DIRTY COOLING WATER DEMAND

No. Tag. No. Descriptio Peak Load Utilisation Data FormPFD Served Area
m3/hr Hrs/Day
To be submiit Based on Bala and his friend

this value
based on Bart
1 FFA 62.1
Information
06.02.'17
CLEAN COOLING WATER DEMAND
No. Tag. No. Description Peak Load Utilisation Data Form PFD
m3/hr Hrs/Day

Seawing Lquid Cooler or 17


1 3E2 Li.q Ring Vacuum Pump Continous FLS RVDF SECTION
2 3E4 Separator liquid Cooler 48 Continous FLS RVDF SECTION
Calculated , as DISTILLATION
Condensor 94 Continous
3 5E2 in PFD SECTION
Calculated , as DISTILLATION
Main Condensor 189 Continous
4 5E5 in PFD SECTION
Calculated , as DISTILLATION
Sec. Condensor 14 Continous
5 5E6 in PFD SECTION

Calculated , as DESOLVENTISING,
6E1 Cooker Condensor 28 Continous
in PFD SWS-SWT Sections
6

Calculated , as DESOLVENTISING,
7E1 Cooker Condensor 6 Continous
in PFD SWS-SWT Sections
7
Calculated , as ABSORPTION
8E6 Vent Condensor 10 Continous
8 in PFD SECTION
Calculated , as ABSORPTION
8E2 PHE Cooler 3.6 Continous
9 in PFD SECTION
Desorption Column Calculated , as ABSORPTION
8E5 32 Continous
10 Condensor in PFD SECTION
FFA Pump Around Cooler- Calculated , as FFA STRIPPING
12E4 42 Continous
11 PHE in PFD SECTION
Calculated , as FFA STRIPPING
12E5 Final E-Oil Cooler - PHE 12 Continous
12 in PFD SECTION
Absortion
94
Chillers
Waste Water this value is
Will Provided 100
Plant assumption
this value is
NEF Will Provided 300
assumption
Total Peak Load 989
Additional Value 15% 1138
Summary for each area
1 Extraction Plant 441.6
2 FFA Plant 54
3 Absorption Chiller 94
4 Waste Water Plant 100
5 NEF 300
Served Area
Extraction Plant FFA Plant Absortion Chillers Waste Water Plant

441.6 54 TBA TBA


Extraction Plant

Extraction Plant

Extraction Plant 495.6

Extraction Plant

Extraction Plant

Extraction Plant

Extraction Plant

Extraction Plant

Extraction Plant

FFA Plant

FFA Plant
NEF

TBA
CHILLED WATER DEMAND
No. Tag. No. Descriptio Peak Load Utilisation Data FormPFD Served Area
m3/hr Hrs/Day
1 2E1 1.9 Extraction
2 8E7 12 Absorption
3 8E3 13.75 Absorption
4 3E1 36 Other Areas
5 Chilling water for filtration SO3 TBA
Total Peak Load 64
Additional Value 15% 73
Summary for each area
1 Extraction Plant 1.9
2 Absorption Chiller 25.75
3 Chilling water for filtration SO3