Abstract- Next to pumps, Fans/Blowers are the most energy consuming motor driven machineries in Nigeria today. Every
home and office rooms in Nigeria have at least one Fan/Blower used for the purpose of ventilation and space conditioning.
Unfortunately, most of the more than 170million Fans/Blowers sold in Nigeria are not accompanied by the Fans/Blowers
performance characteristics curves. Hence, the Fans/Blowers are improperly matched to systems requiring them, which
usually results to inefficient operation of the Fans/Blowers, excessive energy consumption, dissatisfaction of end users and
Fans/Blowers failure. This work aims are developing a simplified theoretical model for predicting the performance
characteristics of axial Fans/Blowers using a combination of aerodynamics involving through-flow analysis and a simplified
classical one dimensional momentum theory. The model was developed using the geometric and basic operating particulars
of the Fans/Blowers to evaluate the interaction of the Total Pressure developed, Power required and efficiency of the blower
for a range of flow volumes. The model developed in this work was validated against several Fans/Blowers models in the
T35 Fans/Blowers series performance data provided by NanFang Ventilator Factory. The flow volume, total Pressure, air
power and efficiency predicted by the model is in reasonable agreement with those of the manufacturers to a mean
percentage of 97.68%, 96.71%, 85.7% and 96.6% respectively. The theoretical model can be used by ventilation systems
designers and Fans/Blowers end users to generate axial Fans/Blowers performance characteristic curves not supplied by
Fans/Blowers manufacturers and thus, effectively specify axial Fans/Blowers for existing or newly designed systems.
Keywords- Axial Fans/Blowers, One Dimensional Momentum Theory, Performance Characteristics Curves (Efficiency,
Total Pressure, Flow Volume and Required Power), Validated.
1
International Journal of Mechanical And Production Engineering, ISSN: 2320-2092, Volume- 3, Issue-2, Feb.-2015
operating expensive Fans/Blowers test rigs. The user It is fair to assume that;
or system designer only makes use of the geometric The absolute velocity V1 is radial (Vf1) and
and the basic operating particulars of the has no prewhirl velocity (Vw1 = 0)
Fans/Blowers stated on the label (where available) to component at the impeller inlet.
establish the axial Fans/Blowers performance The Fans/Blowers manufacturer during the
characteristics. Fans/Blowers assembly or construction, was
careful enough to ensure that the blades are
In Axial flow blowers incoming air is directed into set at angle 1 (blade inlet angle), that results
the impeller, as the air passes through the impeller in a situation where the air (with a relative
along the axis of the Fans/Blowers, the impeller velocity Vr, between the peripheral velocity,
blades increases the air momentum (air velocity) and U1 of impeller at that radius r1 and the radial
generates aerodynamic lifts that pressurizes the air, velocity component of the absolute velocity)
thereby increasing the static pressure of the air after enters the impeller without shock or entry
passing. To predict the performance of an axial loss.
Fan/Blower, a detailed knowledge of the flow Vf = Vf1 = Ucot1 (1)
characteristics of the blower over the full operational D 1 = r and = 2N m/s;
Where U1 = 1
range of air flow volume is required. 2 60
N is measured in RPM, D1 and r1 are hub diameter
The air flow through the Fans/Blowers impeller is and radius respectively
actually three dimensional, the momentum of the
flow can be analysed using a complex CDF analytical II. IMPELLER OUTLET
approach. To simplify the analysis of this 3D flow, a
one-dimensional through-flow momentum analysis At the impeller outlet, the air leaves the impeller with
which focuses on the impeller inlet and outlet with an absolute velocity V2, through a cylindrical surface
recourse to the space where the real energy transfer r2 and makes an angle 2 with the tangent at that
takes place is proposed. This proposal assumes that radius. Unlike the case of the absolute inlet velocity,
the absolute outlet velocity of the air has both the
The blades are infinitely thin and pressure radial Vf2 and whirl velocity Vw2 component.
difference across them is replaced by
imaginary body forces acting on the fluid
producing it.
The number of blades is infinitely so large
that the variation of velocity across blade
passages is reduced and tends to zero.
There is no variation of velocity across the
width of the impeller.
2
International Journal of Mechanical And Production Engineering, ISSN: 2320-2092, Volume- 3, Issue-2, Feb.-2015
2 g g g
H is expressed as Total Pressure in Pascal, PT = 9.810
Eth = VR 2 V2 U
2 2 2
x Ha (Pascal) (8)
2g 2g 2g Equation (8) reveals the relationship between total
(6) Pressure head and air flow which constitutes one the
Eq.6 is form of Bernoullis equation; where, performance characteristics curve of the
2 Fans/Blowers to be validated. This characteristics
Vf 2
curve is compared with the manufacturers or
VR 2 2
sin 2 Static pressure head of the experimentally determined performance
2g 2g
characteristics.
Fans/Blowers
V2 2 = Thus, the Fans/Blowers will develop pressure as a
2g function of the quantity of air it is handling. The
2 slope of the Fans/Blowers performance curve of total
U - Vf cot 2 pressure developed versus flow capacity delivered is
-1
Cos(tan (V f /(U - Vf cot 2 )) Kinetic energy affected by the relative discharge velocity angle
2g (outlet blade angle equivalent) 2. Furthermore, since
of air in the impeller for different Fans/Blowers design, there are different
peripheral speeds [U = f()] and different flow area;
U2 Energy used in setting the air in a circular each Fans/Blowers design will have its own total
2g pressure versus flow capacity performance curve.
motion about the impeller axis Power Pa transferred to the air.
The actual energy transfer by the Fans/Blowers is The power transferred to the air by the Fans/Blowers
smaller than that from by (5) and (6) due to; is given as
(i) Slip Factor which was not considered Pa = agHaQ = PTQ
when the three assumptions were made in order use a where a Density of air (9)
one dimensional flow momentum analysis
methodology to estimate performance characteristics This equation shows the dependence of air power on
of the Fans/Blowers. the quantity of air the Fans/Blowers is handling. This
Theoretical Model for Predicting Axial Fans/Blowers Performance Characteristics
3
International Journal of Mechanical And Production Engineering, ISSN: 2320-2092, Volume- 3, Issue-2, Feb.-2015
IV. RESULTS AND DISCUSSION range of Fans/Blowers models in the T35 series
Fans/Blowers family of NanFang Ventilator Factory.
Table I shows the comparison of Fans/Blowers The Fans/Blowers peripheral speed, Q, PT, P and
parameters calculated using this theoretical model derived from this model is in good agreement with
and those from the Fans/Blowers manufacturer for a that specified by the Fans/Blowers manufacturer. A
4
International Journal of Mechanical And Production Engineering, ISSN: 2320-2092, Volume- 3, Issue-2, Feb.-2015
graph of PT, P and against Q for model 10 shown efficiency point is about 0.9 as against 0.87 stated by
below can be used to predict the performance of the the manufacturer i.e. a 96.7% accuracy for this model
Fans/Blowers over a range of flow rates. The best
CONCLUSION REFERENCES
This theoretical model gives a fair estimate of the [1] US Department of Energy, Energy Efficiency and
Renewable Energy, 1989. Improving Fans/Blowers System
performance of axial Fans/Blowers or blower in the
Performance a sourcebook for industry,
absence Fans/Blowers curves and expensive www1.eere.energy.gov/industry/bestpractices/pdfs/Fans/Blo
experimental Fans/Blowers test rigs that require wers_sourcebook.pdf
certain high level skill to operate. [2] ISO 12759, Fans/Blowers Efficiency classification for
Fans/Blowerss First edition, 2010
Required input values from the buyer or ventilation
[3] Commonwealth of Australia (Department of Climate
system designer includes the measured blade inlet Change and Energy Efficiency), 2011. Product Profile-
and outlet angles; rotational speed, Fans/Blowers Small Fans/Blowers Units, www.energyrating.gov.au
diameter and input electric power (or Voltage and [4] United Nations Environmental Programme, 2006.
Current) got from the Fans/Blowers label. Electrical Energy Equipment: Fans/Blowersand Blowers,
www.energyefficiencyasia.org
The output is the total PT, and P versus Q [5] Douglas J.F Gasiorek J.M, Swiffield J.A., Fluid
characteristic curves for the Fans/Blowers under Mechanics, 3rd Edition, Longman Singapore Publishers,
consideration as well as for Fans/Blowers that are Singapore,1997.
geometrically similar. Caution must be exercised [6] Cermak J. and J. Murphy Select Fans/BlowersUsing
when measuring the blade angles as values obtained Fans/Blowers Total Pressure To Save Energy, ASHRAE
are very sensitive to Fans/Blowers performance Journal, July 2011. Available at www.amca.org/feg/best-
parameters derived and crucial to the successful practices.aspx.
application of the model. [7] Daniel Boyle, Results of New Furnace Blower
Application Research and Development Furnace-Burners-
Incinerators, Washington D.C 20535-0001, USA, March 27,
Deciding the Fans/Blowers efficiency rating is also of 2005.
major importance to the derivation of the
Fans/Blowers pressure and power, this issue will be [8] John Cermak, Fans/Blowers Efficiency Requirements for
standard 90.1-2013, ASHRAE Journal, April, 2013.
easily resolved when all Fans/Blowers categories
(domestic and industrial) are given standard [9] Armin Hauer and Joe Brooks, Fans/Blowers Motor
Efficiency Grades in European Market, AMCA
Fans/Blowers Efficiency Grades (FEG) as contained International, Summer, 2012.
in Standard 90.1-2013 and AMCA 205 and all
Fans/Blowers sold in the market are certified for [10] Michael Brendel, The Role of Fans/Blowers Efficiency in
Achieving Energy Reduction Goals, AMCA International,
meeting such standards. Summer, 2012.