Professional Documents
Culture Documents
9
International Journal of Electrical and Electronics Engineering 1:1 2007
especially during major disturbances. This presents difficulties III. A short overview of GA is presented in Section IV.
for designing the FACTS controllers in that, the controllers Simulation results are provided and discussed in Section V
designed to provide desired performance at small signal and conclusions are given in Section VI.
condition do not guarantee acceptable performance in the
event of major disturbances. II. POWER SYSTEM UNDER STUDY
In [5], a systematic procedure for modeling, simulation and The SMIB power system with TCSC shown in Fig. 1 is
optimal tuning of TCSC controller in a SMIB power system considered in this study. The synchronous generator is
was presented where the MATLAB/SIMULINK based model delivering power to the infinite-bus through a double circuit
was developed and genetic algorithm (GA) was employed to transmission line and a TCSC. In Fig. 1, Vt and Eb are the
design the TCSC controller. However, the model only takes
into account the generator main field winding and the generator terminal and infinite bus voltage respectively; X T ,
synchronous machine was represented by model 1.0. For more X L and X TH represent the reactance of the transformer,
reasonable evaluation of a SMIB power system with FACTS transmission line per circuit and the Thevenins impedance of
controller, a higher-order synchronous machine model (model the receiving end system respectively.
1.1), which includes one damper winding along the q-axis, is
reported in the literature [6]. As power system stabilizers Vt Eb 0
jX L
(PSS) are now routinely used in the industry, this paper jX TH
considers a SMIB power system installed with a PSS and a TCSC
FACTS controller, where the synchronous machine is
jX T jX L
represented by a higher order model (model 1.1). Generator Infinite-bus
The problem of PSS parameter tuning in the presence of
FACTS-based controller is a complex exercise, as Fig. 1 Single-machine infinite-bus power system with TCSC
uncoordinated local control of these controllers may cause
A. Modelling the Synchronous Generator Infinite-bus
destabilizing interactions. To improve overall system
Power System
performance, many researches were done on the coordination
between PSS and FACTS power oscillation damping (POD) The synchronous generator is represented by model 1.1, i.e.
controllers [7]-[9]. A number of conventional techniques have with field circuit and one equivalent damper on q-axis. The
machine equations are [12]:
been reported in the literature pertaining to design problems of
conventional power system stabilizers namely: the eigenvalue
d
assignment, mathematical programming, gradient procedure = B (S m S mo ) (1)
for optimization and also the modern control theory. dt
Unfortunately, the conventional techniques are time
consuming as they are iterative and require heavy computation dS m 1
burden and slow convergence. In addition, the search process
= [ D (S m S mo ) + Tm Te ] (2)
dt 2H
is susceptible to be trapped in local minima and the solution
[ E' q + ( xd x' d ) id + E fd ]
obtained may not be optimal [10].
GA is becoming popular for solving the optimization
dE ' q 1
= (3)
problems in different fields of application, mainly because of dt T' do
their robustness in finding an optimal solution and ability to
provide a near-optimal solution close to a global minimum.
Unlike strict mathematical methods, the GA does not require
the condition that the variables in the optimization problem be
dE ' d
dt
=
'
1
T qo
[ (
E ' d + x q x' q i q ) ] (4)
( )
single-point search and work with the coded structure of
variables instead of the actual variables, require only the Te = E ' d id + E ' q iq + x' d x' q id i q (5)
objective function, thereby making searching for a global
optimum simpler [11]. Therefore, in the present work GA is
For a lossless network, the stator algebraic equations and
employed to simultaneously tune the parameters of PSS and
the network equations are expressed as:
FACTS controller.
This paper is organized as follows. In Section II, the
modeling of power system under study, which is a SMIB E' q + x ' d id = vq (6)
power system with a PSS and a thyristor controlled series
compensator (TCSC), is presented. The proposed controller E' d x ' q iq = v d (7)
structures and problem formulation are described in Section
10
International Journal of Electrical and Electronics Engineering 1:1 2007
Max.
The above notation for the variables and parameters
described are standard and defined in the nomenclature. For 0 0 + 1 X TCSC ( )
more details, the readers are suggested to refer [12]-[13]. 1 + sTTCSC
+ Output
B. Modelling the Thyristor Controlled Series Compensator +
Min.
(TCSC) 1 + sT3T 1 + sT1T sTWT
TCSC is one of the most important and best known series 1 + sT4T KT
1 + sT2T 1 + sTWT Input
FACTS controllers. It has been in use for many years to
increase line power transfer as well as to enhance system Two stage Washout Gain
stability. It consists of three components: capacitor banks, lead-lag Block Block Block
bypass inductor and bidirectional thyristors. The firing angles
of the thyristors are controlled to adjust the TCSC reactance in Fig. 2 Structure of TCSC-based controller
accordance with a system control algorithm, normally in
response to some system parameter variations. From the viewpoint of the washout function, the value of
According to the variation of the thyristor firing angle ( ) TWT is not critical and may be in the range of 1 to 20 seconds
or conduction angle ( ), this process can be modelled as a [13]. The phase compensation block (time constants T1T, T2T
fast switch between corresponding reactance offered to the and T3T, T4T) provides the appropriate phase-lead
power system. Assuming that the total current passing characteristics to compensate for the phase lag between input
through the TCSC is sinusoidal; the equivalent reactance at the and the output signals. In the Fig. 2, 0 represents the initial
fundamental frequency can be represented as a variable conduction angle as desired by the power flow control loop.
reactance XTCSC. There exists a steady-state relationship The steady state power flow loop acts quite slowly in practice
between and the reactance XTCSC. This relationship can be and hence, in the present study, 0 is assumed to be constant
described by the following equation [14]: during large disturbance transient period.
B. Structure of the PSS
X C2 ( + sin )
X TCSC ( ) = XC
( XC X P )
4 X C2 cos 2 ( / 2 ) [ k tan( k / 2 ) tan( / 2 ) sTWP 1 + sT1P 1 + sT3 P VS
+ KP
( X C XP ) ( k2 1) Input 1 + sTWP 1 + sT2 P 1 + sT4 P Output
(12) Gain
Two stage
Block Washout
lead-lag Block
Since the relationship between and the equivalent Block
fundamental frequency reactance offered by TCSC, Fig. 3 Structure of the power system stabilizer
X TCSC ( ) is a unique-valued function, the TCSC is
modeled here as a variable capacitive reactance within the A widely used conventional lead-lag PSS is considered in
operating region defined by the limits imposed by . Thus this study. Its structure is shown in Fig. 3. It consists of a gain
XTCSCmin XTCSC XTCSCmax, with XTCSCmax = XTCSC (min) and block with gain KP, a signal washout block, and two-stage
XTCSCmin = XTCSC(1800) = XC. In this paper, the controller is phase compensation block with time constants T1P, T2P and
assumed to operate only in the capacitive region, i.e., min > r T3P, T4P . In this structure, TWP is the washout time constant;
where r corresponds to the resonant point, as the inductive is the speed deviation and VS is the stabilizing signal out
region associated with 900 < < r induces high harmonics put of PSS.
that cannot be properly modeled in stability studies.
11
International Journal of Electrical and Electronics Engineering 1:1 2007
C. Problem Formulation
In the present study, a washout time constant of TWT = TWP Start
=1.0s is used. The controller gains KT & KP and the time
constants T1T , T2T , T3T , T4T & T1P , T2P , T3P and T4P are to be
determined. In case of PSS, the stabilizing signal output VS is Specify the parameters for GA
zero during steady state conditions. Following a disturbance,
the signal VS is modified according to the change in the
Generate initial population
during dynamic conditions. In case of TCSC-based controller,
and 0 are constant during steady state conditions. Gen.=1
No
D. Objective Function
Apply GA operators:
It has been shown that that for the TCSC-based controller selection,crossover and mutation
design problem, the best system response is obtained when the
controller parameters are optimized using integral of time
Fig. 4 Flowchart of the genetic algorithm
multiplied absolute value of the error (ITAE) as objective
function [15]. In view of the above, in this paper, the objective
function is defined as follows: The computational flow chart of the GA optimization
approach followed in the present paper is shown in Fig. 4.
t sim
J = t | (t )| dt (14) V. RESULTS AND DISCUSSIONS
0 A. Application of GA Optimization Technique
In order to simultaneously tune the parameters of the
where, (t ) is the speed deviation following a PSS and the TCSC-based controller, as well as to assess their
disturbance and t sim is the time range of simulation. performance and robustness under wide range of various fault
disturbances, the MATLAB/SIMULINK model of the
IV. OVERVIEW OF GENETIC ALGORITHM (GA) example power system shown in Fig. 1 is developed using
equations (1)(11). The developed MATLAB/SIMULINK
GA has been used for optimizing the parameters of the model of synchronous generator with PSS and TCSC
control system that are complex and difficult to solve by controller is shown in Fig. 5. The SIMULINK model for
conventional optimisation methods. GA maintains a set of
candidate solutions called population and repeatedly modifies calculation of i d , iq , E ' d , E ' q and Pe is shown in Fig. 6.
them. At each step, the GA selects individuals from the The relevant parameters are given in appendix.
current population to be parents and uses them to produce the The objective function is evaluated for each individual by
children for the next generation. Candidate solutions are simulating the system dynamic model considering a three-
usually represented as strings of fixed length, called phase fault at the generator terminal busbar at t = 1.0 sec. For
chromosomes. A fitness or objective function is used to reflect the purpose of optimisation of equation (16), routines from
the goodness of each member of the population. Given a GA toolbox were used. The fitness function comes from time-
random initial population, GA operates in cycles called domain simulation of power system model shown in Fig. 5.
generations, as follows: Using each set of controllers parameters, the time-domain
Each member of the population is evaluated using a simulation is performed and the fitness value is determined.
fitness function. Good solutions are selected, and by means of the GA
The population undergoes reproduction in a number of operators, new and better solutions are achieved. This
procedure continues until a desired termination criterion is
iterations. One or more parents are chosen stochastically,
achieved. Although the chances of GA giving a local optimal
but strings with higher fitness values have higher
solution are very few, sometimes getting a suboptimal solution
probability of contributing an offspring. is also possible. While applying GA, a number of parameters
Genetic operators, such as crossover and mutation, are are required to be specified. An appropriate choice of these
applied to parents to produce offspring. parameters affects the speed of convergence of the algorithm.
The offspring are inserted into the population and the For different problems, it is possible that the same parameters
process is repeated.
12
International Journal of Electrical and Electronics Engineering 1:1 2007
Damping
1 2*pi*f Power angle
Mechanical
Smo 1
power input -K- [delta]
Electrical power s
after fault clearence 1
Peo -K- s Speed
[pe] sigo
1/2H sig
xtcsc sig
Reactance
before & after fault
xd-xd'
iq=(Ebsin(delta) + E'd)/(Xe+x'q)
[id]
xd-xd'1 (xd-x'd)id f(u) [iq]
xq-xqd
1/T'qo
[iq] 1 [id]
-K- [edd] Vt = Sqrt (vq ^2 +vd^2)
(xd-xx'q)id s
E'd [delta]
Mux f(u)
[iq]
Vt = sqrt [(( -Xe id + Ebcos(delta))^2)
+((Xe iq -Eb sin(delta))^2)]
[edd] [XL]
Electrical power
[eqd] after fault clearence Reference voltage
400
[id] Mux f(u) [pe] [efd] Vref1
0.025s+1
Efd Saturation` Excitation
[iq] Pe = E'q iq + E'd id +(x'd - x'q) id iq [Vs]
xdd-xqd Signal from PSS
.
Fig. 6 SIMULINK model for calculation of i d , i q , E ' d , E ' q , E fd and Pe
13
International Journal of Electrical and Electronics Engineering 1:1 2007
0.01
0.0118 NC
T CSC
0.005
0.0116 T CSC & PSS
(pu)
0.0114 0
0 20 40 60 80 100
Generation
-0.005
Fig. 7 Convergence rate of objective function J.
B. Simulation Results -0.01
In order to show the effectiveness of the proposed model of 1 2 3 4 5 6
power system with PSS and TCSC-based controller and Time (sec)
simultaneous tuning the controller parameters in the way Fig. 9 Variation of speed deviation : Case-1
presented in this paper, simulation studies are carried out for
14
International Journal of Electrical and Electronics Engineering 1:1 2007
1.005
NC
1 T CSC 1
V t (pu)
0.6
0.99
0.4
0.985 NC
0.2 T CSC
0.98 T CSC & PSS
0
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
Fig. 10 Variation of electrical power Pe : Case-1 Fig. 14 Variation of terminal voltage Vt : Case-1
-0.18 0
NC
T CSC
-0.2 T CSC & PSS -0.2
-0.4
-0.22
E'd (pu)
Id (pu)
-0.6
-0.24
-0.8 NC
-0.26 T CSC
-1 T CSC & PSS
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
1 0.6
0.95
0.5
0.9
E'q (pu)
0.4
Iq (pu)
0.85
0.3 NC
0.8 NC
T CSC T CSC
T CSC & PSS 0.2 T CSC & PSS
0.75
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
6
0.65
4
0.6
2
XTCSC (pu)
0.55
Efd (pu)
0
0.5
-2
NC NC
-4 T CSC 0.45 T CSC
T CSC & PSS T CSC & PSS
-6 0.4
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
Fig. 13 Variation of voltage E fd : Case-1 Fig. 17 Variation of X TCSC : Case-1
15
International Journal of Electrical and Electronics Engineering 1:1 2007
-0.2
75 NC T CSC T CSC & PSS
NC
70 T CSC -0.3
T CSC & PSS
65
-0.4
Id (pu)
(deg)
60
-0.5
55
50 -0.6
45
-0.7
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
Fig. 18 Variation of power angle : Case-2 Fig. 21 Variation of current I d : Case-2
-3
x 10
6
NC T CSC T CSC & PSS 0.45
4
2 0.4
Iq (pu)
(pu)
-2
0.35
0.8 0.65
0.7
0.6
XTCSC (pu)
Pe (pu)
0.6
0.5 0.55
NC
T CSC
0.4
NC T CSC T CSC & PSS T CSC & PSS
0.5
1 2 3 4 5 6
1 2 3 4 5 6
Time (sec)
Time (sec)
Fig. 20 Variation of electrical power Pe : Case-2 Fig. 23 Variation of X TCSC : Case-2
Figs. 9 - 17 shows the variation of speed deviation, electrical of the proposed modelling and simultaneous tuning approach.
'
power Pe , voltages E d , E ' q , E fd , Vt , currents i d , iq and It is also clear from the Figs. that PSS and TCSC-based
controller operate in a coordinated manner and improves the
reactance offered by TCSC: X TCSC , respectively all with stability performance of the power system compared to the
respect to time for the above mentioned contingency in Case- case where only TCS-based controller is acting.
1. It is clear from these Figs. that, the simultaneous design of
Case-3: Small Disturbance
PSS and TCSC-based controller by the proposed approach
significantly improves the stability performance of the In order to verify the effectiveness of the proposed
example power system and power system oscillations are well simultaneous design approach under small disturbance, the
damped out. mechanical power input to the generator is increased by 1 pu
at t = 1 sec. The system response under this small disturbance
Case-2: Line-outage Disturbance contingency is shown in Figs. 24-27. It is clear form the Figs.
In this case another severe disturbance is considered. One 24-27 that, the proposed GA optimized PSS and TCSC-based
of the transmission line is permanently tripped out at t = 1 sec. controller act in a coordinated has good damping
The system response for the above contingency is shown in characteristics to low frequency oscillations and quickly
Figs. 18-26. The simulation results show the effectiveness stabilizes the system under this small disturbance.
16
International Journal of Electrical and Electronics Engineering 1:1 2007
0.8
52
0.75
50
(deg)
Pe (pu)
0.7
48
NC
46 T CSC 0.65
T CSC & PSS NC
T CSC
44 0.6 T CSC & PSS
1 2 3 4 5 6
Time (sec) 1 2 3 4 5 6
Fig. 27 Variation of power angle : Case-3 Time (sec)
Fig. 29 Variation of electrical power Pe : Case-3
-3
x 10
2 0.65
NC NC
T CSC T CSC
1 T CSC & PSS 0.64
T CSC & PSS
XTCSC (pu)
0.63
(pu)
0
0.62
-1
0.61
-2 0.6
1 2 3 4 5 6 1 2 3 4 5 6
Time (sec) Time (sec)
Fig. 28 Variation of speed deviation : Case-3 Fig. 31 Variation of X TCSC : Case-3
VI. CONCLUSION
APPENDIX
A systematic procedure for modelling and simulation of a
System data: All data are in pu unless specified otherwise.
power system installed with a PSS and a FACTS-based
controller is presented in this paper. The model is developed in
Generator: H = 3.542, D = 0, Xd=1.7572, Xq=1.5845,
the MATLAB/SIMULINK environment which provides a
Xd =0.4245, Xq =1.04, Tdo = 6.66, Tqo=0.44, Ra=0, Pe=0.6,
means for carrying out power system stability analysis and for
Qe=0.02224, 0=44.370.
explaining the generator dynamic behaviour as effected by a
PSS and FACTS. In this model, the synchronous generator
Exciter: KA=400, TA=0.025 s
with field circuit and one equivalent damper on q-axis is
considered which is far more realistic compared to the model
Transmission line: R=0, XL = 0.8125, XT=0.1364,
available in open literature. Further, to avoid adverse
XTH=0.13636, G=0, B=0;
interactions, the proposed controllers are simultaneously
designed. For the design problem, a parameter-constrained,
TCSC Controller: TTCSC = 15 ms, 0 = 1420, XTCSC0 = 0.62629,
time-domain based, objective function, is developed to
k=2, TW = 10 s, XMAX = 0.8 XL, XMIN = 0.
improve the performance of power system subjected to a
disturbance. Then, GA is employed to coordinately tune the
REFERENCES
parameters of the PSS and TCSC controller. The performance
of the proposed controllers is tested on example power system [1] N. G. Hingorani and L. Gyugyi, Understanding FACTS: Concepts and
Technology of Flexible AC Transmission System. IEEE Press. 2000.
subjected to various large and small disturbances. Simulation [2] H.F.Wang and F.J.Swift, A unified model for the analysis of FACTS
results show that, application both PSS and TCSC where the devices in damping power system oscillations part I: single-machine
controllers are tuned by the proposed simultaneous design infinite-bus power systems, IEEE Transactions on Power Delivery,
approach gives the best response in terms of overshoot and Vol. 12, No. 2, pp. 941-946, 1997.
[3] H.F.Wang Phillips-Heffron model of power systems installed with
settling time. The first swings in the power angle, speed STATCOM and applications IEE Proceedings on Generation
deviation and the electrical power are also greatly suppressed Transmission and Distribution, Vol. 146, No. 5, pp. 521-527, 1999.
and the settling time is greatly reduced with the simultaneous [4] H.F.Wang A Unified Model for the Analysis of FACTS Devices in
design approach. Damping Power System OscillationsPart III: Unified Power Flow
Controller, IEEE Transactions on Power Delivery, Vol. 15, No. 3, pp.
978-983, 2000.
17
International Journal of Electrical and Electronics Engineering 1:1 2007
Narayana Prasad Padhy was born in India and received his Degree
(Electrical Engineering), Masters Degree (Power Systems Engineering) with
Distinction and Ph.D., Degree (Power Systems Engineering) in the year 1990,
1993 and 1997 respectively in India. Then he has joined the Department of
Electrical Engineering, Indian Institute of Technology (IIT) India, as a
Lecturer, Assistant Professor and Associate Professor during 1998, 2001 and
2006 respectively. Presently he is working as a Associate Professor in the
Department of Electrical Engineering, Indian Institute of Technology (IIT)
India. He has visited the Department of Electronics and Electrical
Engineering, University of Bath, UK under Boyscast Fellowship during 2005-
06 . His area of research interest is mainly Power System Privatization,
Restructuring and Deregulation, Transmission and Distribution network
charging, Artificial Intelligence Applications to Power System and FACTS.
18