NUEVOS PABELLONES DE LA UNAMAD

TAMBOPATA-MADRE DE DIOS

DISEO ESTRUCTURAL DE PRGOLAS

1.0 DISEO DE LA LOSA MACIZA PLEGADA DE TECHO

ESPESOR TOTAL DE LA LOSA: t = 0.125 M

PERALTE EFECTIVO: d = 0.125 0.03 = 0.095

PESO PROPIO DE LA LOSA: PP = 0.125X2400 = 300 KG/M2

PESO DE PLANCHAS DE COBERTURA: 50 KG/M2

CARGA VIVA DE TECHO: 30 KG/M2

CARGA DISTRIBUIDA TOTAL: W = 300 + 50 + 30 = 380 KG/M2

CALIDAD DE MATERIALES:

fc = 245 KG/CM2, fy = 4200 KG/CM2

LUCES DE CLCULO DE LOSA DE TECHO: L= 3.10 M

MOMENTOS FLEXIONANTES MXIMOS EN LOSA DE TECHO:

Mmax = 1/10 (380)(3.10)2 = 365 KG-M/M

REA REQUERIDA DE REFUERZO EN FLEXIN:

As = 1.50X365/(0.81X4200X0.095) = 1.69 CM2/M

REA MNIMA DE REFUERZO EN FLEXIN:

As min = 0.002X100X12.5 = 2.50 CM2/M

CONTROLA EL REFUERZO MNIMO EN FLEXIN.

As = As min = 2.50 CM2/M = BARRAS DE 3/8 @ 71/2.50 = 28 CM

SE DISPONDRN DOS PARRILLAS DE BARRAS DE 3/8 @ 0.25 M, UNA EN EL LECHO INFERIOR Y LA


OTRA EN EL LECHO SUPERIOR.

1
2.0 DISEO DE LAS VIGAS DE CIMENTACIN

2.1 CONFIGURACIN ESTRUCTURAL DE LA CIMENTACIN

TENIENDO EN CUENTA EL REDUCIDO PESO DE LAS PRGOLAS, SE HA CONSIDERADO CONVENIENTE


NO DISEAR ZAPATAS AISLADAS, SINO MS BIEN UNA PARRILLA DE VIGAS DE CIMENTACIN
APOYADAS EN UN COTA DE CIMENTACIN QUE SE ENCUENTRA 1.00 M POR DEBAJO DEL NIVEL DE
PISO TERMINADO NPT +0.00.

A ESTA PROFUNDIDAD, LA CAPACIDAD ADMNISIBLE DE CARGA DEL SUELO DE CIMENTACIN ES


BASTANTE MENOR QUE LA ESPECIFICADA POR EL ESTUDIO DE MECNICA DE SUELOS PARA UNA
PROFUNDIDD DE 2.00 M POR DEBAJO DEL NIVEL DEL TERRENO.

CONSERVADORAMENTE, LA CAPACIDAD ADMISIBLE DE CARGA A LA PROFUNDIDAD DE 1.00 M SE


HA DE CONSIDERAR IGUAL AL 50% DE LA CAPACIDAD ADMISIBLE DE CARGA UTILIZADA EN EL
DISEO DE LAS ESTRUCTURAS DE CIMENTACIN DE LOS DIFERENTES BLOQUES DE ESTE NUEVO
PABELLN DE LA UNIVERSIDAD.

POR TANTO, PARA EL DISEO DE LAS VIGAS DE CIMENTACIN DE LAS PRGOLAS, SE HA DE


CONSIDERAR: q adm = 5.45 TON/M2.

2.2 METRADO DE CARGAS PARA EL DISEO DE LA CIMENTACIN

PARA REALIZAR ESTE METRADO, SE HA DE CONSIDERAR UNO DE LOS BLOQUES RECTANGULARES


DE MAYOR TAMAO DE LAS PRGOLAS QUE TIENE 7.20 METROS DE LARGO Y 6.50 METROS DE
ANCHO.

CARGA DISTRIBUIDA TOTAL SOBRE LA BASE DE LAS VIGAS DE CIMENTACIN:

PESO DE LOSA DE TECHO e = 0.125 M: 300 KG/M2

PESO DE COBERTURA DE TECHO: 50 KG/M2

CARGA VIVA EN TECHO INCLINADO: 30 KG/M2

PESO DE CANALETAS Y VIGAS DE SOPORTE DE TECHO: 150 KG/M2

PESO DE COLUMNAS CIRCULARES DE SOPORTE DE TECHO: 50 KG/M2

PESO DE PARRILLA DE VIGAS DE CIMENTACIN DE 0.30X0.60 M: 50 KG/M2

CARGA DISTRIBUIDA TOTAL:

W = 300 + 50 + 30 +150 +50 + 50 = 630 KG/M2

PESO TOTAL DEL BLOQUE DE PRGOLAS: WT = 630X6.50X7.20 = 29,484 KG

2
2.3 DIMENSIONAMIENTO DE LAS VIGAS DE CIMENTACIN

LONGITUD TOTAL EFECTIVA DE VIGAS DE CIMENTACIN:

LT = 2X6.50 + 7.20 = 20.2 M

CARGA DISTRIBUIDA LINEAL SOBRE EL SUELO DE CIMENTACIN:

Q = WT/LT = 29,484/20.2 = 1460 KG/M = 1.46 TON/M

ANCHO REQUERIDO DE LAS VIGAS DE CIMENTACIN:

b = Q/q adm = 1.46/5.45 = 0.27 M

SE ADOPTAR UN ANCHO DE 0.30 M PARA TODAS LAS VIGAS DE CIMENTACIN.

PERALTE DE LAS VIGAS DE CIMENTACIN: h = L max/12

h = 7.20/12 = 0.60 M

POR TANTO, TODAS LAS VIGAS DE CIMENTACIN TENDRN UNA SECCIN TRANSVERSAL DE
0.30X0.60 M.

PERALTE EFECTIVO DE LAS VIGAS DE CIMENTACIN: d = 0.60 -0.06 = 0.54 M.

2.4 CARGA DISTRIBUIDA LINEAL EFECTIVA SOBRE LAS VIGAS DE CIMENTACIN

Qef = (630 -50)6.50X7.20/20.2 = 1,344 KG/M = 1.344 TON/M

2.5 DISEO POR FLEXIN DE LAS VIGAS DE CIMENTACIN

LUZ LIBRE MAYOR DE CLCULO: L = 7.20 0.30 = 6.90 M

M OMENTOS FLEXIONANTES NEGATIVOS MXIMOS DE DISEO:

M max (-) = 1/12 (1.344)(6.90)2 = 5.33 TON-M

REA DE REFUERZO REQUERIDO PARA MOMENTOS FLEXIONANTES NEGATIVOS:

As (-) = 1.50X5.33/(0.81X4.20X0.54) = 4.35 CM2.

SE DISPONDRN 3 BARRAS DE 5/8 DE DIMETRO (As = 6.00 CM2) EN EL LECHO SUPERIOR DE LAS
VIGAS DE CIMENTACIN.

LUCES LIBRES DE CLCULO PARA MOMENTOS POSITIVOS: L = 6.50 -0.30 = 6.20 M

MOMENTOS FLEXIONANTES POSITIVOS MXIMOS DE DISEO:

Mmax (+) = 1/10 (1.344) (6.20)2 = 5.16 TON-M

3
AUNQUE ESTOS MOMENTOS POSITIVOS SON MENORES QUE LOS NEGATIVOS, IGUALMENTE SE
HAN DISPONER TAMBIN 3 BARRAS DE 5/8 DE DIMETRO EN EL LECHO INFERIOR DE TODAS LAS
VIGAS DE CIMENATCIN DE PRGOLAS.

2.6 DISEO PARA FUERZAS CORTANTES

FUERZAS CORTANTES MXIMAS QUE ACTAN EN LOS EXTREMOS DE LAS VIGAS DE MAYOR
LONGITUD:

V max = 1.344X6.90/2 = 4.64 TONS

FUERZAS CORTANTES LTIMAS DE DISEO:

Vu/0.85 = 1.50X4.64/0.85 = 8.18 TONS.

CORTANTE LTIMO NOMINAL QUE ABSORBE EL CONCRETO:

Vc = 0.53 (210)1/2 30X54/1000 = 12.44 TONS

Vc ES MAYOR QUE Vu/0.85. POR TANTO, ES SUFICIENTE DISPONER ESTRIBOS MNIMOS DE


REFUERZO TRANSVERSAL.

SE DISPONDRN ESTRIBOS CERRADOS DE DOS RAMAS DE 3/8 DE DIMETRO, CON SEPARACIONES


DE 0.25 M, ENTRE EJES.

3.0 DISEO DE LAS VIGAS HORIZONTALES DE SOPORTE DE LOSA DE TECHO

SE DISEARN LAS VIGAS HORIZONTALES MS CRTICAS, QUE SON AQUELLAS QUE SE HALLAN
DISPUESTAS EN LOS EJES ESTRUCTURALES DE LAS PRGOLAS, POR DEBAJO DE LAS CANALETAS DE
CONCRETO Y CONECTANDO LAS COLUMNAS CIRCULARES.

ESTAS VIGAS TIENEN UNA SECCIN TRANSVERSAL DE 0.25X0.45 M.

NO SE TOMARN EN CUENTA LAS CONTRIBUCIONES DE LAS CANALETAS DE CONCRETO EN EL


INCREMENTO DE LAS RESISTENCIAS DE ESTAS VIGAS.

3.1 METRADO DE CARGAS

PESO DE LOSA MACIZA DE TECHO: 300 KG/M2

PESO DE COBERTURA DE TEJAS: 50 KG/M2

CARGA VIVA DE TECHO: 30 KG/M2

CARGA DISTRIBUIDA TOTAL DE TECHO: W = 380 KG/M2

PESO PROPIO DE VIGA:

PPV = 0.25X0.45X2400 = 270 KG/M

4
ANCHO DE INFLUENCIA DE LAS VIGAS: B = 6.50/2 = 3.25 M

CARGA DISTRIBUIDA TOTAL QUE GRAVITA SOBRE LAS VIGAS:

WT = 380X3.25 + 270 = 1505 KG/M = 1.505 TON/M

3.2 DISEO POR FLEXIN

LUCES DE CLCULO DE LAS VIGAS HORIZONTALES: L = 7.20 0.60 = 6.60 M

MOMENTOS FLEXIONANTES MXIMOS POSITIVOS Y NEGATIVOS:

Mmax = 1/14 (1.505) (6.60)2 =4.68 TON-M

REAS DE REFUERZO REQUERIDAS POR FLEXIN:

As = 1.50X4.68/(0.81X4.20X0.39) = 5.29 CM2

SE DISPONDR 3 BARRAS DE 5/8 DE DIMETRO, TANTO EN EL LECHO SUPERIOR, COMO EN EL


LECHO INFERIOR, DE TODAS LAS VIGAS HORIZONTALES DE SOPORTE DEL TECHO DE PRGOLAS.

3.3 DISEO POR CORTANTE

FUERZAS CORTANTES MXIMAS EN LOS EXTREMOS DE LAS VIGAS:

V max = 1.505X 6.60/2 = 4.97 TONS

FUERZAS CORTANTES LTIMAS DE DISEO:

Vu/0.85 = 1.50X4.97/0.85 = 8.76 TONS

CORTANTE LTIMO NOMINAL QUE ABSORBE EL CONCRETO:

Vc = 0.53 (210)1/2 25X39/1000 = 7.49 TONS

CORTANTES LTIMOS QUE DEBEN TOMAR LOS ESTRIBOS DE REFUERZO:

Vs = 8.76 7.49 = 1.27 TONS.

ESTAS FUERZAS CORTANTES SON PEQUEAS. POR TANTO, ES SUFICIENTE REFORZAR LAS VIGAS
HORIZONTALES CON ESTRIBOS MNIMOS.

SE DISPONDRN ESTRIBOS CERRADOS DE DOS RAMAS DE 3/8 DE DIMETRO, CON SEPARACIONES


DE 0.20 M, ENTRE EJES.

4.0 DISEO DE LAS VIGAS HORIZONTALES INTERMEDIAS DE TECHO

ESTAS VIGAS TIENEN SECCIONES TRANSVERSALES DE 0.25 M DE ANCHO Y PERALTES MXIMOS


(MEDIDOS HASTA EL VRTICE CENTRAL) DE 0.50 M.

5
POR TANTO, TIENEN SECCIONES MAYORES QUE LAS VIGAS HORIZONTALES QUE CONECTAN LAS
COLUMNAS Y RECIBEN APROXIMADAMENTE LA MISMA CARGA VERTICAL DE TECHO.

POR ESTAS RAZONES, SE DECIDI REFORZAR ESTAS VIGAS INTERMEDIAS ELEVADAS CON LAS
MISMAS CANTIDADES DE REFUERZO QUE LAS VIGAS HORIZONTALES DE 0.25X0.45 M.

POR TANTO, EN ESTAS VIGAS SE DISPONDRN LOS SIGUIENTES REFUERZOS:

REFUERZO POR FLEXIN: 3 BARRAS DE 5/8 EN EL LECHO SUPERIOR Y 3 BARRAS DE 5/8 TAMBIN
EN EL LECHO INFERIOR.

REFUERZO POR CORTANTE: ESTRIBOS DE 3/8 @ 0.20 M.

5.0 DISEO DE LAS COLUMNAS CIRCULARES DE PRGOLAS

DIMETRO DE LAS COLUMNAS CIRCULARES: D = 0.30 M

ALTURA LIBRE DE LAS COLUMNAS: H = 3.50 M

5.1 METRADO DE CARGAS

PESO DE LOSA DE TECHO: 300 KG/M2

PESO DE COBERTURA DE TEJAS: 50 KG/M2

CARGA VIVA DE TECHO: 30 KG/M2

PESO DE VIGAS DE TECHO: 150 KG/M2

PESO DE COLUMNAS: 50 KG/M2

CARGA DISTRIBUIDA TOTAL QUE REPRESENTA EL PESO DEL TECHO Y DE COLUMNAS:

W = 300 + 50 + 30 + 150 + 50 = 580 KG/M2

REA DE INFLUENCIA DE LAS COLUMNAS:

A = 6.50X7.20/2 = 23.4 M2

CARGA VERTICAL DE COMPRESIN DE SERVICIO PARA CARGA MUERTA Y CARGA VIVA EN


COLUMNAS:

P = PD + PL = 0.58X23.4 = 13.57 TONS

MOMENTOS FLEXIONANTES DE SERVICIO PARA CARGAS MUERTAS Y CARGAS VIVAS:

M = MD + ML = 4.68 TON-M

6
COEFICIENTE SSMICO DE DISEO:

FACTOR DE ZONA: Z = 0.30

FACTOR DE USO E IMPORTANCIA: U = 1.50

FACTOR SUELO: S = 1.40

PERODO PREDOMINANTE DE VIBRACIN DEL SUELO DE CIMENTACIN: Tp = 0.90 SEG

PERODO FUNDAMENTAL DE VIBRACIN DE LA PRGOLA: T = 0.10 SEG

FACTOR DE AMPLIFICACIN DINMICA: C = 2.50

FACTOR DE REDUCCIN POR DUCTILIDAD: R = 8

POR TANTO: Cs = (0.30X1.50X1.40X2.50)/8.0 = 0.197

FUERZAS CORTANTES POR SISMO EN COLUMNAS:

Vs = Cs*P = 0.197X13.57 = 2.67 TONS

MOMENTOS POR SISMO EN LOS EXTREMOS DE COLUMNAS:

Ms = Vs*H/2 = 2.67X3.50/2 = 4.68 TON-M

CARGA LTIMA DE DISEO DE COLUMNAS:

Pu = 1.25 (13.57) = 16.96 TONS

MOMENTO LTIMO DE DISEO DE COLUMNAS:

Mu = 1.25 (4.68 + 4.68) = 11.70 TON-M

EXCENTRICIDAD DE LA CARGA VERTICAL DE COMPRESIN:

e = 11.70/16.96 = 0.69 M

PARMETROS DE DISEO DE COLUMNAS:

D = 0.30 M, d = 0.30 0.05 = 0.25 M

d/D = 0.25/0.30 = 0.83

e/D = 0.69/0.30 = 2.30

fc = 245 KG/CM2

fc = 0.85X245 = 208.2 KG/CM2

fy = 4200 KG/CM2

7
K = 16.96/(0.70X302X0.208) = 0.129

R = 0.129X2.30 = 0.298

ABACOS DE DISEO DE COLUMNAS DEL INSTITUTO DE INGENIERA DE LA UNAM-MXICO:

NDICE DE REFUERZO DE ACERO: q = 0.60

CUANTA DE REFUERZO LONGITUDINAL:

p = 0.60X208/4200= 0.030 > p min = 0.010

REA TOTAL DE REFUERZO DE COLUMNAS:

Ast = 0.030X3.15X302/4 = 21.26 CM2 (8 BARRAS DE 3/4)

REFUERZO TRANSVERSAL:

ANILLOS CIRCULARES DE 3/8 @ 0.25 M.

CUSCO, FEBRERO DEL 2013