Professional Documents
Culture Documents
User Manual
General
B4065 Rev. C
This manual is the property of Nera Networks AS. No parts of the manual may be copied, rewritten or distributed to
third parties without the written permission from Nera Networks AS.
In addition to the WEB
edition, the manual is
available in paper
format:
or in PDF format
If you don't have Adobe Acrobat Reader installed on your computer, you can download it below.
General This part gives a general overview of the Evolution Series equipment
Operation Describes how to operate the system with emphasis on the Evolution Series Manager
INFORMAL
esky NERA Networks AS tmto prohlauje, e tento Evolution Series je ve shod se zkladnmi poadavky a dalmi pslunmi ustanovenmi smrnice
1999/5/ES.
Dansk NERA Networks AS erklrer herved, at Evolution Series overholder de vsentlige krav og vrige relevante krav i direktiv 1999/5/EF.
Deutch Hiermit erklrt NERA Networks AS, dass sich das Gert Evolution Series in bereinstimmung mit den grundlegenden Anforderungen und den
brigen einschlgigen Bestimmungen der Richtlinie 1999/5/EG befindet.
Eesti Kesolevaga kinnitab NERA Networks AS seadme Evolution Series vastavust direktiivi 1999/5/E phinuetele ja nimetatud direktiivist
tulenevatele teistele asjakohastele stetele.
English Hereby, NERA Networks AS, declares that Evolution Series is in compliance with the essential requirements and other relevant provisions of
Directive 1999/5/EC.
Espaol Por medio de la presente NERA Networks AS declara que el Evolution Series cumple con los requisitos esenciales y cualesquiera otras
disposiciones aplicables o exigibles de la
NERA Networks AS Evolution Series
S G 1999/5/.
Franais Par la prsente NERA Networks AS dclare que l'appareil Evolution Series est conforme aux exigences essentielles et aux autres dispositions
pertinentes de la directive 1999/5/CE.
Italiano Con la presente NERA Networks AS dichiara che questo Evolution Series conforme ai requisiti essenziali ed alle altre disposizioni pertinenti
stabilite dalla direttiva 1999/5/CE.
Latviski Ar o NERA Networks AS deklar, ka Evolution Series atbilst Direktvas 1999/5/EK btiskajm prasbm un citiem ar to saisttajiem noteikumiem.
Lietuvi iuo NERA Networks AS deklaruoja, kad is Evolution Series atitinka esminius reikalavimus ir kitas 1999/5/EB Direktyvos nuostatas.
Nederlands Hierbij verklaart NERA Networks AS dat het toestel Evolution Series in overeenstemming is met de essentile eisen en de andere relevante
bepalingen van richtlijn 1999/5/EG.
Malti Hawnhekk, NERA Networks AS, jiddikjara li dan Evolution Series jikkonforma mal-tiijiet essenzjali u ma provvedimenti orajn relevanti li hemm fid-
Dirrettiva 1999/5/EC.
Magyar Alulrott, NERA Networks AS nyilatkozom, hogy a Evolution Series megfelel a vonatkoz alapvet kvetelmnyeknek s az 1999/5/EC irnyelv
egyb elrsainak.
Polski Niniejszym NERA Networks AS owiadcza, ze Evolution Series jest zgodny z zasadniczymi wymogami oraz pozostaymi stosownymi
postanowieniami Dyrektywy 1999/5/EC.
Portugus NERA Networks AS declara que Evolution Series est conforme com os requisitos essenciais e outras disposies da Directiva 1999/5/CE.
Slovensko NERA Networks AS izjavlja, da je ta Evolution Series v skladu z bistvenimi zahtevami in ostalimi relevantnimi doloili direktive 1999/5/ES.
Slovensky NERA Networks AS tmto vyhlasuje, e Evolution Series spa zkladn poiadavky a vetky prslun ustanovenia Smernice 1999/5/ES.
Suomi NERA Networks AS vakuuttaa tten ett Evolution Series tyyppinen laite on direktiivin 1999/5/EY oleellisten vaatimusten ja sit koskevien
direktiivin muiden ehtojen mukainen.
Svenska Hrmed intygar NERA Networks AS att Evolution Series str i verensstmmelse med de vsentliga egenskapskrav och vriga relevanta
bestmmelser som framgr av direktiv 1999/5/EG.
slenska Hr me lsir NERA Networks AS yfir v a Evolution Series er samrmi vi grunnkrfur og arar krfur, sem gerar eru tilskipun 1999/5/EC.
Norsk NERA Networks AS erklrer herved at utstyret Evolution Series er i samsvar med de grunnleggende krav og vrige relevante krav i direktiv
1999/5/EF.
Intended use of equipment
Evolution Series is a point to point microwave radio. It is typically used for interconnection of
access points in private or public networks. It is used both in Ethernet and TDM based networks.
Note! Use of this equipment requires a separate frequency license to be applied for by the
operator.
WARNINGS!
High Frequency Electromagnetic Fields
Exposure to strong high frequency electromagnetic fields may cause
thermal damage to personnel. The eye (cornea and lens) is easily exposed.
Any unnecessary exposure is undesirable and should be avoided.
In radio-relay communication installations, orderly setup for normal
operation, the general RF radiation level will be well below the safety limit.
In the antennas and directly in front of them the RF intensity normally will
exceed the danger level, within limited portions of space.
Dangerous radiation may be found in the neighbourhood of open
waveguide flanges or horns where the power is radiated into space.
To avoid dangerous radiation the following precautions must be taken:
During work within and close to the front of the antenna; make sure
that transmitters will remain turned off.
Before opening coaxial - or waveguide connectors carrying RF
power, turn off transmitters.
Consider any incidentally open RF connector as carrying power,
until otherwise proved. Do not look into coaxial connectors at closer
than reading distance (30 cm). Do not look into an open waveguide
unless you are absolutely sure that the power is turned off.
ESD
This equipment contains components which are sensitive to "ESD" (Electro
Static Discharge).
It is therefore essential that whenever disassembling the equipment and/or
handling PC boards, special precautions to avoid ESD have to be made.
These precautions include personnel grounding, grounding of work bench,
grounding of tools and instruments as well as transport and storage in
special antistatic bags and boxes.
Laser
CAUTION
Use of controls or adjustments or performance of procedures other than those specified
herein may result in hazardous radiation exposure.
The optical interface must only be serviced by qualified personnel, who are
aware of the hazards involved to repair laser products.
When handling laser products the following precautions must be taken:
Never look directly into an open connector or optical cable
Before disconnecting an optical cable from the optical transmitter,
the power should be switched off. If this is not possible, the cable
must be disconnected from the transmitter before it is disconnected
from the receiver.
When the cable is reconnected it must be connected to the receiver
before it is connected to the transmitter.
EARTHING
This equipment has a connection between the earthed conductor of the d.c.
supply circuit and the earthing conductor.
Lithium battery warning!
Caution. Danger of explosion if battery is incorrectly replaced. Replace only
with the same or equivalent type recommended by the manufacturer.
Dispose of used batteries according to the manufacturers instructions.
Avertissement de batterie de lithium!
Attention: Il y a danger d'explosion s'il y a remplacement
incorrect de la batterie. Remplacer uniquement avec une
batterie du mme type ou d'un type recommand par le
constructeur. Mettre au rbut les batteries usages
conformment aux instructions du fabricant.
NOTE!
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own
expense.
System Overview
Introduction
The Evolution Series microwave radio is designed to transmit data rates from about 6 Mb/s to 600Mb/s, in the
frequency bands 5 GHz to 38 GHz. The configuration of capacity and modulation is software configurable, giving an
optimal balance between system gain and spectral efficiency.
Available interfaces are: E1, T1, E3, DS3, STM-1/OC-3, STM-4/OC12, 100BASE-TX, Gigabit Ethernet.
The Evolution Series products can be configured in two different modes, selected by the SW license.
Scalable 8, 16, 32, 40, 80, 100, 150 Mb/s transmission capacity
7, 14 and 28 MHz BW
Scalable TDM/Ethernet mix (step of 2Mb/s)
4, 8, 16, 20, 40, 50, 75 E1 capacity
Ethernet 1xFE, scalable with 2 Mbit/s granularity
Ring protection for E1s, based on SNCP
The XPAND mode (ANSI)
Scalable 6, 12, 24, 48, 100, 128, 150 Mb/s transmission capacity
5, 10, 20 and 30 MHz BW
Scalable TDM/Ethernet mix (step of 1.5Mb/s)
4, 8, 16, 32, 64, 80, 96 T1 capacity
Ethernet 1xFE, 1.5 Mbit/s granularity
Ring protection for T1s, based on SNCP
Features
The ODU can be mounted directly on the antenna, both in unprotected and protected configurations. The ODU can
also be mounted on the antenna pole, using a short flexible waveguide to the antenna.
The Universal IFU can easily be expanded from a single channel system up to a traffic node handling up to 8
ODUs. The Universal IFU contains the line interface, baseband processing and multiplexing, management and
radio interfaces.
The optional embedded ADM/DXC function provides multiplexing for user traffic into the STM-1/OC-3 signal. In
traffic node systems, the digital cross connect (DXC) routes the user traffic between the various link directions
without the need for cabling or external multiplexers. Chain, ring, star and mesh topologies are supported, with
individual choice of unprotected or protected (SNCP) traffic circuits. The multiplexer supports a mix of traffic types,
such as E1, T1, E3, DS3 and Ethernet.
The equipment configuration, licences and the operating software version, can be stored on the memory key
available for plug-in, at the front of the equipment or downloaded to a computer. When a new Supervisory Unit is
inserted, the equipment configuration can then easily be restored to the radio equipment.
System description
The Evolution Series microwave radio system comprises an indoor part (Universal IFU), and an outdoor part (ODU)
and an antenna. The Universal IFU and ODU are interconnected using a coaxial cable which carries the transmit
and receive user traffic, management communication between the Universal IFU and ODU, and the power supply
to the ODU. In protected configurations, two cables are used; one for each ODU.
The Universal IFU Basic Frame is common in all configurations and up to four IFU frames can be stacked together
by an IFU connection panel.
The lower left position contains the Supervisory Unit. The Supervisory Unit is handling the configuration of all
the system units as well as reporting system status to the NMS system.
The rightmost position houses the FAN unit, handling the ventilation and temperature management of the IFU
frame.
The Line Interface slots house the various user traffic interfaces and optional DXC mux unit. The PDH and
Ethernet traffic interfaces are full height and cover the upper Aux/Serv. position as well.
The two Radio Interface slots house the RIU unit(s). The RIU unit provides connection to the ODU and
supplies power to the IFU Basic Frame with plug-in units and the ODU.
The upper Aux/Serv. slots house any Auxiliary or Service Channel units, such as Alarm Unit, Wayside Traffic
Unit, 64 kb Data Channels unit and EOW unit.
All units can be replaced in the field. Non traffic carrying units can be replaced without interrupting the service.
Configuration examples
Legend
ALM External alarm input/output
AUX Auxiliary function plug-in units
EMF Embedded Management Functions
EOW Engineering Order Wire
LAN Local Area Network port (10/100BASE-TX Ethernet)
LIU Line Interface Unit (plug-in unit)
RIU Radio Interface Unit (plug-in unit)
PWR Power Supply
SERV Service function (plug-in unit)
SU Supervisory (plug-in unit)
USB Universal Serial Bus
XCVR Transmitter/Receiver
Interface Unit (IFU) overview
The IFU is modular based and can be configured in different ways by means of plug-in units.
By pointing the cursor at a unit below, possible slot positions are indicated in the figure above.
To learn more about the different units; click on a unit in the illustrations below.
SU overview
LIU 25xE1 overview
RIU overview
Gigabit Ethernet Unit
overview
PWIU overview
EOW overview
64kb/s overview
FAN overview
LIU Electrical
overview
LIU Optical overview
One IFU is capable of handling radio systems for 1+0, 1+1, HSB and 2+0 channel arrangements. Larger systems
are implemented by interconnecting IFUs using the expansion port on the back of the IFU and a sub-rack. A total
of 4 IFUs and 1 DXC Frame can be stacked and connected together. Each IFU and DXC frame is 1U (Unit) high,
and can be mounted in both an ETSI and a 19 rack solution as well as standalone. The IFU handles
SDH/SONET overhead termination for one or two radio channels depending on radio system configuration.
Supervisory Unit overview
The SU is responsible for configuration and alarm collecting from all the boards in one IFU system. The maximum
IFU system may consist of 5 IFUs that can be controlled from only one SU located in an arbitrary IFU slot. The
SU communicates with all boards and functions needing SU awareness.
Connectors
USB
The USB device connector (USB type B connector) is used to open a text based console interface to the SU. This
interface can be used for basic SU configuration, for instance setting the IP address. The USB device interface
complies with USB v1.1
The USB host connector (USB type A connector) can be used for connecting a USB disk on key, to perform
software update. This host connector can also be used as a RS232 interface using a USB to RS232 converter.
The USB host interface complies with USB Rev 2.0 full-speed (12Mbit/s).
Ethernet
The Ethernet Port A (ETH1) is the SU management interface port. The Web server, FTP, SNMP and Telnet
server are available from this port.
When the SU is configured for 100/10 Mbit/s Ethernet over the radio hop, port B is the physical interface for
this connection
Else port B is equivalent with port A. Port A and Port B together with the SU CPU form a 3-port Ethernet
switch
The Line Interface Electrical STM-1/STS-3 Unit has a CMI encoded 155 Mb/s customer interface.
Electrical interface is according to ITU-T Rec. G.703, ANSI T1.102 and Telecordia GR-253-CORE.
Jitter Performance is compliant with ANSI T1.105.03, ITU-T G.825 and Telecordia GR-253-CORE.
Some of the characteristic parameters of this interface are given below:
Bitrate: 155.520 Mb/s 20 ppm
Line code: CMI
Impedance: 75 unbalanced
Return loss (8 MHz to 240 MHz): 15 dB
Pulse amplitude: 1.0 V 0.1 V
Maximum attenuation of input signal at 78 MHz: 12.7 dB
Connector type: DIN47297; 1.0/2.3mm
See Evolution Manager for setup of the Line Interface Unit
Line Interface Optical STM-1/OC-3 Unit overview
The Line Interface Optical STM-1/OC-3 unit is delivered in the following versions:
Line Interface Unit Optical SFP S-1.1/OC-3 IR-
1 LIU S-1.1/OC-3 IR-1
Line Interface Unit Optical SFP OC-3 SR-0 LIU OC-3 SR-0
The Optical Line Interface Unit has a 155.520 Mb/s (OC-3/STM-1) customer interface, according to ITU-T recommendation G.957 and
ANSI recommendation T1.105.06-2002.
In the receive direction, the optical LIU receives a 155.52 Mb/s NRZ encoded optical signal and converts it to an electrical NRZ signal.
In the transmit direction, the LIU receives a STM-1 framed signal and converts it to a NRZ-encoded optical signal.
Warning! The optical interface plugin module (SFP) is an integrated part of the Optical Line Interface Unit and has been tested to comply with Nera Networks
recommendations. The module is not intended for field replacement.
Line Interface 25xE1 Unit overview
The 25xE1 Intfc Unit contains 25 x E1 electrical interfaces, according to the ITU-T Rec; G.703
In the RX direction the 25xE1 Intfc Unit will receive 25 bipolar line signals from (HDB3), and maps them in to a
155Mb/s STM-1 frame.
The STM-1 signal is routed to the main data switch on the motherboard.
In the TX direction the 25xE1 Intfc Unit receives a STM-1 framed signal from the motherboard and maps it to 25 x
E1signals (HDB3).
The Radio Interface Unit is used for interconnection between the IFU and Radio
The RIU is supplied with -48V DC via the power connector. -48V DC is then fed to the radio and to the IFU. Short
circuit and over voltage protection for the radio is placed in the RIU. The Short circuit and over voltage protection
for the IFU is placed on the mother board.
The IFU has two RIU slots.
In order to control the temperature as well as increase component lifetime, a Fan Unit is implemented as cooling
mechanism.
Port1; Service Telephone handset. Selective call (00 to 99) or collective call (*)
Port2; 64kb/s, G.703 Co-directional / Analog interface
Port3; 64kb/s, G.703 Co-directional / HDLC / Analog interface
Port4; 4Wire transformer isolated interface
1......8
All the interfaces (Ports) may be enabled / disabled individually. However if the 1000 Base-X (SFP) is selected, a
maximum of 3x10/100 Base-T are available.
Connectors
Port 1 to 3
Port 4
RJ45 connectors for 10/100/1000 Base-T traffic
Port 5
B4065 Rev. C
This manual is the property of Nera Networks AS. No parts of the manual may be copied, rewritten or distributed to
third parties without the written permission from Nera Networks AS.
In addition to the WEB
edition, the manual is
available in paper
format:
or in PDF format
If you don't have Adobe Acrobat Reader installed on your computer, you can download it below.
General This part gives a general overview of the Evolution Series equipment
Operation Describes how to operate the system with emphasis on the Evolution Series Manager
Tools
Mounting of equipment rack Hammer drill
Masonry bit, 12mm
Hammer, small
Square
Spirit level
Tape measure and pencil
Hacksaw and file (for cutting of support bar, if required. Standard length;
225mm)
Spanner 17mm (Qty 2)
Adjustable spanner 0-20mm
Installation Kits
Rack Assembly Kit ABZ6478 Strips
4 ea. adjustable feet
50 ea. rack nuts (Cage Nuts)
Termination bracket
Earthing bar
Rack earthing cable (station earth), 2.5m
Rack top earthing cable (earth jumper), 20cm
20 ea. cable ties
Screws, nuts and washers
Rack Support
Screw and Bracket Kit MSK5371 Coach screws w/plastic plugs
Brackets for Suppoert bar
Screws, nuts and washers
UWA6511
Note! The IFU is ventilated through vent holes in the IFU sides and back panel. It is important that these holes are not complete or partly covered,
to ensure proper air flow through the IFU interior. When mounting in rack, make sure that cables or other obstacles do not block the air flow.
Sub Rack
1. Mount the Sub-rack in the Main-rack by using two screws in the upper mounting holes.
2. Mount the lower IFU in the Sub-rack by sliding it on the bottom guides and carefully enter the back plane connectors.
Note! Do not use excessive force. Make sure that the connectors enter smoothly.
Fasten the IFU with four screws (torque 10 Nm).
3. Remove the two screws in the upper Sub-rack mounting holes.
4. Mount the upper IFU in the Sub-rack by sliding it on the lid of the lower IFU and carefully enter the back plane connectors.
Note! Do not use excessive force. Make sure that the connectors enter smoothly.
Fasten the IFU with four screws (torque 10 Nm).
Note! It is important that the lower IFU is mounted in the Sub-rack before the upper IFU is mounted.
ODU and Antenna mounting
Note! The installation, maintenance, or removal of antenna systems requires qualified, experienced personnel. This installation
instruction has been written for such personnel. Antenna systems should be inspected once a year by qualified personnel to verify proper
installation, maintenance and condition of equipment.
Nera disclaims any liability or responsibility for the result of inproper or unsafe installation practices.
Warning! Use protective wear to avoid skin contact with the pre-applied conductive grease on threads. Keep away from mouth. Wash
thoroughly after use with liberal amounts of liquid soap and rinse with water. Do not store open near food or food sources. Dispose of empty
or partially filled containers according to governmental regulations for petroleum products. Contents oil, clay and zinc dust.
The following procedure describes the principle of mounting the equipment on a pole.
The mounting sequence depends on available lifting equipment and the site architecture. Sometimes it is more convenient to assemble the
ODU and antenna on the ground and lift as one unit, for placement on the antenna tower or platform, but the priciple of assembling will be the
same.
Polarization
Antennas are delivered from the factory with default vertical polarization.
Change of polarization is easiest to perform before the antenna is mounted to the antenna mount.
Procedure for polarization change Antenna
Tip! After mounting and coarse alignment of the antenna, the Waveguide Interface should be
aligned vertically or horizontally by means of a spirit level, to ensure that the signal has correct
polarization direction.
From vertical to
horizontal
polarization
change
From
horizontalal to
vertical
polarization
change
Tip! After mounting and coarse alignment of the antenna, the Waveguide Interface should be aligned vertically or horizontally by means
of a spirit level, to ensure that the signal has correct polarization direction.
Note! To avoid damaging the adjustment bolts, do not try to adjust the antenna (elevation/azimuth fine adjustment bolts) without
slackening the four corresponding fastening bolts.
Elevation Adjustment
Azimut Adjustment
Antenna Alignment
The purpose of the alignment procedure is to obtain maximum signal level
and cross polarization discrimination by aligning two antennas in opposite
directions.
The antennas should be properly mounted (follow the manufacturers
mechanical alignment instructions) and polarized in the same direction. It
must be possible to transmit from one antenna and receive on the other. The
best way is to have a transmitter and a receiver connected to both antennas.
Note: In order to transmit and receive signals, the initial system settings
must be performed through the built-in web-server; Evolution Manager.
Procedure for Coarse alignment
Adjust both antennas to correct directions as precisely as possible by using
magnetic compass or optical sight.
Procedure for Fine alignment
Fine adjustment is achieved by sending a signal from one of the antennas.
On the receive side various methods may be used.
a) Measure the RSSI (Received Signal Strength Indicator) voltage
from the transceiver
b) Read the received level on a spectrum analyser
c) Measure the received power with a power meter
This procedure describes antenna alignment by use of RSSI:
The RSSI Voltage is available at the
BNC-connector on the
Transceiver.
Operate the Evolution Manager to
manually switch the equipment to
Ch1.
Mute the transmitter at the local
station to exclude interference
from this source.
A voltmeter must be connected to
the RSSI connector, and
preferably monitored by the
person who is adjusting the
antenna. Adjust alternatively in
azimuth and elevation until the
received signal reaches maximum
level (minimum RSSI voltage
level). Try a few times in each
direction.
The antenna should be turned so
much that the first side lobes are
seen, thereby ensuring that the
antenna is aligned to the main
lobe.
When the antenna is correctly
adjusted, secure all bolts. Monitor
the instrument during this
operation and if necessary realign
the antenna.
When adjustments are completed
on the first antenna, the same
procedure is performed on the
opposite antenna.
Cross Polarization Adjustment
After alignment of the antenna, the antenna feed must be adjusted
horizontally and vertically. Loosen the flange which secures the feed to the
reflector. Align the feed by using a spirit level. Secure the flange.
Final Control
When all
adjustments
are
performed,
check that
the input
level
corresponds
with the one
theoretically
calculated. If
the input level is too low, adjust the antennas once more. Finally, ensure that
all bolts and ensure that nuts are properly mounted and secured.
Getting Started
License
A payload license may be required to enable traffic on the equipment. The License Key is a 40 character alpha numeric string distributed
with the equipment or purchased separately. For payloads below 80 Mb/s, no payload licence is required. The License Key document must
be kept in a safe place.
PC connection
Note! A screen resolution >1024x768 is recommended.
Connect the SU Unit to a PC by means of a TP cable. The cable is connected to the ETH1 connector on the SU and to the LAN connector
on the PC. See illustration below.
First Time Log On
PC Setup
To obtain contact between the PC and SU, it is necessary to have an IP address on the PC within the same subnet as the SU. The default
SU IP address is 10.0.0.10. Set the PC address to e.g. 10.0.0.100 and subnet mask to e.g. 255.0.0.0. Note the initial settings before
changing.
Note! The SU IP address as well as password, should be changed before the system is released for operation. See separate
procedures.
Note! The IP set-up can alternatively be set using Hyperterminal and the SU USB interface. This function is useful if NE IP address is
unknown or the IP address is accidentally set to an address outside the subnet.
Log on
Open an Internet browser (supported browsers are Internet Explorer 6.0+ and Mozilla Firefox 1.5.0+).
Type in the default IP address "10.0.0.10" in the Address Bar.
Configuration
The picture below appears. Follow the steps to initiate the equipment.
Note! The equipment may be factory pre-configured. In this case only frequency and power settings on the ODU have to be attended
to. The picture below shows an unconfigured Network Element (red text stating "Network Element not Configured").
Tip! The procedures in the examples below, are described in detail in the Operation Section.
1
License
1 Licence
2 Unit Housekeeping
3 Frequency
IP Configuration via USB
Hyperterminal is used for connection between the PC USB port and the SU. A USB cable with a USB B plug (for
connection to the SU) in one end and a USB A plug (PC side) in the other end.
Install drivers
Connect the USB cable to PC and SU
The following picture appears
Select "No, not this time"
Click "Next"
Select "Install from a list or specific location (Advanced)"
Browse to the "USB_drivers" folder on the "Evolution Series Manual" CD
Click "OK"
Click "Next"
Select "No, do not connect to the Internet now"
Click "Next"
Click "Continue Anyway"
Click "Finish"
HyperTerminal set-up
Start HyperTerminal from "Start" button as shown below
Click "Yes"
The options in this dialogue box are not relevant. Click "OK"
The options in this dialogue box are not relevant. Click "OK"
Type in the name for the connection e.g. "Evolution" and select an optional icon
Select the COM port assosiated with the IFU
Select options as described above
Click "OK"
Hit the "Enter" key on the keyboard
Log on using User name and password (default User: "admin", Password: "admin")
IP Configuration
The following parameters can be red or set:
ipconfig
iprange
iprangeset
reloadtask
reset
To view current ipconfig, type ipconfig and hit the "Enter" key on the keyboard.
Type help and hit the "Enter" key on the keyboard to learn about the available commands.
Evolution Series
User Manual
Operation
B4065 Rev. C
This manual is the property of Nera Networks AS. No parts of the manual may be copied, rewritten or distributed to
third parties without the written permission from Nera Networks AS.
In addition to the WEB
edition, the manual is
available in paper
format:
or in PDF format
If you don't have Adobe Acrobat Reader installed on your computer, you can download it below.
General This part gives a general overview of the Evolution Series equipment
Operation Describes how to operate the system with emphasis on the Evolution Series Manager
To start the Unit Housekeeping Wizard; Click on Configuration and then Housekeeping. By clicking the same sequence on the figure below, a Unit
Housekeeping tutorial will start.
Housekeeping Wizard
Step 1 of 5 - Station Configuration
Click on the Next or Previous etc. buttons to navigate in the Housekeeping wizard tutorial.
Housekeeping Wizard
Step 2 of 5 - Antenna Configuration
Housekeeping Wizard
Step 3 of 5 - IFU Frame Configuration
Housekeeping Wizard
Step 4 of 5 - Interface Configuration
Housekeeping Wizard
Step 4 of 5 - Individual Interface Configuration
Housekeeping Wizard
Step 5 of 5 - Auxiliary Interface Configuration
Frequency setting
To enter the frequency setting page; Click on Configuration and then Frequency. Click the same sequence on the figure below to view the fre-
quency setup page description.
IP setting
To enter the IP setting; Click on Configuration and then Network. Click the same sequence on the figure below to view the IP confiuration page description.
Step1
Step2
Add new user
To enter the Add New User page; Click on Security. Click security on the figure below to view the Add User page description.
Step1
Step2
User Name Length: 4-32 characters (alpha
numeric)
Possible characters: A-Z, a-z, 0-9 (not case
sensitive)
Privilege;
Passive: System monitoring
Active: Communication
settings and data
collection
Master: All commands
including software
download
Admin: All commands
including software
download and
administration of user
accounts
Feature Description
A wide range of configuration, tests and system monitoring can be performed by means of the Evolution Manager. The screenshots shown in this chapter and
the navigation is the same as in the Evolution Manager program, for a certain equipment configuration. The screenshots in the Evolution Manager will change
dynamically with the actual equipment configuration and may differ from this example on certain sub-menus.
Note! This is only a tutorial and no parameters can be set from this manual. The alarms and system configuration details are fictive and not related to a "live"
system.
Menu Details
A brief description of the functionallity is shown when the cursor is placed over the menue items or the IFU Frame Plug-in units (including Mother board), in the
screenshot below.
Click on a menue item or IFU Plug-in unit, to get a detailed description of the specific item.
Note! The Mother board is accessed by clicking the yellow bar on the IFU lower part or the grey bar on the top.
Configuration
In the Configuration menu the system can be configured according to user preferences and license parameters.
Click on the sub-menues to explore the functionality.
For configuration of Plug-in units and ODU, click on the Radio/IFU picture on the screenshot.
Note! The Mother board is accessed by clicking the yellow bar on the IFU lower part or the grey bar on the top.
Housekeeping Wizard Step 1
The Housekeeping wizard must be run initially when the system is set up for the first time and if the hardware configuration has been changed.
Note! click the Next, Previous.. etc buttons to navigate in this tutorial.
Housekeeping Wizard Step 2
Housekeeping Wizard Step 3
Housekeeping Wizard Step 4
Housekeeping Wizard Step 4 individual Interface
Housekeeping Wizard Step 5
Radio Protection Switching
Radio Protection Switching (RPS) operations for N+1and Hot Stand-by systems are managed by the Supervisory Unit This RPS module interacts with other
system hardware resources to achieve automatic protection switch operations based on switch criteria inputs from the individual radio channels. This module also
supports manually controlled switch operations and status reporting.
Hot Standby configurated systems
Switch Section (Hot Stby)
Hot Standby system configurations implement local equipment protection within the network element (radio station). A protection switch section is then comprised of the dupli-
cated transmit- and receive-equipment required to serve one antenna. This switch section is monitored and controlled by a single RPS module. The two equipment paths are
identified as Ch. 1 and Ch. 2. The protection switch state is either Ch. 1 active or Ch. 2 active. Each traffic direction (transmit and receive) has its own set of switch criteria.
The system may be set up as Unidirectional (radio transmit switch and baseband receive switch operates completely independent of one another) or Bi-directional (radio
transmit switch will follow the baseband receive switch if there is no conflicting criteria, and vice versa).
Bi-directional
Bi-directional means that assertion of a criterion in one or the other of the two traffic directions will cause the affected channel to be switched to standby mode for both of its
traffic directions. Restoring it to its working mode will not be permitted until the active criteria for both directions are cleared.
Uni-directional
Uni-directional means that the two traffic directions for a switching section are controlled individually and independent of each other (treated as two independent switch sections).
If the HSB Dual Baseband option for HSB systems is specified, the RPS will refrain from doing any Rx switching. In this case the external equipment (mux) will duplicate the
line traffic input onto two input ports, and the RR equipment will duplicate the RF signal onto two Rx branches (receiver-demodulator-baseband) and make both data streams
available on the two output ports. The RPS will only switch on the Tx side.
Function Button: Set Setting of Switch Section parameters
Manual switch/restore requests are considered local to the station and, for a given antenna direction, involves transceiver RF switch for Tx and baseband align-
ment switch for Rx. This operation is implemented as a bidirectional locked switch.
Pull down Menu: Active Channel Choose channel to carry traffic. Alternatives: 1, 2
Switch Section Status (Hot Stby)
Displays the Switch Section status.
Start Polling Start the polling function. The polling sequence will continue until Stop Polling is selected
Start Polling Start the polling function. The polling sequence will continue until Stop Polling is selected
Aligned switching will be performed if possible.The active channel which is to be protected, is polled for data alignment status. When the data stream from the
protector demodulator is aligned with the data stream from the active channel demodulator, an errorless switchover is performed.
In case the alignment process fails, a forced switchover may be performed dependent upon active criteria and configuration settings for the RPS system (if a
continuity criterion is active initially the RPS will not check for alignment but immediately select the forced switchover option)
When the criteria for protecting the channel are no longer active the channel will be restored if the RPS is set to revertive mode.
Function Button: Set Setting of Switch Section parameters
Non-Revertive mode
An active channel set to standby will continue to be in standby mode even if all criteria are deasserted,
until another active channel needs protection or the protecting channel becomes degraded, in which
case a restore operation is performed.
Switch Channel (Freq. Div.)
Pull down Menu: Channel Number to Protect Choose channel to protect. Alternatives: 1, P
If "P" is selected means that the protected channel is reverted to its regular state unless the
degradation is at or above the level defined by "No Lock Revert Limit"
Alignment Alternatives:
Aligned
Checks that the signal from protection channel is aligned with the signal from the regular channel
before the switch operation is performed. If no alignment is achieved within a certain period of time,
the switch operation is aborted.
Forced
Performs an immediate switch operation (no alignment)
No Lock Revert Limit Revert limit for a manually switched channel. Only applicable if "Switch Type" is Nolock.
Alternatives: LOWRF, EW, LBER, HBER, OOS, RXINPUT
Switch Section Status (Freq. Div.)
Displays the Switch Section status.
Start Polling Start the polling function. The polling sequence will continu until Stop Polling is selected
Start Polling Start the polling function. The polling sequence will continu until Stop Polling is selected
The Frequency page displays the frequency settings for all transceiver units in the same antenna direction.
Pull-down menu settings Selected plan Select the correct Frequency plan
Description:
Click on the page tabs to explore the individual functionality.
Miscellanous
Function Buttons: Upload Upload the configuration from the NE to your local computer as a safety copy
Backup Make a backup file (locally on the NE) of the current configuration.
Function Buttons: Browse Browse your local computer for a configuration file to download to the NE
The configuration from the replaced SU will be downloaded to the new SU. In addition the licenses from the replaced SU will be temporary enabled for a maxi-
mum period of 90 days in addition to any existing licenses on the new SU. These temporary licenses can be used while ordering new license keys from Nera.
Function Buttons: Browse Browse your local computer for a configuration file to download to the NE
Download Downloads the selected configuration file to the NE and replaces the current NE configuration file
Software
The Software page is divided in 2 sub-pages: SU SW Versions and SW Download. Click on the page tabs to explore the individual functionality.
SU Software Versions
When new software is downloaded to the element it will initially be set in inactive state (Active no).
Click the "Switch software" button to swap the Software Package. The system will perform a warm start when software is swapped.
Note! If only one software package is present on the Network Element, only one table will be visible in "Overview" in the screenshot above.
Function Buttons: Switch Software Swap between the two available software packages.
Note! Bit error may occur when software packages are switched.
Note! It is recommended that you clear the file cache in your web browser after a software switch. The reason for this is to make sure that the browser
receives the correct files.
Complete state
If all the required files are present and the checksum is OK, the software package is in Complete state.
Compatible state
Each software package contain a list of hardware compatibility requirements. This consists of a list of hardware modules with an accompanying version range. If
all the detected modules in the system are found in this list, and their versions fall within the specified ranges, the software package is compatible.
Software Download
A software release generally consists of several ".tar" files. When a new software version is downloaded to the NE, it is recommended to start with the ".tar" file
with the lowest number (e.g. "SW-EVOULUTION-APP-R1A00_1.tar" and then "SW-EVOULUTION-APP-R1A00_2.tar" etc). Follow the instructions on the screen.
If there is an inactive software package on the NE already, this software package will be overwritten.
Dependent on the system configuration it is not always necessary to download all ".tar" files in the actual software release. After downloading the first file, you will
be prompted for the next file to download, if required. When all required files are downloaded, the following message will be displayed:
The downloaded software is still inactive. Activation of new software is performed from the "SU SW Versions" page.
Function Buttons: Browse Browse your local computer for "Tar" files to download to the NE
Download Downloads the selected "Tar" file and builds software hierarchy on the NE
Element
The Element page is divided in 6 sub-pages: Licenses, Time and SNTP, SNMP, Web and Unconfigured Boards. Click on the page tabs to explore the indi-
vidual functionality.
Licenses
A payload license may be required to enable traffic on the equipment. The license can be permanent or time-limited.
A Network Element can have several licenses installed, enabling different functions, such as transmission capacity, ethernet traffic and ethernet wayside traffic.
For payloads below 80 Mb/s, no payload licence is required.
The License Key is a 40 character alpha numeric string.
The system also provides SNTP functionality for syncronization of all clocks in the network. This function requires an SNTP server, either locally or on the internet
(requires internet connection).
This screenshot shows the Time and SNTP page with SNTP not selected.
Function Buttons: Time Status Get Get Time Status
SNTP Configuration Set Click this button when the SNTP button has been unchecked, for returning to "Manual time setting"
Synchronize with computer Synchronizes the NE time setting with the local computer clock
Check Box: SNTP enabled Enables SNTP when the "Set" button is pushed. The SNTP IP address must be entered
Input Field: SNTP Server's IP-address Input the IP address to the SNTP server
Pull down Menus: Threshold-level for stratum alarm The stratum level indicates the accuracy of the SNTP server clock. Highest accuracy is level 1.
Alternatives: 1 to 15. Default value 2.
Tip! If stratum alarm occurs frequently, the threshold-level should be set to lower accuracy
(higher number). This will not influence the equipment performance.
Poll Interval (seconds) Determins the intervals between each clock update.
Alternatives: 64 to 1024.
SNMP
Simple Network Management Protocol (SNMP) is an application layer protocol that facilitates the exchange of management information between network devices.
SNMP enables network administrators to manage network performance and find and solve network problems.
SNMP is a simple request/response protocol. The network-management system issues a request, and managed devices return responses.
Definitions
Community Strings
Function Buttons: Set Set Community Strings
Check Boxes: Global Polling System wide status poll. Enable/Disable background status polling for all web pages containing status
information. You have the opportunity to override this setting. The overridden setting will only occur in the
page where you override the settings and only last as long as the page is active. Default : OFF
Alarm Polling System wide alarm poll setting. Will display the highest alarm severity in the system, on the bottom of the
page. Default: OFF
Housekeeping Polling System wide configuration polling. Will give notification if the system configuration has been changed.
Default: OFF
Note! Poll settings are not persistent across sessions, i.e. when the browser window is closed the poll settings will go back to their defaults.
Unconfigured Boards
A list of any unconfigured boards and units.
Man At Work
Routing
The Routing page is divided in 7 sub-pages: General Settings, Active Routes, Static Routes, Software, Element, Routing and Network. Click on the page
tabs to explore the individual functionality.
General Settings
The general settings page allows the user to control the general use of the OSPF and RIP 1 and 2 protocols for the NE. Enabling of protocols on specific inter-
faces are performed in the Rip Interfaces and OSPF Interfaces property pages.
Active Routes
This is a list of currently active routes in the routing table. These are the routes that IP forwarding is based on. Inactive routes are not shown.
Static Routes
Edit static routes regarding IP Routing using this page.
Function Button: Add Add a static route
Pull Down Menus: Interface Gateway interface if specified. Default Any interface
Gateway Route gateway in x.x.x.x notation if needed. Note! Gateway must be present if interface is set to Any.
Pull Down Menus: Interface The name of the interface being configured. Select between the alternatives: Io#, eth#, DIR0@#
Metric The metric associated with the interface. Possible values: 0-16
RIP Version The version of RIP to run on an interface. (RIP v. 1 or RIP v. 2). Alternatives: 1, 2
Note! When running RIP v.1 on an interface, limitations in the RIP v.1 protocol will restrict which routes may be
announced through this interface
OSPF Interfaces
This configures which interfaces to run OSPF on and the parameters used for each interface.
Note! In order to edit the OSPF areas settings, the OSPF protocol must be disabled in the General Settings page.
Function Button: Add Add an Interface to run OSPF on
Pull Down Menus: Interface Id The name of the interface being configured. Select between the alternatives: Io#, eth#, DIR0@#
Transmit delay The estimated transmit delay through this interface in seconds
- Default value is 1 second.
- Possible values: 1 - 65535.
Designated Router Priority Indicates the current NEs reliability as a designated router (DR).
Higher values = higher reliability.
- 0 = cannot be DR.
- Possible values: 0 - 255.
Retransmit Interval
Hello Interval The interval between OSPF hello packets on this interface.
Router Dead Interval The time before declaring a link down in the absence of hello packets
OSPF Areas
This configures OSPF areas for this router.
Note! In order to edit the OSPF areas settings, the OSPF protocol must be disabled in the General Settings page.
Function Buttons
OSPF Areas: Add Add/Edit OSPF area
Input Fields: Area Id The ID of the area. Either in x.x.x.x notation or plain number
Default Cost Sets the default cost for this area. Possible values: 0-65535
Virtual Links
This configures OSPF virtual links for this router.
Pull Down Menus: Transit area The ID of the area to use as transit area for the link
Input Field: Router Id The ID of the backbone router on the other end of the link
Network
Setting of Interface IP address
Pull Down Menus Physical Position Physical position of the unit where the performance measurements are performed
If Configuration, Fault or Performance are selected from the Menu bar, with the LIU Unit highlighted, the Configuration, Fault or Performance data for the LIU Unit
are displayed.
LIU Inventory
List of LIU Inventory including Software versions, Serial Number Article Code and Revision.
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
LIU Looping
Two different loops can be activated on the LIU. One loop at the customer interface side and one on the IFU Frame side.
The loop is activated by clicking the actual arrow. An active loop will turn red.
Only one loop can be active at the time. The active loop must be deactivated, by clicking the arrow, before the other loop can be activated.
A time out value must be selected for the loop.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
PRBS
A PRBS signal can be inserted instead of the regular traffic to test the LIU.
The LIU contains one PRBS Generator and two Checker. Only one Checker is active at the time. When one checker is enabled, by clicking the arrow on the
block diagram, the other will automatically be disabled.
The red arrow on the diagram indicates the Generator. The green arrow is the active Checker. The black arrow is the inactive Checker.
The Generator is started by clicking the Generator arrow on the block diagram. The arrow turns red.
Note! When the Generator is activated, traffic on this LIU will be broken.
Activate the uppermost Checker, to test the Customer Interface side of the LIU.
Note! A loop must be activated at the Customer interface side.
Activate the rightmost Checker, to test the IFU Basic Frame interface side of the LIU.
Note! A loop must be activated at the IFU Basic Frame interface side.
Function Buttons: Single Bit Error Inserts a single error bit in the Signal Frame. This is a helpful feature to check the system (check that the total
errors are increased by one when this button is pushed).
Checker Reset Resets the error counting on the Checker.
Get Gets Error Status
Start Polling Starts Error polling.
Stop Polling Stop Error Polling
Pull Down Menus: Generator Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
Checker Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
Input Fields: Send Trace string User defined ASCII string max. 15 characters
Receive Expected User defined ASCII string max. 15 characters
AIS
The Path Trace functionality and the AIS (Alarm Indicator Signal) functionality are used to verify that the received signal frames are the frames we want to receive
(correct routing, frequency alignment. . . . ). This is done by either inserting a fixed byte or a user defined ASCII string in the J0 slot in the RSOH. This is done
from the path trace sheet. The radio that receives the signal frames must have the same Trace string (J0) defined in the AIS insert sheet. If there is a mismatch,
an AIS can be inserted (if configured). An AIS can also be inserted if the HBER threshold is exceeded (configured on the RIU).
Check Boxes: Insert AIS on Trace Identifier Mismatch (TIM) When this box is checked, an Alarm Indicating Signal is inserted when there is a
mismatch between the Path Trace string or fixed byte sent and the expected Receive
signal
Remove Delay Enabled Remove AIS delay
Pull Down Menu: AIS remove delay (in sec) Setting of AIS remove dela: 0-300 seconds
If Configuration, Fault or Performance are selected from the Menu bar, with the LIU Unit highlighted, the Configuration, Fault or Performance data for the LIU Unit
are displayed.
LIU 25xE1, Inventory
List of LIU 25xE1 Inventory including Software versions, Serial Number Article Code and Revision.
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
LIU 25xE1, Looping
50 loops can be activated on the LIU 25xE1 Unit, two for each E1 Port (Near end and Far end).
Note! When a loop is activated, traffic on the actual port will be broken.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
LIU 25xE1, PRBS
A PRBS signal can be inserted instead of the regular traffic to test the LIU 25xE1 Ports.
The LIU 25xE1 contains one PRBS Generator and two Checkers. Only one Checker is active at the time. When one checker is enabled, by clicking the arrow on
the block diagram, the other will automatically be disabled.
A red arrow on the diagram indicates an active Generator. A green arrow is an active Checker.
The Generator is started by clicking the Generator arrow on the block diagram. The arrow turns red.
Note! When the Generator is activated, traffic on the actual port will be broken.
Activate the rightmost Checker, to test the IFU Basic Frame interface side.
Note! A far end loop must be activated.
Function Buttons: Generator Set Setting of Generator parameters
Checker Set Setting of Checker parameters
Single Bit Error Inserts a single error bit in the Signal Frame. This is a helpful feature to check the system (check that the total
errors are increased by one when this button is pushed).
Checker Reset Resets the error counting on the Checker.
Get Gets Error Status
Start Polling Starts Error polling.
Stop Polling Stop Error Polling
Pull Down Menus: Port The port where the PRBS signal is to be inserted. Alternatives: 1 to 25.
Generator Pattern Signal pattern selection. Available pattern: PRBS 2*23-1
Checker Pattern Ssignal pattern selection. Available pattern: PRBS 2*23-1
If Configuration, Fault or Performance are selected from the Menu bar, with the Gigabit Ethernet Interface Unit highlighted, the Configuration, Fault or Perform-
ance data for the Gigabit Ethernet Interface Unit are displayed.
Gigabit Ethernet Unit, Inventory
List of Gigabit Ethernet Unit Inventory including Software versions, Serial Number, Article Code and Revision.
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
Gigabit Ethernet Unit, Looping
Two different loops can be activated on the Gigabit Ethernet Unit (Near end and Far end).
Note! When a loop is activated, traffic on the Gigabit Ethernet Unit will be broken.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
Gigabit Ethernet Unit, Ports
All ports can be configured individually
Port 1 to 3 can be configured as 10/100 Base-T (half or full duplex).
Port 4 can be configured as 10/100/1000 Base-T (half or full duplex).
Port 5 is intended for optical interface by means of an SFP module (1000 Base-X)
Note! Only one 1000 Mb/s port can be enabled at the time.
Speed Auto, 10/100 Half/Full Duplex for Port 1 to 3, and in addition for Port 4; 1000 Full Duplex. Port 5, SFP, is
1000 Base-X only.
Ingress rate Stepwise limits from 500 kb/s to 83 Mb/s or Not Limited (100 Mb/s or link capacity) for Port 1 to 3. Stepwise
from 500 kb/s to 125 Mb/s or Not Limited (link capacity) for Port 4 and 5.
See Ethernet page; Ingress rate limiting
Check Boxes: Flow control Enable/Disable for Port 1 to 4. This is available only when the Ingress Rate is activated. Note that Burst
drop mode must be selected for proper operation. See Ethernet page.
Link loss forwarding Enable/Disable Link loss forwarding. See description below
Note! Link Loss Forwarding must be enabled on both corresponding Network Elements
In the figure below, an Ethernet link loss will be detected on NE2. A LLF signal will be sent to NE1 and the Ethernet port will be shut down.
In the figure below, a loss of signal will be detected on both Network Elements and the Ethernet ports will be shut down.
Pull Down Menus: MAC address aging timeout Select MAC address aging timeout. Options; 15 sec, 5 min or Learning off.
Ingress rate limiting Select Ingress rate limiting drop mode.
Options; Continous drop or Burst drop. Ref appendix; Gigabit Ethernet Configuration
Gigabit Ethernet Unit, QoS (Quality of Service)
Used for traffic prioritizing.
Function Buttons: Set Set selected parameters
Pull Down Menus: QoS priority scheme The QoS priority scheme has 4 options: OFF, Port, VLAN, DSCP/TOS
OFF
All traffic has equal priority.
DSCP/TOS (IPv4/IPv6)
DSCP is represented by 64 decimal values (0-63), which is mapped into four traffic queues. Click the actual
decimal value in the screen and select required priority from pull down menu.
Fair queueing
An 8, 4, 2, 1 weighting is applied to the four priorities. This approach prevents the lower priority frames from
being starved out with only a slight delay to the higher priority frames.
Strict queueing
All top priority frames egress for a port untill that priority's queue is empty. Then the next lower priority
queue's frames egress, etc. This ensures that all high priority frames egress as soon as possible.
Port (Ethernet input ports)
If Configuration, Fault or Performance are selected from the Menu bar, with the RIU Unit highlighted, the Configuration, Fault or Performance data for the RIU Unit
are displayed.
RIU, Inventory
List of RIU Inventory including Software versions, Serial Number Article Code and Revision.
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
RIU, Looping
One loop can be activated on the RIU.
Note! When the loop is activated, traffic on this RIU will be broken.
Before activating the loop, the Time Out Value must be selected.
The loop is activated by clicking the arrow and the symbol will turn red.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
RIU, BER Threshold
Setting of thresholds for Bit Error Rate alarms
Pull Down Menus: HBER Selection of High Bit Error Rate Threshold.
Alternatives: 1.0E-3, 1.0E-4, 1.0E-5, 1.0E-6 or SES (Severely Errored Seconds)
Check Box: Insert AIS on HBER Insert AIS signal if HBER occurs
FAN
Displays the Fan status.
Fan 1 is the fan nearest to the Front Panel.
Fan 1 and 2 are used for temperature control of the Plug-in Units.
Fan 3 is used for temperature control of the Motherboard.
If Configuration, Fault or Performance are selected from the Menu bar, with the Fan Unit highlighted, the Configuration, Fault or Performance data for the Fan Unit
are displayed.
If Configuration, Fault or Performance are selected from the Menu bar, with the EOW Unit highlighted, the Configuration, Fault or Performance data for the EOW
Unit are displayed.
EOW, Inventory
List of EOW Inventory including Software versions, Serial Number Article Code and Revision.
EOW
Engineering Order Wire can be inserted in dedicated SOH (ETSI) / TOH (ANSI) bytes, or the NOH (Nera Overhead) channels. The NOH channels are not avail-
able when Direction: Line (Traffic over Line Interface Unit) is selected.
The check box "Enable" must be checked for setup of EOW connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for EOW traffic.
Main Traffic Channel Selection of Main Traffic Channel. Dependent on the number of Regular Channels
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
4 Wire interface:
This is a balanced, galvanic isolated interface meant to interface various types of equipment. Input- and output- gain can be adjusted over a wide range.
- Port input level (dBm): Adjustable range: 4dBm to -10.0dBm.
- Port output level (dBm): Adjustable range: 4dBm to -10.0dBm.
Pull Down Menus: Remote (4 Wire) Port input level Adjustable range: 4dBm to -10.0dBm.
Remote (4 Wire) Port output level Adjustable range: 4dBm to -10.0dBm.
Check Boxes: Enable analog port Enabling of the analog ports. If the check box is unchecked, the analog ports are
disabled.
Transit other equipment 1 to other equipment 2 By checking this box, the signal is through conncted between Port 2 and Port 3 on the
EOW Unit.
EOW, G.703 on Port 2
G.703 can be inserted in dedicated SOH (ETSI) / TOH (ANSI) bytes, or the NOH (Nera Overhead) channels. The NOH channels are not available when Direc-
tion: Line (Traffic over Line Interface Unit) is selected.
The check box "Enable" must be checked for setup of G.703 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for G.703 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of G.703 parameters
The check box "Enable" must be checked for setup of G.703 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for G.703 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of G.703 parameters
The check box "Enable" must be checked for setup of 64kb/s connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The byte will turn yellow
indicating that the byte is selected for 64kb/s traffic.
G.703 Co-directional
The check box "Enable" must be checked for setup of G.703 Co-directional connections.
Enables the HDLC device to send data between Port 3 and the SU, which provide two different functions
Terminal-server function
This function provide access to Port 3 from a telnet-connection on the Supervisory Unit. Ex. connect a PC to the SU and start the telnet application on the PC and
connect to the targets IP address and TCP port #. This will then provide some simple means to access and control other devices and units.
Main Traffic Channel Selection of Main Traffic Channel. Dependent on the number of Regular Channels
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of new parameters
Note! When a loop is activated, traffic on the EOW Port will be broken.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
EOW, PRBS
A PRBS signal can be inserted instead of the regular traffic to test the EOW Unit.
The EOW contains two PRBS Generators and two Checkers. Only one Generator and one Checker are active at the time. When one checker is enabled, by
clicking the arrow on the block diagram, the other will automatically be disabled.
The Generator is started by clicking the Generator arrow on the block diagram. The arrow turns red.
Note! When the Generator is activated, traffic on this Port will be broken.
Activate the uppermost Checker, to test the Customer Interface side of the EOW.
Note! A loop must be activated at the Customer interface side.
Activate the rightmost Checker, to test the IFU Basic Frame interface side of the EOW.
Note! A loop must be activated at the IFU Basic Frame interface side.
Function Buttons: Active Generator Set Sets parameters on the active generator.
Active Checker Set Sets parameters on the active checker.
Single Bit Error Inserts a single error bit in the Signal Frame. This is a helpful feature to check the system (check that the
total errors are increased by one when this button is pushed).
Active Checker Reset Resets the error counting on the Checker.
Get Gets Error Status
Start Polling Starts Error polling
Stop Polling Stop Error Polling
Pull Down Menus: Active Generator Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
Active Checker Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
If Configuration, Fault or Performance are selected from the Menu bar, with the 64kb/s Unit highlighted, the Configuration, Fault or Performance data for the
64kb/s Unit are displayed.
4x64kb/s Unit, Inventory
List of 4x64kb/s Unit Inventory including Software versions, Serial Number Article Code and Revision.
4x64kb/s Unit, Port 1 - G.703 Contra Directional
G.703 can be inserted in dedicated SOH (ETSI) / TOH (ANSI) bytes, or the NOH (Nera Overhead) channels.
The check box "Enable" must be checked for setup of G.703 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for G.703 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of G.703 parameters
The check box "Enable" must be checked for setup of G.703 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for G.703 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of G.703 parameters
The check box "Enable" must be checked for setup of G.703 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for G.703 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of G.703 parameters
The check box "Enable" must be checked for setup of V.11 connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The Byte will turn yellow
indicating that the byte is selected for V.11 traffic.
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of V.11 parameters
The check box "Enable" must be checked for setup of 64kb/s connections.
When SOH / TOH button is pushed, an SOH / TOH matrix is displayed. Available SOH / TOH bytes (white colour) can be selected. The byte will turn yellow indicating that the
byte is selected for 64kb/s traffic.
G.703 Co-directional
The check box "Enable" must be checked for setup of G.703 Co-directional connections.
Enables the HDLC device to send data between Port 3 and the SU, which provide two different functions
Terminal-server function
This function provide access to Port 3 from a telnet-connection on the Supervisory Unit. Ex. connect a PC to the SU and start the telnet application on the PC and connect to
the targets IP address and TCP port #. This will then provide some simple means to access and control other devices and units.
Port 4 - V.11
The check box "Enable" must be checked for setup of V.11 connections.
Enables the HDLC device to send data between Port 4 and the SU, which provide two different functions; Terminal-server function and Local Management connection.
See G.703 Co-directional description.
SOH / TOH
NOH
G.703 Co-directional
V.11
Function Buttons SOH / TOH Selection of available Section Overhead / Traffic Overhead byte
NOH Selection of Nera Overhead Channel. Alternatives: Channel 1 or Channel 2
Set Setting of new parameters
Note! When a loop is activated, traffic on the 64kb/s Port will be broken.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
4x64kb/s Unit, PRBS
A PRBS signal can be inserted instead of the regular traffic to test the 4x64kb/s Unit.
The 4x64kb/s Unit contains two PRBS Generators and two Checkers. Only one Generator and one Checker are active at the time. When one checker is enabled,
by clicking the arrow on the block diagram, the other will automatically be disabled.
The Generator is started by clicking the Generator arrow on the block diagram. The arrow turns red.
Note! When the Generator is activated, traffic on this Port will be broken.
Activate the uppermost Checker, to test the Customer Interface side of the 4x64kb/s Unit.
Activate the rightmost Checker, to test the IFU Basic Frame interface side of the 4x64kb/s Unit.
Note! A loop must be activated at the IFU Basic Frame interface side.
Function Buttons: Active Generator Set Sets parameters on the active generator.
Active Checker Set Sets parameters on the active checker.
Single Bit Error Inserts a single error bit in the Signal Frame. This is a helpful feature to check the system (check that the
total errors are increased by one when this button is pushed).
Active Checker Reset Resets the error counting on the Checker.
Get Gets Error Status
Start Polling Starts Error polling.
Stop Polling Stop Error Polling
Pull Down Menus: Active Generator Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
Active Checker Pattern Setting of signal pattern. Available pattern: PRBS 2*23-1
If Configuration, Fault or Performance are selected from the Menu bar, with the Mother Board highlighted, the Configuration, Fault or Performance data for the
Mother Board are displayed.
METRO
Mother Board, Inventory (METRO)
List of Mother Board Inventory including Software versions, Serial Number Article Code and Revision.
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
Mother Board, Path Trace (METRO)
The Path Trace functionality and the AIS (Alarm Indicator Signal) functionality are used to test that the received STM-1 frames are the frames we want to receive
(correct routing, frequency alignment. . . . ). This is done by either inserting a fixed byte or a user defined ASCII string in the J0 slot in the RSOH (Send). The
radio that receives the STM-1 frames must have the same Trace string (J0) defined. If there is a mismatch, an AIS can be inserted. An AIS can also be inserted
if the HBER threshold is exceeded.
Check Boxes: Enable send Enable send Trace string
Enable receive Enable Receive Trace string
Input Fields: Send Trace string User defined ASCII string max. 15 characters
Receive Expected User defined ASCII string max. 15 characters
Mother Board, AIS (METRO)
The Path Trace functionality and the AIS (Alarm Indicator Signal) functionality are used to verify that the received STM-1 frames are the frames we want to re-
ceive (correct routing, frequency alignment. . . . ). This is done by either inserting a fixed byte or a user defined ASCII string in the J0 slot in the RSOH. This is
done from the Path Trace sheet. The radio that receives the STM-1 frames must have the same Trace string (J0). If there is a mismatch, an AIS can be inserted.
An AIS can also be inserted if the HBER threshold is exceeded.
Check Boxes: Insert AIS on Trace Identifier Mismatch (TIM) When this box is checked, an Alarm Indicating Signal is inserted when there is a
mismatch between the Path Trace string or fixed byte sent and the expected Receive
signal.
Remove Delay Enabled Remove AIS delay
Pull Down Menu: AIS remove delay (in sec.) Setting of AIS remove dela: 0-300 seconds
Pull Down Menus: Time Out Value Setting of Time Out Value for IFU Test
Input Field: Log Log available for user defined text input
Function Button: Set Log Saves the text entries to the Log
Mother Board, IFU System Test (XPAND)
By clicking the TEST buttons on the screenshot below, direct access to the Looping /PRBS pages on the "E1" and RIU units is available. By clicking the corre-
sponding "looping arrows", loops can be set for testing purposes.
Pull Down Menus: Time Out Value Setting of Time Out Value for IFU Test
If Configuration, Fault or Performance are selected from the Menu bar, with the RIU Unit highlighted, the Configuration, Fault or Performance data for the RIU Unit
are displayed.
ODU, Inventory
List of ODU Inventory including Software versions, Serial Number Article Code and Revision.
Input Field: Log Log available for user defined text input
Note! In XPIC configurations it is highly recommended that the ATPC function is enabled.
The values in the example below are typical and will vary according to the calculated values from the system propagation.
Input Field: MTPC
Output Level ATPC is disabled and constant manual output level is selected.
ATPC Output level is automatically adjusted according to the specified ATPC settings.
Input Reference Level -The desired input level. If ATPC is enabled on the remote transmitter, the remote transmitter will
regulate its output power such that the received input level at this receiver is equal to the reference
level.
See table below for recommended Input Reference Level.
Max. Output Level -The Transmitters maximum output level (dBm)
Default Output Level -The Transmitters default output level (dBm). The output power to be used if ATPC regulation loop fails
(The "ATPC" alarm is raised).
Before activating the loop, the Time Out Value must be selected.
The loop is activated by clicking the arrow and the symbol will turn red.
Pull Down Menus: Time Out Value Setting of loop Time Out values; Week, Day, Hour, Min, Sec
ODU, Analogues
List of analogue levels
Fault
In the Fault menu the alarm status can be monitored.
Different functions are provided for acquisition, presentation and storage of alarm data:
Current alarm status and historical alarm information can be collected from the network element and presented in different user interfaces.
Historical alarm data can be logged into a database system.
Alarm information can be gathered by two different methods:
Polling: Regularly requests alarm update information from the NE.
Get: Get the current alarm status
Colours and symbols are used to indicate the alarm severity of the network element. Each alarm severity class has a corresponding colour and symbol.
Note! If you from the Fault menu click one of the IFU Frame Units, the Fault status for that particular Unit is displayed.
Active
Displays a list of all active alarms.
Note! If you from the Active menu click one of the IFU Frame Units, the active alarm status for that particular Unit is displayed.
Function Buttons: Apply Filter Filter alarm list according to selections.
Set Severity Accept selected severity level on selected alarms.
Block Block alarms that are checked in the list above.
Blocked Alarms View Blocked alarms.
Get Get Alarm Status
Start Polling Start the polling function. The polling sequence will continu until Stop Polling is selected
Stop Polling Stops Polling sequence
Print Table Send the Alarm List to your default printer.
Pull Down Menues Alarm Filter; Physical Position Select all or alarms from a specific unit
Alarm Filter; Severity Filter alarms according to severity level.
Alarm Filter; State Filter alarms according to alarm state
Severity Select severity level for selected alarms
All
Displays a list of all alarms.
Note! If you from the All menu click one of the IFU Frame Units, the alarm status for that particular Unit is displayed.
Function Buttons: Apply Filter Filter alarm list according to selections.
Set Severity Accept selected severity level on selected alarms.
Block Block alarms that are checked in the list above.
Blocked Alarms View Blocked alarms.
Get Get Alarm Status
Start Polling Start the polling function. The polling sequence will continu until Stop Polling is selected
Stop Polling Stops Polling sequence
Print Table Send the Alarm List to your default printer.
Pull Down Menues Alarm Filter; Physical Position Select all or alarms from a specific unit
Alarm Filter; Severity Filter alarms according to severity level.
Alarm Filter; State Filter alarms according to alarm state
Severity Select severity level for selected alarms
Event Log
The Event Log is a log that displays all events on the Network Element.
Pull Down Menu Log Mode Select Log Mode. Alternatives: Wrap when full or Halt when full. Note! If "Halt when full" is selected, new events
will not be logged when Event log is full.
Input Fields: Entries Type in the entry number to be deleted from the Events list
Performance
Different functions are provided for acquisition, presentation and storage of performance data. Cumulative measurements, Registers (15Min, Day and Month) and
Thresholds can be selected from the sub-menu.
Note! If you from the Performance menu click one of the IFU Frame units, the Performance status for that particular Unit is displayed.
Definitions
Physical Pos Physical position of the unit where the performance measurements are performed
Source SOH bytes (ETSI)/TOH bytes (ANSI) allocated for system monitoring
Reg The sequence number of the performance register. Register 0 is the running measurement, register 1 is the latest completed measurement, ,
register 16 is the oldest completed measurement.
ES Errored Seconds
The number of one second periods with one or more errored blocks.
15Min measurements start at h:00:00, h:15:00, h:30:00 and h:45:00, where h denotes hour.
24Hour measurements start at each midnight (00:00:00).
Month measurements start at midnight at each month transition.
Note that the NE is using GMT time, such that the measurement start time is relative to GMT time and not to your PCs local time.
For 15Min measurements the NE keeps the 16 latest periods. For 24Hour and Month measurements only the latest period is kept.
Note that the running performance measurements will be reset due to a SW restart on the corresponding board/unit. E.g. restarting a Line Interface Unit will reset
all periodic measurements on that unit.
Measurement Types (Source)
B1 One byte of the SOH frame is allocated for regenerator section error monitoring. This B1 byte contains a Bit Interleaved Parity 8 (BIP-8) code
using even parity. The BIP-8 is computed over all bits of the previous STM-1 frame after scrambling and is placed in byte B1 of the current
frame before scrambling.
Parity: The number of parity errors detected.
Block: The number of blocks in which one or more parity errors are detected.
B2 Three bytes of the SOH frame is allocated for multiplex section error monitoring. The B2 bytes contain a Bit Interleaved Parity 24 (BIP-24) code
using even parity. The BIP-24 is computed over all bits of the previous STM-1 frame except for the first three rows of SOH and is placed in the
B2 bytes of the current frame before scrambling.
Parity: The number of parity errors detected.
Block: The number of blocks in which one or more parity errors are detected.
MS-REI The M1 byte of the SOH frame is allocated for multiplex section remote error indication. The M1 byte conveys the count of interleaved bit block
errors that have been detected by the BIP-24 (B2) at the remote multiplex site.
Parity: The number of parity errors detected.
Block: The number of blocks in which one or more parity errors are detected.
G.826 15 Min
G.826: ITU-T Recommendation defines standardized performance measurements.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
G.826 Day
G.826: ITU-T Recommendation defines standardized performance measurements.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
G.826 Month
G.826: ITU-T Recommendation defines standardized performance measurements.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
EC 15 Min
Error Count. Counts errors within the designated time cycle.
Function Buttons: Apply Filter Filter Error list according to selections.
Get Get Error Status
Start Polling Start the polling function. The polling sequence will continue until Stop Polling is selected
Stop Polling Stops Polling sequence
Print Table Send the Error List to your default printer.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
EC Day
Error Count. Counts errors within the designated time cycle.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
EC Month
Error Count. Counts errors within the designated time cycle.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
Cumulative
Cumulative measurements are counting the number of errors since the last counter reset. These counters can be manually reset, and will also be reset by a SW
Restart of the corresponding board/unit.
G.826
G.826: ITU-T Recommendation defines standardized performance measurements.
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
Error Count
Counts errors comulatively.
Function Buttons: Apply Filter Filter Error list according to selections.
Reset Resets selected Errors
Print Table Send the Error List to your default printer.
Get Get Error Status
Start Polling Start the polling function. The polling sequence will continue until Stop Polling is selected
Stop Polling Stops Polling sequence
Pull Down Menues Filter; Physical Position Select all or errors from a specific unit
Filter; Source Filter errors according to type
Threshold
Thresholds can be configured such that alarms are generated when performance measurements exceed the specified limits. Note that performance measure-
ments are evaluated continuously through the measurement period, and an alarm is raised immediately when the threshold value is exceeded. An active per-
formance threshold alarm is not cleared before a measurement period has completed with a measurement value less than the corresponding threshold.
Function Buttons: Apply Filter Filter Error list according to Source selection.
Print Table Send the Error List to your default printer.
Function Buttons: Apply Filter Filter Error list according to Source selection.
Cumulative, Display Displays a graph showing cumulative measurements of the RF input and RF output levels since last reset (clear).
Cumulative, Clear Resets the Cumulative measurement graph
Time Series, Display Displays a graph showing the RF input and RF output levels as a function of time. Only the last 15 minutes
are shown. A total of 2 time series can be active simultaneously.
Time Series, Start/Stop Starts/Stops the time series registration.
Pull Down Menu: Physical Position Select all or readings from a specific ODU
Filter; Source Select source
Cumulative Plot, RF Input Level
Cumulative Plot, RF Output Level
Time Series Plot, RF Input Level
Time Series Plot, RF Output Level
Security
The Security Manager Module handles the user administration for the Evolution system. This module maintains the database of all the available users in the
system and provides interface for accessing the system. Based on the privilege level, each user shall be provided with the necessary access permission to
interact with the system.
Dependent on the user privileges, different pages in the Security Session are visible (see table below the screenshot).
User privileges
ADMIN User Administration
User Sessions
Change Password
Security Settings
Log
User name 4-32 characters alphanumeric (A-Z, a-z, 0-9 not case sensitive)
Privilege
Passive: System monitoring
Active: Communication settings and data collection
Master: All commands including software download
Admin: All commands incl. software download and administration of user accounts
Remove User
Click the Check box for the actual User and push the "Remove User" Button.
User Sessions
List of all in-logged Users
Change Password
Check Box: Enable IP Range When this box is checked, only IP addresses within the range can access the NE.
Log
Log of all security operations on the NE. Maximum events: 1000. Clear the list by pushing the "Purge Log" button.
B4065 Rev. C
This manual is the property of Nera Networks AS. No parts of the manual may be copied, rewritten or distributed to
third parties without the written permission from Nera Networks AS.
In addition to the WEB
edition, the manual is
available in paper
format:
or in PDF format
If you don't have Adobe Acrobat Reader installed on your computer, you can download it below.
General This part gives a general overview of the Evolution Series equipment
Operation Describes how to operate the system with emphasis on the Evolution Series Manager
It is impossible to make a block schematic that covers all possible faults, therefore the following block-diagrams
only cover the most common problems.
Potentional problems are also related to installation of IFU-ODU cables and connectors. Water penetration,
lightening, or mechanical stress, may give IFU-ODU cable-problems. Sometimes it is difficult to find the reason
for the problem since a faulty cable, connector, power supply and different ODU-faults are giving exactly the same
alarm-picture in Evolution Manager. Normally when the link connection is lost, the alarm-information from the
remote station is also lost.
Check if the IFU-ODU cable is shorted or open, by measuring the resistance on the IFU-side of the cable. It is
also recommended to measure -48 V on the IFU connector as well as on the ODU side of the cable.
Whenever unscrewing the connector on the ODU, make sure that it is always reconnected properly and protected
from water penetration, by using the rubber sleeve or vulcanizing tape.
Note! Check all cable connections and that all units are completely seated in the IFU Basic Frame housing
before further troubleshooting is performed.
A red LED indicates alarm status on the unit. A blinking red LED indicates that the speciffic unit is placed in
wrong slot according to "Unit Housekeeping".
Complete LED description for each unit is described in section General/System Overview/IFU Overview.
In order to show all plug-in and AUX units 3 different IFU configurations are shown.
Click on the Unit below which has red LED alarm indication.
Note! The RIU has two front LEDs. Click on the LED with alarm indication.
EOW
4x64kb/s
SU
LIU Electrical
LIU Optical
RIU Left LED
RIU Right LED
FAN/IFU Basic
LIU 25xE1
Gigabit Ethernet
Unit Replacement
The new unit must have exactly the same unit code (Code:) as the unit to
be replaced.
The unit revision (Rev:) is on the format "R1A" (revision 1A). The new unit
must have the same or higher digit (1) on the revision tag to be compatible
with the one to be replaced. The letter (A) is not significant for
interchangeability. See a typical label below:
The Supervisory Unit stores a copy of the configuration and SW for the
different units. If a unit is replaced, the configuration will be automatically
downloaded from the Supervisory Unit to the new unit.
Note! This equipment contains components which are sensitive to
"ESD" (Electro Static Discharge). It is therefore essential that whenever
disassembling the equipment and/or handling PC boards, special
precautions to avoid ESD are made. These precautions include personnel
grounding, grounding of work bench, grounding of tools and instruments as
well as transport and storage in special antistatic bags and boxes.
IFU Basic Frame Replacement
Note! When a complete IFU Basic Frame is replaced, the traffic
through this IFU will be broken.
1. Unplug the power connector(s) on the RIU unit(s).
2. Disconnect all cables on the IFU front carefully. Mark all cables to
ensure that the cables can be reconnected to the correct terminals on
the new IFU.
3. IF the IFU is mounted in an equipment rack, unscrew the IFU from the
rack (four screws).
4. Pull the IFU out carefully.
5. Remove all plug-in units except the Fan unit (the FAN unit is part of the
IFU Basic Frame).
Replacement
1. Replace the plug-in units in the spare IFU Basic Frame.
2. Insert the new IFU in the Equipment rack (if rack mounted) carefully.
Note! If the IFU is part of a system with more than 2 channels, make
sure that the plate, covering the IFU rear connectors, is removed and
slide the IFU to enter the corresponding connectors in the IFU shelf,
without the use of excessive force.
3. Fasten the four screws.
4. Reconnect the front cables.
5. Reconnect the power cable(s).
IFU Units
Note! If the Radio system is protected (1+1, 2+1 etc.), manually
switch the protection switching to the functioning channel (see
Configuration/RPS/Manual Switch) before a RIU carrying traffick, is
removed from the IFU. Otherwise the traffic can be broken.
For SU replacement, see paragraph SU Replacement.
1. Unplug all cables on the unit to be replaced.
2. Unscrew the two "finger" screws that secure the unit to the IFU. A
screwdriver may be used if necessary to unscrew the screws.
3. Remove the unit carefully from the IFU by pulling the screws.
Replacement
1. Insert the new unit carefully. Ensure that the unit enters the guides
inside the IFU and gently press the unit to enter the internal connectors
without the use of excessive force.
2. Fasten the two screws with your fingers. Do not use a screwdriver.
3. Reconnect all cables.
SU Replacement
In addition to the steps in the paragraph above, it is important that the
correct system configuration is reloaded from a backup file when the SU is
replaced by a spare unit. (See Operation Section; Evolution
Manager/Feature Description/Configuration/Backup)
Evolution Series
User Manual
Appendices
B4065 Rev. C
This manual is the property of Nera Networks AS. No parts of the manual may be copied, rewritten or distributed to
third parties without the written permission from Nera Networks AS.
In addition to the WEB
edition, the manual is
available in paper
format:
or in PDF format
If you don't have Adobe Acrobat Reader installed on your computer, you can download it below.
General This part gives a general overview of the Evolution Series equipment
Operation Describes how to operate the system with emphasis on the Evolution Series Manager
Element Alarms
Perceived
Alarm Name Alarm Info Source
Severity
SW LICENCE One of the licenced features will expire within 10 days, or has
EXPIRES WARNING /ne
already expired
SW LICENCE
INVALID Licence file is invalid or corrupt WARNING /ne
SW LICENCE
TEMPORARY All licences are temporary since SU has been replaced WARNING /ne
RPS MANUAL
SWITCHING A manual RPS switching is active INFO /ne
RPS CH1 ON
PROTECTION Channel1 is using the protection channel INFO /ne
RPS CH1
ACTIVE Rx System is receiving on Channel 1 (HSB only) INFO /ne
RPS CH2
ACTIVE Rx System is receiving on Channel 2 (HSB only) INFO /ne
RPS CH1
ACTIVE Tx System is transmitting on Channel 1 (HSB only) INFO /ne
RPS CH2
ACTIVE Tx System is transmitting on Channel 2 (HSB only) INFO /ne
RPS SET TX /ne/frame-x/slot-
Setting of mute Tx signal on ODU failed MAJOR
MUTE FAILED x/ODU
RPS CHAN
NOT ALLIGNED RPS receive switch failure due to no alignment MAJOR /ne/frame-x
The SU has been without power for more than 24 hours and lost
RTC ALARM the power for the real time clock (RTC), or the RTC has been set /ne/frame-1/slot-
WARNING
to a date in the past 1/su
IFU Alarms
Perceived
Alarm Name Alarm Info Source
Severity
ILLEGAL SLOT
POSITION One or more boards have been placed in an illegal slot position. WARNING /NE/frame-x
One or more new boards have been inserted into slots where they
NEW BOARD have not been configured. The alarm indicates that the
DETECTED WARNING /NE/frame-x
housekeeping should be run in order to configure the new boards
/ne/frame-
Signal from plug-in unit to IFU Basic Frame missing (transmit x/ifu/Ch.1
AIS-INSERT CRITICAL
direction) /ne/frame-
x/ifu/Ch.2
/ne/frame-
x/ifu/Ch.1
RX FAILURE Signal from RIU to IFU Basic Frame missing (receive direction) MAJOR
/ne/frame-
x/ifu/Ch.2
/ne/frame-
x/ifu/Ch.1
/ne/frame-
x/ifu/Ch.2
LOF STM-1 / STS-3 Loss Of Frame CRITICAL
/ne/frame-
x/ifu/Ch.3
/ne/frame-
x/ifu/Ch.4
/ne/frame-
x/ifu/Ch.1
/ne/frame-
x/ifu/Ch.2
RS-TIM / TIM-S Regenerator section trace identifier mismatch MAJOR
/ne/frame-
x/ifu/Ch.3
/ne/frame-
x/ifu/Ch.4
/ne/frame-
MS-AIS (SDH) SDH multiplex section alarm indication signal / SONET Line x/ifu/Ch.1
WARNING
AIS-L (SONET) alarm indication signal /ne/frame-
x/ifu/Ch.2
/ne/frame-
MS-RDI (SDH) SDH multiplex section remote defect indication / SONET Line x/ifu/Ch.1
WARNING
RDI-L (SONET) remote defect indication /ne/frame-
x/ifu/Ch.2
PDH SYNCLOSS
ALARM OOF after alignment block CRITICAL /ne/frame-x/ifu/1
SU Alarms
Perceived
Alarm Name Alarm Info Source
Severity
TEST IN A test function is established on the unit. The test function can /ne/frame-1/slot-
PROGRESS WARNING
be a signal loop 1/su
CONFIGURATION /ne/frame-1/slot-
FAILURE Configuration of SU failed MAJOR
1/su
SDH Multiplex Section Alarm Indication Signal / SONET Line /ne/frame-1/slot-
MS-AIS / AIS-L WARNING
Alarm Indication Signal 1/su
SDH Multiplex Section Remote Defect Indication / SONET Line /ne/frame-1/slot-
MS-RDI / RDI-L WARNING
Remote Defect Indication 1/su
SDH Administrative Unit Alarm Indication Signal / SONET Path /ne/frame-1/slot-
AU-AIS / AIS-P WARNING
Alarm Indication Signal 1/su
HP-UNEQ / UNEQ- SDH Higher Order Path received Unequipped signal level / /ne/frame-1/slot-
P WARNING
SONET STS Unequipped 1/su
SDH Higher order Path Remote Defect Indication / SONET STS /ne/frame-1/slot-
HP-RDI / RDI-P WARNING
Path Remote Defect Indication 1/su
SDH Higher order Path Trace Identifier Mismatch / STS Trace /ne/frame-1/slot-
HP-TIM / TIM-P MAJOR
Identifier Mismatch 1/su
SDH Higher order Path Payload Label Mismatch / SONET STS /ne/frame-1/slot-
HP-PLM / PLM-P WARNING
Payload Label Mismatch 1/su
/ne/frame-1/slot-
GFP- LFD General Framing Procedure - Loss Of Frame Delineation WARNING
1/su
/ne/frame-1/slot-
GFP MISMATCH General Framing Procedure - invalid/not supported GFP frame WARNING
1/su
/ne/frame-1/slot-
LINK LOSS Traffic Ethernet link down CRITICAL
1/su
FORCED LINK /ne/frame-1/slot-
LOSS Traffic Ethernet link is forced down due to remote link loss MAJOR
1/su
/ne/frame-1/slot-
LOC Signal from IFU Basic Frame to SU is missing MAJOR
1/su
RIU Alarms
The source is given for a RIU placed in slot position 4 in IFU number x.
Perceived
Alarm Name Alarm Info Source
Severity
/ne/frame-x/slot-
LOST CONTACT Communication between SU and RIU failed MAJOR
4/riu
TEST IN A test function is enabled on the unit. The test function can be a /ne/frame-x/slot-
PROGRESS WARNING
signal loop 4/riu
CONFIGURATION /ne/frame-x/slot-
FAILURE Configuration of RIU failed MAJOR
4/riu
/ne/frame-x/slot-
EW Estimated Bit Error Rate is above configured threshold WARNING
4/riu
/ne/frame-x/slot-
LBER Estimated Bit Error Rate is above configured threshold MINOR
4/riu
/ne/frame-x/slot-
HBER Estimated Bit Error Rate is above configured threshold MAJOR
4/riu
DEMOD SYNC /ne/frame-x/slot-
LOSS Demodulator is out of synchronization MAJOR
4/riu
CABLE MISSING
/ne/frame-x/slot-
(IOCOM LOST Communication from ODU to RIU failed MAJOR
4/riu
CONTACT)
/ne/frame-x/slot-
TX FAILURE Missing signal from IFU Basic Frame MAJOR
4/riu
ODU POWER /ne/frame-x/slot-
FAILURE Current exceeding limit on power supply to ODU MAJOR
4/riu
EXT AGC AT /ne/frame-x/slot-
MAX Signal power level from ODU to RIU is below limit MAJOR
4/riu
ADC /ne/frame-x/slot-
OVERRANGE Signal power level from ODU to RIU is above limit MAJOR
4/riu
XPIC SYNC LOSS
/ne/frame-x/slot-
Only for XPIC Signalling between RIUs for XPIC has failed MAJOR
4/riu
systems
Fan Alarms
Perceived
Alarm Name Alarm Info Source
Severity
/ne/frame-1/slot-
UNIT MISSING Fan Unit is missing. MAJOR
6/fan
Combined alarm for the 3 fans on the fan unit. Fan speed is too /ne/frame-1/slot-
FAN ALARM MINOR
low 6/fan
ODU Alarms
The ODU connected to RIU in Slot No. 4.
Perceived
Alarm Name Alarm Info Source
Severity
NEED /ne/frame-x/slot-
CONFIGURATION ODU configuration is missing MAJOR
4/odu
/ne/frame-x/slot-
LOST CONTACT Communication between SU and ODU failed MAJOR
4/odu
/ne/frame-x/slot-
TX LO Transmitter Local Oscillator failure MAJOR
4/odu
/ne/frame-x/slot-
RX LO Receiver Local Oscillator failure MAJOR
4/odu
/ne/frame-x/slot-
Cable LOF Signal from RIU not received properly in the ODU MAJOR
4/odu
RF Output /ne/frame-x/slot-
TOO_LOW Measured RF Output level is below setting MAJOR
4/odu
TRANSMITTER /ne/frame-x/slot-
FAILURE Transmitter power amplifier is overheated MAJOR
4/odu
ATPC LOOP /ne/frame-x/slot-
BROKEN ATPC feedback signal from remote receiver failed MINOR
4/odu
/ne/frame-x/slot-
RF INPUT LOS RF input signal level is below critical limit MAJOR
4/odu
/ne/frame-x/slot-
RF INPUT LEVEL RF input level is outside configured range WARNING
4/odu
POWER SUPPLY One or more of the secondary (internal) power sources out of /ne/frame-x/slot-
FAILURE MAJOR
order 4/odu
TRANSMITTER /ne/frame-x/slot-
PA OVERHEAT Temperature in ODU is above limit MAJOR
4/odu
/ne/frame-x/slot-
x/aux/port1
/ne/frame-x/slot-
x/aux/port2
/ne/frame-x/slot-
OHC LINK LOSS The internal packet channel has an error MAJOR
x/aux/port3
/ne/frame-x/slot-
x/aux/port4
/ne/frame-x/slot-
x/aux/hdlc
/ne/frame-x/slot-
x/eow/port1
/ne/frame-x/slot-
x/eow/port2
/ne/frame-x/slot-
OHC LINK LOSS The internal packet channel has an error MAJOR
x/eow/port3
/ne/frame-x/slot-
x/eow/port4
/ne/frame-x/slot-
x/eow/hdlc
E1 Units Alarms
The source is given for a E1 Unit placed in slot position x in IFU number x
Perceived
Alarm Name Alarm Info Source
Severity
LOST CONTACT Communication between SU and E1 Unit failed MAJOR /ne/frame-x/slot-x/e1
One or more of the secondary (internal) power sources out
POWER FAILURE WARNING /ne/frame-x/slot-x/e1
of order
TEST IN A test function is enabled on the unit. The test function can
PROGRESS WARNING /ne/frame-x/slot-x/e1
be a signal loop
CONFIGURATION
FAILURE Configuration of the E1 Unit failed MAJOR /ne/frame-x/slot-x/e1
/ne/frame-x/slot-x/e1/1
/ne/frame-x/slot-x/e1/2
/ne/frame-x/slot-x/e1/3
LOS Loss of E1 input signal CRITICAL
-
-
/ne/frame-x/slot-x/e1/25
/ne/frame-x/slot-x/e1/1
/ne/frame-x/slot-x/e1/2
/ne/frame-x/slot-x/e1/3
AIS Alarm Identification Signal in E1 output signal WARNING
-
-
/ne/frame-x/slot-x/e1/25
Performance Alarms
Perceived
Alarm Name Alarm Info Source
Severity
/ne/frame-x/slot-2/liu
The 15 min calculation has exceeded the quality level /ne/frame-x/slot-3/liu
G826-B1-15M threshold set for a 15 min calculation. The alarm will not be WARNING
clared until a complete 15 min period below threshold occurs /ne/frame-x/ifu/ch.1
/ne/frame-x/ifu/ch.2