAN 6-1/2 FEET OFF
X2
THE GROUND FOR COMPLIANCE WITH 1
NEC. 1A
"J"
2
3

References BUL. 2112 SIZE 1 (0.5 SF) ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 09/08/93 Tolerances Unless
Otherwise Specified
H 2 Place Decimal
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70020770
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

26
5 6 7 8
1L1 M T1
L1
TO
BUS OL
A
1L2 T2 1
L2 MTR
480V
3 PH OL
60 HZ
1L3 T3
L3
FDS GRD
OL
B

2 H1 H2
FU GRD
TRANS.
X1 X2
OFF
1 HAND AUTO 3 3A OL X2
(A1)
CR (A2)
BA
D
BB 1A 1 M 2

ELAPSED
ETM TIME METER

CR 23 M
(13) (14)

NOTES: 4 M 5 6 M 7
F
1
REMOTE DEVICE

2
THIS UNIT IS SUPPLIED X1 1 2 3 45 67 TB
2 A
WITH AN INTERNALLY
PROTECTED TRANSFORMER.
PRIMARY FUSING NOT G

REQUIRED.

References BUL. 2112 SIZE 5 ACAD


Revision Dimensions Apply Before
Release Surface Treatment Type B
Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024134
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

27
5 6 7 8

M OL'S T1
L1 1L1
TO A
BUS 1L2 T2 1
L2 MTR
480V
3 PH 1L3 T3
60 HZ L3
CB

2
120V SEPARATE CONTROL
OFF
HAND START
OL HAND AUTO HAND STOP
1 24 1C 2 3 X2
M
LB
SUP
M M ON C
4
R
1

LA 1A 1

M 5 OFF
G
1 D

OL OVERLOAD
22
A
1

6 M 7

NOTES: X1 12 34 5 67 T T T TB
2 A 1 2 3
1

REMOTE DEVICE

ADDITIONAL CONTROL
F
CIRCUIT OVERCURRENT
PROTECTION MAY BE
REQUIRED WHEN THE
CONTROL CIRCUIT
CONDUCTORS EXTEND
BEYOND THE ENCLOSURE.
G
REFER TO NATIONAL
ELECTRICAL CODE.

References BUL. 2113 SIZE 1-2 ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024135
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

28
5 6 7 8

M A1 OL'S
L1 1L1 T1 A
TO
BUS A2 1
L2 1L2 T2
480V MTR
3 PH A3
60 HZ L3 1L3 T3
CB

FUA1 1A1 B

FUA2 1A2 P.F.


CAPACITOR

FUA3 1A3

FU 2 H1 H2 C

TRANS. GRD
X1 X2
STOP START
1 OL 1A 2 3 X2
24 M
"J"
ON
M
A D

OFF
M 4
A

5 M 6 21 OL 22 E

NOTES:
1
REMOTE DEVICE

2
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY F

PROTECTED TRANSFORMER.
PRIMARY FUSING NOT
REQUIRED.

THIS IS AN EXTERNAL CIRCUIT


BREAKER AUXILIARY AND X1 1 2 3 4 5 6 2 2 TB
2 A 12 G
SHOULD NOT BE USED FOR
BREAKER TRIP INDICATION. "J"

References Bul. 2113 Size 4 (2.5SF) ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size CS70024150
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

29
5 6 7 8

L
1L1 L OL'S T1
L1 A
TO
BUS
L2 1L2 T2
480V
3 PH
60 HZ L3 1L3 T3
FDS H 1 2
H OL'S T11 MTR

T12
B

T13

1FU 2FU

HIGH
L H STOP
1 OL 8 OL 24 1A 2 3 L 6 X2
H
"J1"
H HIGH
"J2" R
LOW
D
4 5 H 7
L

L LOW
G

E
H
OL 22 OVERLOAD
A

L
OL
NOTES:
1 REMOTE DEVICE

2 T11 T1
F
MOTOR
WINDINGS

X 11 2 3 4 5 TB
2 A
T13 T12 T3 T2
"J1"
NEMA STANDARD
MOTOR CONNECTIONS
LINES
SPEED OPEN
L1 L2 L3 G
LOW T1 T2 T3 T11 T12 T13
HIGH T11 T12 T13 T1 T2 T3

References Bul. 2122E Size 1-2 ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
Tolerances Unless
A 10/18/93 Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size CS70024136
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

30
5 6 7 8

L L
1L1 OL'S
L1 T1 A
TO H
BUS 1L2 T2
L2
480V
3 PH 1L3 H
60 HZ L3 T3
FDS 1 2
H
H OL'S T6 MTR

T4
B

T5

3
120V SEPARATE CONTROL C

1A 2 3 L
1 6 H
"J1"
H
"J2"
R
E L H D
4 5 H S OL OL
7 9 8 X2
L

L
NOTES:
1
REMOTE DEVICE
2 E
MOTOR
T4 WINDINGS T4
T1
T3 T1 T3 X 1 12 3 4 5 TB
2 A
T5 T6 T5 T6
T2 T2
CONSTANT VARIABLE
"J1"
TORQUE TORQUE

NEMA STANDARD
MOTOR CONNECTIONS
LINES
SPEED OPEN TOGETHER
L1 L2 L3
LOW T1 T2 T3 T4 T5 T6 NONE F
HIGH T6 T4 T5 NONE T1 T2 T3

3
ADDITIONAL CONTROL
CIRCUIT OVERCURRENT
PROTECTION MAY BE
REQUIRED WHEN THE
CONTROL CIRCUIT
CONDUCTORS EXTEND
BEYOND THE ENCLOSURE. G
REFER TO NATIONAL
ELECTRICAL CODE.

References Bul. 2122F Size 4 ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70006989
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

31
5 6 7 8

S
1L1 S OL'S T1
TO
BUS L1 A
1L2 T2
480V L2
3 PH T3
60 HZ L3 1L3
1 2
CB F F T11 MTR
OL'S

T12

T13 B

CB 3 H1 H2
TRANS. GRD
OFF X1 X2 C
FAST SLOW S F
3 S 6 9 OL OL X2
1 8
F
BA
SUP
F 2 FAST
R

BB 5 F 7 D
S
SUP
S 4 SLOW
R

NOTES: 1A 10 S 11
1 REMOTE DEVICE (SPARE) F E
12 13

2
T11 T1
MOTOR
WINDINGS

T13 T12 T3 T2

NEMA STANDARD
MOTOR CONNECTIONS F
LINES OPEN
SPEED L1 L2 L3
SLOW T1 T2 T3 T11 T12 T13
FAST T11 T12 T13 T1 T2 T3

3
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY
PROTECTED TRANSFORMER.
PRIMARY FUSING NOT
REQUIRED. G

References BUL 2123E SIZE 3 ACAD


Revision Dimensions Apply Before
Release Surface Treatment TYPE A
Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024137
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

32
5 6 7 8

L
1L1 L OL'S T1 A
TO L1
BUS H
1L2 T2
480V L2
3 PH H
1L3 T3
60 HZ L3 1 2
CB H
H OL'S T6 MTR

T4
B

T5

FU X1
120V SEPARATE CONTROL C

HIGH
STOP L
1A 2 3 6
1 H
"J1"
H HIGH
"J2" R
R
LOW E L H D
H S OL OL
4 5 7 L 9 8 X2
NOTES:
1 LOW
REMOTE DEVICE L
R
MOTOR
2 WINDINGS
T4 T4
T3 T1 T3 T1
T5 T6 T5 E
T2 T2 T6
CONSTANT VARIABLE
TORQUE TORQUE
NEMA STANDARD
MOTOR CONNECTIONS
LINES
SPEED OPEN TOGETHER
L1 L2 L3
LOW T1 T2 T3 T4 T5 T6 NONE
HIGH T6 T4 T5 NONE T1 T2 T3 X 1 12 3 4 5 TB
2 A
"J1"
F

References BUL. 2123F SIZE 3 ACAD


Revision Dimensions Apply Before
TYPE B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer. CS70024139
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

33
5 6 7 8
L
F L OL'S T1
L1 1L1 1A1
TO
BUS T2
L2 1L2 1A2 A
480V
3 PH T3
60 HZ L3 1L3 1A3
FDS H 1 2
R H OL'S T11 MTR

T12

T13
B

1FU 2FU

H1 H4
H2 H3
H1 H4
FU TRANS. GRD C

X1 X2
L H
1 1A 2 3 L 3A OL OL X2
H

4 5 H
L
(TYPE "B" WIRING ONLY)
NOTES: L T1
T2
1 T3
REMOTE DEVICE T11
6 7 R T12
E
2 F T13
T11 T1
TB
MOTOR F
WINDINGS

T13 T12 T3 T2
8 9 F
R
SYNOPSIS OF
MOTOR CONNECTIONS
F
SPEED
LINES
OPEN
R
L1 L2 L3
LOW
FOR. T1 T2 T3 T11 T12 T13
(TYPE "B" WIRING ONLY) X 1 1 2 3 4 5 6 7 8 9 TB
HIGH 2 A
FOR. T11 T12 T13 T1 T2 T3

LOW
REV. T3 T2 T1 T11 T12 T13

HIGH G
REV. T13 T12 T11 T1 T2 T3

References BUL. 2126E SIZE 1-2 ACAD


Revision Dimensions Apply Before
TYPE A
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70043575
9-17-93 Packaged Control Cadds

34
5 6 7 8

L
F L OL'S T1
1L1 1A1
L1
TO H A
BUS 1L2 1A2 T2
L2
480V H
3 PH 1L3 1A3 T3
60 HZ L3
FDS H 1 2
R H OL'S T6 MTR

T4
B
T5

3
120V SEPARATE CONTROL

L H
1 1A 2 3 L 3A OL OL X2
H
C
"J"
H HIGH
A

NOTES: H
4 5
1 L
REMOTE DEVICE
2 L LOW D

T4
MOTOR
WINDINGS T4 B
T1
T3 T1 T3
T5 T6 T5 T6 R
T2 T2 6 7
CONSTANT VARIABLE F
TORQUE TORQUE

SYNOPSIS OF F FORWARD
MOTOR CONNECTIONS C
LINES E
SPEED OPEN TOGETHER
L1 L2 L3
8 9 F
LOW
T1 T2 T3 T4 T5 T6 NONE R
FOR.

HIGH
FOR. T6 T4 T5 NONE T1 T2 T3
R REVERSE
LOW
G
REV. T3 T2 T1 T4 T5 T6 NONE

HIGH 12 F 13 16 H 17
REV. T5 T4 T6 NONE T1 T2 T3 F

14 R 15 18 L 19
3 T1
ADDITIONAL CONTROL T2
CIRCUIT OVERCURRENT T3
PROTECTION MAY BE T4
REQUIRED WHEN THE T5
CONTROL CIRCUIT T6
CONDUCTORS EXTEND
BEYOND THE ENCLOSURE. X1 1 2 3 4 5 6 7 8 91 1 1 1 1 1 1 1 TB TB
2 A 23456789
REFER TO NATIONAL G
ELECTRICAL CODE. "J"

References BUL. 2126F SIZE 1-2 ACAD


Revision Dimensions Apply Before
Surface Treatment TYPE B
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
.02
Dr.PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date N/A Dwg

CS70043572
Size
Angles 1
Refer.
Book Appd.N/A Date N/A
D
91793 Packaged Control Cadds

35
5 6 7 8
F L
1L1 1A1 L OL'S T1
TO L1
BUS
1L2 1A2 T2
480V L2 A
3 PH 1L3 1A3 T3
60 HZ L3
CB R

1 2
MTR
H
H OL'S T11
B
T12
1FU 2FU
H1 H4 T13
H2 H3
FU H1 H4
TRANS. GRD
X1 X2
LOW OFF L H
HIGH REV 3 L 3A OL OL X2
1 H C
WA
H 2

5 H
L
WB
L 4 D

BA2
7 R
F
WB1
F 6

BA 9 F E
R
NOTES:
R 8
1 REMOTE DEVICE
T1
2 T1 MOTOR T11 T2
WINDINGS T3
T11
T12
T13
T3 T2 T13 T12 1A F
TB
(SPARE)
SYNOPSIS OF
MOTOR CONNECTIONS
LINES X 1123456789 TB
SPEED
L1 L2 L3
OPEN 2 A
LOW
FOR. T1 T2 T3 T11 T12 T13

HIGH
FOR. T11 T12 T13 T1 T2 T3
G
LOW
REV. T3 T2 T1 T11 T12 T13

References BUL. 2127J SIZE 1-2 ACAD


Revision Dimensions Apply Before
Surface Treatment Type B
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
.02
Dr.PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date N/A Dwg
Size
CS70043573
Angles 1
Refer.
Book Appd.N/A Date N/A
D
91793 Packaged Control Cadds

36
5 6 7 8
L
1L1 F 1A1 L OL'S T1
TO L1
BUS H T2
1L2 1A2
L2 A
480V
3 PH 1L3 1A3 H T3
60 HZ L3
CB R

1 2
MTR
H
H OL'S
T6
B
T4

H2 H3 T5
FU 3 H1 H4
TRANS.
LOW OFF X1 X2
NOTES: HIGH REV 3 L
L H
1 3A OL OL X2
1 H
REMOTE DEVICE WA C

H HIGH
2 MOTOR 2
T4 T4 G
WINDINGS
T1
T3 T1 T3
5 H
T5 T6 T5 T6 L
T2 T2 WB
CONSTANT VARIABLE
L LOW
TORQUE TORQUE 4
G

SYNOPSIS OF
BA2 D
MOTOR CONNECTIONS 7 R
LINES F
SPEED
L1 L2 L3
OPEN TOGETHER WB1
F FORWARD
LOW
T1 T2 T3 T4 T5 T6 NONE 6
FOR. G
HIGH
T6 T4 T5 NONE T1 T2 T3
FOR.
BA 9 F
LOW R
REV. T3 T2 T1 T4 T5 T6 NONE

R REVERSE E
8
G
3
THIS UNIT IS SUPPLIED H L OFF
WITH AN INTERNALLY 10 11 R
PROTECTED TRANSFORMER. H
PRIMARY FUSING NOT OL OVERLOAD
REQUIRED. 22 A

L
OL
F
(TYPE "B" WIRING ONLY)
T1
T2
1A 12 F 13 T3
T4
(SPARE) 14 R 15 (TYPE "B" WIRING ONLY) T5
T6
X 1 12 3 4 5 6 7 8 9 1 1 1 1 TB TB
2 A 2345 G

References BUL. 2127K SIZE 1-2 ACAD


Revision TYPE A
Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 06/16/94 Tolerances Unless
Otherwise Specified
2 Place Decimal H
.02
Dr.PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date N/A Dwg
Size
CS70043574
Angles 1
Refer.
Book Appd.N/A Date N/A
D
91793 Packaged Control Cadds

37
5 6 7 8
SCR
MFU FUSES 2L1 IC OL
L1 L1A 1L1 3L1 4L1 T1
(L1/1) (T1/2) L1/1 T1/2
TO
BUS 1
L2 L2A 1L2 2L2 3L2 4L2 T2 A
480V (L2/3) (T2/4) L2/3 T2/4 MTR
3 PH
60 HZ L3 L3A 1L3 2L3 3L3 4L3 T3
(L3/5) (T3/6) L3/5 T3/6
DS
SMC-2 2

H2 H3
3 H1 H4 C
FU TRANS. GRD
X1 X2
IC OFF
5
G
1

START
4 3A OL X2
(A1)
IC (A2)

ON
1 STOP 1A 2 IC 3
(13) (14)
R E

"J" 1

10 20 30 50 60 40

(TO BE SET FOR F


AUXILIARY INSTANTANEOUS
CONTACT CONTACT)

6 IC 7
SMC-2TM CONTROL TERMINALS 2

NOTES: 2 3
BULLETIN 150 SOLID STATE THIS UNIT IS SUPPLIED X 1 12 3 4 5 6 7 T T T
1 MOTOR CONTROLLER. REFER WITH AN INTERNALLY 2 A 1 2 3
G
REMOTE DEVICE TO PUBLICATION 150-804 PROTECTED TRANSFORMER.
FOR APPLICATION DATA. PRIMARY FUSING NOT "J"
REQUIRED. TB

References Bul . 2154E 4-5 Amp ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70006994
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

38
5 6 7 8
1L1 IC 2L1 3L1 OL T1
TO L1 (L1/1) (T1/2) L1/1 T1/2
BUS
1L2 2L2 3L2 T2 1
480V L2 (L2/3) (T2/4) L2/3 T2/4 MTR A
3 PH 1L3 2L3 3L3 T3
60 HZ L3 (L3/5) (T3/6) L3/5 T3/6
FDS
SMC PLUS 2

3 H1 H2
FU TRANS. GRD
X1 X2

FAN

4 3A OL X2
(A1)
IC (A2)

SUP
D

NOTES: ON
A
1
REMOTE DEVICE START
1 STOP 2 3 OFF
2 5
B
BULLETIN 150 SOLID
STATE MOTOR CONT- SOFT STOP
ROLLER. REFER TO 1A E

PUB. 150-811 FOR APP-


LICATION DATA.

3
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY 10 20 30 40 80 90 70 50 60
PROTECTED TRANS-
FORMER PRIMARY F
FUSING NOT REQUIRED.
AUXILIARY (TO BE SET FOR
4 CONTACTS INSTANTANEOUS
CONTACT)
FOR SET-UP OF SOFT SMC PLUS TM
CONTROL TERMINALS 4 2
STOP FEATURE, REFER
TO PUB. 150-805.
X 1 T1
2 1A2 3 4 5 T2
T3 G

TB TB

References BUL. 2154F 45-54 AMP ACAD


Revision Dimensions Apply Before
Surface Treatment TYPE B
Release
A 10/18/93
Dimensions in Inches
Tolerances Unless WITH SOFT STOP FEATURE
Otherwise Specified
2 Place Decimal H
.02
Dr.PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date N/A Dwg
Size
CS70043576
Angles 1
Refer.
Book Appd.N/A Date N/A
D
91793 Packaged Control Cadds

39
5 6 7 8

SCR
1L1 FUSES 2L1 IC 3L1 4L1 OL T1
TO L1 (L1/1) (T1/2) L1/1 T1/2
BUS 3L2 4L2 A
1L2 2L2 T2 1
480V L2 (L2/3) (T2/4) L2/3 T2/4 MTR
3 PH 3L3 4L3
60 HZ L3 1L3 2L3 T3
(L3/5) (T3/6) L3/5 T3/6
CB
SMC PLUS 2
BC
(L1/1) (T1/2)

(L2/3) (T2/4) B

(L3/5) (T3/6)

H2H3
FU 3 H1 H4
TRANS. GRD
X1 X2
IC 5 ON
R C
1
IC 6 OFF
G
1
START SLOW SPEED
1 STOP 1A 2 BRAKE 3 4 7 3A OL X2
(A1)
CR (A2)
"J"
SUP
CR D

(13) (14)

CR IC 14
13
NOTES: (33) (34) (13) (14) (K1) TDR (K2)
1 4 SUP
REMOTE DEVICE TDR 15
(D1X) (D1Y) (A1) BC (A2)
2 2 T.C.
BULLETIN 150 SOLID STATE SUP
CR 16 17 E
MOTOR CONTROLLER. REFER IC
(43) (44) (A1) (A2)
TO PUBLICATION 150-811
FOR APPLICATION DATA. SUP
8
3
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY
PROTECTED TRANSFORMER. 10 20 30 40 80 90 70 50 60
PRIMARY FUSING NOT
REQUIRED. F
4 (TO BE SET FOR
AUXILIARY INSTANTANEOUS
TDR TIME DELAY SETTING MUST CONTACTS CONTACT)
EXCEED SMC PLUS STARTING SMC PLUS TM
CONTROL TERMINALS 5 2
TIME & MOTOR ACCELERATION
TIME BY 2 TO 5 SECONDS.
5
FOR SET-UP OF SLOW SPEED X 1 12 3 4 5 6 7 8 T T T
2 A 1 2 3
WITH BRAKING FEATURE, G
REFER TO PUB. 150-810. "J"
TB

References BUL. 2155F 30-35 AMP ACAD


Revision Dimensions Apply Before
Surface Treatment TYPE B
Release
A 10/18/93
Dimensions in Inches
Tolerances Unless WITH SLOW SPEED WITH
Otherwise Specified
2 Place Decimal BRAKING FEATURE H
.02
Dr.PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
.005 Chkd.N/A Date Dwg
CS70043577
N/A
Size
Angles 1
Refer.
Book Appd.N/A Date N/A
D
91793 Packaged Control Cadds

40
5 6 7 8

1L1 L1 T1 M1 OL T1
TO L1
BUS L2 T2
600V L2 1L2 M2 T2 1 A
3 PH MTR
60 HZ 1L3 L3 T3 M3 T3
L3
FDS
1FU 2FU

H1 H2
H1 H2
FU X2 GRD
20 TRANS.
X1 X2 B

FAN

TB4 MOD-G4
(1) (3)
GRD
TB3
MOD-G4
3 3 (1) C

AT SPEED 0-10V
19 19 4 (2)
B 4
4-20 mA
RUN 21 5
21 5
R
SPEED 1 3 D

20 20 (3)
3A
4A (4)
DRIVE START
7 7 (5)
5A
FOR REV
8 GRD
8 6 (6)
BA E
NOTES: (LA)
6A (7)
1 DRIVE STOP 9 10
9 10 (8)
REMOTE DEVICE
2
REFER TO BUL. 1333-5.2 11 11 (9)
FOR INTERNAL WIRING.

3 11 11 F
SPEED POT WIRING MUST BE
TWISTED THREE CONDUCTOR
SHIELDED WIRE, HAVING (2) JOG
TO (3) TWISTS PER INCH. IF
12 12
THE POT IS REMOTELY MOUNTED
THE WIRING MUST BE RUN IN
TB2 16 OL
SEPARATE STEEL CONDUIT TO
AUTO MANUAL 16
ELIMINATE THE POSSIBILITY
OF ELECTRICAL NOISE.
MOD-G4
THE SHIELD MUST BE GROUNDED 2 2A (2)
AT THE CONTROLLER END ONLY. CUSTOMER'S BA
120V, 1PH, 60HZ 1
(LA)
(1) 17 17
DRIVE LEGEND SUPPLY G

2 BUL. 1333 VARIABLE FREQUENCY


DRIVE TERMINAL BLOCKS
AC DRIVE
References BUL. 2162J 15HP AC DRIVE-NEMA 1 ACAD
Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024152
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

41
5 6 7 8

1L1 MFU 2L1 L1 M1 T1


TO L1
BUS 1L2 L2 M2 1 A
2L2 T2
600V L2 MTR
3 PH
60 HZ 1L3 2L3 L3 M3 T3
L3
CB H1 1FU
2FU
H2
H1 H2
11 FU X2 GRD
TRANS.
X1 X2 B

FAN1
4
FAN2
FAN3 0-10V
5

4-20 mA
C
6

TB1 MOD-G1
(1) (2) (3)
TB2 MOD-G1
TB2 MOD-G1
7 8 (1)
(3)
11 8 7 (2) D
11
X2 21
23 23 (4)
OFF
HAND AUTO 19
19
BA
(LB)
20
19A
BB
(LA) E

FOR REV
23
NOTES: 23
BA DISPLAY AND
1 (LA) PROGRAMMING
REMOTE DEVICE PANEL
2
REFER TO BUL. 1336-5.0 F
FOR INTERNAL WIRING. 28
11 SERIAL
COMMUN-
DRIVE LEGEND CATION
30 PORTS

TB1 TERMINAL BLOCKS


2 BUL. 1336 ADJUSTABLE FREQUENCY
AC MOTOR DRIVE
TB2 TERMINAL BLOCKS W/ 115VAC LOGIC INTERFACE BOARD G
TB3 TERMINAL BLOCKS

References ACAD
BUL. 2163K 75HP AC DRIVE-NEMA 12
Revision Dimensions Apply Before
Release Surface Treatment
Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
+.005 Chkd. N/A Date N/A Dwg

Refer.
Book Angles + 15
Appd. N/A Date N/A
Size
D CS70024154
9-17-93 Packaged Control Cadds

42
5 6 7 8

1L1 R 53 OL T1
L1
65% A
2S 80% 50% 1S
TO 100% 0%
BUS 50 56
1L2 R 54 T2 1
L2 MTR
65%
480V 2S 80% 50% 1S
3 PH 100% 0%
60 HZ 51 57
1L3 R 55 T3
L3 B
FDS 65%
2S 80% 50% 1S
100% 0%
(TYPE "B" WIRING ONLY) 52 58
ST
X 1 12 3 5 6 12 2 2 2 2 2 T T T TB
2 A 9 0 12 3 4 5 1 2 3
2
120V SEPARATE CONTROL
C

13 OL (ST)
1 2 3 18 X2
(A1) ISTR (A2)
THERMAL
CUT-OUT
ISTR
(33) (34)

D
ISTR 1B ISTR 3A 2S R
11 12
(13) (14) (55) (56) (56) (55) 1S
T.O. T.O.

1S R
14 15
2S
(L.B.)

2S 2S 16 1S 17
(68) (67) R E
T.C.

R
4
(A1)
CR (A2)

ELAPSED F
ISTR 5 ETM TIME METER
(43) (44)

NOTES: 1 2 19 CR 6 22 CR 23
REMOTE DEVICE ADDITIONAL CONTROL CONTROL CIRCUIT
(21) (22) (13) (14)

CONDUCTORS EXTEND 20 CR 21 24 CR 25
CIRCUIT OVERCURRENT (31) (32) (43) (44)
PROTECTION MAY BE BEYOND THE ENCLOSURE. G
REQUIRED WHEN THE REFER TO NATIONAL
ELECTRICAL CODE.

References Bul. 2172 Size 2 ACAD


Revision Dimensions Apply Before
Type A
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024144
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

43
5 6 7 8
1L1 R 53 OL T1
L1
65%
2S 80% 50% 1S
TO 100% 0% A
BUS 50 56
1L2 R 54 T2 1
L2
65% MTR
480V 2S 80% 50% 1S
3 PH 100% 0%
60 HZ 51 57
1L3 R 55 T3
L3
CB 65%
2S 80% 50% 1S
100% 0% B
52 ST 58

1FU 2FU

H1 H4
H2 H3 C

H1 H4
TRANS. GRD
X1 X2

1A 2 3 13 OL (ST)
1 18 X2
(A1) ISTR (A2)
"J" THERMAL
CUT-OUT D
ISTR
(33) (34)

ISTR 1B ISTR 3A 2S R
11 12
(13) (14) (55) (56) (56) (55)
1S
T.O. T.O.

1S R
14 15
2S E
(L.B.)
2S 2S 1S
16 17
(68) (67)
R
T.C.

ISTR
5
(43) (44)

NOTES:
1 G

REMOTE DEVICE

References BUL. 2173 SIZE 3 ACAD


Revision Dimensions Apply Before
Release Surface Treatment TYPE B
Dimensions in Inches
A 04/15/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70006998
9-17-93 Packaged Control Cadds

44
5 6 7 8

CONNECT BETWEEN SIMILARLY MARKED TERMINALS

A
1FU
1L1 H1 TO BUS
L1 L2 L3 POWER
2FU
1L2 H4 DISTRIBUTION
BLOCKS
DS

H1 H4 1L1 1L2 GRD


H1 H3 H2 H4 X1 G
S
TRANS.
GRD. X2 X1
X2 1 G X2
S B
X1 FU
1 1X1 2X1

1771-P7

1X1 L1
X2 L2/N
GND
ON
POWER
OFF
C
FUSE
3A 250V
NORM BLOW

P/S
ACTIVE

12 3 4 5 6 7 8
ON D
OFF

1771-CP2

216 CA TB'S E

References
BUL. 2182E ACAD

Revision Dimensions Apply Before


Release Surface Treatment
Dimensions in Inches
A 10/21/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
+.005 Chkd. N/A Date N/A Dwg

Refer. Appd. N/A Date N/A


Size
D
CS70024646
Book Angles + 15
9-17-93 Packaged Control Cadds

45
1 2 3 4 5 6 7 8

CONNECT BETWEEN SIMILARLY MARKED TERMINALS

FUSE SLC500 SLC5/01 SLC500 SLC500 SLC500


1746-P1/P2 1747-L511 1747-DCM 1746-OW16 1746-IA16
POWER PC RUN FAULT
CPU FAULT COMM
100/120V
FORCED I/O
BATTERY LOW VAC-VDC 1 IN 0
C 200/240V
OUT 0 IN 1
OUT 1 IN 2
OUT 2 IN 3
BATTERY OUT 3 IN 4
1747-BA OUT 4 IN 5
OUT 5 IN 6
OUT 6 IN 7
OUT 7 IN 8
D VAC-VDC 2 IN 9
OUT 9 IN 10
OUT 8 IN 11
OUT 11 IN 12
OUT 10 IN 13

PWR OUT +24VDC OUT 13 IN 14


LINE 1
PWR OUT COM OUT 12 IN 15
SHIELD
LINE 2 OUT 15 AC COM
1 120/240VAC
OUT 14 AC COM
X2 VAC NEUT
E
EARTH GND

References BUL. 2182J ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
H
2 Place Decimal
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024147
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

46
5 6 7 8

1771-P4S

P/S
B
ACTIVE

P/S
PARALLEL

ON

POWER
OFF
C
1.5A 250V
SLOW BLOW

120VAC
L 1
1

N X2

D
G
N
D

12 3 4 5 6 7 8
ON TO GRD
OFF BUS OR
CUST'S
GRD SYS

References Bul. 2183E ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024148
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

47
5 6 7 8

CUSTOMER'S
INCOMING LINE CABLES
VOLTS, 3 PH., HZ
A

DIGITAL METERING SYSTEM

(H1) 1
1 (X1)
(H1A) B
1CT
(H1) 2
1 (X1)
(H1B)
2CT
(H1) 3
1 (X1)
(H1C)
3CT
4 C

(H2A)
GRD

(H2B)

/
0L1 /
0L2 /
0L3 LUGS
(H2C) D
IQ
DATA PLUS
NOTES:
POWER
1 MODULE
AMPS NAMEPLATE RATIO
AMPS EFFECTIVE RATIO WITH
PRIMARY TURNS
L1 1L1
SECONDARY TURNS
BE SURE TO CONNECT PER (A)
POLARITY MARKINGS. L2 1L2
E
SECONDARY CONNECTIONS OF
CURRENT TRANSFORMER MUST (B)
BE CONNECTED TO A LOAD OR L3 1L3
SHORTED TOGETHER TO AVOID
A HIGH VOLTAGE ACROSS
SECONDARY LEADS. DS (C)
CUSTOMER IS TO MOUNT AND
WIRE CURRENT TRANSFORMERS.
(NEU)

L1
L2
L3
HORIZONTAL BUS

References BUL.2190 METERING PANEL ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70002602
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

48
5 6 7 8
CUSTOMER'S
OUTGOING LOAD CABLES
VOLTS, 3 PH., HZ
A

AMMETER
11 AM 12

(H1) 2 OFF 1 2 3
1 (X1) (2) (1)

1CT (4) (3)


(H1) 8
1 (X1) (6) (5)
2CT
(8) (7)
11 AMMETER SWITCH C

GRD

/
0L1 /
0L2 /
0L3 LUGS
VOLTMETER D

14 VM 13

L1-L2 L2-L3
L1 1FU 1PT O L3-L1
1L1 1
H1 X1 (1) (2)

L2 2FU
1L2 H2 X2 GRD (5) (6)

(3) (4) E
2PT 4
H1 X1 (7) (8)
3FU VOLTMETER SWITCH
L3 1L3 H2 X2 7

L1 NOTES: 1
AMPS NAMEPLATE RATIO
AMPS EFFECTIVE RATIO WITH
ON 6 S.F. INCOMING LINE LUG
L2 PRIMARY TURNS COMPARTMENTS, THE CURRENT
SECONDARY TURNS TRANSFORMERS ARE FACTORY
BE SURE TO CONNECT PER MOUNTED AND WIRED.
L3 POLARITY MARKINGS.
HORIZONTAL BUS SECONDARY CONNECTIONS OF 2
CURRENT TRANSFORMER MUST - BOTTOM TERMINAL
BE CONNECTED TO A LOAD OR
SHORTED TOGETHER TO AVOID - TOP TERMINAL
A HIGH VOLTAGE ACROSS G
SECONDARY LEADS. VIEW FACING TERMINAL
SCREWS WITH DRUM SWITCH
CUSTOMER IS TO MOUNT AND IN VERTICAL POSITION.
WIRE CURRENT TRANSFORMERS.

References Bul. 2191F Outgoing Feeder Lug ACAD


Revision Dimensions Apply Before
Compartment
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70024643
9-17-93 Packaged Control Cadds

49
5 6 7 8

CUSTOMER'S
INCOMING LINE CABLES A
VOLTS, 3 PH., HZ

AMMETER
(H1)
2 AM
1 (X1)
1CT 11

GRD
C

D
/
0L1 /
0L2 /
0L3 LUGS
NOTES:
1
AMPS NAMEPLATE RATIO
AMPS EFFECTIVE RATIO WITH
PRIMARY TURNS
SECONDARY TURNS
BE SURE TO CONNECT PER
POLARITY MARKINGS.
SECONDARY CONNECTIONS OF E
CURRENT TRANSFORMER MUST
BE CONNECTED TO A LOAD OR
SHORTED TOGETHER TO AVOID
A HIGH VOLTAGE ACROSS
SECONDARY LEADS.
CUSTOMER IS TO MOUNT AND
WIRE CURRENT TRANSFORMERS.
ON 6 S.F. INCOMING LINE LUG
COMPARTMENTS, THE CURRENT
TRANSFORMERS ARE FACTORY
MOUNTED AND WIRED.

L1
L2
L3
HORIZONTAL BUS G

References Bul. 2191M Incoming Line Lug ACAD


Revision Dimensions Apply Before
Compartment
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024642
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

50
5 6 7 8

TO HORIZONTAL BUS
B
L1 L2 L3

FDS FDS

1T1 1T2 1T3 2T1 2T2 2T3

USER'S OUTGOING LOAD CABLES USER'S OUTGOING LOAD CABLES

References BUL. 2192F DUAL ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 07/16/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70015974
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

51
5 6 7 8

USER'S INCOMING LINE CABLES

OL1 OL2 OL3

L1

1L1 C

L2 BPS

1L2 C

L3

1L3 C

DOOR
E
(REAR VIEW) L1
L1

GRD
L2
L2

L3
F
L3

HORIZONTAL BUS

References BUL. 2192M ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/21/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70024644
9-17-93 Packaged Control Cadds

52
5 6 7 8

TO HORIZONTAL BUS

L1 L2 L3

T1 T2 T3

USER'S OUTGOING LOAD CABLES

References BUL. 2193F ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70002993
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

53
5 6 7 8
HORIZONTAL BUS
L1

L2

L3

C
RED

BLU

BLK
GRD

WHT
1
D
CURRENT
SENSOR
GRY

YEL

GRN

OL1 OL2 OL3 N

NOTES: USER'S INCOMING LINE CABLES

1 IF THE SYSTEM NEUTRAL IS GROUNDED AND PHASE TO


NEUTRAL LOADS ARE USED, THEN THE NEUTRAL CURRENT
SENSOR MUST BE USED. ! ATTENTION F
__________________________________
IF THE SYSTEM NEUTRAL IS GROUNDED, BUT NO PHASE
TO NEUTRAL LOADS ARE USED, THE NEUTRAL CURRENT Line side power connected to
SENSOR IS NOT NECESSARY. bottom of switch.
BE SURE TO CONNECT PER POLARITY MARKINGS.
SECONDARY CONNECTIONS OF CURRENT SENSOR MUST De-energize power to switch
BE CONNECTED TO A LOAD OR SHORTED TOGETHER TO before servicing.
AVOID A HIGH VOLTAGE ACROSS SECONDARY LEADS.
Failure to de-energize power G

INTERNAL CB AUXILIARIES SUPPLIED WITH UNMOUNTED can result in severe injury or


CONNECTION BLOCKS. death.

References Bul. 2193M ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70003259
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

54
5 6 7 8

PANEL NEUTRAL
1
A

1 2

3 4

5 6 B

7 8

9 10

11 12
C

13 14

15 16

17 18
D

X1 X2 X3

E
GFI CIRCUIT BREAKER
NOTES: CONNECTIONS
(WHERE SPECIFIED)
1 OTHER SIDE OF EACH CIRCUIT IS
ALSO CONNECTED TO PANEL NEUTRAL. PANEL NEUTRAL

WHITE WIRE

F
LIGHTING PANEL SUPPLIED WITH:
7 - 15A. - 1 POLE BREAKER(S) BRANCH
CIRCUIT N
6 - 30A. - 1 POLE BREAKER(S)
5 - 20A. - 1 POLE BREAKER(S)

REFER TO MANUFACTURERS
G
INSTRUCTIONS FOR GFI PANEL
INSTALLATION AND TESTING. CIRCUIT BREAKER BUS

References BUL. 2193LE 3-PHASE LIGHTING PANEL ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024145
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

55
5 6 7 8

TO BUS
L1 L2 L3 A

FDS

C
1L1

1L2

480 VOLTS

E
H1 H3 H2 H4

TRANS.
GRD. X2 X1

X2
120V

FU

References Bul. 2196 2kVA ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/.93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024146
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

56
5 6 7 8

TO BUS
L1 L2 L3 A

INTERNAL CB AUXILIARIES
CB
SUPPLIED WITH UNMOUNTED
CONNECTION BLOCKS.
RED

BLU B

BLK

RED

BLU

BLK

TAP 480 600 1L3 C


CONNECTION VOLTS VOLTS 1L2
1-2 504 630 1L1

2-3 492 615

3-4 480 600 SECONDARY


FUSES
4-5 468 585
D

5-6 456 570

TO
LOAD

TO X0 X0 X1 X2 X3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 H1 H2 H3
GRD BUS
OR CUST. PRIMARY TAP CONNECTIONS PRIMARY
GRD SYS. SECONDARY
H1 H2 H3
F

5 3 1 2 4 6 5 3 1 2 4 6 5 3 1 2 4 6

TRANS.

X0 X0 X1 X2 X3
G

References Bul. 2197 37.5 kVA ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size CS70024151
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

57
5 6 7 8

1L1 C T1
L1 (1/L1) (2/T1)
TO
BUS 1L2 T2 1
L2 LOAD
480V (3/L2) (4/T2)
3 PH
60 HZ 1L3 T3
L3 (5/L3) (6/T3)
B

FDS

2 H1 H2
FU TRANS. GRD C
X1
X1 X2
ON
OFF
1 1A 2 3 X2
(1) (2) (3) (4) (A1)
C (A2)
"J"
C ON
D
(14) (13)
C

4 C 5 6 C 7
(53) (54) (61) (62)

(TYPE "B" WIRING ONLY)


NOTES: X2
1 1
REMOTE DEVICE 1A
"J"
2
2 3 ON TYPE "A" WIRING,
THIS UNIT IS SUPPLIED 4 JUMPER "J" WILL BE
WITH AN INTERNALLY 5 LOCATED ON DOOR F
PROTECTED TRANSFORMER. 6 MOUNTED PUSH BUTTONS.
PRIMARY FUSING NOT 7
REQUIRED.
TB

References BUL. 2402 30 AMP (0.5 SF) ACAD


Revision Dimensions Apply Before
TYPE A
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70024106
9-17-93 Packaged Control Cadds

58
5 6 7 8

1L1 C T1
L1 (1/L1) (2/T1)
TO 1
BUS 1L2 T2
L2 (3/L2) (4/T2) LOAD
600V
3 PH 1L3 T3
60 HZ L3 (5/L3) (6/T3)
CB
B

1FU 2FU

H1 H2

H1 H2
FU TRANS. GRD
X1
C
X1 X2
OFF ON

1 3 X2
C
(3) (4) (A1) (A2)

C 2
(13) (14) D

1A
(SPARE)

X 1
1 2 3 TB
2 A
F

NOTES:

1
REMOTE DEVICE
G

References BUL. 2403 100 AMP ACAD


Revision Dimensions Apply Before
TYPE B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024107
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

59
5 6 7 8

3
TO 1L1 F OL'S T1 A
BUS L1 (1/L1) (2/T1) (2/T1)
1L2 T2
1
600V L2 (3/L2) (4/T2) (4/T2) MTR
3 PH 1L3 T3
60 HZ L3 (5/L3) (6/T3) (6/T3)
FDS
R
(1/L1) (2/T1)

(3/L2) (4/T2) B

(5/L3) (6/T3)

1FU 2FU
H1 H2
H1 H2
FU X1 TRANS. GRD
C
X1 X2

1A 2 3 R 8 OL
1 6 X2
(21) (22) (A1)
F (A2) (95) (96)
"J1"
F FORWARD
"J2" (13) (14) (X1)
R (X2)

D
4 5 F
7
(21) (22) (A1)
R (A2)

R REVERSE
(13) (14) (X1) R (X2)

OL OVERLOAD
22 A (X2)
(97) (98) (X1)

NOTES:
1
9 F 10 13 F 14
REMOTE DEVICE (53) (54) (63) (64)

F
11 R 12 15 R 16
3 (53) (54) (63) (64)

! ATTENTION
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
X 1 1 1 1 1 1 1 1
UNEXPECTED AUTOMATIC 2
1
A
2 3 4 5 9
0 1 2 3 4 5 6
TB

RESTART OF THE MOTOR CAN


CAUSE INJURY TO PERSONS OR "J1" "J2" G

DAMAGE TO EQUIPMENT.

References BUL. 2406 18-24 AMP ACAD


Revision Dimensions Apply Before
TYPE B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70024108
9-17-93 Packaged Control Cadds

60
5 6 7 8
1CT 3
1L1 F 1A1 T1
L1 (1/L1) (2/T1) (1L1) (2T1)
TO
BUS (B) OL (A) A
2CT
1L2 1A2 T2 1
L2 (3/L2) (4/T2) (3L2) (4T2) MTR
480V (D) OL (C)
3 PH
60 HZ 1L3 1A3
3CT
T3
L3 (5/L3) (6/T3) (5L3) (6T3)
CB GRD
(F) OL (E)
B
R
(1/L1) (2/T1)

(3/L2) (4/T2)

(5/L3) (6/T3)

C
2 H1 H2
FU X1 TRANS. GRD
OFF X1 X2
FOR REV
1 OL 24 3 R
6 F X2
(95) (96) (4) (3) (21) (22) (A1) (A2)

F FORWARD
2 D
(14) (13) (X1) G (X2)

5 F
7 R
(3) (4) (21) (22) (A1) (A2)

R REVERSE
4
(14) (13) (X1) G (X2)

E
F R OFF
9 10
(X1) B (X2)

NOTES:
1
REMOTE DEVICE
2
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY
PROTECTED TRANSFORMER. 1A F
PRIMARY FUSING NOT (SPARE)
REQUIRED.
(TYPE "B" WIRING ONLY)
3 ! ATTENTION X 1123 4 5
2 A TB
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN G
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.

References Bul. 2407 304 Amp ACAD


Revision Dimensions Apply Before
Type A
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005 Size
Refer.
Book Angles + 15 Appd. N/A Date N/A
D CS70024640
9-17-93 Packaged Control Cadds

61
5 6 7 8

3
1L1 M OL'S T1 A
L1 (1/L1) (2/T1) (2/T1)
TO
BUS 1L2 T2 1
L2 (3/L2) (4/T2) (4/T2) MTR
240V
3 PH 1L3 T3
60 HZ L3 (5/L3) (6/T3) (6/T3)
FDS

B
1FU 2FU

H1 H2 H4
H3
H1 H4
FU TRANS. GRD
X1
X1 X2
OFF
HAND START C
HAND AUTO HAND STOP
OL 24 1C 2 3 X2
1
(95) (96) (4) (3) (1) (2) (3) (4) (A1)
M (A2)

M M ON
4
(14) (13) (X1)
R (X2)

D
1
1A
(3) (4)

M OFF
5
(X1)
G (X2)

NOTES:

1
REMOTE DEVICE
F
X 1
1 2 3 4 5 TB
2 A
3 ! ATTENTION
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT. G

References Bul. 2412 38 - 45 Amp ACAD


Revision Dimensions Apply Before
Type B
Surface Treatment
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024110
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

62
5 6 7 8

1L1 M 2L1 1CT 3 T1


L1 A
(1/L1) (2/T1) (1L1) (2T1)
TO
BUS (B) OL (A)

1L2 2L2 2CT T2 1


L2 (3/L2) (4/T2) (3L2) (4T2) MTR
480V (D) OL (C)
3 PH
60 HZ 1L3 2L3 3CT T3
L3 (5/L3) (6/T3) (5L3) (6T3)
CB GRD B

(F) OL (E)

2 H1 H2 C
FU X1 TRANS. GRD
X1 X2
STOP
1 1A 2 3 OL
3A X2
(1) (2) (A1) M (A2) (95) (96)
"J"
M ON
(14) (13)
A
1 D

OVERLOAD
OL 22 E
(97) (98) A
1

NOTES:
1
REMOTE DEVICE
2
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY
PROTECTED TRANSFORMER.
PRIMARY FUSING NOT F
REQUIRED. X1 12 3 TB
2 A
"J"
3 ! ATTENTION
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
G
RESTART OF THE MOTOR CAN
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.

References Bul. 2413 180 Amp (2.5 SF) ACAD


Revision Dimensions Apply Before
Surface Treatment Type B
Release Dimensions in Inches
A 10/18/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size
CS70024111
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

63
5 6 7 8

L3 T3

TO USER'S OUTGOING
HORIZONTAL L2 T2 LOAD CABLES
BUS
D

L1 T1

FDS E

NOTES:

UNIT INSTALLATION

THE HANDLE EXTENDER KIT, 2100-


NE1, MAY BE NECESSARY FOR ANY
TOP UNIT OPERATING HANDLES THAT
ARE HIGHER THAN 6-1/2 FEET OFF
THE GROUND FOR COMPLIANCE WITH NEC

References Bul. 2492F ACAD


Revision Dimensions Apply Before
Surface Treatment
Release Dimensions in Inches
A 10/21/93 Tolerances Unless
Otherwise Specified
2 Place Decimal H
+.02 Dr. PPEN577B Date 10/02/93
Sheet 1 Of 1
3 Place Decimal
Chkd. N/A Date N/A Dwg
+.005
Refer.
Size CS70024626
Book Angles + 15 Appd. N/A Date N/A
D
9-17-93 Packaged Control Cadds

64
AllenBradley , a Rockwell Automation Business, has been helping its customers improve pro
ductivity and uality for more than 90 years. W e design, manufacture and support a broad range
of automation products worldwide. They include logic processors, power and motion control
devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds
leading technology companies.

Worldwide representation.
Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia Costa Rica Croatia Cyprus Czech Republic
Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala onduras ong ong ungary Iceland India Indonesia
Ireland Israel Italy Jamaica Japan Jordan orea uwait Lebanon Malaysia Mexico Netherlands New ealand Norway Pakistan Peru
Philippines Poland Portugal Puerto Rico atar Romania RussiaCIS Saudi Arabia Singapore Slovakia Slovenia South Africa, Republic Spain
Sweden Switzerland Taiwan Thailand Turkey United Arab Emirates United ingdom United States Uruguay Venezuela Yugoslavia

AllenBradley eaduarters, 1201 South Second Street, Milwaukee, WI 53204 USA, T el (1) 414 3822000 Fax (1) 414 3824444

Publication 2100-WD1 - April, 1995


Copyright 1985 AllenBradley Company , Inc. Printed in USA